Test Specification Number 4 December 2020
Test Specification Number 4 December 2020
December 2020
© Lloyd's Register Group Limited 2020. All rights reserved.
Except as permitted under current legislation no part of this work may be photocopied, stored in a retrieval system, published, performed in
public,
adapted, broadcast, transmitted, recorded or reproduced in any form or by any means, without the prior permission of the copyright owner.
Enquiries
should be addressed to Lloyd's Register Group Limited, 71 Fenchurch Street, London, EC3M 4BS.
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
FOREWORD
2 Lloyd's Register
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
Section
Foreword
n
Foreword
This Specification details the type tests required for reciprocating internal combustion engines operating on liquid, gas or dual fuel
for use in marine offshore and industrial applications. Type test specifications are also provided for turbochargers, crankcase
explosion relief valves and oil mist detection and alarm systems.
This Specification should be read in conjunction with the Lloyd’s Register (hereinafter referred to as LR) Type Approval Procedure.
The interpretation of this Specification is the sole responsibility, and at the discretion, of LR. Any uncertainty in the meaning of the
Specification is to be referred to LR for clarification ([email protected]).
Failure to comply with these requirements may render the test results unacceptable for the purposes of LR Type Approval.
Note This Test Specification No. 4 will be subject to future amendments which will be required to incorporate statutory and
other conventions and codes.
Lloyd's Register 3
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
Contents Chapter 1
SECTION 1 GENERAL
4 Lloyd's Register
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
Section
1 General
n Section 1
General
1.1 Introduction
1.1.1 This test specification specifies LR’s requirements for the type testing of engines and associated ancillary equipment. It
incorporates the International Association of Classification Societies (IACS) requirements concerning the type testing of
reciprocating internal combustion engines (hereinafter referred to as engines), operating on liquid, gas or dual fuel.
1.1.2 The requirements of this test specification apply to complete engines including the control system, all ancillary systems
and equipment referred to in the Rules that are used for operation of the engine and for which there are Rule requirements. This
includes systems for use with different fuel types. The extent of components / items that will need to be tested together with the
bare engine will depend on the specific design of the engine, its control system and the fuel(s) used and may include, but not be
limited to, the following:
(a) Turbocharger(s)
(b) Crank case explosion relief devices
(c) Oil mist detection and alarm devices
(d) Piping
(e) Electronic monitoring and control system(s) – software and hardware (note that the type test requirements for electrical and
control equipment are located in test specification No. 1)
(f) Fuel management system (where dual fuel arrangements are fitted)
(g) Engine driven pumps
(h) Engine mounted filters
(i) Other safety systems necessary for the engine type (may be linked to the fuel(s) used)
1.2 Scope
1.2.1 This Specification covers engines for marine and offshore applications and separates engines into three categories
defined by engine operating speed:
(a) Low-Speed Engines - rated speed of less than 300 rpm.
(b) Medium-Speed Engines - rated speed of 300 rpm and above, but less than 1400 rpm.
(c) High-Speed Engines - rated speed of 1400 rpm or above.
1.2.2 The type testing, documented in this test specification, is to be arranged to represent typical foreseen service load
profiles, as specified by the engine builder, as well as to cover for required margins due to fatigue scatter and reasonably foreseen
in-service deterioration.
1.2.3 This applies to:
(a) Parts subjected to high cycle fatigue (HCF) such as connecting rods, cams, rollers and spring tuned dampers where higher
stresses may be provided by means of elevated injection pressure, cylinder maximum pressure, etc.
(b) Parts subjected to low cycle fatigue (LCF) such as “hot” parts when load profiles such as idle - full load - idle (with steep
ramps) are frequently used.
(c) Operation of the engine at limits as defined by its specified alarm system, such as running at maximum permissible power
with the lowest permissible oil pressure and/or highest permissible oil inlet temperature.
1.2.4 Engines for emergency use shall be approved in accordance with the general type test requirements (see Ch 2, 1 Type
Testing of Engines) together with the enhanced requirements for emergency engines (see Ch 2, 2.1 Type testing of engines
designated for emergency use).
1.2.5 Engines for auxiliary power generation shall be approved in accordance with the general type test requirements (see Ch
2, 1 Type Testing of Engines). The test programme may be modified by agreement with LR.
Lloyd's Register 5
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
1.2.6 Lifeboat and rescue boat engines will be approved in accordance with the appropriate IMO requirements (see Ch 2, 2.3
Type testing of engines used as lifeboat engines and outboard motors used for rescue boats). All other engines are to be tested as
required by Ch 2, 1 Type Testing of Engines, except small engines used for general duties where a simplified approach has been
agreed between LR and the manufacturer (see Ch 2, 2.2 Type testing of high speed engines used for general duties).
1.2.7 Engines to be approved for industrial applications shall be tested to a procedure agreed with LR.
6 Lloyd's Register
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
1.3.4 If an engine has been design approved, and internal testing per Stage A (see Ch 2, 1.2 Stage A – Internal tests) is
documented to a rating higher than the one type tested, the Type Approval may be extended to the increased power/mep/rpm
upon submission of an Extended Delivery Test Report at:
(a) Test at over speed (only if nominal speed has increased)
(b) Rated power, i.e. 100% output at 100% torque and 100% speed corresponding to load point 1, 2 measurements with one
running hour in between
(c) Maximum permissible torque (normally 110%) at 100% speed corresponding to load point 3 or maximum permissible power
(normally 110%) and speed according to nominal propeller curve corresponding to load point 3a, ½ hour
(d) 100% power at maximum permissible speed corresponding to load point 2, ½ hour
1.4 Safety
1.4.1 In the first instance it shall be the responsibility of the provider(s) of the test facility to ensure adequate measures are
taken to safeguard all personnel from health and safety risks at all points of observation and means of access. However, where the
manufacturer/licensor has appointed a third party to provide the test facility, he shall be responsible for ensuring that the appointed
third party is notified of, and has acknowledged, the following:
(a) Details of personnel invited to witness, or participate otherwise, during the test.
