Reinforced Concrete Design
Reinforced Concrete Design
STRENGTH DESIGN METHOD 409.3.5 — For post-tensioned anchorage zone design, a load 1. There are two or more spans,
(formerly Ultimate Strength Design) factor of 1.2 shall be applied to the maximum tendon jacking
force. 2. Spans are approximately equal, with the larger of two
Design Principle: adjacent clear spans not greater than the shorter by
Strength Strength Required to more than 20 percent,
2015 NSCP Load Combinations Summary
Provided Carry Factored Loads From Table 405.3.1 3. Loads are uniformly distributed,
U = 1.4(D) (405.31a)
U = 1.2(D ) + 1.6(L) + 0.5(Lr or R) (405.31b) 4. Unfactored live load, L, does not exceed three times
Provisions from 2010 NSCP: U = 1.2D + 1.6(Lr or R) + (1.0L or 0.5W) (405.31c) unfactored dead load, D, and
409.3 — Required strength U = 1.2D + 1.0W + 1.0L + 0.5(Lr or R) (405.31d) 5. Members are prismatic.
409.3.1 — Required strength U shall be at least equal to the U = 1.2D + 1.0E + 1.0L (405.31e)
effects of factored loads in Eq. (409-1) through (409-7). The U = 0.9D + 1.0W (405.31f)
effect of one or more loads not acting simultaneously shall be U = 0.9D + 1.0E (405.31g) Positive Moment
investigated. End spans:
U = 1.4(D + F ) (409-1) Design strength Discontinuous end
U = 1.2(D + F + T) + 1.6(L + H) + 0.5(Lr or R) (409-2) Design strength provided by a member, its connections to unrestrained . . . . . . . . . . . …. . . . wuln²/11
U = 1.2D + 1.6(Lr or R) + (1.0L or 0.8W) (409-3) other members, and its cross sections, in terms of flexure, axial Discontinuous end integral
U = 1.2D + 1.6W + 1.0L + 0.5(Lr or R) (409-4) load, shear, and torsion, shall be taken as the nominal with support . . . . . . . . . . . . . . . ... wuln²/14
U = 1.2D + 1.0E + 1.0L (409-5) strength calculated in accordance with requirements and Interior spans . . . . . . . . . . . . . . . . . . . . ….. wuln²/16
U = 0.9D + 1.6W + 1.6H (409-6) assumptions of this Section, multiplied by the strength
U = 0.9D + 1.0E + 1.6H (409-7) reduction factor φ.
except as follows: Negative Moment at exterior face
1. The load factor on the live load L in Eq. 409-3 to 409-5 shall Values of φ: of first interior support
be permitted to be reduced to 0.5 except for garages, areas 2001 2010/2015 Two spans . . . . . . . . . . . . . . . . . . . . . . ……. wuln²/9
occupied as places of public assembly, and all areas where NSCP NSCP More than two spans . . . . . . . . . . . . …... wuln²/10
L is greater than 4.8 kN/m2. Flexure (tension-controlled) 0.9 0.9 Negative Moment at other faces of
Compression-controlled Section interior supports . . . . . . . . . . . . . . ….. . . . wuln²/11
2. Where wind load W has not been reduced by a directionality 0.75 0.75
with spirals Negative Moment at face of all
factor, it shall be permitted to use 1.3W in place of 1.6W in Other compression-controlled
0.70 0.65 supports for:
Eq. 409-4 and 409-6. Section Slabs with spans not exceeding
3. Where E, the load effects of earthquake, is based on service- Shear and torsion 0.85 0.75 3m; and Beams where ratio of
level seismic forces, 1.4E shall be used in place of 1.0E in Bearing on concrete (except sum of column stiffnesses to
0.70 0.65
Eq. 409-5 and 409-7. for post-tensioned anchorage) beam stiff-nesses exceeds eight
post-tensioned anchorage zones 0.85 0.85 at each
4. The load factor on H, loads due to weight and pressure of soil,
water in soil, or other materials, shall be set equal to zero 2010/2015 NSCP: For sections in which the net tensile strain end of the span . . . . . . . . . …….. . . . . . . . . wuln²/12
in Eq. 409-6 and 409-7 if the structural action due to H εt, is between the limits for compression-controlled and Negative Moment at interior face of
counteracts that due to W or E. Where lateral earth tension-controlled sections, φ shall be permitted to be linearly exterior supports for members built
pressure provides resistance to structural actions from increased from that for compression-controlled sections to integrally with supports
other forces, it shall not be included in H but shall be 0.90 as εt increases from the compression-controlled strain Where support is a spandrel
included in the design resistance. limit to 0.005. beam . . . . . . . . . . . . . . . …….. . . . . . . . wuln²/24
409.3.2 — If resistance to impact effects is taken into account When support is a column………………. wuln²/16
in design, such effects shall be included with live load L.
