Autronica AutroPrimeFireDetectionHandbook TM
Autronica AutroPrimeFireDetectionHandbook TM
Configuration Handbook
116-P-APRIME-CONFIGU/EGB 2007-11-27
COPYRIGHT ©
Table of Contents
1. Introduction.......................................................................6
1.1 About the Handbook ......................................................................... 6
1.2 The Reader ....................................................................................... 6
1.3 Reference Documentation ................................................................ 6
1.4 Ready-to-use in a Pre-configured State............................................ 7
1.5 Saving a Configuration and Restarting the System .......................... 7
1.6 Configuration Examples .................................................................... 7
Page 1
Table of Contents
Page 2
Table of Contents
Page 3
Table of Contents
9. Configuration Examples...................................................98
9.1 Before you Start ................................................................................ 98
9.2 Example 1: Basic Configuration Example......................................... 99
9.2.1 Site information – Excel Sheet................................................ 100
9.2.2 Buttons .................................................................................... 100
9.2.3 Initial Startup – Default Configuration ..................................... 101
9.2.4 Save Configuration / Restart System...................................... 101
9.2.5 Site-specific Configuration – Example 1 ................................. 102
9.2.6 Step 1: Create Detection Zones and Connect Points............. 103
9.2.7 Add a Site-specific Name to each Point (if needed) ............... 104
9.2.8 Step 2: Connect the new Detection Zones to the Alarm
Zone ........................................................................................ 105
9.2.9 Step 3: Save Configuration / Restart System ......................... 105
9.3 Example 2: Configuration with several alarm zones and control
functions ............................................................................................ 106
9.3.1 Site-specific Configuration – Example 2 ................................. 108
9.3.2 Step 1: Create Detection Zones and Connect Points............. 109
9.3.3 Add a Site-specific Name to each Point (if needed) ............... 110
9.3.4 Step 2: Connect Fire Alarm Devices to new alarm zones
(5.5.3)...................................................................................... 111
9.3.5 Step 3: Connect already configured detection zones to a
new alarm zone (Alarm Zone 1). (5.2.3) ................................. 111
9.3.6 Step 4: Connect the new detection zones to a new alarm
zone (Alarm Zone 2). (5.2.3)................................................... 112
9.3.7 Step 5: Define Alarm Zone 1 and Alarm Zone 2 as
Neighbour Alarm Zones (5.3.3) .............................................. 112
9.3.8 Step 6: Connect a point in Detection Zone 6 to the Parent
Alarm Zone (5.2.3) .................................................................. 113
9.3.9 Step 7: Configure outputs for ventilation control and door
control (5.4.4 and 5.2.4).......................................................... 113
9.3.10 Step 8: Save Configuration / Restart System ......................... 114
Page 4
Table of Contents
Page 5
Introduction
1. Introduction
Page 6
Introduction
By default the system has one Detection Zone and one Alarm Zone. A
point in alarm will activate all Fire Alarm Devices and Fire Alarm
Routing Equipment.
Page 7
Service Commands
2. Service Commands
All these options and many more are available in the Service menu.
Page 8
Service Commands
Save Configuration
Restart System
Enter Service Mode Day Mode Operation Times
Service Mode Password
Date and Time
Sound Patterns
Automatic Resound
DZ Delay Timers
DZ Global Dependency
Battery Parameters Connect to Alarm Zone
Panel Name Connect to Output
Connect to Disable Input Device
Language Connect to Panel (special panel only)
FARE and FWRE Disablement Disconnect from Alarm Zone
Mains Power Fault Indication Disconnect from Output
Disconnect from Disable Input Device
System Shutdown Disconnect from Panel (special panel only)
Restore Factory Settings Show Member Points
Service System Settings Show Connected Units
Loop Operation Enable Connect to Neighbour Alarm Zone
Unit Configuration Disable Disconnect from Neighbour Alarm Zone
Unit Test Change Disable Time Span Show Member Fire Alarm Devices
Show Neighbour Alarm Zones
System Topology Show Polluted Detectors Show Activating Detection Zones
Export and Import
Move to Detection Zone (/Create New)
Connect to Output
Connect to Activation Group (/Create New)
(Functions) Disconnect from Output
Detection Zones Disconnect from Activation Group
Show Connected Units
Alarm Zones
Points
Fire Alarm Devices Move to Alarm Zone
Show Connected Units
Loop Outputs
Local Outputs
Loop Inputs (Not applicable to FAD, FARE and FWRE:)
Connect to Output
Local Inputs Connect to Activation Group
Mimic Panels Disconnect from Output
Activation Groups Disconnect from Activation Group
Show Activating Detection Zones
External Interfaces Show Activating Points
Detection Loops Show Activating Inputs
Operator Panels Show Activating Groups
Show Activating Outputs
Connect to Output
Disconnect from Output
(Applicable only if Mimic Show Connected Units
Panels are used)
Configure
Show Mimic Inputs
Show Mimic Outputs
Connect to Output
Disconnect from Output
Show Member Points
Show Connected Units
Detection Zones
Serial Port Settings
Alarm Zones Ethernet Port Settings
Fire Alarm Devices ESPA
Loop Outputs MODBUS
VDR
Local Outputs
Exit Service Mode
Mimic Panels
Show Topology
Show Faults
Clear Loop Config. – Restart System
Deactivate/Activate
Refresh Topology
Export Log
Select Configuration & Restart System
Backup Current Configuration
Export Configuration
Import Configuration
116-P-APRIMEMENUSTR/MGB, 2007-11-27
Page 9
Service Commands
• First, to enter the Menu Mode from operation mode or the panel’s
idle state, press and hold down the Enter button for a few
seconds.
• Use the arrow down button to scroll down and select Enter Service
Mode.
• Press Enter twice, then use the alphanumeric keypad and type the
password that has been selected during commissioning (4
characters).
The menu selections Service and Exit Service now appear in the
display.
Page 10
Service Commands
To enter the Service menu, use the arrow down button to scroll down
and select Service, then press the Enter.
Page 11
System Settings
3. System Settings
)
• Press the arrow down button to select Save Configuration, then
)
press Enter twice.
• Type a new Site Name, or accept the existing one by pressing the
arrow down button.
• Type a new Operator Name, or accept the existing one by pressing
the arrow down button.
• Press Enter to type a new Site Configuration Version then press
Enter, or accept the existing one by pressing the arrow down
button.
• Press Enter to type a new Description then press Enter, or accept
the existing one by pressing the arrow down button.
To confirm, press Enter.
Page 12
System Settings
)
changed, the following message will appear:
”System configuration data has been changed. If the system is
restarted without saving configuration data, the changes will be
lost. Save data before restarting?”
o Use the left arrow button to select Accept, then press Enter
twice.
o Type a new Site Name, or accept the existing one by pressing
the arrow down button.
o Type a new Operator Name, or accept the existing one by
pressing the arrow down button.
o Press Enter to type a new Site Configuration Version then press
Enter, or accept the existing one by pressing the arrow down
button.
o Press Enter to type a new Description then press Enter, or
accept the existing one by pressing the arrow down button.
o To confirm, press Enter.
After a short period the message “Configuration has been
saved” will appear.
o Press the left arrow button, then press Enter to confirm.
Page 13
System Settings
The system menu Day Mode Operation Times allows you to configure
settings for automatic delay of the activation of outputs to Fire Alarm
Devices (FAD) and/or Fire Alarm Routing Equipment (FARE) at
certain periods.
The settings will only affect points that have been set to “Override
Delay and Dependency NO” in detection zones configured as Delayed
Action Detection Zones or Delayed Dependency Detection Zones.
To achieve this, you simply choose the days in the week when you
want the system to automatically enable the delays, plus the exact
duration of the disablement in hours and minutes (the start time and
end time).
)
o Unspecified
o Every day
o Monday to Friday
o Saturday, Friday, Thursday, Wednesday, Tuesday, Monday,
Sunday.
• Press Enter.
• Use the alphanumeric keypad to specify the start time*
(hours:minutes), then press Enter.
• Specify the end time* (hours:minutes), then press Enter.
Page 14
System Settings
The number of times you have to press the arrow down button
before “Unspecified” is shown in the display depends on the
number of settings that already are defined.