(b) The requirement to ensure the safety of personnel referred to above.
1.4.2 Before any testing is carried out, all relevant equipment for the safety of attending personnel is to be made available by
the manufacturer/shipyard and is to be operational; its correct functioning is to be verified. This applies especially to crankcase
explosion relief valves, overspeed protection and any other safety shutdown function.
1.4.3 Where fitted, inspection of jacketing of high-pressure fuel oil lines and proper screening of pipe and interlock test of
turning gear are to be carried out before testing.
1.4.4 Interlock test of turning gear is to be performed when installed.
1.4.5 For gas engines, measures to verify that gas fuel piping on engine is gastight are to be carried out prior to start-up of the
engine.
Lloyd's Register 7
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
1.7.3 Indicated Power: The power developed in the working cylinders as a result of measured gas pressure acting on the
pistons.
1.7.4 Brake Power: The power measured at the driving shaft of the engine.
1.7.5 Rated Output: The output corresponding to that declared by the manufacturer/licensor and agreed by LR, i.e., the
actual maximum power which the engine is capable of continuously delivering between the normal maintenance intervals stated by
the manufacturer/licensor at the rated speed and under the stated ambient conditions.
8 Lloyd's Register
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
Contents Chapter 2
Lloyd's Register 9
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
Section
1 Type Testing of Engines
n Section 1
Type Testing of Engines
1.1 General requirements for engine testing
1.1.1 Type testing is required for every new engine type intended for installation on board ships subject to classification.
1.1.2 A type test carried out for a particular type of engine at any place of manufacture will be accepted for all engines of the
same type built by licensees or the licensor, subject to each place of manufacture being found to be acceptable to LR.
1.1.3 The range of fuels suitable for the engine is to be stated by the manufacturer/licensor. The details of all fuels and
mixtures of fuels that are used during the type test are to be recorded and included in the report.
1.1.4 The type testing is divided into three stages as detailed in Ch 2, 1.2 Stage A – Internal tests to Ch 2, 1.4 Stage C –
Component inspection.
1.1.5 The complete type testing programme is subject to approval by LR. The extent of the Surveyor’s attendance is to be
agreed in each case, but at least during stages B and C. Testing prior to the witnessed type testing (stages B and C) is also
considered as a part of the complete type testing programme.
1.1.6 Upon completion of complete type testing (stage A through stage C), a type test report is to be submitted to LR for
review. The type test report is to contain:
(a) overall description of tests performed during stage A. Records are to be kept by the builders QA management for
presentation to LR;
(b) detailed description of the load and functional tests conducted during stage B;
(c) inspection results from stage C.
1.1.7 In addition to the three stage type testing, an integration test demonstrating that the response of the complete
mechanical, hydraulic and electronic system is as predicted shall be carried out for acceptance of any sub- systems (Turbo
Charger, Engine Control System, Dual Fuel, Exhaust Gas treatment…) separately approved. The scope of these tests shall be
proposed by the designer/licensor taking into account any impact on the engine.
1.1.8 During all testing the ambient conditions shall be recorded (see Ch 1, 1.5 Ambient conditions).
1.1.9 As a minimum the following engine data are to be measured and recorded during internal tests and at each load point of
the witnessed tests:
(a) External cooling water temperature.
(b) Engine revolutions per minute.
(c) Brake power.
(d) Torque.
(e) Maximum combustion pressure for each cylinder (see Note 1).
(f) Mean indicated pressure for each cylinder (see Note 1).
(g) Exhaust smoke (with an approved smoke meter).
(h) Fuel and lubricating oil pressure and temperature.
(i) Exhaust gas temperature in exhaust manifold and, where facilities are available, from each cylinder.
(j) Fuel rack position or similar parameter related to engine load.
(k) Charging air pressure and temperature
(l) For the turbocharger, where applicable:
(i) Revolutions per minute.
(ii) Air temperature and pressures before and after turbo-blower and charge cooler.
10 Lloyd's Register
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
(iii) Exhaust gas temperature and pressures before and after the turbine.
(iv) Cooling water inlet temperature to the charge air cooler.
(m) All engine parameters that are required for control and monitoring for the intended use (propulsion, auxiliary, emergency).
(n) For gas engines:
(i) Each fuel index for gas and diesel as applicable (or equivalent reading).
(ii) Gas pressure and temperature at the inlet of the gas manifold.
(iii) Gas concentration in the crankcase.
(iv) Additional measurements may be required in connection with the design assessment
Note 1. For engines where the standard production cylinder heads are not designed for such measurements, a special
cylinder head made for this purpose may be used. In such a case, the measurements may be carried out as part of Stage A
and are to be properly documented. Where deemed necessary e.g. for dual fuel engines, the measurement of maximum
combustion pressure and mean indicated pressure may be carried out by indirect means, provided the reliability of the
method is documented.
Note 2.Calibration records for the instrumentation used to collect data as listed above are to be presented to, and reviewed
by, the attending Surveyor.
Note 3.Additional measurements may be required in connection with the design assessment.
1.1.10 The measurements to be included in the test report shall be made when the engine or component under test has
reached steady state operating conditions, except when transient conditions are specified.
1.1.11 The engine to be tested is to be selected from the production line and agreed by LR.
1.1.12 During testing, the engine shall be fitted with, and have operational, all ancillary systems and equipment as defined in Ch
1, 1.1 Introduction 1.1.2. Where these include stand-by units, these shall be in their normal state of readiness.