409.3.3 — Estimations of differential settlement, creep, Shear in end members at face of
SHEAR AND MOMENT COEFFICIENTS First interior support . . . . . ……………….. . . . . 1.15wuln/2
shrinkage, expansion of shrinkage-compensating concrete, or
temperature change shall be based on a realistic assessment of Shear at face of all other supports . . . .... . . . wuln/2
408.4.3 As an alternate to frame analysis, the following
such effects occurring in service. approximate moments and shears shall be permitted to be
Note: ln = clear span for positive moment or shear and
409.3.4 — If a structure is in a flood zone, or is subjected to used in design of continuous beams and one-way slabs (slabs
forces from atmospheric precipitations, the flood loads and the average of adjacent clear spans for negative moment
reinforced to resist flexural stresses in only one direction),
appropriate load combinations of ASCE/SEI 7 shall be used. provided:
Case 1:
Discontinuous end
If S/L < 0.5, one way slab.
unrestrained:
Spandrel:
Column:
Equivalent uniform load carried by the shorter beam.
q𝑠
𝑤
(b) beams with two spans only 3
𝐿 𝐿
Where:
S = shorter span
L = longer span
m = S/L
q = floor load per unit area
Figure – 2
Problem 8
A continuous beam is to be subjected to a total uniform
dead load of 10 kN/m and live load of 25 kN/m. Use NSCP
coefficient method. Refer to Figure – 4. U = 1.2D + 1.6L.
Problem 7 RC-006
A reinforced concrete beam has a width of 300 mm and Minimum bend diameters
an overall depth of 510 mm. The beam is simply supported Inside diameter of bend for stirrups and ties
over a span of 5.3 m. Steel strength fy = 415 MPa and concrete shall not be less than 4db for ø16mm bar and
strength fc’ = 28 MPa. Concrete cover is 70 mm from the smaller.
centroid of the steel area. Unit weight of concrete is 23.5
kN/m3. Other than the weight of the beam, the beam carries a
superimposed dead load of 19 kN/m and a live load of 15 Spacing limits for reinforcement
kN/m. Use U = 1.2D + 1.6L at ultimate condition. The minimum clear spacing between parallel
1. Determine the maximum factored moment on the bars in a layer shall be db, but not less than 25
mm.
beam.
Where parallel reinforcement is placed in two or
2. Determine the required number of 20 mm tension more layers, bars in the upper layers shall be placed
bars. directly above bars in the bottom layer with clear
3. If the beam will carry an additional factored load of distance between layers not less than 25mm.
20 kN at midspan, determine the required number of
25 mm tension bars.
Bundled Bars
Groups of parallel reinforcing bars bundled in
contact to act as a unit shall be limited to four
Problem 8 bars in one bundle.
Refer to RC-006 for minimum requirements.
A reinforced concrete beam has the following given Bars larger than 𝜙36 mm shall not be bundled
in beams.
data:
Beam depth, h = 600 mm Where spacing limitations and minimum
Tension steel reinforcements: concrete cover are based on bar diameter db, a
6-28mmϕ bars in 2-layers unit of bundled bars shall be treated as a single
with 3 bars per layer bar of a diameter derived from the equivalent
total area.
Clear bar covering = 40mm
Stirrups = 10mmϕ
Concrete, fc’ = 28 MPa
Steel bars, fy = 415 MPa
Determine the following:
1. If beam width is 300mm, determine the horizontal clear
spacing (mm) of the bars. Assume that bars in a layer are
perfectly aligned.
2. The value of the minimum width (mm) of the beam based
on code requirements for cover and spacing limits.
3. Determine the effective depth, d, and depth dt of the beam
in mm.
4. If the outer layer has 4 bars, and the other layer has 2
bars, determine the effective depth, d (mm) of the beam.
0.375𝑑
1. Equate CC to T1 to solve A s1. 3. Solve A s2. 1. Determine the stress in the compression steel.
𝒅′
𝟎. 𝟖𝟓𝒇𝒄 𝒂𝒃 𝑨𝒔𝟏 𝒇𝒚 𝑴𝒏𝟐 𝑨𝒔𝟐 𝒇𝒚 𝒅 𝒅′ 𝒇𝒔 𝟔𝟎𝟎 𝟏 𝒇𝒚
𝒄
𝟎. 𝟖𝟓𝒇𝒄 𝒂𝒃 𝑴𝒏𝟐
𝑨𝒔𝟏 𝑨𝒔𝟐 2. Equate Cs to T2 to solve A s’.
𝒇𝒚 𝒇𝒚 𝒅 𝒅′
𝑨𝒔 ′ 𝒇𝒔 𝟎. 𝟖𝟓𝒇𝒄 𝑨𝒔𝟐 𝒇𝒚
𝑨𝒔𝟐 𝒇𝒚
2. Determine the excess moment, Mn2. 4. Finally, 𝑨𝒔 ′
𝑨𝒔 𝑨𝒔𝟏 𝑨𝒔𝟐 𝒇𝒔 𝟎. 𝟖𝟓𝒇𝒄
𝑴𝒖
𝑴𝒏𝟐 𝑴𝒏 𝑴𝒏𝟏 𝒐𝒓 𝑴𝒏𝟐 𝑴𝒏𝟏
𝝋
𝑨𝒔
where: 𝝆
𝒃𝒅
2. Determine the maximum design moment capacity for a Simply One end Both ends Cantile
Member
singly-reinforced beam section. supported continuous continuous -ver
Solid
3. Find the number of 28mmØ tension steel.
one-way
4. Calculate the stress in compression steel. slabs l/20 l /24 l /28 l /10
5. Find the number of 28mmØ compression steel. Values given shall be used directly for members with normal
density concrete (wc = 2400kg/m3) and Grade 415 reinforcement.
