Technical Requirements For Plumbing Works in Buildings (Dec 2021)
Technical Requirements For Plumbing Works in Buildings (Dec 2021)
List of Figures
- List of Symbols (2 of 2)
Fig. 35 Suspension Notice of Fresh Water Supply/ Temporary Mains Water for Flushing
Fig. 44 Schematic Piping Diagram for Improvised Hose Reel System (Direct-feed type)
December 2021 version
List of Appendix
Preface
Water Supplies Department (WSD) published two booklets in the past, viz. the Handbook on
Plumbing Installation for Buildings and the Hong Kong Waterworks Standard Requirements
for Plumbing Installation in Buildings. Together with the Waterworks Ordinance (Chapter 102)
(WWO), the Waterworks Regulation (Chapter 102A) (WWR), and the WSD Circular Letters
to Licensed Plumbers and Authorized Persons, they depict the technical requirements and
practical guidelines to be adopted in the design and construction of inside service and fire
service in local buildings. Over the years, practitioners need to cross reference among these
documents when designing and constructing plumbing installations. These documents are
now consolidated into this single document entitled ‘Technical Requirements for Plumbing
Works in Buildings’ for easy reference.
WSD would like to thank the stakeholders, industry practitioners and government departments
who have given valuable comments to this document.
-1-
December 2021 version
1. General
1.1 Definitions
1.1.1 The definitions used in this Technical Requirements, which bear the same
meanings as in WWO and WWR, are as follows:-
-2-
December 2021 version
Transitional Flow Rate Flow rate between the permanent flow rate and the minimum flow
Q2 rate that divides the flow rate range into two zones, the upper flow
rate zone and the lower flow rate zone, each characterized by its own
maximum permissible errors.
Water Authority The Director of Water Supplies
Waterworks Any property occupied, used or maintained by the Water Authority
for the purpose of water supply, including all water gathering
grounds.
-3-
December 2021 version
1.2 Abbreviations
1.2.1 Abbreviations used in this booklet are as follows:-
-4-
December 2021 version
-5-
December 2021 version
Fitting Function
Loose Jumper Type a screwdown pattern valve with horizontal inlet and outlet
Stopcock connections. It incorporates a loose jumper valve permitting flow in
one direction only. In case the supply main is shut off and drained
down for any reason, the ‘non-return’ action of the loose valve plate
will stop any backflow from the service pipe.
Non-return Valve a valve that prevents reversal of flow in the pipe of a water supply by
means of the check mechanism, the valve being opened by the flow
of water and closed by the action of the check mechanism when the
flow ceases, or by back pressure. It is also known as check valve.
Pressure Reducing Valve a valve that reduces the pressure of a fluid immediately downstream
of its position in a pipeline to a preselected value or by a
predetermined ratio.
Pressure Relief Valve a self-acting valve that automatically opens to prevent a
predetermined safe pressure being exceeded.
Temperature Relief Valve a self-acting valve that automatically opens to prevent a
predetermined safe temperature being exceeded.
Stop Valve A valve that can shut off the water flow.
-6-
December 2021 version
2. General Principles
2.1 General Principles for Installing Plumbing Works
2.1.1 A person who designs, constructs, installs, alters or removes any part of a plumbing
installation shall adhere to the following general principles for installing plumbing
works:-
*(a) all pipes and fittings shall comply with the requirements of WWO and WWR;
*(b) all plumbing works, except those works of a minor nature, shall be carried out
by a designated person;
#(c) communal service shall not run through individual premises;
#(d) plumbing installations shall be arranged to avoid water contamination, water
quality deterioration, water leakage and to ensure proper metering for water
consumption; and
#(e) inside service of individual consumer shall not pass through the premises of
another consumer.
*2.1.2 In accordance with WWO and WWR, fresh water is generally supplied for the six
main purposes, namely domestic purpose; trade purpose; shipping purpose;
construction purpose; flushing purpose; and firefighting purpose. The purpose for
water supply shall generally be related to its usage by the occupants of the premises.
-7-
December 2021 version
3. Metering
3.1 General
3.1.1 Not Used.
*3.1.2 The size, number and siting of water meters will be determined by the WA and
water meters will be provided by the WA. Water meters may be installed either by
the WA, a LP, a registered plumbing worker or a registered plumbing worker
(provisional).
#3.1.3 Meter position shall be provided by the Licensed Plumber (LP) (employed by the
applicant) for meter installation. The type of the water meter will be determined
by the WA. Recommended meter types are given in Table 3.1.3.1. All domestic
units shall be separately metered.
#3.1.5 In case the meters are sited at roof level, and system pressure is lower than 15m,
fullway gate valves shall be fitted before meter positions.
#3.1.6 For connections up to and including 40 mm diameter, a loose jumper type stopcock
shall be provided and placed with spindle in the vertical position at each meter
position on the inlet side of the meter where the meter is not sited at roof level and
where the pressure is considered adequate.
-8-
December 2021 version
#3.1.7 For connections larger than 40 mm diameter, a gate valve shall be provided before
the meter position and a non-return or check valve fitted on the delivery side as
close as possible to the meter.
#3.1.8 For single jet meter and turbine meter installed in direct supply system, a strainer
shall be installed upstream of the meter.
#3.1.9 Salt water supply will not be metered, but a meter position shall be provided for
the purpose of periodic checking of consumption. It should be close to the lot
boundary and connection to the Government mains or close to the point of
connection from internal distribution mains whichever is applicable.
#3.1.10 For salt water flushing supply, a stop valve shall be fitted at the inlet side of the
meter position and a non-return or check valve shall be fitted on the delivery side
as close as possible to the meter.
#3.1.11 Minimum meter size requirement for business in categories as shown Table
3.1.11.1 shall be followed.
Table 3.1.11.1 Minimum Meter Size Requirement for Trade Fresh Water Supply to Designated
Business Categories
Classification Code of business account Minimum Size of Meter (mm)
categories
SIC 641100 – Restaurants – Chinese 50
SIC 641998 – Restaurants – other eating places 25
SIC 641200 – Restaurants – non-Chinese
SIC 641300 – Restaurants – fast food shops
SIC 311100 – Slaughtering, preparing and
preserving meat
SIC 952000 – Laundries
#3.1.12 With an aim to prevent tampering of water meters, security seals shall be installed
for all newly installed meters of size 40mm or above. 1
1
Demonstration on installation of security seals are uploaded to the WSD webpage.
https://www.wsd.gov.hk/en/plumbing-engineering/information-for-licensed-plumbers/demo-videos-on-
installation-of-security-seals/index.html
-9-
December 2021 version
#3.2.1.2 The meter position for a 15mm diameter meter shall be constructed to include
20mm x 15mm bushes at both sides of the meter position with a clear effective
length of 200mm distance piece of 15mm tube placed in between as shown in Fig
3. The tube shall be hollow with conspicuous holes drilled through the body. A
long screw connector shall be provided immediately after the bush at the delivery
side. The meter position for meter of all sizes shall also be similarly provided with
corresponding fittings of appropriate sizes. Fig. 4 shall be referred for the length
of the distance piece.
#3.2.1.3 If a section of copper pipe is used either before or after a water meter position, the
section of copper pipe between the water meter position and the first pipe clamp
shall be jointed by screwed or flanged joints or soldering/brazing joint.
#3.2.1.4 PVC-U fittings shall be used at the meter position if PVC-U materials are used as
inside service. Brass/copper longscrew (connector) shall be used at TMF position.
Brass/copper fittings shall be used at the meter position if copper, lined galvanized
steel or thermo-plastic materials are used as inside service.
#3.2.1.5 Operational range and specifications for different type water meters currently
adopted by WSD are given in Table 3.2.1.5.5.
- 10 -
December 2021 version
Table 3.2.1.5.5 Operational range and specification of different type water meters
STRAIGHT PIPE LENGTH REQUIREMENT,
WHERE D IS THE NOMINAL BORE OF THE
SIZE
METER TYPE WATER METER
(mm)
(mm)
UPSTREAM DOWNSTREAM
50
SINGLE JET 80 5D 2D
100
50
80
100
TURBINE/WOLTMANN 150 5D 2D
200
250
300
ULTRASONIC 50 3D 2D
50
80
ELECTROMAGNETIC 3D 2D
100
150
3.2.2 Architectural and Mechanical and Electrical (M&E) Requirements for Meter
Room/Box/Cabinet/Chamber
#3.2.2.1 All water meters, including vacant meter positions and check meter positions, shall
be arranged in groups of more than one meter positions and housed in meter rooms
/ boxes / cabinet / chamber.
#3.2.2.3 No other building services such as drainage systems, fire hoses, M&E installations
(equipment, cables and ducting, etc.) shall pass through or be placed inside all
water meter room / box / cabinet / chamber and check meter position except
lighting, ventilation, drainage, and smart metering if required by the WA etc.,
- 11 -
December 2021 version
- 12 -
December 2021 version
#3.2.2.6 Standard configuration of meter box/ cabinet/ room for master meter, check meter,
sub-meter and water meter for all new developments are shown in Fig. 31, Fig. 32
and Fig. 36.
#3.2.2.7 The minimum longitudinal working clearance between both ends of meter flange
of water meter / check meter position and any obstruction should be 150 mm.
- 13 -
December 2021 version
3.2.5 Location of Water Meter at Construction Sites/ Sites for Short-Term Tenancy
#3.2.5.1 The meter position of a supply to a construction site shall be provided within a
meter room/box/cabinet located at the hoarding recess area so that reading and
maintenance of the meter can be carried out outside the construction site.