1.1.13 During testing, no additional measures, other than any required to maintain the engine at a particular operating
condition, or those normally required during operation, may be taken.
1.1.14 The test shall proceed, so far as practicable, in a continuous uninterrupted manner with any significant interruption being
recorded in the test report. Where a significant defect or malfunction becomes evident, the test shall be stopped and the cause
identified, reported to LR and rectified. The test shall then continue after agreement with LR concerning the running period for the
rectified part.
1.1.15 New engine or component types or developments of existing types are to be subjected to an agreed programme of
type testing to complement the design appraisal and review of documentation. For prototype engines, the duration and
programme of tests are to be specially agreed between the manufacturer and LR.
1.1.16 Type tests are to be conducted with the engine control systems operational in the approved configuration. Configuration
records are to be reviewed at testing to validate the approval of the control systems and are to be referenced in the type test
report.
1.1.17 A type test will be considered to cover engines of a given design for a range of cylinder numbers in a given cylinder
arrangement.
1.1.18 For engines that are to be type approved for different purposes (multi-purpose engines), and that have different
performances for each purpose, the programme and duration of test will be modified to cover the whole range of the engine
performance taking into account the most severe values.
1.1.19 Where engines incorporate electronic control systems, the test programme is to include tests and trials necessary to
verify the conclusions of the risk-based analysis required by LR Rules. This is to apply to all electronically controlled engines
regardless of the intended function of propulsion, auxiliary or emergency power purpose. The details of how the conclusions of the
risk-based analysis have been verified are to be included in the test report.
1.1.20 Where separate items are provided for speed governor and engine control system, the test report is to include details of
the manufacturer, type and approval status of each item fitted to the engine under test.
1.1.21 The type testing is to substantiate the capability of the design and its suitability for the intended operation. Special
testing such as Low Cycle Fatigue (LCF) and endurance testing will normally be conducted during stage A.
1.1.22 High speed engines for marine use are normally to be subjected to an endurance test of 100 hours at full load. Omission
or simplification of the type test may be considered for the type approval of engines with long service experience from non-marine
Lloyd's Register 11
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
fields or for the extension of type approval of engines of a well-known type, in excess of the limits given in Ch 1, 1.3 Definition of
engine type 1.3.2.
Propulsion engines for high speed vessels that may be used for frequent load changes from idle to full are normally to be tested
with at least 500 cycles (idle - full load - idle) using the steepest load ramp that the control system (or operation manual if not
automatically controlled) permits. The duration at each end is to be sufficient for reaching stable temperatures of the hot parts.
1.1.23 In addition to the above, for gas engines, testing needs to be carried out in gas mode at the different percentages of the
maximum power available in gas mode. The maximum continuous power that a Dual Fuel (DF) engine can develop in gas mode
may be lower than the approved MCR of the engine (i.e. in oil fuel mode), depending on the gas quality in particular. This maximum
power available in gas mode and the corresponding conditions shall be stated by the engine manufacturer and demonstrated
during the type test.
The 110 per cent load tests are not required in the gas mode. The influence of the methane number and Lower Heating Value
(LHV) of the fuel gas is not required to be verified during the Stage B type tests. It shall however be justified by the engine designer
through internal tests or calculations and documented in the type approval test report. Methane number is a measure of resistance
of a gas fuel to knock, which is assigned to a test fuel based upon operation in knock testing unit at the same standard knock
intensity. LHV means the amount of heat produced from the complete combustion of a specific amount of fuel, excluding latent
heat of vaporisation of water.
12 Lloyd's Register
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
Lloyd's Register 13
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
Marine and Offshore Engines Chapter 2
Section 1
Overload power
110 106.6
110 3 3a 100
Rated power
(continuous power)
100 3 90
1 2
Power (%)
90 4
80
80 0%
= 1 0 0%
10 5 9 70
ue 6
orq ep =
t m
70 b
2
rve
60
cur
elle
60
rop
lp
50
na
mi
50 7 1
no
10
40
40
30 30
8 11
100 103.2
Speed (%)
Figure 2.1.1 Type Test Load Points (taken from IACS UR M71)
1.3.6 Operation with damaged turbocharger: For 2-stroke propulsion engines, the achievable continuous output is to be
determined in the case of turbocharger damage. Engines intended for single propulsion with a fixed pitch propeller are to be able
to run continuously at a speed (r.p.m.) of 40 per cent of full speed along the theoretical propeller curve when one turbocharger is
out of operation. (The test can be performed by either by-passing the turbocharger, fixing the turbocharger rotor shaft or removing
the rotor).
14 Lloyd's Register
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
Marine and Offshore Engines Chapter 2
Section 1
1.3.7 Gas engines are to undergo the tests given in the above requirements in this Section.
1.3.8 For DF engines, all load points must be run in both gas and diesel modes that apply to the engine type as defined by
the engine designer (see Ch 2, 1.1 General requirements for engine testing 1.1.23). This also applies to the overspeed test.
1.3.9 In the case of DF engines with variable liquid / gas ratio, the load tests are to be carried out at different ratios between
the minimum and the maximum allowable values.
1.3.10 Functional tests are to be carried out to determine or verify the following:
(a) Lowest engine speed according to the nominal propeller curve (during this test, no alarm shall occur).
(b) Starting and, where applicable, reversing to determine minimum air pressure and consumption for a start.
(c) Function and activation point of overspeed and low lubricating oil pressure protection and alarm devices.
(d) Engine running when inclined at ± 22,5 transversely and ±10° longitudinally. If not function-tested, this is to be demonstrated
to LR’s satisfaction.