For other conditions, the values shall be modified as follows:
(a) For structural lightweight concrete having unit
ONE‐WAY SLAB weights in the range 1500-2000 kg/m3 , the values shall be
Problem 3 multiplied by (1.65 – 0.0003 wc ) but not less than 1.09,
where wc is the unit mass in kg/m3
A two-span continuous one-way slab with clear spans
of 4.2 meters is supported on beams 300 mm wide. In (b) For fy other than 415 MPa, the values shall be
addition to its dead weight, the slab carries a liveload of multiplied by (0.4 + fy / 700).
2500 Pa. f’c = 21 MPa and fy = 275 MPa. Unit weight of
concrete 23.5 kN/m3. Refer to RC-05.
1. Determine the minimum depth of slab if deflection is
not to be computed.
B1 B2 B3 2. Calculate the moment at the most critical section of the 1. Determine the number of pieces of 20mm tension steel
slab considering a 1 m strip if the depth of slab is for a singly-reinforced section reinforced with maximum
4m 8m 6m 150mm. steel for tension control.
A. 4 B. 5 C. 6 D. 7
3. Calculate the spacing of 12mm main reinforcing bars
1. Calculate the minimum thickness of slab B1 in at the most critical section of the interior slab. 2. Determine the number of pieces of 20mm tension
millimeters. reinforcements if beam is to carry a factored design moment
of 80 kN-m.
2. Calculate the minimum required thickness of slab B2 in
A. 3 B. 4 C. 5 D. 6
millimeters.
3. Calculate the minimum required thickness of slab B3 in
millimeters.
Manila: https://www.facebook.com/ReviewInnovationsOfficial Davao: https://www.facebook.com/reviewinnovations.davaobranch
Civil Engineering May 2022 Review Innovations Concrete 3
Problem 11
A reinforced concrete beam has a width of 300 mm
and an effective depth of 600 mm. Compressive
reinforcement (if required) will be placed at d’ = 60mm.
f’c = 27.5 MPa and fy = 415 MPa. Use 2010 NSCP. The beam
is to support a factored bending moment of 670 kN-m.
1. Determine the area of steel required as tension
reinforcement if the minimum strain in the extreme
tension steel is permitted to be 0.004.
2. Determine the area of steel required as tension
reinforcement if the minimum strain in the extreme
tension steel is limited to 0.005.
3. Determine the number of 28mm bars required as
tension reinforcement if the reduction factor, 𝜙 =0.90.
using Stress 𝒇𝒔 𝒇𝒚
Note:
0.85𝑓 600 𝑑
𝜌 𝛽
𝑓 600 𝑓 𝑑
0.85𝑓 3 𝑑
𝜌 𝛽
𝑓 8 𝑑
0.003 ε
𝜌
0.008
Problem 9
Given Beam Data:
Beam width, bw = 300mm
Concrete strength , fc’ = 24 MPa
Steel yield strength, fy = 415 MPa
Use 2010/2015 NSCP.
Problem 2
A T-beam section has a flange width of 600 mm, flange
thickness of 100 mm, width of web of 350 mm, effective depth
Minimum Flexural Reinforcement: of 535 mm and a total depth of 600 mm. Use f’c = 21 MPa and
fy = 415 MPa. The section is required to resist a total service
𝑓𝑐 dead load moment of 260 kN-m and a service live load moment
𝐴 𝑏 𝑑
4𝑓 of 142 kN-m. Use 𝜙 = 0.90 and U = 1.2D + 1.6L.
1.4 1. Determine the required nominal strength for the
𝐴 𝑏 𝑑 concrete beam section.
𝑓
2. Determine the maximum height of the rectangular stress
If flange is in tension, bw is replaced by either block for a tension-controlled section.
2bw or the width of the flange, whichever is smaller.
3. Calculate the required depth of the concrete rectangular
stress block.
4. Calculate the required reinforcement area.
5. Determine the number of 28mm required as tension
reinforcement.
