OMX 333DC Omx 333uni Omx 333Pwr: Standard Functions Operation

The OMX 333 is a family of DIN rail mountable signal converters that includes universal (UNI), DC voltage/current, power, and universal counter/frequency (UQC) models. They feature programmable analog and digital inputs and outputs, calibration, filtering, and output of measured data via RS-485. The instruments provide high accuracy measurement via a 12-bit ADC and DAC on a microcontroller chip and allow configuration via front panel buttons or PC software.

Uploaded by

Thien Nguyen Van
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
27 views2 pages

OMX 333DC Omx 333uni Omx 333Pwr: Standard Functions Operation

The OMX 333 is a family of DIN rail mountable signal converters that includes universal (UNI), DC voltage/current, power, and universal counter/frequency (UQC) models. They feature programmable analog and digital inputs and outputs, calibration, filtering, and output of measured data via RS-485. The instruments provide high accuracy measurement via a 12-bit ADC and DAC on a microcontroller chip and allow configuration via front panel buttons or PC software.

Uploaded by

Thien Nguyen Van
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

OMX 333

OMX 333
Model range OMX 333 are simple DIN rail mountable programmable signal
convertors. The range consists of UNI, DC, PWR and UQC versions.
Type OMX 333UNI is a multifunction device which allows for selection from 8
inputs easily configuralbe in the instrument‘s menu.
OMX 333DC a OMX 333PWR are versions used for measurement of higher DC
and AC voltage and current.
This instrument is based on a single-chip microcontroler with a 12bit A/D and
D/A convertor, which provides high accuracy, stability and ease of use.
Type OMX 333UQC is a universal counter/frequency meter.

 PROGRAMMABLE ISOLATED TRANSMITTERS


OMX 333DC
 MULTIFUNCTION INPUT UNI (DC, PM, RTD, T/C, DU) DC VOLTMETER AND AMMETER
 TEACH-IN, DIGITAL FILTER, TARE
OMX 333UNI OMX 333PWR
 OUTPUT: 0/4…20 mA/0…5 mA/0…2/5/10 V/±10 V AC VOLTMETER AND AMMETER
DC VOLTMETER AND AMMETER
 POWER SUPPLY 10…30 V AC/DC PROCESS MONITOR AC NETWORK ANALYSER
OHMMETR
 Option THERMOMETER PRO Pt/Cu/Ni/TC OMX 333UQC
Comparators  Data output FOR LINEAR POTENTIOMETERS UNIVERSAL COUNTER

OPERATION STANDARD FUNCTIONS

Instrument can be controlled by two push buttons and a DIP switch located on PROGRAMMABLE INPUT
the front panel. When frequent changes of settings are needed, we recomend Setting: manual, any type and range of analogue output can be assigned to any min. and
the use of OM Link interface, which in conjunction with free control SW alows for max. values of input singal
modification and storage of all instruemnt‘s settings and also for firmware upload
Setting (UQC): measuring mode counter/frequency with adjustable calibration coefficient
(using OM Ling cable) from a PC.
and time base
The above mentioned SW can also be used for visualisation and archiving of
measured values from a number of instruemnts via the RS 485 line. ANALOG OUTPUT
All instrument‘s settings are stored in the instruemnt‘s EEPROM memory (even Type: isolated, programmable with resolution of max. 12 bit, type and range of output
after power-off). selectable in the menu
Ranges: 0…2/5/10 V/±10 V, 0…5 mA/0/4…20 mA (comp. < 500 Ω)

COMPENSATION

OPTIONS of conduct (RTD, OHM): automatic (3- and 4-wire) or manual in menu (2-wire)
of conduct in probe (RTD): internal connection (conduct resistance in measuring head)
N

COMPARATORS are assigned to monitor two limit values with relay output. The of CJC (T/C): manual or automatic, in menu it is possible to perform selection of the type
limits have adjustable hysteresis within the full range of the display as well as of thermocouple and compensation of cold junctions, which is adjustable or automatic
selectable delay of the switch-on in the range of 0...99,9 s. Reaching the preset (temperature at the input brackets)
limits is signalled by LED and simultaneously by the switch-on of the relevant
LINEARIZATION
E

relay.
DATA OUTPUTS are for their rate and accuracy suitable for transmission of the Linearization: through linear interpolation in 25 points (solely via OM Link)
measured data for further projection or directly into the control systems. We offer
DIGITAL FILTERS
an isolated RS485 with the ASCII protocol.
W

Exponential average: from 2…100 measurements


Rounding: setting the projection step for display
Filtration constant (UC): transmits input signal up to 10…1 000 Hz

FUNKCE
Preset (UQC): initial non-zero value, which is always read after resetting the instrument
to zero
Tare: resetting display upon non-zero input signal

EXTERNAL CONTROL
Hold: display/instrument blocking
Lock: control keys blocking
Resetting (UC): counter resetting