(e) Function of engine governors (compliance with LR Rules and Regulations for the Classification of Ships Pt 5, Ch 2, 7 Control
and monitoring of main, auxiliary and emergency engines, see Notes 1 and 2
(f) In addition to the functional tests given in the above, for gas engines, the following tests are to be carried out:
(i) For DF engines, the lowest specified speed is to be verified in diesel mode and gas mode.
(ii) For DF engines, switch over between gas and diesel modes is to be tested at different loads.
(iii) The efficiency of the ventilation arrangement of the double walled gas piping system is to be verified.
(iv) Simulation of a gas leakage in way of a cylinder gas supply valve.
Note 1. Applicable criteria for overspeed protective device performance may be found in LR Rules.
Note 2.For engines driving electric generator sets, additional governor tests may also be carried out to demonstrate
compliance with LR Rules.
1.3.11 During the test, samples of the fuel(s) are to be taken from the fuel supply line. These are to be analysed and the
following characteristics reported:
For liquid fuels:
(a) Net calorific value.
(b) Density.
(c) Viscosity (with corresponding temperature).
(d) Water content.
(e) Sulphur content.
For Gas fuels:
(a) Net calorific value.
(b) Supply temperature and pressure as applicable.
Note Lubricating oil characteristics are to be verified with respect to those recommended by the engine manufacturer/licensor for
normal operation.
1.3.12 Gas engines intended to produce electrical power are to be tested as follows:
(a) Capability to take sudden load and loss of load in accordance with the provisions of LR Rules and Regulations for the
Classification of Ships Pt 5, Ch 2, 7 Control and monitoring of main, auxiliary and emergency engines.
(b) For gas fuel only (GF) and premixed engines, the influences of LHV, methane number and ambient conditions on the dynamic
load response test results are to be theoretically determined and specified in the test report. Referring to the limitations as
specified in LR Rules and Regulations for the Classification of Ships Pt 5, Ch 2, 15.4 Design requirements, the margin for
satisfying dynamic load response is to be determined.
Note 1. For DF engines, switchover to oil fuel during the test is acceptable.
Note 2. Application of load is stated in LR Rules and Regulations for the Classification of Ships Pt 5, Ch 2, 7 Control and
monitoring of main, auxiliary and emergency engines.
1.3.13 Integration test: For electronically controlled engines, integration tests are to verify that the response of the complete
mechanical, hydraulic and electronic system is as predicted for all intended operational modes. The scope of these tests is to be
Lloyd's Register 15
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
Marine and Offshore Engines Chapter 2
Section 2
agreed with LR for selected cases based on the engine control system’s risk-based analysis, as required in LR Rules and
Regulations for the Classification of Ships Pt 5, Ch 2, 4.2 Risk-based analysis.
1.3.14 Gas engines are to undergo integration tests to verify that the response of the complete mechanical, hydraulic and
electronic engine system is as predicted for all intended operational modes. The scope of these tests is to be agreed with LR for
selected cases based on the risk analysis required in LR Rules and Regulations for the Classification of Ships Pt 5, Ch 2, 15.3 Risk
analysis, and shall at least include the following incidents:
(a) Failure of ignition (spark ignition or pilot injection systems), both for one cylinder unit and common system failure;
(b) Failure of a cylinder gas supply valve;
(c) Failure of the combustion (to be detected by e.g. misfiring, knocking, exhaust temperature deviation, etc.);
(d) Abnormal gas pressure;
(e) Abnormal gas temperature; this test may be carried out using a simulation signal of the temperature.
1.3.15 Fire protection measures: Verification of compliance with requirements for jacketing of high-pressure fuel oil lines,
screening of pipe connections in piping containing flammable liquids and insulation of hot surfaces:
(a) The engine is to be inspected for jacketing of high-pressure fuel oil lines, including the system for the detection of leakage,
and proper screening of pipe connections in piping containing flammable liquids.
(b) Proper insulation of hot surfaces is to be verified while running the engine at 100 per cent load, or alternatively at the overload
approved for intermittent use. Readings of surface temperatures are to be done by use of Infrared Thermoscanning
Equipment. Equivalent measurement equipment may be used when so approved by LR. Readings obtained are to be
randomly verified by use of contact thermometers.
n Section 2
Type Testing of Engines for Specific Applications
2.1 Type testing of engines designated for emergency use
2.1.1 The requirements of this Section apply in addition to the requirements of Section 1.
16 Lloyd's Register
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
Marine and Offshore Engines Chapter 2
Section 2
2.1.2 Engines for emergency power generation are to be tested as a complete unit with generator and other auxiliary
components attached.
2.1.3 Cold starting performance is to be tested in accordance with the test regime set out in MSC.81(70), Sections 6.10.2 to
6.10.4 but at a temperature of 0°C.
2.1.4 The stored energy capacity of the automatic starting arrangements is to be tested by repeated starting of the engine.
Both the main and auxiliary starting arrangements are to be capable of a minimum of three consecutive starts. (The secondary
source of energy must be capable of three starts within 30 minutes).
2.1.5 Emergency engines are to operate with the vessel at an athwart ships inclination of 22,5° and fore-and-aft inclination of
10°. Where facilities are not available to test this, documented design features that ensure correct operation of the engine under
these conditions may be accepted by LR on a case-by-case basis. Note that engines may be installed athwart ships as well as
fore-and-aft.
2.2 Type testing of high speed engines used for general duties
2.2.1 Engines with a cylinder bore of less than 250mm and a power output of 110kW or lower that are to be used for general
duties may be permitted to follow a simplified test regime as agreed between LR and the manufacturer. The manufacturer is to
submit a test programme for approval, as a minimum this should include, but is not necessarily limited to, the provisions laid out
below.