Greater of:
409.6.3.1 A minimum area of shear reinforcement, Av,min , shall Prestressed with 𝑽𝒖 𝝓 𝑽𝒄 𝟎. 𝟔𝟕 𝒇𝒄 ′𝒃𝒘 𝒅 (422.5.1.2)
be provided in all regions where Vu > 0.5𝜙Vc except for 𝐴 𝑓
the cases in Table 409.6.3.1, where at least Av.min shall be 𝑏 422.5.1.3 For non-prestressed members, Vc shall be calculated
0.40 𝐴 𝑓 0.35 b
provided where Vu > 0.5𝜙Vc. 𝐴 𝑓 𝑓 in accordance with Sections 422.5.5, 422.5.6, or 422.5.7.
creep, shrinkage, and temperature change, based on a 𝐴 𝑓 0.35 422.5.5.1 For non-prestressed members without axial force,
d
realistic assessment of these effects occurring in service. 0.40 𝐴 𝑓 𝑓 Vc shall be calculated by:
𝐴 𝑓 𝑽𝒄 𝟎. 𝟏𝟕λ 𝒇𝒄 ′𝒃𝒘 𝒅 (422.5.5.1)
409.6.3.3 If shear reinforcement is required and torsional 𝐴 𝑓 𝑑
effects can be neglected according to Section 409.5.4.1, e
80𝑓 𝑑 𝑏 unless a more detailed calculation is made in accordance
Av,min shall be in accordance with Table 409.6.3.3.
with Table 422.5.5.1.
Table 422.5.5.1 422.5.7 VC FOR NON‐PRESTRESSED MEMBERS WITH 422.5.10.5.5 For each rectangular tie, stirrup, hoop, or
Detailed Method for Calculating Vc SIGNIFICANT AXIAL TENSION crosstie, Av shall be the effective area of all bar legs or
4422.5.7.1 For non-prestressed members with significant wires within spacing s.
𝑽𝒄 axial tension, Vc shall be calculated by:
422.5.10.5.6 For each circular tie or spiral, Av shall be two
𝑉𝑑 𝑵𝒖 times the area of the bar or wire within spacing s.
0.16λ 𝑓 ′ 17𝜌 𝑏 𝑑 (a) 𝑽𝒄 𝟎. 𝟏𝟕 𝟏 λ 𝒇𝒄 ′𝒃𝒘 𝒅 422.5.7.1
𝑀 𝟑. 𝟓𝑨𝒈
Least of (a),
(b) and (c): 0.16λ 𝑓 ′ 17𝜌 𝑏 𝑑 (b) where Nu is negative for tension, and Vc shall not be less
than zero.
0.29λ 𝑓 ′𝑏 𝑑 (c)
Problem 8
Refer to RC-02 for simplified calculation for shear.
Given: Column diameter, D = 600mm
Longitudinal steel, Ast= 8x28mm𝜙 bars w/ fy = 415 MPa
Lateral ties, 12mm𝜙 with fyt = 275 MPa
Concrete (normal weight), fc’ = 27.5 MPa
Shear strength reduction factor = 0.75
Factored axial compression force = 3,000 kN
600
1. What is the shear stress area of concrete, in mm2?
2. What is the design shear strength capacity of the concrete
along the x-direction, in kN.
3. What is the design shear strength capacity of ties, in kN, if 450
the spacing of the ties is 75mm.
Problem 9 Figure 2
Refer to RC-02 simplified calculation for shear and
FIGURE-2.
Data of a concrete column are as follows :
Dimensions, b x h = 450mm x 600mm
Ast = 16-25mmϕ bars with fy = 415 MPa
Lateral ties = 12mmϕ spaced at 100mm on centers
Effective cover to centroid of vertical
steel bars on each side = 65 mm
Concrete (normal-weight) , fc’ = 27.5 MPa with λ = 1.0
Lateral ties, fyt = 275 MPa
Shear strength reduction factor = 0.75
Factored axial compression force, Nu = 3560 KN
1. Determine the shear capacity of the concrete, Vc (KN),
along the y-axis.
2. Determine the shear capacity of the concrete, Vc (KN),
along the x-axis.
3. Determine the shear capacity of the tie reinforcements, Vs
(KN), along the x-axis.
407.11.5.1 All nonprestressed bars shall be enclosed by lateral 410.10.3 Volumetric spiral reinforcement ratio, s, shall not
410.4.6.2 For nonprestressed members with tie
ties, at least Ø10 mm in size for longitudinal bars Ø32 mm be less than the value given by
reinforcement conforming to Section 407.11.5:
or smaller, and at least Ø12 mm in size for Ø36 mm, Ø42
mm, Ø58 mm bars and bundled longitudinal bars. Deformed 𝑨𝒈 𝒇𝒄
wire or welded wire fabric of equivalent area shall be Pn (max) 0.80 0.85f c Ag Ast fy Ast (410-2) 𝝆𝒔 𝟎. 𝟒𝟓
𝑨𝒄𝒉
𝟏
𝒇𝒚𝒕
410 5
permitted.
410.4.7 Members subject to compressive axial load shall be where the value of 𝑓 used in Eq. 410-6 shall not exceed
407.11.5.2 Vertical spacing of ties shall not exceed 16 designed for the maximum moment that can accompany the 700 MPa. For 𝑓 greater than 415 MPa, lap splices
longitudinal bar diameters, 48 tie bar or wire diameters, or axial load. The factored axial load Pu at given eccentricity according to Section 407.11.4.5(1) shall not be used.
least dimension of the compression member. shall not exceed that given in Section 410.4.6. The
maximum factored moment Mu shall be magnified for
407.11.5.3 Ties shall be arranged such that every corner and slenderness effects in accordance with Section 410.11.
alternate longitudinal bar shall have lateral support provided
by the corner of a tie with an included angle of not more than
135 degrees and no bar shall farther than 150 mm clear on
each side along the tie from such a laterally supported bar.