#3.2.5.2 Safe, free and uninterrupted access to the meter room/box/cabinet should be
provided and maintained at all time to ensure the safety of personnel undertaking
meter reading or maintenance adjacent to construction activities. The door of the
meter room/box/cabinet shall be made of 50mm x 50mm wire mesh. Details of the
meter room or meter box are subject to the approval of the WA. Meter dials should
be installed at the face of wire mesh for WA to conduct any necessary works related
to water meter (e.g. to inspect the meter and take meter readings).
#3.3.2.2 Subject to Clause 3.3.2.3, for single detached village type buildings and single
block buildings, master meters will not be required but all pipework between the
connection to the main and meter positions shall be exposed or laid in a proper
service trench/duct, except that branch mains of less than one straight pipe length
of 6 metres from tee-connection to a building block may be buried.
#3.3.2.3 Master meters shall be provided to fresh water and TMF inside service and fire
service in all new government premises (including developments with no building
- 14 -
December 2021 version
block and single block building), no matter the connecting water pipes are buried,
exposed or laid in service trench (applicable to all new government premises with
Form WWO 542 submitted to WSD on or after 1st January 2021).
3.3.3 Principles of Sub-meters Provision for Buried Fresh Water Inside Service and Fire
Service
3.3.3.1 Not Used.
#3.3.3.2 Sub-meter chambers with check meter positions shall be provided at underground
branch mains on a building-cluster basis except for developments with 5 or less
building blocks of the same type only. Each building-cluster shall not include more
than 5 building blocks of the same type in general. For typical configuration of
master meter and sub-meter chambers in a multiple-block development, Fig. 24
shall be referred. For details of sub-meter chambers, Fig. 25 shall be referred.
#3.3.3.3 The installation of sub-meter chambers for TMF inside service are not required.
#3.3.3.4 Construction of a separate sub-meter chamber at a branch main is not required if:-
(i) the check meter room inside a building block is located less than one straight
pipe length of 6m from the tee-connection; or
(ii) all the pipework between the tee-connection and the building block is exposed.
#3.3.4.2 The master meter room/cabinet/box shall be located at-grade where feasible.
Otherwise, full justifications for non-compliance with such requirement shall be
provided to the WA for consideration and approval.
#3.3.4.3 Standard master meter room/cabinet/box configuration for all new developments
are shown in Figs. 26 to 31.
#3.3.4.4 In general, a minimum straight pipe lengths immediately upstream and downstream
of a master meter or check meter shall be provided to ensure accuracy of master
meters and check meters.
#3.3.4.5 The upstream and downstream straight pipe length requirements for different type
- 15 -
December 2021 version
of meters shall not be less than the straight length requirement shown in Fig. 30.
#3.3.4.9 Due to omission of by-pass pipe arrangement for inside service and fire service,
master meters of diameter less than or equal to 100mm could be housed in a box
or cabinet as shown in Fig. 31. A master meter room will be required for master
meters larger than 100mm in diameter.
#3.3.4.10 If the water main is to be laid underneath private roads which is scheduled to be
handed over to government within 5 years after completion, master meters shall be
installed for each FW/TMF/FS inlet pipe supplying each group of buildings/podia
at their respective boundaries. On top of this, master meters are also required at the
estate’s boundary as illustrated in Fig. 24.
#3.3.4.11 If the handover is scheduled beyond 5 years after completion, the said master meter
positions mentioned in Clause 3.3.4.10 are still required, except the positions are
temporarily bridged over by short pieces.
#3.3.4.12 Fire service supply needs to be unaffected by potable supply interruption as far as
practicable. Fire service needs to be separated from the potable supply right at the
lot boundary.
#3.3.4.13 Architectural and M&E requirements for the master meter room shall comply with
the requirements in Sections 3.2.2.4 and 3.2.2.5. However, applicant may request
for relaxation of the requirement with justifications and flexibility may be allowed
at the discretion of the WA.
#3.3.4.15 For pressure monitoring, a pressure tapping point at the straight pipe after flange
adapter to master meters of 50mm and above shall be provided as shown in Fig. 27,
28, 31 and 43. As an alternative, pressure tapping point provided on a flange ring
after the straight pipe is also permitted. The connection details of pressure tapping
- 16 -
December 2021 version
point installed by other methods shall be provided to the WA for consideration and
approval.
#3.3.5.2 The check meter position shall be located at accessible communal areas for ease of
meter reading and maintenance at all times.
2
http://www.wsd.gov.hk/en/plumbing-engineering/automatic-meter-reading/index.html
- 17 -
December 2021 version
- 18 -
December 2021 version
4. Inside Service
4.1 Pipe & Fitting Materials
4.1.1 General
#4.1.1.1 Pipes and fittings shall conform to the relevant standards as listed in Part B of this
Technical Requirements and the WWR.
#4.1.1.2 All plumbing works using soldering for connecting copper pipes shall require prior
permission of the WA.
#4.1.1.3 Plumbing designers should, as far as practicable, avoid using the same pipe size
and material for fresh water, flushing water and/or fire services at the same location
in order to minimize the difficulty in identifying the fresh, flushing and fire services
water mains.
#4.2.1.2 All domestic supplies and concessionary supplies shall be separately metered. For
different applications of concessionary supplies, Section 4.2.5 shall be referred.
- 19 -
December 2021 version
#4.2.2.2 Fresh water supply to buildings with an overall height of more than 12m shall be
supplied by indirect supply systems as illustrated in Fig. 6 (i.e. a sump and pump
system or a hydro-pneumatic pump system) or any equivalent system as approved
by the WA for all floors. [This clause is applicable to new applications with Form
WWO 542 submitted on or after 1 January 2019 except for those applications
which have Form WWO 132 submitted before 1 September 2018.]
#4.2.2.3 The minimum residual pressure for fresh water would be 15 to 20 meter head
measured at the connection to the main. The fresh supply inside service should be
designed to the minimum available residual pressure as advised by the WA.
#4.2.3.1.2 No device or system that may cause contamination of a water supply shall be
connected directly or indirectly to any part of an inside service without appropriate
cross-connection prevention or backflow prevention control suitable for the level
of hazard.
3
The meaning of the height of building is similar to that defined under the Buildings Ordinance (Application to
the New Territories) Ordinance, Chapter 121. For more detailed illustration, Appendix I to III of the ‘Building
New Territories Exempted Houses’ published by the Lands Department (available in
http://www.landsd.gov.hk/en/images/doc/Building NT Exempted Houses_e.pdf) could be referred.
- 20 -
December 2021 version
some typical installations are listed in Table 4.2.3.7.2. For other installations, the
backflow prevention devices shall be provided based on the fluid category
applicable to the installations according to BS EN 1717.
#4.2.3.3.2 Backflow prevention devices shall comply with the latest BS EN 1717 and all
relevant standard(s) for the devices.
- 21 -
December 2021 version
- 22 -
December 2021 version
Fire service (improvised sprinkler system) Details please refer to FIG. 17 under TR
Drinking Fountains (not located at street Details please refer to FIG. 37 to 39 under
side) TR
Drinking Fountains (located at street side) Details please refer to FIG. 40 under TR
- 23 -
December 2021 version
- 24 -
December 2021 version
#4.2.4.2 If the connection is not laid in an exposed manner at the lot boundary, then it shall
be laid inside underground service trench/duct with adequate cover. The
underground/buried water mains should be laid with cover according to the latest
required minimum depth of services and associated installations stipulated by
Highways Department. The current minimum cover requirements stated in the
Conditions of Excavation Permit are 450mm and 900mm on non-carriageway and
carriageway respectively.
#4.2.4.3 No water pipe shall be embedded within load bearing structural elements in
longitudinal direction. Such structural elements include, but not limited to, columns,
beams and slabs. Screeding above slabs should not be considered as structural
elements. Hence, water pipe embedded in screeding is acceptable. The water pipe
in screeding shall be considered as embedded pipes.
#4.2.4.4 Vertical water pipes piercing through structural slabs and transfer plates; and
horizontal water pipes piercing through beams, columns and structural walls shall
be protected by sleeving or other suitable means.
#4.2.4.5 A tee-branch valve, i.e. an isolation valve at a branch pipe, shall be provided for all
underground water pipes, and for all communal inside service, and shall be located
close to the main pipe. This requirement is applicable to both cold and hot water
systems.
#4.2.4.6 Sufficient cleansing taps shall be provided at each floor of car parks of a building
for car/floor washing. The cleansing supply at the car park shall be given from a
fresh water cistern with a separate meter unless it is a part of the cleansing supply
system of the building. Schematic layouts are shown in Fig 6A for reference.
#4.2.4.7 No draw-off point in inside services shall be subject to a pressure of 6 bar or above.
#4.2.4.8 The inside service shall be constructed from each flat to the existing common meter
connection or in such other locations as determined by the WA.
#4.2.4.9 For new sump and pump systems, a standby pumpset shall be provided.
#4.2.4.10 For existing sump and pump systems, a standby pumpset shall be provided unless
this proves to be impracticable.
- 25 -
December 2021 version
#4.2.5.2 The concessionary usages and requirements on mode of supply are summarized in
Table 4.2.5.2.1. Permissions for such supplies shall be given by WSD.
- 26 -
December 2021 version
- 27 -
December 2021 version
#4.2.5.3 An anti-vacuum valve and a non-return valve should be installed at the draw-off
point in lieu of a water storage tank for preventing back syphonage when the
potential hazard of water contamination is relatively low. ‘Section B Irrigation’ of
Table 4.2.5.2.1 shall be referred for relevant usages.