Page 15
System Settings
)
• Press the arrow down button to select Service Mode Password,
then press Enter twice.
• Type the new password, then press Enter.
• Type the new password once more, then press Enter.
• To confirm the new password, press Enter once more.
The message “Please wait…” will appear in the display and the
new password will take effect within a couple of seconds.
)
• Press the arrow down button to select Date and Time, then press
Enter twice.
• To change the time, overwrite the time (hours, minutes, seconds),
then press Enter.
• To change the date, overwrite the date (day, month, year), then
press Enter.
• To confirm the new settings, press Enter once more.
Page 16
System Settings
Pattern Activation
Detection zones are connected to alarm zones (Main Alarm Zones).
An alarm signal from the detection zones activates the EVACUATE
pattern in these alarm zones. Neighbour Alarm zones may be
connected to the Main Alarm Zones. The Neighbour Alarm Zones will
have the ALERT pattern activated.
Prolong Signal: It is possible to prolong the last signal (i.e. the last
bit) for a chosen sound pattern from 1 to a maximum of 99 seconds.
bits 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
0=OFF 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
1=ON
)
• Press the arrow down button to select Sound Patterns, then press
Enter.
• Scroll downwards to select the desired Sound Pattern, then press
Enter twice.
• To change the pattern, use the Cancel button to delete the bits,
then type the new ones and press Enter. To change the bit values,
use the arrow down/up buttons.
• To prolong the last signal, type the seconds (from 1 to 99), then
press Enter.
• To confirm the new settings, press Enter once more.
Page 17
System Settings
Holding the Silence button down for more than 5 seconds will activate
the Resound function (this message appears in the information field).
)
• Press the arrow down button to select Automatic Resound, then
press Enter twice.
• To select YES, press the right arrow button, then press Enter.
• To change the Time Delay, use the Cancel button to delete it,
then type the new one and press Enter.
• To confirm the new settings, press Enter once more.
The delay is divided into two (configurable) delay periods, Initial delay,
T1 and Prolonged Delay, T2.
• The default value for T1 is 60 seconds
• The default value for T2 is 120 seconds.
• The maximum delay (T1 plus T2) is 10 minutes (600 seconds).
The (T1) delay period is started when a Fire Alarm signal from a point
is received. Actions will be initiated after the T1 delay period has
expired. Pressing the Prolong Delay button, will terminate T1 and the
delay period T2 will start.
)
• Press the arrow down button to select Detection Zone Delay
Timers, then press Enter twice.
• To change the delay timers, use the Cancel button to delete the
present T1 Delay Timer (seconds), then type the new one and
press Enter.
• Repeat this procedure for the T2 Delay Timer, then press Enter.
• To confirm the new settings, press Enter once more.
Page 18
System Settings
A fire alarm signal from a single detector will initiate no actions, i.e.
there will be no actioning of outputs to;
• Fire Alarm Devices (FAD)
• Fire Alarm Routing Equipment (FARE)
• Fire Protection Equipment (FPE)
)
• Press the arrow down button to select DZ Global Dependency,
then press Enter.
)
press Enter twice.
• Press the right arrow button to select the minimum charge voltage
(default 21000mV, minimum 20000mV, maximum: 31000mV),
then press Enter.
• Press the right arrow button to select the battery low voltage limit
(default 21000mV, minimum 17900mV, maximum: 31000mV),
then press Enter.
• Press the right arrow button to select the maximum charge
current (default 1500mA, minimum 1000mA, maximum: 2000mA),
then press Enter.
• Press the right arrow button to select the maximum resistance limit
(default 800mOhm, minimum 200mOhm, maximum: 5000 mOhm),
then press Enter.
• To confirm the new setting, press Enter once more.
Page 19
System Settings
)
• Press the arrow down button to select Panel Name, then press
Enter twice.
The current Panel Name will appear.
• Press Enter, then overwrite the Name. The Panel Type will
appear in the display.
• To confirm the new Name, press Enter.
• Use the Cancel button to leave this menu selection.
3.13 Language
This menu allows you to change the language.
)
• Press the arrow down button to select Language, then press
Enter twice.
• To select the desired language, use the left arrow button to the
language appears in the display, then press Enter.
• To change the date, overwrite the date (day, month, year), then
press Enter.
• To confirm the new language, press Enter once more.
The message “Please wait…” will appear in the display, meaning
that the selected language file is now being imported. The import
of the new language file may take a couple of minutes.
Page 20
System Settings
Note that the disablement will only have effect on the system when
the system is in access level 2 or 3.
)
• Press the arrow down button to select FARE and FWRE
Disablement, then press Enter twice.
• To disable FARE in access level 2 and 3, use the right arrow
button to select YES, then press Enter.
• To disable FWRE in access level 2 and 3, use the right arrow
button to select YES, then press Enter.
• To confirm the settings, press Enter once more.
)
• Press the arrow down button to select Mains Power Fault
Indication, then press Enter twice.
• Type the desired number of minutes (Delay Fault Indication), then
press Enter.
• Use the right arrow button to choose whether you want to disable
the outputs to Fire Warning Routing Equipment (YES/NO), then
press Enter.
• To confirm the settings, press Enter once more.
Page 21
System Settings
)
• Press the arrow down button to select System Shutdown.
• Press Enter, and the following message will appear in the display:
• To execute the command, use the left arrow button, then press
Enter.
Note that all configuration data will be deleted, and the system will
return to its pre-configured state (factory settings).
)
• Press the arrow down button to select Restore Factory Settings.
• Press Enter, and the following message will appear in the display:
• To execute the command, use the left arrow button, then press
Enter.
Page 22
Loop Operation
4. Loop Operation
)
• Use the arrow up/down buttons to select the detection loop in
question.
• Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
Page 23
Loop Operation
4.2 Enable
This menu selection allows you to enable detection loops that are
currently disabled. To execute the command, access level 3 is
required.
)
• After pressing the Function button for the selected detection
loop(s), select Enable (the first menu selection), then press Enter.
• To confirm the enablement, press Enter once more.
4.3 Disable
During service a technician is able to disable one or several loops. To
execute the command, access level 3 is required.
)
loop(s), use the arrow down button to select Disable, then press
Enter twice.
• Enter the hours and minutes, then press Enter.
• To confirm the disablement, press Enter once more.
Page 24
Loop Operation
)
loop(s), use the arrow down button to select Change Disable
Time Span, then press Enter twice.
• Enter the hours and minutes, then press Enter.
• To confirm the new disable time span, press Enter once more.
The menu also allows you to reset the compensation level for units
exceeding the limit.
)
Detectors, then press Enter twice.
• Use the alpanumeric keypad to specify a limit for dust pollution,
then press Enter.
• To confirm the setting, press Enter once more.
Page 25
Unit Configuration
5. Unit Configuration
Page 26
Unit Configuration
)
• To view or change properties for the selected detection zone
(name and alarm organization), refer to Configure Properties for
a Detection Zone (chapter 5.2.2).
• Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
Page 27
Unit Configuration
Note that the default Detection Zone will always have the detection
zone type “Immediate Action”, i.e. it cannot be changed.
)
• Type a new Name then press Enter, or accept the existing one by
pressing the arrow down button.
• If the detection zone is the default detection zone, press Enter to
confirm the setting.
• Use the left or right arrow button to select the detection zone
type, then press Enter.
• To confirm the setting, press Enter once more.
Page 28
Unit Configuration
)
zone(s), select Connect to Alarm Zone (the first menu selection),
then press Enter.
• Use the arrow down button to select an existing alarm zone.
• Press Enter to connect the detection zone to this alarm
zone.
• To confirm the setting, press Enter once more.
)
zone(s), use the arrow down button to select Connect to Output,
then press Enter.
Only local outputs of the type General Output will be listed.
• Use the arrow down button to select the output, then press Enter
twice.
• Use the arrow left/right buttons to select the Detection Activation
State (Prealarm, Small Alarm, Large Alarm, Silent Alarm), then
press Enter.
• To confirm the setting, press Enter once more.
Page 29
Unit Configuration
)
• After pressing the Function button for the selected detection
zone(s), use the arrow down button to select Connect to Disable
Input Device, then press Enter twice.
• Use the arrow button to select the Disable Input Device, then
press Enter.
• To confirm the setting, press Enter once more.