Where longitudinal bars are located around the perimeter of
a circle, a complete circular tie shall be permitted.
RC-07
Ties shall be arranged such that every corner and
alternate longitudinal bar shall have lateral support
provided by the corner of a tie with an included angle
of not more than 135 degrees and no bar shall farther
than 150 mm clear on each side along the tie from such
a laterally supported bar. Where longitudinal bars are
located around the perimeter of a circle, a complete
circular tie shall be permitted.
3-28mm 2-28mm
a
450mm x
a
60 60
480mm
Figure - 1
y
d1 d2
55 55
84mm
b1 b2
6-20mmØ
4-28mmØ
Figure - 2
-------------------------------------------------------------------------------
( Ec I g / 5) Es I sx slabs
Q
P
u o
(406.6.4.4.1)
r (406.2.5.2) Vus lc
( Ec Ag / 5) Es Asx Note: For continuous flexural members, I shall be permitted
structural steel or within transverse reinforcement horizontal storey shear, respectively, in the story being
calculated from the load combination under consideration, or
surrounding a structural steel core shall be permitted to be the combination of Pu and Mu that produces the least value of evaluated, and o is the first-order relative lateral deflection
used in calculating Asx and Isx ꞏ I.
between the top and the bottom of that storey due to Vus .
406.6.3.1.2 For factored lateral load analysis, it shall be
406.2.6 Unless slenderness effects are neglected as permitted permitted to assume I = 0.5Ig for all members or to calculate
by Section 406.2.5, the design of columns, restraining I by a more detailed analysis, considering the reduced
beams, and other supporting members shall be based on the stiffness of all members under the loading conditions.
Manila: https://www.facebook.com/ReviewInnovationsOfficial Davao: https://www.facebook.com/reviewinnovations.davaobranch
Civil Engineering May 2022 Review Innovations Concrete 8
406.6.4.4.2 The critical buckling load, Pc, shall be calculated 406.6.4.5.2 Magnification factor shall be calculated by:
by:
cm
1.0 406.6.4.6.2 The moment magnifier s shall be calculated by
2 ( EI )eff Pu (406.6.4.5.2)
Pc (406.6.4.4.2) 1 (a), (b), or (c). If s exceeds 1.5, only (b) or (c) shall be
( klu )2 0.75Pc
permitted:
406.6.4.5.3 Cm shall be in accordance with (a) or (b): 1
406.6.4.4.3 The effective length factor k shall be calculated a. s 1.0 (406.6.4.6.2a)
using Ec in accordance with Section 419.2.2 and I in a. For columns without transverse loads applied between 1 Q
accordance with Section 406.6.3.1.1. For nonsway members, supports:
k shall be permitted to be taken as 1.0, and for sway 1
b. s 1.0
members, k shall be at least 1.0. M
cm 0.6 0.4 1 (406.6.4.5.3a) 1
P u
(406.6.4.6.2b)
Figure 6A Figure 6B
Figure 5
422.6.5.1 For non-prestressed two-way members, 𝒗𝒄 shall be 413.3.1.2 Overall depth of foundation shall be selected such
calculated in accordance with Section 422.6.5.2. that the effective depth of bottom reinforcement is at least 150
mm.
Table 422.6.5.2
Calculation of 𝒗𝒄 for Two-way Shear 413.3.2 One-Way Shallow Foundations
𝒗𝒄 413.3.2.1 The design and detailing of one-way shallow
foundations, including strip footings, combined footings, and
0.33𝜆 𝑓 ′ (a)
grade beams, shall be in accordance with this section and the
2 applicable provisions of Sections 407and 409.
Least of (a), 0.17 1 𝜆 𝑓′ (b)
(b) and (c): 𝛽
𝛼 𝑑 413.3.2.2 Reinforcement shall be distributed uniformly across
0.083 2 𝜆 𝑓′ (c) entire width of one-way footings.
𝑏
Note: 𝛽 is the ratio of long side to short side of the column, concentrated load, or
reaction area and 𝛼 , is given in Section 422.6.5.3.
413.3.3 Two-Way Isolated Footings
413.2.7 CRITICAL SECTIONS FOR SHALLOW 413.3.3.1 The design and detailing of two-way isolated
FOUNDATIONS AND PILE CAPS footings shall be in accordance with this section and the
applicable provisions of Sections 407 and 408.
413.2.7.1 Mu at the supported member shall be permitted to be
calculated at the critical section defined in accordance with 413.3.3.2 In square two-way footings, reinforcement shall be
Table 413.2.7.1. distributed uniformly across entire width of footing in both
Table 413.2.7.l directions.
Location of Critical Section for Mu
Supported member Location of critical section 413.3.3.3 In rectangular footings, reinforcement shall be
distributed in accordance with (a) and (b).
Column with steel base Halfway between face of column and
plate edge of steel base plate a. Reinforcement in long direction shall be distributed
uniformly across entire width of footing.