#4.2.5.4 Draw-off tap that is freely accessible by the general public should be kept in an
external protective box with lock and key.
- 28 -
December 2021 version
#4.2.5.5 Installation of water points for internal cleansing of open yards and for other
miscellaneous domestic purposes in private houses of bungalow type or the like
can be permitted as part of the domestic supply. This will not be taken as a
concessionary supply. It is not necessary to install any receptacle for this type of
water points.
- 29 -
December 2021 version
#4.2.6.2.2 The premises shall have separate access, proper drainage system and bear a proper
postal address.
#4.2.6.3.2 Either fresh or salt mains water supply may be given for cooling / air-conditioning
/ humidification purposes if the system designed belongs to one of the following
categories:-
(a) Closed circuit cooling systems designed for any purpose where operational
losses are negligible and no water is rejected to waste;
(b) Cooling systems designed to have no evaporative losses, while all the water is
re-used after cooling for an industrial process; (The water consumption
required for normal trade must not be less than that required for air-
conditioning/ cooling purposes at peak cooling load);
(c) Evaporative cooling systems designed for an essential industrial process for
cooling or air-conditioning purposes, provided that system losses arise from
evaporation, drift and bleed-off only;
(d) Evaporative cooling/ air-conditioning/ humidification systems designed for
essential purposes other than industrial processes, provided that system water
losses arise from evaporation, drift and bleed-off only; or
(e) Humidification system designed for essential industrial processes, e.g. the
spraying of a fine mist in textile weaving plants.
- 30 -
December 2021 version
#4.2.6.3.3 The application of mains water in evaporative type plants for purposes other than
industrial process is limited to those cases where the cooling / air-conditioning /
humidification system(s) is/ are critical for normal operation. The type of
evaporative plant used should be of an enclosed design, so that wastage of water
due to splashing is prevented. Examples are as follows:-
(a) Air-conditioning system serving hospital areas where air-conditioning is
essential for operation requirement, such as operating theatres, intensive care
units and mortuaries etc.;
(b) Cooling system for cold storage purpose or laboratory testing; or
(c) Air-conditioning/ humidification system for major computer facilities, art
galleries or testing laboratories.
(d) Air-conditioning/ humidification system designed to achieve higher energy
efficiency performance.
#4.2.6.3.4 Prior to the installation of the fresh water cooling towers (FWCT), applicants
should apply for participation in the ‘Fresh Water Cooling Towers Scheme’
(FWCT Scheme) for air-conditioning systems administered by the Electrical and
Mechanical Services Department (EMSD). The participation in the FWCT Scheme
should comply with the requirements stipulated in the ‘Code of Practice for Fresh
Water Cooling Towers’ promulgated by EMSD and the requirements of WSD. For
details of the FWCT Scheme and all relevant requirements, EMSD’s website4 and
WSD’s website5 shall be referred.
*4.2.7.1.2 When the factory test pressure of the heater is less than 1.5 times the maximum
4
http://www.emsd.gov.hk/
5
https://www.wsd.gov.hk/en/plumbing-engineering/information-for-licensed-plumbers/do-not-install-
unauthorised-fresh-water-cooling-to/index.html
- 31 -
December 2021 version
static water pressure at the mains water supply point then, for premises on direct
supply, a water heater must be supplied with water from a cold water cistern.
#4.2.7.1.3 A separate mains water storage cistern of 45 litres capacity shall be provided for
each flat to supply such hot water apparatus in Clause 4.2.7.1.2.
*4.2.7.1.4 Pressure type thermal storage heaters other than unvented electric thermal storage
water heaters satisfying the requirements stipulated in Clauses 4.2.7.1.12 shall be
supplied from storage cisterns no matter what the pressure at inlet point should be,
except these are installed in flats supplied through the indirect or sump and pump
system.
#4.2.7.1.5 For premises on direct supply, a separate mains water storage cistern of 45 litres
capacity shall be provided for each flat to supply such hot water apparatus in Clause
4.2.7.1.4.
#4.2.7.1.6 For flats supplied from the roof storage cistern of an indirect or sump and pump
system, no separate storage for hot water apparatus will be required but the supply
to the apparatus shall be by a separate down feed supplying the apparatus only
unless the arrangement in Clause 4.2.7.1.7 is applied.
#4.2.7.1.7 If the flats on the indirect system are supplied through an oversized down feed pipe,
the pipe supplying the hot water apparatus shall be branched from the down feed
at a point above the top of the apparatus.
#4.2.7.1.8 When gas geysers are to be installed on the top floor of a building supplied through
storage cisterns, gas geysers with low pressure governors should be installed when
the head available is less than 5 metres to the highest hot water draw-off point.
*4.2.7.1.9 If mixing valves, water blenders or combination fittings are to be used, the cold
water supply to these fixtures shall be drawn from the same source as is supplying
the hot water apparatus in order to provide a balanced pressure and to obviate the
risk of scalding should the supply at the source fail or be restricted for any reason.
*4.2.7.1.10 Except for unvented electric thermal storage water heaters satisfying the
requirements stipulated in Clauses 4.2.7.1.12 and 4.2.7.1.13, all pressure type
thermal storage heaters shall be provided with a vent or expansion pipe taken from
its highest point and discharge in the atmosphere above the storage cistern at
sufficient height to prevent a constant outflow of hot water therefrom.
- 32 -
December 2021 version
*4.2.7.1.11 A loose jumper type valve shall be fitted on the inlet of the water heater if a non-
return valve is not incorporated in such water heater, but this requirement does not
apply to an electric water heater of the thermal storage type satisfying the
requirements stipulated in Clauses 4.2.7.1.12 and 4.2.7.1.13.
*4.2.7.1.12 All unvented electric thermal storage water heaters shall comply with the safety
requirements under the Electrical Products (Safety) Regulation (Chapter 406 sub.
leg.).
*4.2.7.1.13 Every system incorporating an unvented electric water heater of the thermal storage
type shall be provided with:-
(a) a supply pipe that branches off from the feed pipe at a point above the top of
the water heater, or some other device to prevent the water from draining down
from the water heater if there is a failure at the source of water supply;
(b) an anti-vacuum valve or some other device to prevent heated water from being
syphoned back to the supply pipe; and
(c) a vessel to accommodate the expansion of heated water where that expansion
is constrained by a non-return valve or some other device, incorporated at the
inlet of the water heater.
#4.2.7.2.2 The cold water feed pipe from sump tank with booster pump shall also be the same
source for the hot water system.
#4.2.7.2.3 If mixing valves, water blenders or combination fittings are to be used, the cold
water supply to these fixtures shall be drawn by a separate down feed from the hot
water storage cistern. This outlet from storage tank shall be slightly lower than the
feed to the hot water system in order to provide a balanced pressure and obviate
the risk of scalding should the mains supply fail or be restricted.
#4.2.7.2.4 All centralised hot water systems utilising a boiler and cylinder, or calorifier, shall
be provided with an expansion pipe taken from the highest point of the cylinder or
- 33 -
December 2021 version
#4.2.7.2.5 Under no circumstances shall safety valves, air valves or relief valves be used as a
substitute or replacement for an expansion pipe.
*4.2.7.2.6 Under no circumstances shall any control valve be installed on the expansion pipes
between the highest point of the cylinder or calorifier, and the free end of such
pipes.
#4.2.7.2.7 When a centralised hot water system of the boiler /cylinder or calorifier type is
installed, in addition to the expansion pipe as required in Clause 4.2.7.2.4, a safety
valve or pressure relief valve shall be provided to the boiler or to the primary flow
pipe as close to the boiler as possible. Such valve shall be set to discharge when
the pressure in the boiler exceeds 35kPa above that of the static pressure of the
system.
*4.2.7.2.8 No tap or other fittings of drawing off water, (other than a screwed plug with a
removable key for emptying the system for cleansing and repair), shall be
connected to any part of the hot water system below the top of the hot water
cylinder in such a way that the level of the water in cylinder can be lowered.
#4.2.7.2.9 In a hot water system comprising more than one storage cylinders at different levels,
Clause 4.2.7.2.8 should read as applying to the lowest cylinder.
#4.2.7.2.10 To avoid wastage of water when repairs are being effected, a stop valve shall be
fitted on the cold feed pipe at the outlet from the storage cistern.
#4.2.7.2.11 If the storage cylinder is installed in a lower floor, an additional stop valve shall be
fitted near the inlet to the cylinder.
#4.2.7.2.12 Such stop valve as provided under Clauses 4.2.7.2.10 and 4.2.7.2.11 shall have
loose keys or hand-wheels which shall be kept in a safe place to prevent
unauthorised interference.
#4.2.7.2.13 A screwed plug with a removable key shall be provided at the lower part of the
- 34 -
December 2021 version
#4.2.7.2.14 No stop valve shall be installed in the primary flow or return pipes except when a
vent pipe is connected to the boiler and such installation shall only be made under
skilled supervision.
*4.2.7.2.16 Installation of boilers/ steam boilers shall comply with the relevant Boilers and
Pressure Vessels Regulations (Chapter 56).
#4.2.7.2.17 Temperature and pressure relief valve, air vent and vacuum breaker shall be
provided to hot water storage tanks and calorifiers.
#4.3.1.2 For sea-front lots where the private salt water supply is available, mains supply for
flushing may be withheld or withdrawn depending on the Lease Conditions.
#4.3.3.3 Water meters shall be installed in each flushing system receiving a TMF supply.