)
• After pressing the Function button for the selected detection
zone(s), use the arrow down button to select Connect to Panel,
then press Enter twice.
• Use the arrow button to select the Panel, then press Enter.
• To confirm the setting, press Enter once more.
)
• After pressing the Function button for the selected detection
zone(s), use the arrow down button to select Disconnect from
Alarm Zone, then press Enter twice.
• Use the arrow down/up button to select the alarm zone to be
disconnected, then press Enter.
• To confirm the setting, press Enter once more.
Page 30
Unit Configuration
)
• After pressing the Function button for the selected detection
zone(s), use the arrow down button to select Disconnect from
Output, then press Enter twice.
• Use the arrow down/up button to select the output to be
disconnected, then press Enter.
• To confirm the setting, press Enter once more.
)
• After pressing the Function button for the selected detection
zone(s), use the arrow down button to select Disconnect from
Disable Output Device, then press Enter twice.
• Use the arrow down/up button to select the device to be
disconnected, then press Enter.
• To confirm the setting, press Enter once more.
)
• After pressing the Function button for the selected detection
zone(s), use the arrow down button to select Disconnect from
Panel, then press Enter twice.
• Use the arrow down/up button to select the panel to be
disconnected, then press Enter.
• To confirm the setting, press Enter once more.
Page 31
Unit Configuration
)
Points, then press Enter.
• To view detailed information for a selected point, use the arrow
down/up button to select the point, then press Enter.
)
zone(s), use the arrow down button to select Show Connected
Units, then press Enter.
• To view detailed information (name, parent alarm zone and
immediate activation status) for all connections related to a
selected detection zone, use the arrow down/up button to select
an alarm zone, then press Enter.
Page 32
Unit Configuration
)
Enter once more.
• Use the arrow up/down buttons to select the alarm zone that
is to be configured.
• To view or change properties for the selected alarm zone
(name), refer to Configure Properties for an Alarm Zone (chapter
5.3.2).
• Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
Page 33
Unit Configuration
)
• Type a new Name, or accept the existing one by pressing the
arrow down button.
• Press Enter.
• Use the left or right arrow button to select a Parent Alarm Zone,
then press Enter.
• Use the right or left arrow buttons to choose whether you want
Immediate Activation or not (YES/NO), then press Enter.
• To confirm the setting, press Enter once more.
)
select Connect to Neighbour Alarm Zone (the first menu
selection), then press Enter.
• From the list of alarm zones, select an alarm zone that is to be
defined as a neighbour alarm zone, then press Enter.
• To confirm the setting, press Enter once more.
•
• If you want to define another alarms zone as neighbour alarm zone
to the selected alarm zone, repeat the procedure above.
Page 34
Unit Configuration
)
use the arrow down button to select Disconnect Neighbour
Alarm Zone, then press Enter.
• A list will appear, listing all alarm zones that have neighbourhood
relations.
)
use the arrow down button to select Show Member Fire Alarm
Devices, then press Enter.
A list of all Fire Alarm Devices (FADs) will appear in the display.
• Use the arrow down button to select the FAD in question, then
press Enter.
The name of the FAD and the unit function will appear in the display.
)
use the arrow down button to select Show Neighbour Alarm
Zones, then press Enter.
• Use the arrow down button to select the Neighbour Alarm Zone
in question, then press Enter.
The name of the Neighbour Alarm Zone and the unit function will
appear in the display.
Page 35
Unit Configuration
)
use the arrow down button to select Show Activating Detection
Zones, then press Enter.
The name of the Detection Zone and the alarm organization will
appear in the display.
Page 36
Unit Configuration
5.4 Points
)
• Use the arrow up/down buttons to select the point that
is to be configured.
• Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
Page 37
Unit Configuration
)
• Type a new Name then press Enter, or accept the existing one by
pressing the arrow down button.
• Use the left or right arrow button to select Yes or No (Override
Delay and Dependency or not), then press Enter.
• Use the left or right arrow button to select the desired
performance class day setting, then press Enter.
• Use the left or right arrow button to select the desired
operation class day setting, then press Enter.
• Use the left or right arrow button to select the desired
performance class night setting, then press Enter.
• Use the left or right arrow button to select the desired
operation class night setting, then press Enter.
• To confirm the setting, press Enter once more.
Page 38
Unit Configuration
When creating a new detection zone, the alarm organization for the
new detection zone is determined (refer to Detection Zone / Configure
Properties, chapter 5.2.2).
)
then press Enter.
Page 39
Unit Configuration
)
Connect to Output, then press Enter.
Page 40
Unit Configuration
Page 41
Unit Configuration
)
the arrow down button to scroll downwards to
Disconnect from Output, then press Enter.
In the display you will now see a list of all outputs that are connected
to the selected point .
)
the arrow down button to scroll downwards to
Disconnect from Activation Group, then press Enter.
Page 42
Unit Configuration
)
• After pressing the Function button for the selected point(s), use
the arrow down button to scroll downwards to
Show Connected Units, then press Enter.
A list will appear in the display, showing all detection zones, outputs
etc. that are activated by the selected point.
Page 43
Unit Configuration
)
press Enter once more.
• Use the arrow up/down buttons to select the Fire Alarm Device
that is to be configured.
• Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
Page 44
Unit Configuration
)
• Type a new Name and press Enter, or accept the existing one by
pressing the arrow down button.
• To confirm the setting, press Enter once more.
)
• After pressing the Function button for the selected FAD(s), select
Move to Alarm Zone (the first menu selection), then press Enter.
• Use the arrow button to select an existing alarm zone, or select
the menu Create New Alarm Zone.
o If an existing alarm zone is selected, press Enter twice to
connect the detection zone to this alarm zone.
o If a new alarm zone is to be created, select Create New
Alarm Zone, press Enter twice, type the name, then press
Enter.
o Use the left/right arrow buttons to select the Parent Alarm
Zone”, then press Enter twice to confirm.
Page 45
Unit Configuration
)
• After pressing the Function button for the selected FAD(s), use
the arrow down button to select Show Connected Units,
then press Enter.
In the display you will now see the alarm zone that belongs to the
selected Fire Alarm Device.
Page 46
Unit Configuration
)
that is to be configured (if any).
• To view or change properties for the selected Loop Output, refer
to Configure Properties for a Loop Output (chapter 5.6.2).
• Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
Page 47
Unit Configuration
)
• Press Enter, then use the arrow left/right buttons to select among
the unit functions that are available for the selected Loop Output
(see overview below).
• Press Enter.
• To confirm the setting, press Enter once more.
Page 48
Unit Configuration
Output 2
Loop
Output 1
Output 3
Note that the menu selection does not apply to Fire Alarm Devices
(FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning
Routing Equipment (FWRE).
)
select Connect to Output (the first menu selection), then press
Enter.
Note that the menu selection does not apply to Fire Alarm Devices
(FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning
Routing Equipment (FWRE).
)
use the arrow down button to scroll downwards to Connect to
Activation Group, then press Enter.
• Use the arrow up/down button to select the activation group that
is to be connected to the loop output, then press Enter.
• To confirm the setting, press Enter once more.
Page 49
Unit Configuration
Output 2
Loop
Output 1
Output 3
Note that the menu selection does not apply to Fire Alarm Devices
(FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning
Routing Equipment (FWRE).
)
use the arrow down button to scroll downwards to
Disconnect from Output, then press Enter.
In the display you will now see a list of all outputs that are connected
to the selected loop output.
Note that the menu selection does not apply to Fire Alarm Devices
(FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning
Routing Equipment (FWRE).
)
use the arrow down button to scroll downwards to
Disconnect from Activation Group, then press Enter.
In the display you will now see a list of all activation groups that are
connected to the selected loop output.
Page 50
Unit Configuration
Note that the menu selection does not apply to Fire Alarm Devices
(FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning
Routing Equipment (FWRE).
)
• After pressing the Function button for the selected Loop
Output(s), use the arrow down button to scroll downwards to
Show Activating Detection Zones, then press Enter.
In the display you will now see a list of all detection zones that are
connected to the selected loop output.
Note that the menu selection does not apply to Fire Alarm Devices
(FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning
Routing Equipment (FWRE).