2.2.2 Engine speed governor test
(a) The engine is to be adjusted to 100 per cent of the rated power and 100 per cent of the rated speed and its speed is to be
kept stable.
(b) The load is to be suddenly removed allowing the speed of the engine to rise to the maximum allowed by the governor.
(c) The speed value at this moment is to be recorded. It should be <1,15 times full speed. Evaluation of the test is to be made.
2.2.3 Lubricating oil system failure alarm test
(a) During the operating of the engine, a short-time failure of the lubricating oil pressure is to be artificially imposed, namely the oil
pressure is to be lowered sufficiently to give an alarm.
(b) The lubricating oil pressure at alarm should be >1,0 bar (15 psi); it is to be recorded and an evaluation is to be made.
2.2.4 Minimum engine speed test
(a) The engine is to be set to a reliable idling speed and run for 5 minutes.
(b) The idling speed is to be recorded and an evaluation is to be made.
2.2.5 Engine load test
(a) Running tests are to be conducted according to Ch 2, 1.3 Stage B – Witnessed testing.
(b) Engine cooling water temperature at inlet to the engine should be adjusted to 27°C (80,6 °F) and the engine run for 30
minutes at full load. The engine should show no signs of overheating.
(c) During the full load tests, fuel and lubricating oil specifications are to be recorded (to include multiple fuels as applicable).
(d) Measurements recorded during the test programme shall include, as found relevant, those listed in Ch 2, 1.1 General
requirements for engine testing 1.1.8 and Ch 2, 1.1 General requirements for engine testing 1.1.9.
(e) The test result is to be recorded and an evaluation is to be made.
2.3 Type testing of engines used as lifeboat engines and outboard motors used for rescue boats
2.3.1 Engines for these purposes may be submitted for approval against the applicable requirements of the IMO test
procedure set out in the following Sections of Resolution MSC.81(70).
2.3.2 Lifeboat testing requirements
(a) Operational testing for all lifeboats – IMO Resolution MSC.81(70) Part 1, Section 6.10.
(b) Additional testing for totally enclosed self-righting lifeboats – IMO Resolution MSC.81(70) Part 1, Section 6.10.
(c) Operational testing for outboard rescue boat engines – IMO Resolution MSC.81(70) Part 1, Section 7.7.
2.3.3 EMI test
(a) The radio communication equipment used in or with lifeboats is to be made operational and adjusted to the fixed
communication frequency and frequency channel.
(b) Test of transmitting and receiving dispatches is to be carried out during engine running.
Lloyd's Register 17
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
Marine and Offshore Engines Chapter 2
Section 2
(c) The test result is to be recorded and an evaluation of the test is to be made.
2.3.4 Minimum engine speed test
(a) The engine is to be set to a reliable idling speed and the engine run for 5 minutes. Due allowance should be made for the
propeller being submerged.
(b) The idling speed is to be recorded and an evaluation is to be made.
2.3.5 Engine load test. As per Ch 2, 2.2 Type testing of high speed engines used for general duties 2.2.5 of the test
programme for small diesel engines used for general duties.
2.3.6 Additional tests for small diesel engines for totally enclosed lifeboats
(a) Water ingress test.
(b) Water shall be excluded from the engine during capsize and return. Note that water can ingress via the air intake, or
crankcase breather, or other opening.
Note The tests in Ch 2, 2.3 Type testing of engines used as lifeboat engines and outboard motors used for rescue boats
2.3.3 to Ch 2, 2.3 Type testing of engines used as lifeboat engines and outboard motors used for rescue boats 2.3.6 are
not required by the IMO requirements. However, they are considered to be valued tests. Past test results may be accepted.
18 Lloyd's Register
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
Contents Chapter 3
Lloyd's Register 19
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
Section
1 Type testing of turbochargers
n Section 1
Type testing of turbochargers
1.1 Scope
1.1.1 This test specification is applicable to all category B and C turbochargers unless otherwise agreed with LR.
Turbocharger categories are defined in Lloyd’s Register Rules and Regulations for the Classification of Ships, Part 5, Chapter 2,
12.1.2. Those turbochargers that are integral to the engine design should be tested as below in conjunction with the engine type
test.
1.1.2 For a generic range of turbochargers the type testing may either be carried out on an engine (for which the turbocharger
is foreseen) or in a test rig.
1.1.3 LR reserves the right to limit the duration of validity of approval of a mass produced turbo-charger. LR is to be informed,
without delay, of any change in the design of the turbo-charger, in the manufacturing or control processes, in the selection of
materials or in the list of subcontractors for main parts.
20 Lloyd's Register
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
1.4 Containment
1.4.1 In the event of any rotor burst, the turbocharger casing is to fully contain all debris and no part may penetrate the casing
of the turbocharger or escape through the air intake. For documentation purposes (test/calculation) the worst case scenario for
disk disintegration is to be considered.
1.4.2 For category B and C turbochargers containment is to be demonstrated by testing which is to be fully documented. For
approval of a generic range of turbochargers, subject to satisfactory performance, only the largest unit is required to be tested. In
any case, it must be demonstrated (e.g., by calculation) that the selected test unit is representative for the whole generic range.
1.4.3 The minimum test speeds for rotor burst testing is to be the same as those required for the overspeed test specified in
the Rules and Regulations for the Classification of Ships, Pt 5, Ch 2, 12.3 Certification 12.3.1 , relative to the maximum permissible
operating speed, are:
(a) for the compressor: 120%
(b) for the turbine: 140% or the natural burst speed, whichever is lower
1.4.4 Containment tests are to be performed at working temperature.
1.4.5 Calculations using a simulation model and numerical analysis to demonstrate the required containment may be
accepted in lieu of the practical containment test, provided that:
(a) The numerical simulation model has been validated and its suitability/accuracy has been proven by direct comparison
between calculation results and the practical containment test for a reference application (reference containment test). This
test is to be performed at least once by the manufacturer for acceptance of the numerical simulation method in lieu of tests.