TMF flushing water supply would normally be given to the entire building.
Requirements stipulated in Section 3 of this TR is applicable.
- 35 -
December 2021 version
#4.3.4.1 Flushing water supply to buildings with an overall height6 less than or equal to
12m can be effected in one of the two following ways:-
(a) indirect supply system (with direct supply to roof storage tank) as illustrated
in Fig. 14; or
(b) indirect supply system, with a sump and pump system or a hydro-pneumatic
pump system as illustrated in Fig. 14.
#4.3.4.2 Flushing water supply to buildings with an overall height of more than 12m shall
be supplied by indirect supply systems with a sump and pump system as illustrated
in Fig. 14 or a hydro-pneumatic pump system or any equivalent system as approved
by the WA for all floors. [This clause is applicable to new applications with Form
WWO 542 submitted on or after 1 January 2019 except those applications which
have Form WWO 132 submitted before 1 September 2018.]
#4.3.4.3 The minimum residual pressure of salt water supply is 15 meter head measured at
the connection to the main. The flushing supply inside service should be designed
to the minimum residual pressure as advised by the WA.
6
The meaning of the height of building is similar to that defined under the Buildings Ordinance (Application to
the New Territories) Ordinance, Chapter 121. For more detailed illustration, Appendix I to III of the ‘Building
New Territories Exempted Houses’ published by the Lands Department (available in
http://www.landsd.gov.hk/en/images/doc/Building NT Exempted Houses_e.pdf) could be referred.
- 36 -
December 2021 version
*4.3.5.2 A separate water storage tank shall be provided for flushing purposes.
#4.3.5.3 The inlet pipe to the separate storage tank should not be less than 40 mm diameter;
its portion before meter position shall be exposed or laid in a proper service duct
and extended to the lot boundary.
#4.3.5.4 To facilitate meter installation, a meter position shall be provided in the communal
area of the building as close to the fresh supply meters as possible. Regarding
general requirements for meter positions, Section 3.2 shall be referred.
#4.3.5.5 In case a temporary mains fresh water supply is proposed to be provided as the
alternative source to augment an existing independent (not Government) supply,
the storage tank for the flushing cistern shall be constructed in accordance with Fig.
15.
#4.3.5.6 No draw-off point in the inside services shall be subject to a pressure of 6 bar or
above.
#4.3.5.7 A tee-branch valve shall be provided for all underground flushing water pipes, and
for all pipes serving more than one domestic or commercial unit.
#4.3.5.8 Concerning requirement for flushing water storage capacity, Clause 6.2.5 shall be
referred.
#4.3.5.9 All PVC-U pipes must be properly supported and shielded from direct sunray and
must be painted with protective paint when exposed. The paint should not adversely
affect the physical property of the PVC-U pipes.
- 37 -
December 2021 version
5. Fire Service
5.1 General
5.1.1 Not Used.
#5.1.3 Plumbing systems using government water supply for fire services shall comply
with the requirements of the WA.
*5.1.4 The use of water from fire service for purposes other than firefighting is prohibited.
#5.3.2 Consideration can be given for the use of wrought iron pipe and black steel pipe
without being galvanized, upon application, for a fresh water fire service after a
positive air break, i.e. fire service tank or sump tank.
#5.3.3 The materials for pipes and pipe fittings on a salt water fire service shall be capable
of withstanding the corrosive effect of salt water.
- 38 -
December 2021 version
#5.4.1.2 For existing buildings, fire service installations obtaining water supply from
existing fresh water tanks may be considered case-by-case by the WA and the
Director of Fire Services.
#5.4.1.4 All plumbing works between the lot boundary and master/check meter positions
shall be exposed or laid in a proper service trench/duct to facilitate inspection and
repairs. Adequate drainage shall be provided to remove water inside the
trench/duct.
#5.4.1.5 If the connection is not laid in an exposed manner at the lot boundary, then it shall
be laid inside underground service trench/duct with adequate cover. The
underground/buried water mains should be laid with cover according to the latest
required minimum depth of services and associated installations stipulated by
Highways Department. The current minimum cover requirements stated in the
Conditions of Excavation Permit are 450mm and 900mm on non-carriageway and
carriageway respectively.
#5.4.1.6 A fullway gate valve and a non-return valve have to be installed on the fire service
as close to the Government water supply connection as possible.
#5.4.2.2 A dual connection from the Government unrestricted supply ring main shall be
provided for a fire service sprinkler / drencher system situated in the recognised
Waterworks unrestricted industrial supply zone. Twin connections, one from an
unrestricted supply main and one from a distribution main, will be provided for a
fire service sprinkler / drencher system situated outside the recognised unrestricted
industrial supply zone, where practicable.
- 39 -
December 2021 version
#5.4.2.3 Where it is not practical to connect the fire service sprinkler / drencher system to
an unrestricted supply main, FSD may require the provision of fire service tank to
serve as secondary source for the fire service installation. Depending on FSD’s
requirements, a single or dual connection can be given to serve the fire service tank
of secondary source.
#5.4.2.4 No part of any fire service sprinkler / drencher system supplied from the
Government mains shall be used for supplying any other services including other
fire service installations, e.g. hose reels, except that a common suction tank can be
used for both sprinkler and hose reel systems. Any exemption from this
requirement should have the endorsement of the Director of Fire Services.
#5.4.2.5 Where direct connections to a sprinkler/ drencher system are to be from the
government mains, an additional butterfly valve, without stop screw and lock nut
on handle and strapped in open position, shall be installed at a point on the supply
pipe before the fire service inlet and as close as possible to the control valves of the
connections.
#5.4.2.6 FSD’s endorsement shall be sought for the application for improvised sprinkler
systems as illustrated in Fig. 17. The design of the improvised system shall be
vetted by Fire Services Department.
- 40 -
December 2021 version
#5.4.3.2 Common tank arrangements for fire-fighting and flushing or other purposes are not
acceptable when a government supply is involved. Where a building is to be
provided with a non-government flushing supply and where it is proposed to feed
the fire service from that supply, the applicant is advised to install an independent
fire service system if it is envisaged that the fire service system may require to be
connected to the government main at a later stage.
#5.4.3.3 Warning message shall be securely fixed on or near every hose reel outlet and the
message shall be easily visible by the occupier.
消防用水
嚴禁作其他用途
#5.4.4.2 Typical layout drawing for street fire hydrant system in Fig. 21 should be followed.
#5.4.5.2 Fire service ring mains shall not be connected to or used for supplying any other
service, except with the approval of the WA.
- 41 -
December 2021 version
*6.1.2 No cistern for the storage of fresh water supplied from the waterworks shall,
without the written permission of the WA, be so connected that it can be used for
the storage of any water other than that supplied from the waterworks.
*6.2.1.1.2 Safe access shall be provided to all cisterns by means of a secure permanent ladder
or readily available portable ladder.
*6.2.1.1.3 Where a cistern is installed inside a building and, due to limited headroom available,
it is fixed with limited clearance from the ceiling or underside of the roof, a quickly
detachable fitting must be used to enable it to be easily removed for cleansing and
repair.
#6.2.1.1.4 For water cisterns with top access, the access on top of the cisterns should have a
minimum headroom of 800mm.
- 42 -
December 2021 version
#6.2.2.2 For concrete fresh water cisterns/storage tank, all internal surface of floors, walls
(to full height) and soffits of potable water cisterns shall be lined with a non-toxic
smooth finish.
#6.2.2.4 When fibreglass storage tank is to be used, prior approval by the WA must be
sought. Fibreglass storage cistern for potable water shall be of an approved type
or certified to contain no toxic materials and suitable for storage of potable water.
6.2.2.5 Material testing standards and requirements of fresh water tanks in inside service
is given in Part B of this TR.
#6.2.3.2 Every storage cistern shall have a lockable close fitting rigid cover secured by
mechanical means which excludes light and the ingress of particles and / or insects
from the cistern. The cover shall be made of a material or materials which do not
shatter or fragment when broken and which will not contaminate any condensate
which may form on its underside or the stored water. For the potable water storage
cistern, the cover and its base frame shall possess double upstand edges
interlocking one another to provide additional protection.
#6.2.3.3 Double sealed covers with locking devices shall be provided for all storage cisterns
other than cisterns that provide supply solely for irrigation, cleansing, air-
conditioning system make-up water, flushing and fire-fighting. The double-sealed
covers prevent the ingress of surface water.
- 43 -
December 2021 version
*6.2.4.2.2 For ball float valves of a nominal diameter not exceeding 50mm, their valve bodies
must be made of copper alloy or stainless steel. For ball float valves of a nominal
diameter exceeding 50mm, their valve bodies must be made of copper alloy,
stainless steel, epoxy coated cast iron or epoxy coated ductile iron.
*6.2.4.2.3 Floats for use with fresh water must be made of copper alloy or stainless steel.
Floats for use with salt water must be made of plastic or stainless steel.
*6.2.4.2.4 Ball float valves fitted to a cistern must have the size of the orifice, the size of the
float and the length of the lever so proportioned to one another that, when the float
is immersed to an extent not exceeding half its volume, the valve is watertight
against the highest pressure at which the valve may be required to work.
*6.2.4.2.5 A ball float valve or float-operated valve fitted to a cistern must be securely fixed
to the cistern above the waterline of the float of the valve, and must be supported
independently of the inlet pipe (unless the inlet pipe is itself rigid and securely fixed
to the cistern), in a position that no part of the body of the valve is submerged when
the cistern is charged to the overflowing level.