)
• After pressing the Function button for the selected Loop
Output(s), use the arrow down button to scroll downwards to
Show Activating Points, then press Enter.
In the display you will now see a list of all points that are connected
to the selected loop output.
Page 51
Unit Configuration
Note that the menu selection does not apply to Fire Alarm Devices
(FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning
Routing Equipment (FWRE).
)
• After pressing the Function button for the selected Loop
Output(s), use the arrow down button to scroll downwards to
Show Activating Inputs, then press Enter.
In the display you will now see a list of all inputs that are connected
to the selected loop output.
Note that the menu selection does not apply to Fire Alarm Devices
(FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning
Routing Equipment (FWRE).
)
• After pressing the Function button for the selected Loop
Output(s), use the arrow down button to scroll downwards to
Show Activating Groups, then press Enter.
In the display you will now see a list of all activation groups that are
connected to the selected loop output.
Page 52
Unit Configuration
Note that the menu selection does not apply to Fire Alarm Devices
(FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning
Routing Equipment (FWRE).
)
• After pressing the Function button for the selected Loop
Output(s), use the arrow down button to scroll downwards to
Show Activating Outputs, then press Enter.
In the display you will now see a list of all outputs that are connected
to the selected loop output.
Note that the menu selection does not apply to Fire Alarm Routing
Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
)
• After pressing the Function button for the selected Loop
Output(s), use the arrow down button to scroll downwards to
Show Connections, then press Enter.
In the display you will now see a list of all connections that are
connected to the selected loop output.
Page 53
Unit Configuration
)
• To view or change properties for the selected Local Output, refer
to Configure Properties for a Local Output (chapter 5.7.2).
• Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
Page 54
Unit Configuration
)
the following unit functions:
o Fire Alarm Device:
equipment giving warning of fire, for example, a sounder or visual
indicator.
o Disable Out:
output that is activated when there are disablements in the
system
o General Output:
output that is activated according to the configured events, for
example, Pre Alarm, Alarm, Input Activated etc.
o RESET Out:
output activated for approx. 2 seconds when the Reset button
is operated.
o Silent Alarm Output:
output dedicated to be activated at Silent Alarm regardless of alarm
origin
o Silence Out:
output activated for approx. 2 seconds when the Silence button is
operated
o Small Alarm Output:
output dedicated to be activated at Small Alarm regardless of alarm
origin
o Fire Alarm Routing Equipment (FARE):
equipment routing an alarm signal from control and indicating
equipment to a Fire Alarm Receiving Station.
o Fault Warning Routing Equipment (FWRE):
equipment routing a fault warning signal from control and indicating
equipment to a fault warning receiving station.
• Press Enter.
• To confirm the setting, press Enter once more.
Page 55
Unit Configuration
Note that the menu selection does not apply to Fire Alarm Devices
(FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning
Routing Equipment (FWRE).
)
select Connect to Output (the first menu selection), then press
Enter.
Note that the menu selection does not apply to Fire Alarm Devices
(FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning
Routing Equipment (FWRE).
)
use the arrow down button to scroll downwards to Connect to
Activation Group, then press Enter.
• Use the arrow up/down button to select the activation group that
is to be connected to the local output, then press Enter.
• To confirm the setting, press Enter once more.
Page 56
Unit Configuration
Note that the menu selection does not apply to Fire Alarm Devices
(FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning
Routing Equipment (FWRE).
)
use the arrow down button to scroll downwards to
Disconnect from Output, then press Enter.
In the display you will now see a list of all outputs that are connected
to the selected local output.
Note that the menu selection does not apply to Fire Alarm Devices
(FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning
Routing Equipment (FWRE).
)
use the arrow down button to scroll downwards to
Disconnect from Activation Group, then press Enter.
In the display you will now see a list of all Activation Groups
that are connected to the selected local output.
Page 57
Unit Configuration
Note that the menu selection does not apply to Fire Alarm Devices
(FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning
Routing Equipment (FWRE).
)
use the arrow down button to scroll downwards to
Show Activating Detection Zones, then press Enter.
In the display you will now see a list of all detection zones that are
connected to the selected local output.
The name of the detection zone and unit function will appear in the
display.
Note that the menu selection does not apply to Fire Alarm Devices
(FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning
Routing Equipment (FWRE).
)
use the arrow down button to scroll downwards to
Show Activating Points, then press Enter.
In the display you will now see a list of all points that are connected
to the selected local output.
• Use the arrow up/down button to select a point, then press Enter.
Page 58
Unit Configuration
Note that the menu selection does not apply to Fire Alarm Devices
(FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning
Routing Equipment (FWRE).
)
use the arrow down button to scroll downwards to
Show Inputs, then press Enter.
In the display you will now see a list of all inputs that are connected
to the selected local output.
• Use the arrow up/down button to select an input, then press Enter.
Note that the menu selection does not apply to Fire Alarm Devices
(FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning
Routing Equipment (FWRE).
)
Show Activation Groups, then press Enter.
In the display you will now see a list of all activation groups that are
connected to the selected local output.
Page 59
Unit Configuration
Note that the menu selection does not apply to Fire Alarm Devices
(FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning
Routing Equipment (FWRE).
)
use the arrow down button to scroll downwards to
Show Outputs, then press Enter.
In the display you will now see a list of all outputs that are connected
to the selected local output.
Note that the menu selection applies to Fire Alarm Devices (FAD)
only.
)
use the arrow down button to select Move to Alarm Zone, then
press Enter.
• Use the arrow button to select an existing alarm zone, or select
the menu Create New Alarm Zone.
o If an existing alarm zone is selected, press Enter twice to
connect the local output to this alarm zone.
o If a new alarm zone is to be created, select Create New
Alarm Zone, press Enter twice, type the name, then press
Enter.
o Use the left/right arrow buttons to select the Parent Alarm
Zone, then press Enter twice to confirm.
Page 60
Unit Configuration
Note that the menu selection does not apply to Fire Alarm Routing
Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
)
use the arrow down button to scroll downwards to
Show Connections, then press Enter.
In the display you will now see a list of all connections that are
connected to the selected local output.
In the display you will now see the name and unit function.
Page 61
Unit Configuration
)
press Enter once more.
• Use the arrow up/down buttons to select the Loop Input
that is to be configured.
• To view or change properties for the selected Loop Input, refer
to Configure Properties for a Loop Input (chapter 5.8.1.1).
• Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
Page 62
Unit Configuration
• supervisory (Yes/No);
If Yes is selected, the inputs that are defined for technical alarms
will be activated during normal operation, meaning that an
indication of an event will appear in the display (supervisory text)
on the activation of the loop input. The panel will be in Supervisory
Condition.
)
arrow down/up buttons, press Enter twice.
• Type a new Name, or accept the existing one by pressing the
arrow down button.
• Press Enter.
• Use the left/right arrow buttons to select Supervisory:Yes or No,
then press Enter.
• To confirm the setting, press Enter once more.
Page 63
Unit Configuration
)
select Connect to Output (the first menu selection), then press
Enter.
)
use the arrow down button to scroll downwards to
Disconnect from Output, then press Enter.
In the display you will now see a list of all outputs (if any) that are
connected to the selected loop input.
)
use the arrow down button to scroll downwards to
Show Connected Units, then press Enter.
In the display you will now see a list of all connections (if any) that
are connected to the selected loop input.
In the display you will now see the name and unit function of the
connections that are connected to the selected loop input.
Page 64
Unit Configuration
)
press Enter once more.
• Use the arrow up/down buttons to select the Local Input
that is to be configured.
• To view or change properties for the selected Local Input, refer
to Configure Properties for a Local Input (chapter 5.9.2).
• Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
Page 65
Unit Configuration
)
among the following unit functions:
o Day/Night Input:
input used for Day/Night Mode
o User Configurable Input:
input to be used for Supervisory function or general output
activation
o Morse Input:
input that activates onboard Fire Alarm Devices (local outputs)
similar to a morse key
o Mute FAD Input:
input that turns all FADs off while active
o Reset In Input:
input used as an external System Reset (similar to operating
the Reset button)
o Silence In Input:
input used as an external silence of Fire Alarm Devices (similar
to operating the Silence button)
o FARE Feedback:
input used as an acknowledge signal from the Fire Alarm
receiving station, activates a separate LED on the panel
o Activate All Alarms*:
input used to activate all Fire Alarm Devices with a selectable
sound pattern
o FWRE:
It is possible to use a monitored input for the FWRE function.