Concrete wall Face of wall
Halfway between center and face of b. For reinforcement in short direction, a portion of the total
Masonry wall masonry wall reinforcement, 𝜸𝒔 𝑨𝒔 , shall be distributed uniformly over
Manila: https://www.facebook.com/ReviewInnovationsOfficial Davao: https://www.facebook.com/reviewinnovations.davaobranch
Civil Engineering May 2022 Review Innovations Concrete 9
2010 NSCP 415.5.3 In one-way footings and two-way square footings,
SECTION 415 - FOOTINGS reinforcement shall be distributed uniformly across entire
411.12 PROVISIONS FOR SLABS AND FOOTINGS width of footing.
411.12.1 The shear strength of slabs and footings in the vicinity 415.3 LOADS AND REACTIONS
415.5.4 In two-way rectangular footings, reinforcement shall
of columns, concentrated loads or reactions is governed by the be distributed as follows:
more severe of two conditions: 415.3.1 Footings shall be proportioned to resist the factored
loads and induced reactions, in accordance with the appropriate 415.5.4.1 Reinforcement in long direction shall be distributed
411.12.1.1 Beam action where each critical section to be design requirements of this Code and as provided in Section uniformly across entire width of footing.
investigated extends in a plane across the entire width. For 415.
beam action, the slab or footing shall be designed in accordance 415.5.4.2 For reinforcement in short direction, a portion of the
with Sections 411.2 through 411.5. 415.3.2 Base area of footing or number and arrangement of total reinforcement, 𝜸𝒔 𝑨𝒔 , given by Eq. 415-1 shall be
piles shall be determined from unfactored forces and moments distributed uniformly over a band width (centered on centerline
411.12.1.2 Two-way action where each of the critical sections of column or pedestal) equal to the length of short side of
to be investigated shall be located so that its perimeter, bo, is a transmitted by footing to soil or piles and permissible soil
pressure or permissible pile capacity determined through footing. Remainder of reinforcement required in short
minimum but need not approach closer than d/2 to: direction, 𝟏 𝜸𝒔 𝑨𝒔 , shall be distributed uniformly outside
principles of soil mechanics.
1. Edges or corners of columns, concentrated loads or center band width of footing.
reactions. 415.3.3 For footings on piles, computations for moments and
2
2. Changes in slab thickness such as edges of capitals or drop
shears shall be permitted to be based on the assumption that the 𝜸𝒔 = (415-1)
reaction from any pile is concentrated at pile center. ( 1)
panels or shear caps.
For two-way action the slab or footing shall be designed in 415.4 FOOTINGS SUPPORTING CIRCULAR OR where = ratio of long side to short side of footing
accordance with Sections 411.12.2 through 411.12.6. REGULAR POLYGON-SHAPED COLUMNS OR
PEDESTALS 415.8 MINIMUM FOOTING DEPTH
411.12.1.3 For square or rectangular columns, concentrated
loads or reaction areas, the critical sections with four straight For location of critical sections for moment, shear and Depth of footing above bottom reinforcement shall not be less
sides may be permitted. development of reinforcement in footings, it shall be permitted than 150 mm for footings on soil, or not less than 300 mm for
to treat circular or regular polygon-shaped concrete columns or footings on piles.
411.12.2 The design of a slab or footing for two-way action is pedestals as square members with the same area.
based on Equations 411-1 and 411-2. Vc shall be computed in
accordance with Section 411.12.2.1, 411.12.2.2 or 411.12.3.1.
Vs shall be computed in accordance with Section 411.12.3. 415.5 MOMENTS IN FOOTINGS
When moment is transferred between a slab and a column,
Section 411.12.7 shall apply. 415.5.1 External moment on any section of a footing shall be
determined by passing a vertical plane through the footing and
computing the moment of the forces acting over the entire area
411.12.2.1 For non-prestressed slabs and footings, Vc shall be of footing on one side of that vertical plane.
the smallest of (1),(2), and (3): 415.5.2 Maximum factored moment, Mu, for an isolated
1 2 footing shall be computed as prescribed in Section 415.5.1 at
1. Vc 1 fc 'bo d (411-37) critical sections located as follows:
6
where is the ratio of long side to short side of the column, 1. At face of column, pedestal, or wall, for footings
concentrated load or reaction area; supporting a concrete column, pedestal, or wall;
1 sd 2. Halfway between middle and edge of wall, for footings
2. Vc 2 fc 'bo d (411-38) supporting a masonry wall;
12 bo
where s is 40 for interior columns, 30 for edge columns, 20 3. Halfway between face of column and edge of steel base
for corner columns, and plate, for footings supporting a column with steel base
1 plate.