*6.2.4.2.6 If a ball float valve or float-operated valve is provided with a pipe so arranged as
to discharge water into a cistern below its overflowing level, an air hole must be
provided in the outlet chamber of the valve above the overflowing level. The air
hole must be of a size sufficient to prevent syphonage of water back through the
valve.
*6.2.4.2.7 Ball float valves must not be fitted to a cistern that is used to contain heated water.
*6.2.4.2.8 The inlet of a single cistern fed by a pumped supply must be fitted with an
automatic control switch and without any stop valve.
- 44 -
December 2021 version
*6.2.4.2.9 A ball float valve or automatic control switch installed at the inlet of a cistern must
shut off the supply when the water level is 25mm below the invert of the overflow
pipe or warning pipe. The invert of the inlet pipe or the outlet of the ball float valve
must not be less than 25mm above the top of the overflow pipe.
#6.2.4.2.10 In case of a mixed flushing water supplies, the water tank shall be fitted with a ball
float valve with submerged float control and a fullway gate valve for controlling
and isolating the inflow of mains supply respectively. For other source of flushing
water supply, a ball float valve and a fullway gate valve shall be provided. Typical
detail for flushing water tank with mixed supply is illustrated in Fig. 15.
Performance of the ball float valve shall meet the requirements specified in case of
gravity supply.
*6.2.4.3.2 A stop valve must be provided at the outlet of a cistern. Provisions must be made
for a drain-off pipe to enable the cistern to be emptied.
#6.2.4.3.3 Fullway gate valves shall be used with as the stop valves in Clause 6.2.4.3.2 at the
outlet pipe of every water storage cistern. The drain-off pipe in Clause 6.2.4.3.2
shall be properly plugged or adequate means shall be provided to prevent any
unauthorized operation of the control valve at drain-off pipe. If the outlet of a
flushing water cistern is of nominal size 50mm or below, a ball valve can be used
to substitute the above gate valve.
*6.2.4.4.2 An overflow pipe of one commercial size larger than the inlet pipe, and in no case
less than 25mm in nominal diameter, must be fitted to a cistern and be extended to
terminate in a conspicuous position. The overflow pipe must not be connected to a
drain or sewer or to the overflow pipe from another cistern.
#6.2.4.4.3 The position of discharge should be in a communal area easily visible and
- 45 -
December 2021 version
#6.2.4.4.4 If the overflow pipe is not extended to terminate in a conspicuous position, the
overflow pipe shall be installed with an overflow alarm with signal transferred to
a 24-hourly manned management office for timely notification. Full justifications
for such arrangement shall be provided to the WA for consideration and approval.
#6.2.4.4.5 In case of mixed flushing water supply as shown in Fig. 15, the overflow shall be
twice the diameter of largest inlet or of nominal diameter 40mm, whichever is
greater.
#6.2.4.4.6 No part of the overflow pipe shall be submerged inside the storage tank.
#6.2.4.4.7 A grating and a self-closing non-return flap shall be provided at the overflow pipe
outside the storage tank.
#6.2.4.4.8 A warning pipe shall be installed in addition to an overflow pipe. A warning pipe
can be of any size not less than 25 mm in diameter and shall comply with all other
requirements of an overflow pipe.
#6.2.4.4.9 The warning pipes shall be installed at a level below the overflow pipe and shall be
either extended to conspicuous location, i.e. outside of the building periphery for
roof tank or outside the pump room for sump tank, or installed with signal
transferred to a 24-hourly manned management office.
6.2.5 Size of Storage Cisterns for Flushing, Domestic and Trade/Commercial Water Uses
#6.2.5.1 The proportion of capacity of sump cistern to roof cistern is recommended to be in
the order of 1:3. Otherwise, the designer shall demonstrate that the proposed ratio
of sump cistern to roof cistern is capable of fulfilling the designed demand.
#6.2.5.2 The capacity of the flushing water storage shall be designed according to the
criteria in Table 6.2.5.2.1 with a minimum capacity of 250 litres. [This clause is
applicable to new applications with Form WWO 542 submitted on or after 1
January 2019 only.]
- 46 -
December 2021 version
2. Commercial
- Urinal 30
- Water closet 40
#6.2.5.3 Storage criteria for fresh water supply for domestic flats are given in Table 6.2.5.3.1.
Table 6.2.5.3.1 Storage criteria for domestic application (sump and pump system)
135 litres/flat
In case of a sump and pump system, the
Up to 10 flats
minimum total storage including sump tank is
allowed to be 500 litre,
> 10 flats 90 litres for each additional flat
#6.2.5.4 For industrial buildings, the entire inside service shall be supplied from storage
cisterns with separated outlets/downpipes feeding independent systems to serve
separately the industrial and processing purposes and the other general and ablution
appliances. These independent systems shall not be interconnected.
#6.2.5.5 The required capacity of storage tanks for industrial use is one-day demand.
#6.2.5.6 For trade/commercial premises, the storage criteria for fresh water supply shall be
designed according to the criteria in Table 6.2.5.6.1 and Sections 6.2.5.7 to 6.2.5.9.
The criteria shall apply to building types not listed below, yet having similar
functions. In addition, designers should avoid oversize or undersize of the storage
of water tanks which may result in water quality problems. However, applicant
may request for relaxation of the requirement with justifications and flexibility will
be allowed by the WA if justified.
- 47 -
December 2021 version
#6.2.5.7 For laundry, the required storage criterion is given in Table 6.2.5.7.1.
#6.2.5.8 For hospital, the required storage criterion is one day’s consumption as given by
the hospital authorities.
#6.2.5.9 For boilers, the required storage criterion is given in the following formula:-
#6.2.6.2 When the capacity of water cistern exceeds 5,000 litres, adoption of twin-tank
system is required. The applicability shall also be subject to factors such as
availability of plant room space.
#6.2.6.3 A set of inlet, outlet and associated overflow and drain pipes shall be provided to
each cistern compartment.
- 48 -
December 2021 version
*6.2.6.4 Each inlet of a twin-cistern fed by a pumped supply must be fitted with an
automatic control switch and a stop valve for temporary isolation purpose.
#6.2.6.5 For water supplies other than pumped supply, this inlet shall comply with
requirements stated in Clause 6.2.4.2.1.
- 49 -
December 2021 version
*6.7.1.3 Except with the written permission of the WA, fitting with a threaded outlet, or any
device facilitating the connecting of rubber hose or another type of flexible hose,
must not be used.
*6.7.2.2 Every inlet to a bath, lavatory basin or sink shall be distinct from, and unconnected
with, any outlet therefrom and every outlet for emptying such bath, lavatory basin
or sink shall be provided with a well-fitting and easily accessible watertight plug
or some other equally suitable apparatus.
*6.7.2.3 The level of the point of discharge of hot or cold water to a bath, lavatory basin or
sink shall be above the level of the overflow, or if there be no overflow, of the top
edge of the bath, basin or sink.
*6.7.2.4 The water supply to any bidets, sitz bath, slop or sluicing sink or similar
apparatus, shall, if the inlet is liable to be submerged, be provided by:-
(a) a cistern supplying water to such apparatus only;
(b) a cistern for flushing purposes only; or
(c) a hot water distribution system supplying such apparatus only.
- 50 -
December 2021 version
#6.8.1.2 Domestic water purifiers/ filters must not be connected directly to the mains supply
because of the possibility of contamination.
#6.8.1.3 When there is installation of any domestic filter or water filter incorporated in water
using apparatuses (such as drinking fountain etc.), backflow prevention device
shall be installed.
#6.8.1.4 Requirements for backflow prevention and written permission from the WA for
typical types of water filters are summarized in Table 6.8.1.4.1.
- 51 -
December 2021 version
#6.8.1.5 Sterilizers with or without attached filtering devices could be connected directly to
the mains supply provided that backflow prevention device is provided upstream
of the sterilizer such that there is no possibility of contaminating the mains supply.
#6.8.2.2 Washing machines/ dishwashing machines with submerged inlets are considered
to have high level of contamination hazard and must be installed with appropriate
backflow prevention devices according to Table 4.2.3.7.1.
*6.10.1.2 A flushing cistern must in all cases be supplied from a cistern. Except with the
written permission of the WA, the cistern must not be used to supply any other
apparatus, appliance or fitting. The cistern must be fitted with a suitable close
fitting cover and provided with appropriate access to enable the cistern to be
entered and cleaned.
*6.10.1.4 A water-closet fitment or slop sink must be fitted with a flushing cistern. However,
a pressure flushing valve may be installed for flushing without the provision of a
flushing cistern if there is a suitable head of water.
- 52 -
December 2021 version
*6.10.2.2 A flushing cistern for a water-closet fitment or slop sink must be capable of giving
a flush of not more than 15 litres of water on each occasion the fitment is used.
*6.10.2.3 The capacity of the flushing cistern in the case of trough water closets and urinals
shall be approved by the WA subject to the discharge in the case of trough water
closets being not less than 9 litres of water for every metre of the channel and the
discharge in the case of urinal being not less than 4.5 litres of water for every basin
or stall, or in the case of a trough urinal, every metre thereof.
#6.10.2.4 The WA would have no objection to accepting the use of flushing cisterns with
discharge less than that required by the current regulations provided that the design
flushing volume is compatible with the toilet bowl to ensure effective clearance of
waste by a single flush and the flushing apparatus meets the requirements of the
WA.
*6.10.2.5 A flushing cistern operated by mechanical means or a sensor must be fitted with a
ball float valve that is arranged to refill the cistern within 2 minutes.