This requires a special electrical connection using, for example,
an optocoupler.
• Press Enter, use arrow left/right arrow buttons to select
Supervisory YES or NO (where applicable), then press Enter.
• Type a Supervisory text (where applicable), then press Enter.
• State the hardware type, then press Enter.
• To confirm the setting, press Enter once more.
Page 66
Unit Configuration
)
select Connect to Output (the first menu selection), then press
Enter.
)
use the arrow down button to scroll downwards to
Disconnect from Output, then press Enter.
In the display you will now see a list of all outputs that are connected
to the selected local input.
)
use the arrow down button to scroll downwards to
Show Connected Units, then press Enter.
In the display you will now see a list of all connections that are
connected to the selected local input.
In the display you will now see the name and unit function of the
connections that are connected to the selected local input.
Page 67
Unit Configuration
)
press Enter once more.
• Use the arrow up/down buttons to select the mimic panel
that is to be configured.
• Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
)
• After selecting the mimic panel in question by means of the
arrow down/up buttons, press Enter twice.
• Type a new Name, or accept the existing one by pressing the
arrow down button.
• Press Enter
• To confirm the setting, press Enter once more.
Page 68
Unit Configuration
)
Show Mimic Inputs, then press Enter.
In the display you will now see a list of all Mimic Inputs.
The name and function (UGI) of the mimic panel will appear in the
display.
• Connect to output
• Disconnect from output
• Show connected units
)
Show Mimic Outputs, then press Enter.
In the display you will now see a list of all Mimic Outputs.
• name
• function
• output activation delay
• activation group dependency
Page 69
Unit Configuration
)
press Enter once more.
• Use the arrow up/down buttons to select the Activation Group
that is to be configured.
• To view or change properties for the selected Activation Group,
refer to Configure Properties for an Activation Group (chapter
5.11.2).
• Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
Page 70
Unit Configuration
)
arrow down/up buttons, press Enter twice.
• Type a new Name, or accept the existing one by pressing the
arrow down button.
• Press Enter, then use the left or right arrow button to select the
desired unit state (Prealarm/Alarm), then press Enter.
• Use the left or right arrow button to determine how many points
within this activation group that must be in alarm state before
actions are initiated (0-5 and All).
• To confirm the setting, press Enter once more.
)
group(s), select Connect to Output (the first menu selection), then
press Enter.
Page 71
Unit Configuration
)
group(s), use the arrow down button to scroll downwards to
Disconnect from Output, then press Enter.
In the display you will now see a list of all outputs that are connected
to the selected Activation Group.
)
group(s), use the arrow down button to scroll downwards to
Show Connections, then press Enter.
In the display you will now see a list of all connections that are
connected to the selected Activation Group.
)
group(s), use the arrow down button to scroll downwards to
Show Connections, then press Enter.
In the display you will now see a list of all connections that are
connected to the selected Activation Group.
In the display you will now see the name and unit function.
Page 72
Unit Configuration
)
• Use the arrow down button to select External Interfaces, then
press Enter once more.
Note that ESPA and Voice Data Recorder (VDR) require the use of
the serial port. MODBUS can use either the serial or ethernet port.
)
• Select Serial Port Settings (the first menu selection), then press
Enter twice.
• Use the arrow left/right button to select “Bits per second”, then
press Enter.
• Use the arrow left/right button to select “Word Length”, then
press Enter.
• Use the arrow left/right button to select “Parity”, then press Enter.
• Use the arrow left/right button to select “Stop Bits”, then press
Enter.
• Use the arrow left/right button to select “Hardware Interface”,
then press Enter.
• To confirm the setting, press Enter once more.
Page 73
Unit Configuration
)
• Use the arrow down button to select Ethernet Port Settings, then
press Enter twice.
• Use the arrow left/right button to select “Own IP Address”, then
press Enter.
• Use the arrow left/right button to select “Gateway IP Address”,
then press Enter.
• Use the arrow left/right button to select “Subnet Mask”, then
press Enter.
• To confirm the setting, press Enter once more.
Page 74
Unit Configuration
5.12.4 ESPA
This menu selection includes the following submenus:
• Configure Settings (chapter 5.12.4.1)
• Configure Events (chapter 5.12.4.2)
• Configure Receivers (chapter 5.12.4.3)
• Send Test Event (chapter 5.12.4.4)
Note that ESPA always requires the use of the serial port.
)
Enter twice.
• Type a new Name, or accept the existing one by pressing the
arrow down button.
• Press Enter, use the arrow left/right buttons to select the port
(not in use or serial), then press Enter.
• Use the arrow left/right buttons to select the port number, then
press Enter.
• Use the arrow left/right buttons to select whether you want to
restore factory settings or not (No/Yes), then press Enter.
o If No is selected, standard values will be used.
o If Yes is selected, the ESPA Interface settings below will be
skipped.
• Use the arrow left/right buttons to select the display size (default
128), then press Enter.
• Use the arrow left/right buttons to select the line length
(default 12), then press Enter.
• Use the arrow left/right buttons to select the alphabet type (7 bits,
8 bits, or GSM), then press Enter.
• Use the arrow left/right buttons to select the fault detail (Yes/No),
then press Enter.
• Use the arrow left/right buttons to select whether you want to
prepare for a startup message, then press Enter.
• To confirm the settings, press Enter once more.
Page 75
Unit Configuration
)
• Use the arrow down button to select Configure Events, then
press Enter and you can define a text, the number of beeps and
transmissions for the following events:
o Alarm
o Prealarm
o Fault
o Supervisory
o Startup
o Test
)
• Use the arrow down button to select Configure Receivers, then
press Enter.
Page 76
Unit Configuration
)
• Use the arrow down button to select ESPA, then press Enter.
• Use the arrow down button to select Send Test Event, then press
Enter.
Page 77
Unit Configuration
5.12.5 MODBUS
This menu selection includes the following submenus:
• Configure Settings (chapter 5.12.5.1)
• Configure Status Registers (chapter 5.12.5.2)
• Configure Command Registers (chapter 5.12.5.3)
• Set Testbit to 0 (chapter 5.12.5.4)
• Set Testbit to 1 (chapter 5.12.5.5)
• Assign Unique MODBUS Indexes (chapter 5.12.5.6)
)
• Type a new Name, or accept the existing one by pressing the
arrow down button.
• Press Enter, use the arrow left/right buttons to select the port
(not in use, serial or TCP/IP), then press Enter.
• Use the arrow left/right buttons to select the TCP/IP Address,
then press Enter.
• Use the arrow left/right buttons to select the Port Number,
then press Enter.
• Use the arrow left/right buttons to select the mode (slave or
master), then press Enter.
• Use the arrow left/right buttons to select whether you want to
restore factory settings or not (Yes/No), then press Enter.
• Use the arrow left/right buttons to select the slave address
(default 1), then press Enter.
• Use the arrow left/right buttons to select the slave ID (default 12),
then press Enter.
• Use the arrow left/right buttons to select Handshake (Yes/No),
then press Enter.
• Use the arrow left/right buttons to select Report Fault (Yes/No),
then press Enter.
• Use the arrow left/right buttons to select Fault Timer (default 10
seconds), then press Enter.
• To confirm the settings, press Enter once more.
Page 78
Unit Configuration
)
• Use the arrow down button to select MODBUS, then press Enter.
)
following:
• Use the arrow down button to select MODBUS, then press Enter.
)
• Use the arrow down button to select MODBUS, then press Enter.
• Use the arrow down button to select Set Testbit to 0, then press
Enter.
Page 79
Unit Configuration
)
• Use the arrow down button to select MODBUS, then press Enter.
• Use the arrow down button to select Set Testbit to 1, then press
Enter.
)
following:
• Use the arrow down button to select MODBUS, then press Enter.
Page 80
Unit Configuration
5.12.6 VDR
This menu selection allows you to define all settings for the Voyage
Data Recorder (VDR), including the following submenus:
• Configure Settings (chapter 5.12.6.1)
• Send Test Event (chapter 5.12.6.2)
Note that the Voyage Data Recorder (VDR) requires the use of the
serial port.