(b) The corresponding numerical simulation for the containment is performed for the same speeds as specified for the
containment test.
(c) Material properties for high-speed deformations are to be applied in the numeric simulation. The correlation between normal
properties and the properties at the pertinent deformation speed are to be substantiated.
(d) The design of the turbocharger regarding geometry and kinematics is similar to the turbocharger that was used for the
reference containment test. In general, totally new designs will call for a new reference containment test.
n Section 2
Type Testing of Crankcase Explosion Relief Valves
2.1 Scope
2.1.1 This test specification is applicable to all crankcase explosion relief valves intended to be fitted to engines and gear
cases except where Ch 3, 2.1 Scope 2.1.2 applies or otherwise agreed with LR.
2.1.2 The test procedure is only applicable to crankcase explosion relief valves fitted with flame arresters. Where internal oil
wetting of a flame arrester is a design feature of an explosion relief valve, alternative testing arrangements that demonstrate
compliance with these requirements may be proposed by the manufacturer. The alternative testing arrangements are to be
submitted to LR for approval.
2.2 Purpose
2.2.1 The purpose of type testing crankcase explosion relief valves is to:
(a) verify the effectiveness of the flame arrester.
(b) verify that the valve closes after an explosion.
(c) verify that the valve is gas/airtight after an explosion.
(d) establish the level of overpressure protection provided by the valve.
Lloyd's Register 21
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
(c) The test facilities are to be equipped so that they can perform and record explosion testing in accordance with this
procedure.
(d) The test facilities are to have equipment for controlling and measuring a methane gas in air concentration within a test vessel
to an accuracy of ± 0,1 per cent.
(e) The test facilities are to be capable of effective point located ignition of a methane gas in air mixture.
(f) The pressure measuring equipment is to be capable of measuring the pressure in the test vessel in at least two positions, one
at the valve and the other at the test vessel’s centre. The measuring arrangements are to be capable of measuring and
recording the pressure changes throughout an explosion test at a frequency recognising the speed of events during an
explosion. The result of each test is to be documented by video recording and by recording with a heat-sensitive camera.
(g) The test vessel for explosion testing is to have documented dimensions. The dimensions are to be such that the vessel is not
pipe-like with the distance between dished ends being not more than 2,5 times the diameter. The internal volume of the test
vessel is to include any standpipe arrangements.
(h) The test vessel is to be provided with a flange, located centrally at one end at 90 degrees to the vessel longitudinal axis for
mounting the crankcase explosion relief valve. The test vessel is to be arranged in an orientation consistent with how the
valve will be installed in service, i.e., in the vertical plane or the horizontal plane.
(i) A circular flat plate is to be provided for fitting between the pressure vessel flange and valve to be tested with the following
dimensions:
(i) Outside diameter of 2 times the outer diameter of the valve top cover.
(ii) Internal bore having the same internal diameter as the valve to be tested.
(j) The test vessel is to have connections for measuring the methane in air mixture at the top and bottom.
(k) The test vessel is to be provided with a means of fitting an ignition source at a position as specified in Ch 3, 2.4 Explosion
test process 2.4.3.
(l) The test vessel’s volume is to be as far as practicable, related to the size and capability of the relief valve to be tested. In
general, the volume is to correspond to the LR Rule requirement for the free area of the explosion relief valve to be not less
than 115 cm2/m3 of the crankcase gross volume, e.g., the testing of a valve having 1150 cm2 of free area, would require a
test vessel with a volume of 10 m3.
The following is to apply:
(a) Where the free area of relief valves is greater than 115 cm2/m3 of the crankcase gross volume, the volume of the test vessel
is to be consistent with the design ratio.
(b) In no case is the volume of the test vessel to vary by more than ±15 per cent from the design cm2/m3 volume ratio.
22 Lloyd's Register
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
2.5.4 The type testing of valves is to recognise the orientation in which they are intended to be installed on the engine or gear
case. Three valves of each size are to be tested for each intended installation orientation, i.e., in the vertical and/or horizontal
positions.
2.6 Method
2.6.1 The following requirements are to be satisfied at explosion testing:
(a) The explosion testing is to be witnessed by an LR Surveyor.
(b) Where valves are to be installed on an engine or gear case with shielding arrangements to deflect the emission of explosion
combustion products, the valves are to be tested with the shielding arrangements fitted.
(c) Successive explosion testing to establish a valve’s functionality is to be carried out as quickly as possible during stable
weather conditions.
(d) The pressure rise and decay during all explosion testing are to be recorded.
(e) The external condition of the valves is to be monitored during each test for indication of any flame release by video and heat-
sensitive camera.
2.6.2 The explosion testing is to be carried out in three stages for each valve that is required to be approved as being type
tested.
2.6.3 Stage 1: Two explosion tests are to be carried out in the test vessel with the circular plate as specified in Ch 3, 2.3 Test
facilities 2.3.1.(i) fitted and the opening in the plate covered by a 0,05 mm thick polythene film. These tests establish a reference
pressure level for determination of the capability of a relief valve in terms of pressure rise in the test vessel, see Ch 3, 2.7
Assessment and records 2.7.1.(f).