*6.10.2.6 Every flushing cistern shall have an overflow which shall discharge in a
conspicuous location.
#6.10.2.8 The requirements on the use of valve type flushing cisterns are as follows:-
(a) The valve seal of the flushing devices shall be easily replaceable;
(b) A dual flush valve which is designed to give two different volumes of flush
- 53 -
December 2021 version
*6.10.2.9 The components of all valve type flushing devices shall be of material that is
suitable for the use of salt water.
*6.10.2.10 For an existing building with permission to use government water supply for
flushing purposes, any existing flushing apparatus found unsuitable shall be
replaced with a proper apparatus as specified under Section 6.10.
#6.10.2.11 A filter which is readily accessible for inspection and cleaning shall be installed
before a flushing valve. This filter can be replaced by a built-in strainer, which can
be readily inspected and cleaned, in the flushing device.
- 54 -
December 2021 version
*6.10.3.2 The valve components shall be of material that is suitable for the use of salt water.
*6.10.3.3 For an existing building with permission to use mains water (fresh or salt) for
flushing purposes, any existing flushing apparatus found unsuitable shall be
replaced with a proper apparatus as specified under Section 6.10.
6.11 Earthing
#6.11.1 The metal work of an inside service shall not be used as an earth electrode. The use
of non-metallic pipes or fittings should not have had any effect on the earthing
arrangement of the building.
- 55 -
December 2021 version
7. Water Conservation
7.1 General
#7.1.1 To uplift the standard of water efficiency of plumbing fixtures and appliances, a
mandatory Water Efficiency Labelling Scheme (WELS) has been implemented.
For all proposed plumbing works submitted using the Form WWO 46 for
designated part of premises as listed below, the proposed products to be used for
shower heads for bathing, water taps, urinal flushing valves and water-closet
fitments7 should comply with prescribed water efficiency grades registered under
WELS.
7.2 Minimum Flow Requirements for Fittings and water-closet fitments in Inside Service
#7.2.1 The minimum flow requirements for draw-off taps, single and combination taps
shall conform to the specification in the relevant international standards. Relevant
standards for respective tapware has been summarized in Part B of this TR.
7.3 Water Efficiency Requirements for Fittings and water-closet fitments in Inside Service
#7.3.1 Subject to exemption stipulated in Section 7.5.1, designated products (showers for
bathing, water taps and urinal flushing valves) of prescribed water efficiency
requirements registered under WELS shall be used in the following designated part
of premises:-
i. Kitchens of the domestic premises; and
ii. Bathrooms and toilets of all premises.
#7.3.2 the products shall comply with the prescribed water efficiency requirements in
Table 7.3.2.1 below:-
7
In accordance with Section 4.6 of the Scheme Document for WELS on water closets, the term “water closet”
covers toilet suite (one-piece water closet pan); water closet pan only; water closet cistern only; and a
combination of a water closet pan and cistern (close-coupled suite).
- 56 -
December 2021 version
and pantry/kitchen sinks. Water taps equipped with automatic sensing open/close device or automatic
closing mechanism are also included. However, water taps installed at bath tub/shower, any system,
machinery and devices such as irrigation system, washing machines, water dispensers etc. which
serve for bathing/operational use, are excluded. Water taps for construction purposes are exempted.
#7.3.4 Subject to exemption stipulated in Section 7.5.2, all water-closet fitments proposed
in Form WWO 1149 (the “List of Pipes and Fittings”) for proposed plumbing
works should comply with the prescribed water efficiency requirements as detailed
in the Table 7.3.4.1 below.
#7.4.2 When submitting the Form WWO 46, test report(s) of flow rate test on the
‘combined’ water-saving appliance(s) shall be enclosed to demonstrate compliance
with the prescriptions in Table 7.3.2.1. The test shall be conducted within 5 years
before the date of submission.
- 57 -
December 2021 version
#7.5.1a Scenario A
All premises with tenders/quotations concerning the installation of showers for
bathing, water taps or urinal flushing valves therein invited before 1 February 2017
may be eligible for exemption from the mandatory use of designated products
registered under WELS. To apply for exemption, in the submission of the Form
WWO 46, the applicant shall: (a) submit documentary proof of such
tender/quotation or the existence of such tender/quotation; and (b) demonstrate that
the specifications stipulated under the said tender/quotation for the use of those
designated products could not fulfil the prescribed water efficiency requirements
to the WA for verification and approval.
#7.5.1b Scenario B
For all premises, applications for exemption based on technical issues like
inadequate water pressure for the operation of water heater after the installation of
designated products will also be considered on a case-by-case basis. To apply for
exemption, the applicant shall provide information to fully justify why the
mandatory use of designated WELS products cannot be complied with in the
submission of the Form WWO 46.
#7.5.1c Scenario C
For all premises, applications for relaxation of requirements based on reasons other
than those under scenarios (A) or (B) will also be considered on a case-by-case
basis. The relaxation may be in the form of relaxing the flow rate requirements of
certain designated products or exempting certain designated part of premises from
the mandatory requirements. To apply for the relaxation, the applicant shall
provide detailed information in the submission of the Form WWO 46 to fully
justify why the mandatory use of designated WELS products cannot be fully
complied with.
#7.5.2 For Form WWO 1149 submitted after 1 December 2020, an applicant may apply
for exemption from the requirements within the scope of designated part of
premises under the scenarios described in Clauses 7.5.2a to 7.5.2c.
- 58 -
December 2021 version
fitments therein invited before 1 December 2019 may be eligible for exemption
from the mandatory use of water-closet fitments complying with the prescribed
water efficiency grades registered under WELS.
To apply for exemption, in the submission of Form WWO 1149, the applicant shall:
(a) submit documentary proof of such tender/quotation or the existence of
such tender/quotation; and
(b) demonstrate that the specifications stipulated under the said
tender/quotation for the use of those water closets could not fulfill the prescribed
water efficiency requirements to the WA for verification and approval.
- 59 -
December 2021 version
In general, suitable pipe materials for inside service and fire service are as follows:-
(a) Pipes for a fresh water inside service must be made of ductile iron,
unplasticized polyvinyl chloride (PVC-U), steel, stainless steel, copper,
polyethylene (PE), crosslinked polyethylene (PE-X) or chlorinated polyvinyl
chloride (PVC-C). However, pipes made of polyethylene or unplasticized
polyvinyl chloride must not be used for hot fresh water inside service. Pipes
and fittings made of polybutylene (PB) are not permitted to be used in fresh
water inside service ;
(b) Pipes for a salt water inside service must be made of ductile iron, polyethylene
or unplasticized polyvinyl chloride;
(c) Pipes for a fresh water fire service must be made of ductile iron, steel, stainless
steel or copper; and
(d) Pipes for a salt water fire service must be made of steel and internally lined
with chlorinated polyvinyl chloride or of ductile iron.
B2.1.2 WSD has a General Acceptance (GA) system in place to pre-approve plumbing
products used in plumbing projects. To obtain approval for the installation and use
of pipes or fittings in inside service or fire service covered by the Waterworks
Ordinance/Waterworks Regulations from this Authority, the GA applicant is
required to produce one set of certification or test reports confirming their
compliance with the relevant prescribed specification as listed on WSD webpage
from either (a) the British Standards Institution, (b) the U.K. Water Regulations
Advisory Scheme or (c) accredited laboratories acceptable to this Authority. For (a)
- 60 -
December 2021 version
and (b), please ensure that the pipes and fittings are tested against the relevant
British Standard as listed on WSD webpage. For (c), please note that this Authority
will accept laboratories accredited by the Hong Kong Laboratory Accreditation
Scheme (HOKLAS) under the following sub-categories:-
Category Sub-category
Construction (i) Metallic materials
Materials (ii) Pipes
(iii) Showers
(iv) Tapwares and valves
If the submission is accepted, the WSD will include the product in its pre-approved
list. Builders can use the product in plumbing projects before the GA expiry date
of that product (the validity is a maximum period of five years).
Table B2.1.1.1 Applicable materials for fresh water and salt water inside service at different
locations
Fresh Water Inside Service Salt Water
Pipe/ Pipe fitting material Inside
Cold Water Hot Water Service(1)
Copper ✔ ✔ ✖
Ductile iron (with internal coating) ✔ ✔ ✔
Polyethylene (PE) ✔ ✔(2)
Polyethylene-cross-linked (PE-X) ✔ ✔ ✖
Plastic lined steel (PVC-C lining) ✔ ✖ ✖
Plastic lined steel (PVC-U/
✔ ✖ ✖
PE lining)
Polyvinyl chloride - chlorinated
(PVC-C) ✔ ✔ ✖
Polyvinyl chloride - unplasticized (PVC-U) ✔ ✔
Stainless steel ✔ ✔ ✖
✔ : Suitable for use when the relevant standards are complied with in general
✖ : Not suitable for use in general
(1) : Suitable location(s) for installation may refer to fresh water inside service
(2) : When installed in exposed condition, black pipe and pipe fittings shall be used.