)
Enter twice.
• Type a new Name, or accept the existing one by pressing the
arrow down button.
• Press Enter, use the arrow left/right buttons to select the port
(not in use or serial), then press Enter.
• Use the arrow left/right buttons to select whether you want to
restore factory settings or not (Yes/No), then press Enter.
• Use the arrow left/right buttons to select Log Volume Mini
(Yes/No), then press Enter.
If Yes is selected, the amount of information which is sent to the
VDR will be limited; only information on alarms and door control
will be sent.
• Use the arrow left/right buttons to select Alive Time (default 4
minutes), then press Enter.
Alive Time determines how often a message is sent to the
VDR to ensure that there is a proper communication between the
system and the VDR.
• Use the arrow left/right buttons to select Update Time
(default 120 minutes), then press Enter.
Update Time determines how often the VDR receives a full
update of all fire alarms and fault statuses.
• To confirm the settings, press Enter once more.
)
following:
• Use the arrow down button to select VDR, then press Enter.
• Use the arrow down button to select Send Test Event, then press
Enter
Page 81
Unit Configuration
)
Unit Configuration, then press Enter.
• Use the arrow down button to select Detection Loops, then
press Enter.
• Use the arrow up/down buttons to select the Detection Loop
that is to be configured, then press Enter twice.
• Type a new Name, or accept the existing one by pressing
the arrow down button.
• Press Enter, use the arrow left/right button to set the limit for
maximum loop current, then press Enter.
• To confirm, press Enter once more.
)
Unit Configuration, then press Enter.
• Use the arrow down button to select Operator Panels, then
press Enter once more.
• Use the arrow up/down buttons to select the Operator Panel
that is to be configured, then press Enter twice.
• Type a new Name, or accept the existing one by pressing the
arrow down button.
• Press Enter, then use the arrow left/right button to type the panel
type.
Page 82
Unit Test
6. Unit Test
)
selection).
• Use the arrow button to select the detection zone that is to be
tested. Use, if necessary, the multiselect feature to select
several detection zones.
(To view detailed information for one selected detection zone before
testing, you can press Enter, then return to the previous level by
pressing the Cancel button ).
• To stop the test, use the arrow up/down button to select the
detection zone(s) that is set to test mode, press the Function
button , use the arrow down button to select Stop Test, then
press Enter twice.
Page 83
Unit Test
The duration of the signal and the interval between each signal are
configurable (normally 1 second ON and 30 seconds OFF). The test
signal is given the lowest priority. In the event of an alarm, the alarm
signal will thus override the test signal.
)
• Scroll down to Alarm Zone, then press Enter.
• Use the arrow button to select the Alarm Zone that
is to be tested. Use, if necessary, the multiselect feature to select
several alarm zones.
(To view detailed information for one selected alarm zone before
testing, you can press Enter, then return to the previous level by
pressing the Cancel button ).
• To stop the test, use the arrow up/down button to select the
alarm zone(s) that is set to test mode, press the Function button
, use the arrow down button to select Stop Test, then press
Enter twice.
Page 84
Unit Test
The duration of the signal and the interval between each signal are
configurable (normally 1 second ON and 30 seconds OFF). The test
signal is given the lowest priority. In the event of an alarm, the alarm
signal will thus override the test signal.
)
• Scroll down to Fire Alarm Devices, then press Enter.
• Use the arrow button to select the Fire Alarm Device (FAD) that
is to be tested.
(To view detailed information for the selected Fire Alarm Device
before testing, you can press Enter, then return to the previous level
by pressing the Cancel button ).
• To stop the test, use the arrow up/down button to select the Fire
Alarm Device that is set to test mode, press the Function button
, use the arrow down button to select Stop Test, then press
Enter twice.
Page 85
Unit Test
NOTE:
Before this test is performed, make sure that all extinguishers
(or other similar equipment) that are to be tested are
disconnected. During the test, use a measuring instrument to
measure the output on the Fire Protection Equipment that is
to be tested.
)
• Scroll down to Loop Outputs, then press Enter.
• Use the arrow button to select the Loop Output that
is to be tested.
(To view detailed information for the selected loop output before
testing, you can press Enter, then return to the previous level by
pressing the Cancel button ).
• To stop the test, use the arrow up/down button to select the loop
output that is set to test mode, press the Function button ,
use the arrow down button to select Stop Test, then press Enter
twice.
Page 86
Unit Test
NOTE:
Before this test is performed, make sure that all extinguishers
(or other similar equipment) that are to be tested are
disconnected. During the test, use a measuring instrument to
measure the output on the Fire Protection Equipment that is
to be tested.
)
• Scroll down to Local Outputs, then press Enter.
• Use the arrow button to select the Local Output that
is to be tested.
(To view detailed information for the selected local output before
testing, you can press Enter, then return to the previous level by
pressing the Cancel button ).
• To stop the test, use the arrow up/down button to select the local
output that is set to test mode, press the Function button ,
use the arrow down button to select Stop Test, then press Enter
twice.
Page 87
Unit Test
)
• Scroll down to Mimic Panels, then press Enter.
• Use the arrow button to select the mimic panel that
is to be tested.
Note that mimic panels will appear only if mimic panels are
physically connected to the system. If not, the message “No Units
Found” will appear in the display.
• To stop the test, use the arrow up/down button to select the
mimic panel that is set to test mode, press the Function button
, use the arrow down button to select Stop Test, then press
Enter twice.
Page 88
System Topology
7. System Topology
)
A list appears, including all loops and the panel bus.
• Use the arrow button to select the panel bus or a detection loop
you want to view.
Page 89
System Topology
)
System Topology, then press Enter.
A list appears, including all loops and the panel bus.
• Use the arrow button to select the panel bus or the loop you
want to view.
• Press the Function button
• Select Show Topology (the uppermost selection), then press
Enter.
)
System Topology, then press Enter.
A list appears, including all loops and the panel bus.
• Use the arrow button to select the panel bus or the loop you
want to view.
• Press the Function button
• Use the arrow down button to select Show Faults, then press
Enter.
All faults related to the panel bus, or the selected loop in the entire
system will appear in the display.
Page 90
System Topology
• Expanding a system:
If a loop is to be moved from one panel to another, all topology
information for this loop on the replaced panel will be deleted.
Note that the Clear Loop Config. – Restart System command will not
affect the detectors’ Performance Class settings. For example, an
optical detector that has been set to “Industrial” will still have this
setting after the command is executed.
)
System Topology, then press Enter.
A list appears, including all loops and the panel bus.
• Use the arrow button to select the panel bus or the loop.
• Press the Function button
• Use the arrow down button to select Clear Loop Config. –
Restart System, then press Enter.
• Use the left arrow button to select Accept, then press Enter.
Page 91
System Topology
7.6 Deactivate
This menu selection allows you to deactivate a selected detection
loop. If for example, a detection loop is not in use for any reason, this
detection loop can be deactivated.
Note that deactivation of a loop is only allowed when the loop does
not contain any loop units.
)
System Topology, then press Enter.
A list appears, including all loops and the panel bus.
• Use the arrow button to select the detection loop you want to run
this command for.
• Press the Function button
• Use the arrow buttons to select Deactivate, then press Enter.
7.7 Activate
This menu selection allows you to activate a selected detection loop
or the panel bus which is deactivated.
Note that activation of a loop is only allowed when the loop does not
contain any loop units.
)
System Topology, then press Enter.
A list appears, including all loops and the panel bus.
• Use the arrow button to select the panel bus or the detection loop
you want to run this command for.
• Press the Function button
• Use the arrow buttons to select Activate, then press Enter.
Page 92
System Topology
)
System Topology, then press Enter.
A list appears, including all loops and the panel bus.
• Use the arrow button to select the detection loop you want to run
this command for.
• Press the Function button
• Use the arrow buttons to select Refresh Topology, then press
Enter.
Page 93
Export and Import
The USB output J12 is used for this purpose. It is easily accessible
from the inside of the front panel door.
USB
output
J12
Page 94
Export and Import
The Export Log command allows you to export the following two files
NOTE:
to a USB device (memory stick):
When exporting
log files and • ExportLogRaw.txt (a coded file for internal use only)
configuration files,
existing log files
and configuration
files on the USB
memory stick will
be overwritten.