2.6.4 Stage 2:
(a) Two explosion tests are to be carried out on three different valves of the same size. Each valve is to be mounted in the
orientation for which approval is sought i.e., in the vertical or horizontal position with the circular plate described in Ch 3, 2.3
Test facilities 2.3.1.(i) located between the valve and pressure vessel mounting flange.
(b) The first of the two tests on each valve is to be carried out with a 0,05 mm thick polythene bag, having a minimum diameter
of three times the diameter of the circular plate and volume not less than 30 per cent of the test vessel, enclosing the valve
and circular plate. Before carrying out the explosion test the polythene bag is to be empty of air. The polythene bag is
required to provide a readily visible means of assessing whether there is flame transmission through the relief valve following
an explosion. During the test, the explosion pressure will open the valve and some unburned methane/air mixture will be
collected in the polythene bag. When the flame reaches the flame arrester and if there is flame transmission through the flame
arrester, the methane/air mixture in the bag will be ignited and this will be visible.
(c) Provided that the first explosion test successfully demonstrated that there was no indication of combustion outside the flame
arrester and there are no signs of damage to the flame arrester or valve, a second explosion test without the polythene bag
arrangement is to be carried out as quickly as possible after the first test. During the second explosion test, the valve is to be
visually monitored for any indication of combustion outside the flame arrester and video records are to be kept for
subsequent analysis. The second test is required to demonstrate that the valve can still function in the event of a secondary
crankcase explosion.
(d) After each explosion, the test vessel is to be maintained in the closed condition for at least 10 seconds to enable the
tightness of the valve to be ascertained. The tightness of the valve can be verified during the test from the pressure/time
records or by a separate test after completing the second explosion test.
2.6.5 Stage 3: Carry out two further explosion tests as described in Stage 1. These further tests are required to provide an
average baseline value for assessment of pressure rise, recognising that the test vessel’s ambient conditions may have changed
during the testing of the explosion relief valves in Stage 2.
Lloyd's Register 23
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
(e) The pressure rise and decay during an explosion are to be recorded, with indication of the pressure variation showing the
maximum overpressure and steady under-pressure in the test vessel during testing. The pressure variation is to be recorded
at two points in the test vessel.
(f) The effect of an explosion relief valve in terms of pressure rise following an explosion is ascertained from maximum pressures
recorded at the centre of the test vessel during the three stages. The pressure rise within the test vessel due to the installation
of a relief valve is the difference between average pressure of the four explosions from Stages 1 and 3 and the average of the
first tests on the three valves in Stage 2. The pressure rise is not to exceed the limit specified by the manufacturer.
(g) The valve tightness is to be ascertained by verifying from the records at the time of testing that an under-pressure of at least
0,3 bar is held by the test vessel for at least 10 seconds following an explosion. This test is to verify that the valve has
effectively closed and is reasonably gastight following dynamic operation during an explosion.
(h) After each explosion test in Stage 2, the external condition of the flame arrester is to be examined for signs of serious
damage and/or deformation that may affect the operation of the valve.
(i) After completing the explosion tests, the valves are to be dismantled and the condition of all components ascertained and
documented. In particular, any indication of valve sticking or uneven opening that may affect the operation of the valve is to
be noted. Photographic records of the valve condition are to be taken and included in the report.
where
n1 = total depth of flame arrester corresponding to the number of lamellas of size 1 quenching device for a
valve with a relief area equal to S1
n2 = total depth of flame arrester corresponding to the number of lamellas of size 2 quenching device for a
valve with a relief area equal to S2
A1 = free area of quenching device for a valve with a relief area equal to S1
A2 = free area of quenching device for a valve with a relief area equal to S2.
2.8.3 The qualification of explosion relief valves of larger sizes than that which has been previously satisfactorily tested in
accordance with Ch 3, 2.6 Method and Ch 3, 2.7 Assessment and records can be evaluated where valves are of identical type
and have identical features of construction subject to the following:
(a) The free area of a larger valve does not exceed three times +5 per cent that of the valve that has been satisfactorily tested.
(b) One valve of the largest size, subject to (a), requiring qualification is subject to satisfactory testing required by Ch 3, 2.6
Method 2.6.1.(c) and Ch 3, 2.6 Method 2.6.1.(d) except that a single valve will be accepted in Ch 3, 2.6 Method 2.6.1.(a)
and the volume of the test vessel is not to be less than one third of the volume required by Ch 3, 2.3 Test facilities 2.3.1.(l).
(c) The assessment and records are to be in accordance with Ch 3, 2.7 Assessment and records, noting that Ch 3, 2.7
Assessment and records 2.7.1.(f) will only be applicable to Stage 2 for a single valve.
2.8.4 The qualification of explosion relief valves of smaller sizes than that which has been previously satisfactorily tested in
accordance with Ch 3, 2.6 Method and Ch 3, 2.7 Assessment and records can be evaluated where valves are of identical type
and have identical features of construction subject to the following:
(a) The free area of a smaller valve is not less than one third of that of the valve that has been satisfactorily tested.
(b) One valve of the smallest size, subject to (a), requiring qualification is subject to satisfactory testing required by Ch 3, 2.6
Method 2.6.1.(c) and Ch 3, 2.6 Method 2.6.1.(d) except that a single valve will be accepted in Ch 3, 2.6 Method 2.6.1.(a)
and the volume of the test vessel is not to be more than the volume required by Ch 3, 2.3 Test facilities 2.3.1.(l).
24 Lloyd's Register
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
Ancillary Equipment Chapter 3
Section 3
(c) The assessment and records are to be in accordance with Ch 3, 2.7 Assessment and records, noting that Ch 3, 2.7
Assessment and records 2.7.1.(f) will only be applicable to Stage 2 for a single valve.
n Section 3
Type Testing of Crankcase Oil Mist Detection and Alarm Equipment
3.1 Scope
3.1.1 This test specification is applicable to all crankcase oil mist detection and alarm equipment intended to be fitted on
engines unless otherwise agreed with LR. Note that the type test requirements for electrical and control equipment are located in
test specification No. 1.