- 61 -
December 2021 version
Copper ✔ ✖
Ductile iron ✔ ✔
Galvanized steel ✔ ✖
Stainless steel ✔ ✖
Polyvinyl chloride - chlorinated
(PVC-C) ✖ ✔
✔ : Suitable for use when the relevant standards are complied with in general
✖ : Not suitable for use in general
Table B2.1.1.3 Fitting materials for inside service and fire service
Fresh water
Fire service
Valve/Strainer inside service Salt water
component materials inside service
Cold Hot Fresh Salt
water water water water
A. Body and bonnet
Cast iron (with internal coating)* ✔ ✔ ✔ ✔ ✔
Copper alloy – brass** ✔ ✔ ✖ ✔ ✖
Copper alloy – dezincification
resistant (DZR) brass ✔ ✔ ✖ ✔ ✖
(e.g. CW602N/CZ132)
Copper alloy – bronze (gunmetal) ✔ ✔ ✔ ✔ ✔
Ductile iron (with internal coating)* ✔ ✔ ✔ ✔ ✔
Polyethylene (PE) ✔ ✖ ✔ ✖ ✖
Polyvinyl chloride - unplasticized
(PVC-U) ✖ ✖ ✔ ✖ ✖
Stainless steel (Grade 304) ✔ ✔ ✖ ✔ ✖
Stainless steel (Grade 316) ✔ ✔ ✖ ✔ ✖
Duplex Stainless steel (Grade 1.4462
or superior) ✔ ✔ ✔ ✔ ✔
- 62 -
December 2021 version
Table B2.1.1.3 Fitting materials for inside service and fire service
Fresh water
Fire service
Valve/Strainer inside service Salt water
component materials inside service
Cold Hot Fresh Salt
water water water water
B. Stem/ shaft
Copper alloy – brass** ✔ ✔ ✖ ✔ ✔
Copper alloy – dezincification
resistant (DZR) brass ✔ ✔ ✔ ✔ ✔
Copper alloy – bronze (gunmetal) ✔ ✔ ✔ ✔ ✔
Stainless steel (Grade 304) ✔ ✔ ✖ ✔ ✖
Stainless steel (Grade 316) ✔ ✔ ✔ ✔ ✔
Stainless steel (Grade 431) ✔ N/A ✖ ✔ ✔
Polyvinyl chloride - unplasticized
(PVC-U) ✖ ✖ ✔ ✖ ✖
C. Wedge (in gate valves etc.)
Ductile iron (with coating)* ✔ ✔ ✔ ✔ ✔
Resilient material to BS EN 681-1,
Type WA (elastomeric seals)* ✔ ✔ ✔ ✔ ✔
Stainless steel (Grade 304) ✔ ✔ ✖ ✔ ✖
Stainless steel (Grade 316) ✔ ✔ ✔ ✔ ✔
D. Seat and disc
Copper alloy – brass** ✔ ✔ ✔ ✔ ✔
Copper alloy – dezincification
resistant (DZR) brass ✔ ✔ ✔ ✔ ✔
Copper alloy – bronze (gunmetal) ✔ ✔ ✔ ✔ ✔
Polyvinyl chloride - unplasticized
(PVC-U) ✖ ✖ ✔ ✖ ✖
Resilient material to BS EN 681-1,
Type WA (elastomeric seals)* ✔ ✔ ✔ ✔ ✔
Stainless steel (Grade 304) ✔ ✔ ✖ ✔ ✖
Stainless steel (Grade 316) ✔ ✔ ✔ ✔ ✔
E. Bolt, Nut & Washer
Steel ✔ ✔ ✖ ✔ ✖
Stainless steel (Grade 304) ✔ ✔ ✖*** ✔ ✖
Stainless steel (Grade 316) ✔ ✔ ✔ ✔ ✔
F. Cap (disc)/ spring (non-return valve)
Copper alloy ✔ ✔ ✔ ✔ ✔
Ductile iron (with coating)* ✔ ✔ ✔ ✔ ✔
Stainless steel (Grade 304) ✔ ✔ ✖ ✔ ✖
Stainless steel (Grade 316) ✔ ✔ ✔ ✔ ✔
- 63 -
December 2021 version
Table B2.1.1.3 Fitting materials for inside service and fire service
Fresh water
Fire service
Valve/Strainer inside service Salt water
component materials inside service
Cold Hot Fresh Salt
water water water water
G. Screen (strainers)
Stainless steel (Grade 304) ✔ ✔ ✖ ✔ ✖
Stainless steel (Grade 316) ✔ ✔ ✔ ✔ ✔
H. Drain plug (strainers)
Copper alloy – brass** ✔ ✔ ✔ ✔ ✔
Copper alloy – dezincification
resistant (DZR) brass ✔ ✔ ✔ ✔ ✔
Copper alloy – bronze (gunmetal) ✔ ✔ ✔ ✔ ✔
Malleable iron (with coating)* ✔ ✔ ✔ ✔ ✔
I. Lever (ball float valve)
Stainless steel (Grade 304) ✔ ✔ ✖ ✔ ✖
Stainless steel (Grade 316) ✔ ✔ ✔ ✔ ✔
Copper alloy – brass** ✔ ✔ ✔ ✔ ✔
Copper alloy – dezincification
resistant (DZR) brass ✔ ✔ ✔ ✔ ✔
Copper alloy – bronze (gunmetal) ✔ ✔ ✔ ✔ ✔
* Coating material e.g. epoxy shall comply with BS 6920:2014 for respective cold water and/or hot water
applications.
** Except brass containing zinc of more than 15% by mass as it will be susceptible to dezincification.
*** For Bolt, Nut & Washer that do not have any contact with salt water, the material can be Stainless Steel
(Grade 304)
B2.2.2 The GA* Scheme covers but not limited to the following plumbing products:-
- Pipes and pipe fittings (stainless steel, copper or copper alloy);
- Valves;
- Strainers;
- Expansion/settlement/flexible joints; and
- Taps and mixers.
- 64 -
December 2021 version
B2.2.3 Only metallic plumbing products with valid GA are eligible to apply for the GA*
Scheme.
B2.2.4 Low metal leaching rate metallic plumbing products under the GA* Scheme shall
possess supporting document/test report to prove compliance with an
Australian/New Zealand Standard AS/NZS 4020.
B2.2.5 For a particular model of plumbing product designed with different connection
size/diameter, compliant metal leaching test conducted on the smallest
size/diameter fitting is sufficed for the whole range of size/diameter of that model
of plumbing product as stated in the GA letter.
B2.2.6 Any product, or part of a product, installed within 250mL draw-off of a drinking
water delivery point shall be classified as ‘end-of-line’ fitting. ‘End-of-line’ fitting
shall comply with the extraction of metals procedure for testing in Appendix I of
AS/NZS 4020.
B2.2.7 Procedures for testing ‘in-line’ fittings shall comply with the stipulations in
Appendix H of AS/NZS 4020.
B2.2.8 The results of heavy metal concentrations from tests for ‘in-line’ fittings shall be
multiplied by appropriate Scaling Factors.
- 65 -
December 2021 version
B2.2.11 For test reports issued by laboratories under the MRA with HOKLAS, adjustment
on the final metal concentration by using the Scaling Factors above may be
necessary before acceptance of the products by the WSD.
B3. Review of Standards and Requirements
B3.1 The WA regularly reviews the standards and requirements stipulated for water
pipes, fittings and components to allow for innovation and changes in technology
and to ensure relevance.
B3.2 If standards for a plumbing material component are not stipulated in this TR, WA
shall be approached to confirm the necessary standards and requirements for
compliance.
B4. General Conditions for All Pipes, Fittings and Components for Use in Inside Service
B4.1 All pipes, fittings and components installed as Inside Service and/or Fire Service
shall comply with the conditions in this TR where applicable.
B4.2 The details below shall be clearly shown in all pipes, fittings and components
where applicable:-
(a) Body marking showing manufacturer's logo and/or brand name on product
body;
(b) Marking showing the Industrial Standard(s), e.g. BS EN 1057 for copper pipes;
and
(c) Marking showing nominal size and direction of flow.
B4.3 All non-metallic materials and products, that, when used, may come into contact
with water intended for human consumption must comply with all relevant
requirements in BS 6920-1:2014, BS 6920-2.1:2014, BS 6920-
2.2.1:2000+A3:2014, BS 6920-2.2.2:2000+A1:2014, BS 6920-
2.2.3:2000+A2:2014, BS 6920-2.3:2000+A1:2014, BS 6920-2.4:2000+A1:2014,
BS 6920-2.5:2000+A2:2014, BS 6920-2.6:2000+A2:2014 and BS 6920-3:2000.
B4.4 Non-metallic materials, intended for use in cold water supply systems, shall be
suitable for use up to the maximum water temperature of 35 oC and tested to this
concerned temperature under the BS 6920 series. For non-metallic materials
intended for use in hot water supply systems, the test temperature for High
- 66 -
December 2021 version
B4.5 The non-metallic materials shall only be installed in a potable water supply system
with a water temperature not exceeding the test temperature of the High
Temperature Tests.
B4.6 All pipes, fittings and components shall comply with all relevant statutory
requirement and the Standards stipulated by the WA.
- 67 -
December 2021 version
- 68 -
December 2021 version
- 69 -
December 2021 version
- 70 -
December 2021 version
- 71 -
December 2021 version
- 72 -
December 2021 version
Concerned Sections
Stainless Steel Compression Fittings
(AS 3688:2016 - Section 6)
Test item(s) Dimensions (Manufacture requirement)
- (Clause 3)
Leaktightness under internal pressure
test - (Clause 4.2 and Appendix D)
Strength of joint assembly (pressure
cycling test) - (Clause 4.4 and Appendix
F)
Resistance to pull-out of assembled
joints - (Clause 4.5 and Appendix G)
Chemical composition - (BS EN 10088-
1:2014)
Intergranular corrosion test (if
applicable) - (BS EN ISO 3651-2:1998)
- 73 -
December 2021 version
- 74 -
December 2021 version
- 75 -
December 2021 version
- 76 -
December 2021 version
- 77 -
December 2021 version
- 78 -
December 2021 version
Note:-
1) For non-metallic material in contact with fresh water intended for human consumption,
the materials shall comply with the relevant requirements in BS 6920:2014.