)
Export and Import, then press Enter.
• Select Export Log (the uppermost selection), then press Enter.
• To execute the command, use the left arrow button to select
Accept, then press Enter.
Page 95
Export and Import
)
• Press the arrow down button to select Select Configuration &
Restart System, then press Enter twice.
Make sure to save all recent configuration changes (using the Save
Configuration command in the System Settings menu, chapter 3.2)
before executing the Backup Current Configuration command.
)
Export and Import, then press Enter.
• Press the arrow down button to select Backup Current
Configuration, then press Enter.
Page 96
Export and Import
Make sure to save all recent configuration changes (using the Save
Configuration command in the System Settings menu, chapter 3.2)
before executing the Export Configuration command.
NOTE:
When exporting log files and configuration files, existing log files
and configuration files on the USB memory stick will be overwritten.
)
Export and Import, then press Enter.
• Press the arrow down button to select Export Configuration, then
press Enter.
)
Export and Import, then press Enter.
• Press the arrow down button to select Import Configuration, then
press Enter.
Page 97
Configuration Examples
9. Configuration Examples
Page 98
Configuration Examples
BD-300 BH-300
A1001 A1002
BBR-200
CANTEEN A1003
Detection Zone 1 Alarm Zone (indicated in red)
Output to Fire Alarm Device (FAD)
Output to FWRE
Output to FARE
K NU S G LA S SE T
BF-300
Detection Zone 4
TRYKK HER PRESS H ERE
B RE AK G LA S S
A1008
SALES OFFICE
Detection Zone 2
BH-300 BH-320
A1007
A1006 A1005
Page 99
Configuration Examples
9.2.2 Buttons
Enter
Alpha-
numeric Arrow Up/Down
Keypad Arrow Left/Right
Cancel
Select
/ Back
Function
Page 100
Configuration Examples
)
Before you start the site-specific configuration, two commands
should be executed; Save Configuration and Restart System.
In this way, prior to the site-specific configuration, you can
verify that the system works properly using the default
configuration. Furthermore, you will have a fully operational
system while you are performing the site-specific configuration.
The message “System is now shutting down…” will appear, and the
system will reboot automatically.
)
When the system reboot is completed, you can enter Service
Mode, and start the first step of the site-specific configuration.
Page 101
Configuration Examples
• Step 1: Create Detection Zones and connect the points (loop units)
to the Detection Zones (5.4.3)
Note that the electronic sounders (Fire Alarm Devices, FADs) in
this example are not to be connected to detection zones.
• Step 3: Save the configuration and restart the system (3.2 and
3.3)
When the site-specific configuration is completed, you have to save
the new configuration and restart the system (refer to chapter
9.2.4).
• In this example, only one Alarm Zone is defined. By default, all Fire
Alarm Devices are connected to the one default Alarm Zone.
Therefore, no configuration is required (you do not have to connect
Fire Alarm Devices to the Alarm Zone). Refer to chapter 5.5.3
Page 102
Configuration Examples
)
connected to the same detection zone, for example starting with
Detection Zone 1, including:
A1001
A1002
*To select both points at the same time, press and hold down
the Select button to mark the first point A1001, then while
still holding down the Select button, press the Arrow Down button
to select the second point (A1002).
Page 103
Configuration Examples
)
• Select the first point A1001 that is to be added a site-specific
name, then press Enter twice.
• Type space and the name CANTEEN after the address,
for example, A1001 CANTEEN, then press Enter.
• Use the arrow down button to select the next point that is to be
added a site-specific name.
• Repeat the procedure for each point according to the list below:
A1001 CANTEEN
A1002 CANTEEN
A1003 CANTEEN
A1004 SALES OFFICE
A1005 SALES OFFICE
A1006 CORRIDOR SOUTH
A1007 CORRIDOR SOUTH
A1008 Manual Call Point CORRIDOR SOUTH
Page 104
Configuration Examples
9.2.8 Step 2: Connect the new Detection Zones to the Alarm Zone
)
then press Enter.
• As all Detection Zones (DZ1, DZ2, DZ3 and DZ4) are to be
connected to the Alarm Zone in this example, use the multiselect
feature* to select all four Detection Zones.
* To select all four Detection Zones at the same time, press and
hold down the Select button to mark the first Detection Zone
DZ1, then while still holding down the Select button, press the
Arrow Down button to select the second, third and fourth (DZ2,
DZ3 and DZ4).
Page 105
Configuration Examples
Zonal configuration The configuration now includes the following detection/alarm zones:
• One output is used for Fire Alarm Routing Equipment (relay output
1, already configured in Example 1).
• One output is used for Fault Warning Routing Equipment (relay
output 2, already configured in Example 1).
• One output is used for the sounder outside the main building
(Alarm Zone 1).
• One output is used for the sounder outside the Storage/Workshop
building (Alarm Zone 2)
• One output is used for the ventilation control in the
Storage/Workshop building (open collector output 1).
• One output is used for door control in the main building (Sales
Office/Canteen/Corridor South, open collector output 2).
Page 106
Configuration Examples
Detection Loop B
Loop A BBR-200
BD-300
BF-300 K NU S G LA S SE T
BF-300
Detection
K NU S G LA S SE T
TRYK K HER PRESS H ER E
TRYK K HER PRESS H ER E
B RE AK G LA S S
Detection Zone 4
B RE AK G LA S S
Zone 6
A1008 B1002
SALES OFFICE
Detection Zone 2 BH-300
BH-300 BH-320
A1007
B1004
CORRIDOR SOUTH A1004 WORKSHOP
Autronica
Page 107
Configuration Examples
• Step 1: Create the new detection zones and connect the points
(loop units) to the new detection zones (5.4.3)
All new points in the Storage/Workshop building have to be
connected to the new detection zones, DZ5, DZ6 and DZ7. Note
that the electronic sounders (Fire Alarm Devices, FADs) in this
example are not to be connected to detection zones.
Page 108
Configuration Examples
)
connected to the same detection zone, for example starting with
Detection Zone 5, including:
B1001
B1005
B1006
*To select both points at the same time, press and hold down
the Select button to mark the first point B1001, then while
still holding down the Select button, press the Arrow Down button
to select the point B1005 and B1006.
Page 109
Configuration Examples
)
• Select the first point B1001 that is to be added a site-specific
name, then press Enter twice.
• Type space and the name STORAGE after the address,
for example, B1001 STORAGE, then press Enter.
• Use the arrow down button to select the next point that is to be
added a site-specific name.
• Repeat the procedure for each point according to the list below:
B1001 STORAGE
B1005 STORAGE
B1006 STORAGE
B1002 Manual Call Point STORAGE
B1003 WORKSHOP
B1004 WORKSHOP
Page 110
Configuration Examples
9.3.4 Step 2: Connect Fire Alarm Devices to new alarm zones (5.5.3)
One FAD (the sounder outside CORRIDOR SOUTH in the example)
is to be connected to Alarm Zone 1 and another FAD (the sounder
outside the STORAGE) is to be connected to Alarm Zone 2.
)
Devices.
• Use the arrow up/down button to select the first FAD (the sounder
in Alarm Zone 1), then press the Function button
• Select Move to Alarm Zone (the first menu selection), then press
Enter.
• Select Create New Alarm Zone (the first menu selection), then
press Enter twice.
• Type the name of the new Alarm Zone, for example Alarm Zone 1,
then press Enter.
•
• The cursor will move to the line below: Parent Alarm Zone. In this
example the Default Alarm Zone is the Parent Alarm Zone.
•
• Press Enter to select Default Alarm Zone.
• Press Enter to confirm the settings (Accept).
• In the Fire Alarm Devices menu, select the second FAD (the
sounder in Alarm Zone 2) and repeat the entire procedure
described above (create Alarm Zone 2 and connect the second
FAD to this alarm zone, then select the Default Alarm Zone as the
Parent Alarm Zone).
)
detection zones (DZ1, DZ2, DZ3 and DZ4), then press the
Function button
Page 111
Configuration Examples
9.3.6 Step 4: Connect the new detection zones to a new alarm zone
(Alarm Zone 2). (5.2.3)
The new detection zones, DZ5, DZ6 and DZ7 have to be connected to
the new Alarm Zone 2.