3. Vc fc 'bod (411-39)
3
Total Load
A
Allowable GROSS Soil Pressure
Net Load
or A
Allowable NET Soil Pressure
Note: use unfactored load
𝑷
𝒒𝒎𝒂𝒙 𝟔𝒆𝒙 𝟔𝒆𝒚
𝑨 𝒘𝒉𝒆𝒏 𝟏
𝑩 𝑫
𝑷 𝟔𝒆𝒙 𝟔𝒆𝒚
𝒒𝟏 𝟏 𝒒𝒎𝒂𝒙
𝑩𝑫 𝑩 𝑫
𝑷 𝟔𝒆
𝒒𝒎𝒂𝒙 𝟏
𝑩𝑫 𝑫 𝑷 𝟔𝒆𝒙 𝟔𝒆𝒚
𝒒𝟐 𝟏
𝑩𝑫 𝑩 𝑫
𝑷 𝟔𝒆
𝒒𝒎𝒊𝒏 𝟏 𝑷 𝟔𝒆𝒙 𝟔𝒆𝒚
𝑩𝑫 𝑫 𝒒𝟑 𝟏 𝒒𝒎𝒊𝒏
𝑩𝑫 𝑩 𝑫
𝟐𝑷
𝒒𝒎𝒂𝒙 𝒒𝒎𝒊𝒏 𝟎
𝑩 𝟑𝒙
𝑫
𝒘𝒉𝒆𝒓𝒆 𝒙 𝒆
𝟐
Manila: https://www.facebook.com/ReviewInnovationsOfficial Davao: https://www.facebook.com/reviewinnovations.davaobranch
Civil Engineering May 2022 Review Innovations Concrete 9
Problem 1
The 460 mm thick footing supports a 300 mm concrete 2. What is the net foundation pressure in kPa at edge B of
wall as shown in FIGURE-2. The unit weight of the concrete is the footing?
24 kN/cu.m and the unit weight of the soil is 16 kN/cu.m. Use A. 56 B. 77.3 C. 133.3 D. 210.7
fc’ = 24 MPa and fy = 240 MPa.
3. What is the minimum required gross allowable soil
bearing capacity to carry the given loads in kPa?
A. 78.8 B. 82.8 C. 233.5 D. 237.5
FIGURE‐3
4. Determine the no. of pcs 28 mmϕ reinforcements (per Footing effective depth = 1000 mm
side) along the short dimension of the footing outside the Materials : Concrete, fc’ = 30 MPa
center bandwidth of the footing. Steel, fy = 415 MPa
A. 2 B. 3 C. 4 D. 5 Strength Reduction Factors : Shear = 0.75
Bending = 0.90
The footing will be designed for uniform settlement.
Determine the following :
1. The value of the maximum factored moment (kN-m) that
will be used in the design of the longitudinal steel between
the columns.
A. 1924 B. 1836 C. 2138 D. 1542
Manila: https://www.facebook.com/ReviewInnovationsOfficial Cebu FB: Excel-RI CE Review Specialist Inc. Davao: https://www.facebook.com/reviewinnovations.davaobranch
Civil Engineering May 2022 Review Innovations Concrete 11
Retaining Walls 24. Determine the factored moment per meter at
the critical section of the heel slab. Use a load
Situation 5 factor of 1.2 for soil pressure.
The section of a reinforced concrete retaining 25. Calculate the factored moment per meter at
wall is shown in FIGURE 2. There is a surcharge the critical section of the toe slab. Use a load
load of 12 kPa at the surface of the backfill. factor of 1.6 for soil pressure and 0.90 for
Unit weight of concrete = 23.5 kN/m3 weight of toe slab.
Unit weight of soil = 17.0 kN/m3
Angle of internal friction of soil, ϕ = 35°
Coefficient of friction between
soil and concrete, μ = 0.50
Allowable soil bearing capacity = 200 kPa 4.2 m
Minimum factors of safety for stability:
Sliding = 1.50
Overturning = 2.0 FIGURE 2
0.3 m
Use: Situation 6
U = 1.2 D + 1.6 L The section of a retaining wall is shown FIGURE 0.3 0.3
2.1 m
U = 1.2 D + 1.6 (L+H), H being the earth pressure 3. Consider unit weight of 23.6 kN/m3 for
. load concrete and 19.4 kN/m3 for soil. For lateral soil 2.7 m
pressure, consider an equivalent fluid pressure of
14. Determine the stability factor of safety 5.72 kN/m3. FIGURE 3
against overturning. 17. Calculate the moment of vertical loads about
15. Determine the stability factor of safety the toe (Righting Moment).
against sliding. 18. Determine the moment of the lateral force
16. Calculate the factored moment per meter about the toe (Overturning Moment).
length of the wall at the junction of the wall 19. Solve for FS against overturning.
and base. 20. Calculate the FS against sliding if µ=0.50.
21. Solve for the maximum soil pressure at the
base of the retaining wall.
22. Find the minimum soil pressure at the base
of the retaining wall.
23. Calculate the factored moment per meter
length at the critical section of the wall or
stem. Use a load factor of 1.6 for lateral force.