- 79 -
December 2021 version
B6. Valves
Category Valve
Type Flushing Valve
Category Valve
Type Gate Valve (Copper Alloy Body)
Category Valve
Type Gate Valve (Cast Iron Body/Ductile Iron
Body)
- 80 -
December 2021 version
Category Valve
Type Gate Valve (Cast Iron Body/Ductile Iron
Body)
Category Valve
Type Gate Valve (Steel Body)
- 81 -
December 2021 version
Category Valve
Type Check Valve (Copper Alloy Body)
Category Valve
Type Check Valve (Cast Iron/Ductile Iron/
Steel Body)
- 82 -
December 2021 version
Category Valve
Type Check Valve (Cast Iron/Ductile Iron Body)
Category Valve
Type Ball Valve (Copper Alloy Body)
- 83 -
December 2021 version
Category Valve
Type Ball Valve (Copper Alloy Body/Stainless
Steel Body)
Category Valve
Type Globe Valve (Copper Alloy Body)/
Check Valve (Copper Alloy Body)
Category Valve
Type Globe Valve (Steel Body)
- 84 -
December 2021 version
Category Valve
Type Globe Valve
(Cast Iron Body/Ductile Iron Body)
Category Valve
Type Butterfly Valve
- 85 -
December 2021 version
Category Valve
Type Ball Float Valve
Category Valve
Type Ball Float Valve
Category Valve
Type Ball Float Valve
- 86 -
December 2021 version
Category Valve
Type Ball Float Valve
Category Valve
Type Pressure Reducing Valve
- 87 -
December 2021 version
Category Valve
Type Hydrant Valve (Fire Hydrant Systems)
Category Valve
Type Valves (PVC-U)
- 88 -
December 2021 version
Category Valve
Type Valves (PE)
Note:-
1) For chemical composition test, the grade of material shall comply with BS EN
1982:2008, BS EN 12420:2014, BS EN 12163:2016, BS EN 12164:2016, BS EN
12165:2016, BS EN 12167:2016, BS EN 10088-1:2014, BS EN 10088-2:2014, BS EN
10088-3: 2014, BS EN 10283:2010 except those material grades specified by the
prescribed specification in WWR.
2) For non-metallic material in contact with fresh water intended for human consumption,
the materials shall comply with the relevant requirements in BS 6920:2014.
3) Apart from the prescribed components in the summary above, chemical composition
test shall be applied to metallic material in contact with water for a particular product
where applicable.
- 89 -
December 2021 version
B7. Taps/Mixers
Category Tap
Type Single Tap/
Combination Tap
- 90 -
December 2021 version
Category Tap/Mixer
Type Basin Mixing Valve/
Sink Mixing Valve/
Shower Mixing Valve/
Bath Mixing Valve/
Combination Draw-off Tap
- 91 -
December 2021 version
- 92 -
December 2021 version
- 93 -
December 2021 version
Category Tap
Type Self-Closing Draw-off Tap (Non-electronic)
Note:-
1) For chemical composition test, the grade of material shall comply with BS EN
1982:2008, BS EN 12420:2014, BS EN 12163:2016, BS EN 12164:2016, BS EN
12165:2016, BS EN 12167:2016, BS EN 10088-1:2014, BS EN 10088-2:2014, BS EN
10088-3: 2014, BS EN 10283:2010 except those material grades specified by the
prescribed specification in WWR.
2) For non-metallic material in contact with fresh water intended for human consumption,
the materials shall comply with the relevant requirements in BS 6920:2014.
3) Apart from the prescribed components in the summary above, chemical composition
test shall be applied to metallic material in contact with water for a particular product
where applicable.
4) The minimum flow rate requirements specified in the relevant prescribed specification
for the draw-off taps, single and combination taps in table above are waived.
- 94 -
December 2021 version
Remarks: Products shall comply with Waterworks Ordinance (Chapter 102), Waterworks
Regulations (Chapter 102A) and this Technical Requirements, including but not limited to
relevant clauses of the General Conditions stated in Part B of this Technical Requirements.
Remarks: Products shall comply with Waterworks Ordinance (Chapter 102), Waterworks
Regulations (Chapter 102A) and this Technical Requirements, including but not limited to
relevant clauses of the General Conditions stated in Part B of this Technical Requirements.
- 95 -
December 2021 version
- 96 -
December 2021 version
Category Others
Type Expansion Joint /
Settlement Joint /
Flexible Joint /
Rubber Joint
- 97 -
December 2021 version
Category Others
Type Strainer
- 98 -
December 2021 version
- 99 -
December 2021 version
- 100 -
December 2021 version
Note:-
1) For chemical composition test, the grade of material shall comply with BS EN
1982:2008, BS EN 12420:2014, BS EN 12163:2016, BS EN 12164:2016, BS EN
12165:2016, BS EN 12167:2016, BS EN 10088-1:2014, BS EN 10088-2:2014, BS EN
10088-3: 2014, BS EN 10283:2010 except those material grades specified by the
prescribed specification in WWR.
2) For non-metallic material in contact with fresh water intended for human consumption,
the materials shall comply with the relevant requirements in BS 6920:2014.
3) Apart from the prescribed components in the summary above, chemical composition
test shall be applied to metallic material in contact with water for a particular product
where applicable.
- 101 -
Appendix 1A – Essential Aspects of Plumbing Design in New Buildings
(For reference only.)
Section A – Connection
Essential items:
1. Provide site location plan in scale 1:1000
2. Provide connection layout plan with the following details:
(a) Show the lot boundary line clearly
(b) Show the location(s) of connection pipe(s)
(c) Show the size(s) of connection pipe(s) and size(s) to be justified by estimated
consumption
(d) Show the type of connection (single/dual/twin)
(e) [For FS]: provide independent connection for FS
(f) [For FS]: provide appropriate type of connection (single/dual feed)
Example: Connection details (Fresh and Flushing Water Supply)
GOVERNMENT FRESH WATER SUPPLY MAIN
GOVERNMENT FLUSHING WATER SUPPLY MAIN
ΦXXX FRESH WATER SUPPLY PIPE
ΦXXX FLUSHING WATER SUPPLY PIPE
Street name
Street name
INTERVENING VALVE
Street name
Street name
Fig. 1 Typical configuration of Master meter and Sub-meter chambers in Multiple-Block Development
Fig. 2 Typical configuration of Master meter and Sub-meter chambers in Single-Block Development
GOVERNMENT PREMISE WITH NO BLOCK BLOCK/
SINGLE BUILDING BLOCK
MM required
Fig. 3 Typical configuration of Master meter and Sub-meter chambers in Development with no Building Block or
Single-Block Development
Section B – Master Meter (MM), sub-meters (SM), check meters (CM) details
3A. [MM]: Pipe diameter ≤ 100mm
master meter box/cabinet, details conforms to Fig. 3.
Master Meter
M
600mm Clearance
(min) for 1000mm height: DOOR
door closing (min) 2000mm
inward (min)
DOOR
Trade/Commercial premises:
Laundry:
Hospital: the required storage criterion is one day’s consumption as given by hospital
authorities
Industrial use: one-day demand
Boilers: The required storage criterion is given in the following formula:
Overflow pipe
and warning pipe Overflow pipe
Ball float valve Ball float valve Overflow pipe
discharge to Ball float valve and warning pipe
(for gravity supply) (for flushing and warning pipe
conspicuous (for gravity supply) discharge to
supply) discharge to
position conspicuous conspicuous
Automatic control position position
Automatic control
switch Outlet pipe
switch Drain pipe
Outlet pipe (for pumped supply) (for pumped supply) Outlet pipe
Meter Group
800mm
M
(max) for Clearance
600mm
1000mm meter box height: DOOR
(min) for 2000mm
(min)
door (min)
closing
inward
DOOR
Clearance width: 800mm (min)
Display
board
M
200
M
200
1800 M
(max) 200
M 1500
200 (max)
M
200
M
300
FLOOR LEVEL
FLOOR DRAIN
All units are in millimeters.
Fig. 11 Typical layout of 15mm meter position in a meter room/box/cabinet
(d) Minimum clernace should be provided for meters of trade supply according to Fig. 11a
Fig. 11a
Section E – Other Miscellaneous details
1. [FW]: Water using appliances and other water application
Prevention of backflow device(s) to be provided in the following applications:
Application Backflow prevention devices
Irrigation (outlet >150mm above soil Check-valve/non-return valve
level, no fertilizer or insecticides, double check valve
manual point supply) anti-vaccum vavle
General ablution (basin, showers)
Fire services
Irrigation (outlet <150mm above soil Break tank
level, no fertilizer or insecticides, Backflow preventer/Reduced Pressure
drip-feed pipes) Zone Device
Kitchen with submerged inlet
Commercial lanudries
Industrial processes
Fig. 12 Typical layout of unvented electric thermal storage type water heater
Section E – Other Miscellaneous details
4. Layout of pressure type thermal storage heater conform to Fig. 13.
Fig. 13 Typical layout of pressure type thermal storage type water heater
5. Gas Geysers installed on top floor through storage cistern:
low pressure governors required when head available < 5m at the highest hot water
draw-off point
6. Cold water supply to mixing valves, water blenders or combination fittings:
drawn by same source as is supplying the hot water apparatus
[Centralized HW]
7. Layout conform to Fig. 14.