)
detection zones (DZ5, DZ6 and DZ7), then press the Function
button
9.3.7 Step 5: Define Alarm Zone 1 and Alarm Zone 2 as Neighbour Alarm
Zones (5.3.3)
In this example, Alarm Zone 2 is to be the neighbour zone to Alarm
Zone 1, and Alarm Zone 1 is to be the neighbour alarm zone to Alarm
Zone 2.
)
selection), then press Enter.
• Select Alarm Zone 2 as the neighbour alarm zone, then press
Enter.
• To confirm the setting, press Enter once more.
• Use the arrow up/down button to select Alarm Zone 2, then press
the Function button
• Select Connect to Neighbour Alarm Zone (the first menu
selection), then press Enter.
• Select Alarm Zone 1 as the neighbour alarm zone, then press
Enter.
• To confirm the setting, press Enter once more.
Page 112
Configuration Examples
)
• Select Connect to Alarm Zone (the first menu selection), then
press Enter.
• Use the arrow down button to select Default Alarm Zone (the
Parent Alarm Zone).
• Press Enter to connect Detection Zone 6 to the Parent Alarm
Zone.
• To confirm the setting, press Enter once more.
9.3.9 Step 7: Configure outputs for ventilation control and door control
(5.4.4 and 5.2.4)
This menu allows you to connect a selected point to an output, and
give this point certain properties.
)
downwards to Connect to Output, then press Enter.
)
• Press the Function button and use the arrow down button to select
Connect to Output, then press Enter.
Only local outputs of the type General Output will be listed.
• Use the arrow down button to select the output, then press Enter
twice.
• Use the arrow left/right buttons to select the Detection Activation
State (Prealarm, Small Alarm, Large Alarm, Silent Alarm), then
press Enter.
• To confirm the setting, press Enter once more.
Page 113
Configuration Examples
Page 114
Other Functions
10.1.1 Copy
The Copy function is useful when similar names are to be used in a
configuration several times, when, for example, naming detection
zones, “Main Building, 1st floor”, “Main Building, 2nd floor”, etc. To
copy an already written name for, for example, a detection zone,
proceed as follows:
• Go to the detection zone in question, and press Enter to
highlight the name field (the name appears on a black background
with light green text).
• Press and hold down the Select button , then press the arrow
left button repeatedly until the entire name is selected (the name
appears in inverse video; on a light green background with black
text).
• Press the Function button
• Use the arrow down button to select Copy, then press Enter
10.1.2 Cut
To cut an already written name for, for example, a detection zone,
proceed as follows:
• Go to the detection zone in question, and press Enter to
highlight the name field (the name appears on a black background
with light green text).
• Press and hold down the Select button , then press the arrow
left button repeatedly until the entire name is selected (the name
appears in inverse video; on a light green background with black
text).
• Press the Function button
• Select Cut (the first menu selection), then press Enter
• The name is cut, and is placed in the clipboard.
Page 115
Other Functions
10.1.3 Paste
To paste a name (for example, for a detection zone) which is already
placed in the clipboard, proceed as follows:
Page 116
Other Functions
Page 117
Appendix
11. Appendix
The top-level alarm zone (default) is called the Parent Alarm Zone. A
system consists of a Parent Alarm Zone, usually with several “sub-
level” alarm zones in an hierarchy. Each “sub level”-alarm zone is
related to a specific area of, for example, a building. If an alarm occurs
in a Parent Alarm Zone, all Fire Alarm Devices (FADs) within this
zone, plus all FADs belonging to all “sub-level”-alarm zones will be
activated.
Page 118
Appendix
Page 119
Appendix
Page 120
Appendix
When the operator panel receives a fire alarm signal from a point in a
Delayed Action detection zone (configurable), the actioning of outputs
to Fire Alarm Devices (FAD) and/or Fire Alarm Routing Equipment
(FARE) can be delayed.
Delayed Action is based on the first point reporting the fire. A second
point in alarm in the same detection zone will not affect the delay of
the connected outputs.
The operation of delays to outputs for Fire Alarm Devices (FAD) apply
to:
• detectors and/or
• manual call points and/or
• signals from specific zones
The T1 delay period is started when a Fire Alarm signal from a point is
received. Actions will be initiated after the T1 delay period has
expired. Pressing PROLONG DELAY, will terminate T1 and the delay
period T2 will start.
Page 121
Appendix
If one or more Delayed Action detection zones have entered the Fire
Alarm state and are in their T1 or T2 periods, the delayed actions can
be immediately initiated by pressing the Activate Outputs button.
Activation of a manual call point will also give immediate action
(provided that the point has been set to Override Delay and
Dependency, YES).
• When a fire alarm signal from the first detector in alarm is received,
the following will occur:
o The detection zone will enter the Silent Alarm state, and all FPE
outputs configured to be activated on Silent Alarm will be
activated. The T1 delay period will start.
o When the T1 delay period expires, the detection zone will enter
the Small Alarm state. All FPE outputs configured to be activated
on Small Alarm will be activated. The T2 delay period will start.
o When the T2 delay period expires, the detection zone will enter
the Large Alarm state. All FPE outputs configured to be activated
on Large Alarm will operate.
• Note that, at any time, if an alarm from a second detector within the
same detection zone is received, the detection zone will always
enter the Large Alarm State. This means that all (not yet activated)
FPEs configured to be activated on Silent, Small and Large Alarm
will be activated.
Note that when a point sends an alarm signal, and this point
has been set to Override Delay and Dependency, YES, the
Delayed Dependency detection zone will enter the Large Alarm
state directly, regardless of Day or Night Mode.
Page 122
Appendix
The Activate Outputs button can be used to activate the FADs and
outputs that are in this two minute transition period or that have
previously been blocked.
Autroprime also has a Resound function that will reverse the effect of
Silence.
The table on the next page indicates which levels are available for
different types of detection zones.
Page 123
Appendix
Silent Alarm
Any fire alarm signal will be indicated at the panel without any delay,
and this is the Silent Alarm level. An output may be configured to be
activated at this level, as an example to trigger a coded message
through a voice alarm system or an output to make on site technical
personnel aware of the situation.
Small Alarm
In the case of a Delayed Dependency detection zone there is an
automatic transfer from the initial T1 delay period to the prolonged T2
delay period. When this transfer occurs the level will be increased to
Small Alarm. Looking at a shopping centre this level may be used for
another voice alarm message making the employees start the
preparations for an evacuation. The display will show the T2
countdown.
(Small alarm level is also shown for Delayed and Dependency zones,
but should not be used as an activation criteria for outputs.)
Large Alarm
The table below shows that this level is the last one (or only) for all
types of detection zones. There are different ways of getting to this
level, either elapsed timers (T1 and/or T2), a second alarm signal or a
panel operation. If not configured otherwise, all outputs will be
activated at this level, fire brigade (FARE), sounders (FAD) and any
other outputs (FPE).
Page 124
Reader’s Comments
Name: ------------------------------------------------------------------------------------------------
Title: ------------------------------------------------------------------------------------------------
Company: ------------------------------------------------------------------------------------------------
Address: ------------------------------------------------------------------------------------------------
------------------------------------------------------------------------------------------------
------------------------------------------------------------------------------------------------
Telephone: ------------------------------------------------------------------------------------------------
Fax: ------------------------------------------------------------------------------------------------
Date: ------------------------------------------------------------------------------------------------
Tel: + 47 73 58 25 00
Fax: + 47 73 58 25 01
www.autronicafire.com
All products are easily adaptable to a wide variety of applications, among others, hospitals, airports, churches and schools, as
well as to heavy industry and high-risk applications such as power plants, computer sites and offshore installations, world wide.
The company's strategy and philosophy is plainly manifested in the business idea:
Protecting life, environment and property.
Quality Assurance
Stringent control throughout Autronica Fire and Security assures the excellence of our products and services. Our products are
CE marked and developed for worldwide standards and regulations, and conform with the CEN regulation EN54. Our quality
system conforms to the Quality System Standard NS-EN ISO 9001:2000 and is valid for the following product and service
ranges: marketing, sales, development, engineering, manufacture, installation, commissioning and servicing of suppression,
integrated fire and gas detection and alarm systems, plus petrochemical, oil and gas instrumentation systems for monitoring
and control.