Manila: https://www.facebook.com/ReviewInnovationsOfficial Cebu FB: Excel-RI CE Review Specialist Inc. Davao: https://www.facebook.com/reviewinnovations.davaobranch
Civil Engineering May 2022 Review Innovations Concrete 11
Problems for Practice Situation 8 Situation 9
Given data of a concrete footing supported on 7 A 400mm square column is resting on a pile cap
Situation 7 bearing-piles shown in FIGURE - 5. with 5 piles as shown in FIGURE 1. The piles
Refer to FIGURE 4. The columns carry service Footing dimension, W x L = 3.0m x 3.0m have a diameter of 300mm. The footing has an
loads and the footing will be designed for Footing effective depth, d = 300mm effective depth of 300 mm.
uniform settlement. The net soil bearing capacity Column dimension = 400mm x 400mm Column axial loads:
is 300 kPa. Neglect the weight of the footing. Pile diameter = 400 mm D = 420 kN , L = 360 kN, E = 210 kN
Pile spacing = 1.10 m Column moment due to earthquake = 160 kN-m
Column factored loads: The required strength of the footing is based on:
Axial load = 420 kN U=1.2D+1.0E+1.0L
Moment about x-axis = 180 kN-m Strength reduction factor for shear, ϕ = 0.75
Moment about y-axis = 120 kN-m 31. The critical beam shear strength (kN) at
Concrete , fc’ = 24 MPa ultimate loads is nearest to:
Steel bars, fy = 415 MPa A. 430 C. 640
B. 510 D. 859
FIGURE 4 32. Compute the nominal punching shear stress
26. Which of the following gives the position of in MPa.
the column resultant load from end “B” of A. 0.29 C. 0.48
the footing? B. 0.33 D. 1.36
A. 7.36 m C. 8.64 m 33. Compute the maximum design moment (kN-
B. 8.00 m D. 6.42 m m) in the design of the footing reinforcing
27. Which of the following gives the dimension bars.
at end “A” of the footing if a trapezoidal A. 160 C. 240
footing will be used to support the columns? B. 408 D. 370
A. 0.95 m C. 1.83 m FIGURE 5 34. Find the nominal punching shear stress
B. 1.43 m D. 2.24 m (MPa) acting around critical pile.
28. Which of the following gives the dimension 29. Determine the nearest value of the critical A. 0.38 C. 0.60
at end “B” of the footing if a trapezoidal factored shear (kN) for one-way action of the B. 0.51 D. 1.59
footing will be used to support the columns? footing.
A. 2.32 m C. 2.93 m A. 183 C. 115
B. 2.75 m D. 3.47 m B. 290 D. 224
30. Determine the nearest value of the factored
shear (kN) for two-way action of the footing.
A. 360 C. 714
B. 420 D. 511
Manila: https://www.facebook.com/ReviewInnovationsOfficial Cebu FB: Excel-RI CE Review Specialist Inc. Davao: https://www.facebook.com/reviewinnovations.davaobranch
Civil Engineering May 2022 Review Innovations Concrete 11
NSCP Specifications:
415.6.3 Computation of shear on any section
through a footing supported on piles shall be in
accordance with the following:
415.6.3.1 Entire reaction from any pile whose
center is located dp/2 or more outside the section
shall be considered as producing shear on that
section.
415.6.3.2 Reaction from any pile whose center is
located dp/2 or more inside the section shall be
considered as producing no shear on that section.
415.6.3.3 For intermediate positions of pile center,
the portion of the pile reaction to be considered
in producing shear on the section shall be based
on straight-line interpolation between full value
at dp/2 outside the section and zero value at dp/2
inside the section.
Note: dp – diameter of pile
Manila: https://www.facebook.com/ReviewInnovationsOfficial Cebu FB: Excel-RI CE Review Specialist Inc. Davao: https://www.facebook.com/reviewinnovations.davaobranch
Review Innovations CE Review for May 2022 – Working Stress Design (WSD)
I- MATERIAL PROPERTIES: PROBLEMS:
424.6.1 - Strains vary linearly as the distance from the neutral Situation 2: Given are the data for a rectangular concrete
axis, except for deep flexural members with over- all depth- beam to be analyzed by the Working Stress Design (WSD):
span ratios greater than 2/5 for continuous spans and 4/5 for
simple spans, a nonlinear distribution of strain shall be
considered. See Section 410.8 of the Chapter. Beam dimensions, b x h = 200x600
Compression steel, As’ = 3-16mm
424.6.2 - Stress-strain relationship of concrete is a straight line Tension steel, As = 3-25mm
under service loads within permissible service load stresses. Total bar covering, d’ = 60 mm
Concrete, fc = 9.45 MPa
424.6.3 - In reinforced concrete members, concrete resists no Steel bars, fs = 140 MPa
tension. Modular ratio, n = 10
Manila FB: @ReviewInnovationsOfficial Cebu FB: Excel-RI CE Review Specialist Inc. Davao FB: Review Innovations Davao Branch
(02) 8735-9161 0919-227-9194 (032) 268-5989 0919-822 -5048 (082) 221-1121 0930-256-0998
Review Innovations CE Review for May 2022 – Working Stress Design (WSD)
PROBLEMS FOR PRACTICE
Manila FB: @ReviewInnovationsOfficial Cebu FB: Excel-RI CE Review Specialist Inc. Davao FB: Review Innovations Davao Branch
(02) 8735-9161 0919-227-9194 (032) 268-5989 0919-822 -5048 (082) 221-1121 0930-256-0998