3.1.2 This test procedure is also applicable to oil mist detection and alarm arrangements intended for gear cases.
3.2 Purpose
3.2.1 The purpose of type testing crankcase oil mist detection and alarm equipment is to verify:
(a) the functionality of the system.
(b) the effectiveness of the oil mist detectors.
(c) the accuracy of oil mist detectors.
(d) the alarm set points.
(e) time delays between oil mist leaving the source and alarm activation.
(f) functional failure detection.
(g) the influence of optical obscuration on detection.
Lloyd's Register 25
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
Ancillary Equipment Chapter 3
Section 3
26 Lloyd's Register
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
Ancillary Equipment Chapter 3
Section 3
or spray conditions. Testing is to be in accordance with arrangements proposed by the manufacturer and agreed by LR. The
temperature, quantity and angle of impact of the oil to be used is to be declared and their selection justified by the manufacturer.
3.5.9 Detector equipment may be exposed to water vapour from the crankcase atmosphere which may affect the sensitivity
of the equipment; it is to be demonstrated that exposure to such conditions will not affect the functional operation of the detector
equipment. Where exposure to water vapour and/or water condensation has been identified as a possible source of equipment
malfunctioning, testing is to demonstrate that any mitigating arrangements such as heating are effective. Testing is to be in
accordance with arrangements proposed by the manufacturer and agreed by LR. This testing is in addition to that required by Ch
3, 3.4 Equipment testing 3.4.2.(e) and is concerned with the effects of condensation caused by the detection equipment being at
a lower temperature than the crankcase atmosphere.
3.5.10 The ability of the detector equipment to sense the presence of oil mist may be adversely affected by obscuration of the
sensing device(s), such as partial obscuration of a lens. It should be shown that any such degradation is detected and an
indication is given.
3.7 Method
3.7.1 Oil mist generation is to satisfy the following:
(a) The ambient temperature in and around the test chamber is to be at the standard atmospheric conditions defined in the
Rules and Regulations for the Classification of Ships, Pt 6, Ch 2, 1.9 Ambient reference and operating conditions before any
test run is started.
(b) Oil mist is to be generated with suitable equipment using an SAE 40 monograde mineral oil or an equivalent acceptable to LR
and supplied to a test chamber. The selection of the oil to be used is to take into consideration risks to health and safety, and
the appropriate controls implemented. A low toxicity, low flammability oil of similar viscosity may be used as an alternative.
The oil mist produced is to have an average (or arithmetic mean) droplet size not exceeding 5 μm. The oil droplet size is to be
checked using the sedimentation method or an equivalent method to a relevant international or national standard. If the
sedimentation method is chosen, the test chamber is to have a minimum height of 1m and volume of not less than 1m3.
Note: The calculated oil droplet size using the sedimentation method represents the average droplet size.
(c) The oil mist concentrations used are to be ascertained by the gravimetric deterministic method, or an equivalent method
acceptable to LR. For this test, the gravimetric deterministic method is a process where the difference in weight of a 0,8 µm
pore size membrane filter is ascertained from weighing the filter before and after drawing 1 litre of oil mist through the filter
from the oil mist test chamber. The oil mist chamber is to be fitted with a recirculating fan.
(d) Samples of oil mist are to be taken at regular intervals and the results plotted against the oil mist detector output. The oil mist
detector is to be located adjacent to where the oil mist samples are drawn off.
(e) The results of a gravimetric analysis are considered invalid and are to be rejected if the resultant calibration curve has an
increasing gradient with respect to the oil mist detection reading. This situation occurs when insufficient time has been
allowed for the oil mist to become homogeneous. Single results that are more than 10 per cent below the calibration curve
are to be rejected. This situation occurs when the integrity of the filter unit has been compromised and not all of the oil is
collected on the filter paper.
(f) The filters require to be weighed to a precision of 0,1 mg and the volume of air/oil mist sampled to 10 ml.
3.7.2 Oil mist detection equipment is to be tested in the orientation (vertical, horizontal or inclined) in which it is intended to be
installed on an engine or gear case as specified by the equipment manufacturer.
3.7.3 Where sensitivity levels of the oil mist detector can be adjusted, testing is to be carried out at the extreme and mid-point
level settings.
3.7.4 After completing the tests, the detection equipment is to be examined and the condition of all components ascertained
and documented. Photographic records of the monitoring equipment condition are to be taken and included in the report.
3.8 Assessment
3.8.1 Assessment of oil mist detection equipment after testing is to address the following:
(a) The equipment to be tested is to have evidence of design appraisal/approval by LR.
Lloyd's Register 27
Lloyd’s Register Type Approval System - Test Specification Number 4, December 2020
Ancillary Equipment Chapter 3
Section 3
(b) Details of the detection equipment to be tested are to be recorded and are to include:
(i) name of manufacturer;
(ii) type designation;
(iii) oil mist concentration assessment capability and alarm settings;
(iv) The maximum percentage level of lens obscuration used in Ch 3, 3.6 Detectors and alarm equipment to be tested
3.6.2.
(c) After completing the tests, the detection equipment is to be examined and the condition of all components ascertained and
documented. Photographic records of the monitoring equipment condition are to be taken and included in the report.
28 Lloyd's Register
© Lloyd’s Register Group Limited 2020
Published by Lloyd’s Register Group
Limited Registered office (Reg. no. 08126909)
71 Fenchurch Street, London, EC3M 4BS
United Kingdom