60 | ORBIT MERRET ™ 2012.2 en


TECHNICAL DATA

INSTRUMENT ACCURACY DATA OUTPUT OPERATING CONDITIONS


TK: 50 ppm/°C Protocol: ASCII Connection: connector terminal board, section < 1,5/2,5 mm2
Accuracy: ±0,15 % of range + 1 digit (for 20 meas./s) Data format: 8 bit + no parity + 1 stop bit Stabilization period: within 15 minutes after switch-on
±0,3 % of range + 1 digit PWR, T/C Rate: 600…230 400 Baud Working temperature: -20°…60°C
±0,05 % of value + 1 digit UQC RS 485: isolated, addressing (max. 31 instruments) Storage temperature: -20°…85°C
Accuracy of cold junction measurement: ±1,5°C Cover: IP20
ANALOG OUTPUT
Rate: 0,5…100 meas./s El. safety: EN 61010-1, A2
Overload capacity: 10x (t < 30 ms) - not for > 200 V, 5 A; 2x Type: isolated, programmable with 12-bit D/A converter, type and range Dielectric strength: 2,5 kVAC after 1 min between supply/input/outputs
Watch-dog: reset after 20 ms are selectable in programming mode Insulation resistance: for pollution degree II, measuring cat. III.
Functions: HOLD, LOCK, Digital filters, Tare Non-linearity: 0,1 % of range power supply > 550 V (PI), 255 V (DI)
Linearization (DC, PM, DU): by linear interpolation in 25 points TC: 15 ppm/°C EMC: EN 61326-1
Functions (UQC): Preset Rate: response to change of value < 1 ms
Input filters (UQC): Filtration constant, Rounding Ranges: 0…2/5/10 V, ±10 V, 0…5 mA, 0/4…20 mA (comp. < 500 Ω/12 V)
Time base (UQC): 0,5/1/5/10/50 s Ripple: 5 mV residual ripple at output voltage of 10 V
Calibration constant (UQC): 0,01…9999 POWER SUPPLY
Filtration constant (UQC): 0/5/40/100/1000 Hz
10…30 VDC/24 VAC, ±10 %, 3 VA, PF ≥ 0,4, ISTP< 40 A/1 ms
Preset (UQC): 0…999
10…30 VDC/24 VAC, ±10 %, 3 VA, PF ≥ 0,4, ISTP< 40 A/1 ms, isolated
Measuring modes (PWR): voltage (VRMS), current (ARMS), real power (W),
frequency (Hz) and with calculation of Q, S, cos Ω MECHANIC PROPERTIES
OM Link: Company communication interface for operation, setting and Material: PA 66, incombustible UL 94 V-0, blue
update of instruments Dimensions: 90,5 x 79 x 25 mm
Calibration: at 25°C and 40 % r.h. Installation: to DIN rail 35 mm wide
COMPARATOR
Type: digital, setting in prog. mode, contact switch < 50 ms
Limits: 999999
Hysteresis: 0…9999999
Delay: 0…99,9 s
Output: 2x Form A relays (250 VAC/30 VDC, 3 A), 2x open collector

PI - Primary insulation, DI - Double insulation

MEASURING RANGES
CONNECTING INDIVIDUAL INPUTS
OMX 333 is available in these modifications and measuring ranges
OMX 333UNI INPUT 1 INPUT 2 INPUT 3 INPUT 4 INPUT 5
DC: ±90/±180 mA, ±30/±60 mV/±1/±20/±40/±80 V DC ±20/±40/±80 V ±30/60 mV/±1 V ±90/±180 mA
PM: ±5 mA/±20 mA/4…20 mA/±2 V/±5 V/±10 V PM ±2/±5/±10 V ±5/20 mA, 4…20 mA
OHM: 0…100 Ω/0…300 Ω/0…1,5 kΩ/0…3 kΩ/0…24 kΩ/0…30 kΩ T/C J/K/T/E/B/S/R/N/L
RTD: Pt 50/100/500/1 000 ±25/±50/±100 V
DC/Hi ±0,5/±1/±5 A
Cu: Cu 50/Cu 100 ±200/±400 V
Ni: Ni 1 000/10 000 PWR 0…120/450 V 0…10/250 V 0…60/300 mV 0…1/2,5/5 A
T/C: J/K/T/E/B/S/R/N/L
DU: Linear potentiometer (min. 500 Ω)

OMX 333DC ±1 A/±5 A/±25 V/±50 V/±100 V/±200 V/±400 V


OMX 333PWR 0…1 A/0…5 A, 0…60 mV/0…300 mV/0…10 V/0…120 V/0…250 V/0…450 V
OMX 333UQC 0…30 V/0…300 V, comparation levels are adjustable in the menu, range: 0,1 Hz…50 kHz
ORDER CODE SPECIFICATION

PWR - U PWR - I
K 0…60/300 mV
P 0…1/2,5/5 A
S 0…10/120 V
U 0…250/450 V

CONNECTION ORDER CODE

OMX 333 - -
Type U N I 1  
D C 1  
-
DU
+

P W R 1   
INPUT 4

GND

Order code shall not include blank spaces! U Q C   


-
T/C Power supply 10…30 V AC/DC 0
+

ES- ES+
10…30 V AC/DC, isolated 1
S- E-
S- E-
ES+
E+ S+ Measuring range, see table „Order code specification“ ?
RTD, OHM, Ni Comparators no 0
1x relay (Form A) 1
INPUT 2

INPUT 4

INPUT 5
INPUT 1

INPUT 3

2x relays (Form A) 2
EXT.1
GND

1x open collector 3
-
DC, PM 4
+
+
+
+

2x open collector
Output none 0
J K L M N O N O
analog 1
RS 485 2
Other customer version, do not fill in 00

OM Link
4

L1
3
2

L2
1

1 2 3 4 5
+
+

- -
GND
AO - current
AO - voltage

Power supply
+

-
Termination

Rx/Tx-

Rx/Tx+

485

Default execution is shown in bold

ORBIT MERRET ™ 2012.2 en | 61