Afdadf
Afdadf
AC Voltage Controllers
❑ AC Cycloconverter
❑ Matrix Converter
❑ Summary
a
AC Voltage Controllers - Introduction
❑ Controls the voltage, current, and average power delivered to an ac load from an ac
source. The input voltage is ac, and the output is ac (although not sinusoidal), so the
circuit is classified as an ac-ac converter.
❑ Switches connect and disconnect the source and the load at regular intervals.
❑ Another type of control is integral-cycle control, whereby the source is connected and
disconnected for several cycles at a time.
AC Voltage Controllers - Introduction
❑ Light-dimmer circuits-Induction heating
AC Voltage Controllers - Introduction
❑ Tap Changers
AC Voltage Controllers - Introduction
❑ Tap Changers
AC Voltage Controllers - Introduction
❑ Speed Control of AC Motors
The Single-Phase AC Voltage Controller
The Single-Phase AC Voltage Controller
• This SCR connection is called antiparallel or inverse parallel because the SCRs carry current in
opposite directions.
• A triac is equivalent to the antiparallel SCRs. Other controlled switching devices can be used instead
of SCRs.
Figure 1 (a) Single-phase AC voltage controller with resistive load, (b) Waveforms
The Single-Phase AC Voltage Controller
2. The load voltage is the same as the source voltage when either SCR is on.
The load voltage is zero when both SCRs are off.
3. The switch voltage is zero when either SCR is on and is equal to the
source voltage when neither is on.
4. The average current in the source and load is zero if the SCRs are on for
equal time intervals. The average current in each SCR is not zero because of
unidirectional SCR current.
5. The rms current in each SCR is times the rms load current if the SCRs
are on for equal time intervals.
The Single-Phase AC Voltage Controller
❑ S1 conducts if a gate signal is applied during the positive half-cycle. S1 conducts until the
current in it reaches zero.
❑ Where this circuit differs from the controlled half-wave rectifier is when the source is in
its negative half-cycle.
❑ A gate signal is applied to S2 during the negative half-cycle of the source, providing a
path for negative load current.
❑ If the gate signal for S2 is a half period later than that of S1, analysis for the negative
half-cycle is identical to that for the positive half, except for algebraic sign for the voltage
and current.
The Single-Phase AC Voltage Controller
❑ Single-phase controller with Resistive Load
Figure 2 Normalized RMS load voltage vs delay angle for a single-phase AC voltage controller with R-load
The Single-Phase AC Voltage Controller
❑ The power factor of the load:
The average source current is zero because of half-wave symmetry. The average SCR current
is:
Since each SCR carries one-half of the line current, the rms current in each SCR is:
The Single-Phase AC Voltage Controller
❑ Only odd harmonics exist in the line
current ---(half-wave symmetry).
The extinction angle β is the angle at which the current returns to zero, when ωt= β
❑ The gate signal to S2 must be delayed at least until the current in S1 reaches
zero, at ωt=β. The delay angle is therefore at least β-π.
The Single-Phase Controller with RL Load
For 0<α<60:
Two or three SCRs conduct at any one time for this range of . Figure 7b
shows the load line-to-neutral voltage van for α=30. At ωt=0, S5 and S6 are
conducting and there is no current in Ra, making van=0. At ωt=π/6 (30°), S1
receives a gate signal and begins to conduct; S5 and S6 remain on, and
van=vAN. The current in S5 reaches zero at 60°, turning S5 off. With S1 and
S6 remaining on, van=vAB/2. At 90°, S2 is turned on; the three SCRs S1, S2,
and S6 are then on; and van=vAN. At 120°, S6 turns off, leaving S1 and S2
on, so van vAC/2. As the firing sequence for the SCRs proceeds, the
number of SCRs on at a particular instant alternates between 2 and 3. All
three phase-toneutral load voltages and switch currents re shown in Fig. 7c.
For intervals to exist when three SCRs are on, the delay angle must be less
than 60°.
AC Voltage Controllers
Three-Phase Voltage Controller
For 60<α<90:
Only two SCRs conduct at any one time when the delay angle is between 60° and 90°.
Load=voltage van for α =75° is shown in Fig. 7d. Just prior to 75°, S5 and S6 are conducting,
and van=0. When S1 is turned on at 75°, S6 continues to conduct, but S5 must turn off
because vCN is negative. Voltage van is then vAB/2. When S2 is turned on at 135°, S6 is
forced off, and van=vAC/2. The next SCR to turn on is S3, which forces S1 off, and van=0. One
SCR is always forced off when an SCR is turned on for in this range. Load voltages are one-
half line-to-line voltages or zero.
For 90°<α<150°:
Only two SCRs can conduct at any one time in this mode. Additionally, there are intervals
when no SCRs conduct. Figure 7e shows the load voltage van for α=120°. In the interval just
prior to 120°, no SCRs are on, and van=0. At α=120°, S1 is given a gate signal, and S6 still has
a gate signal applied. Since vAB is positive, both S1 and S6 are forward-biased and begin to
conduct, and van=vAB/2. Both S1 and S6 turn off when vAB becomes negative. When a gate
signal is applied to S2, it turns on, and S1 turns on again.
For α>150°, there is no time interval when an SCR is forward-biased while a gate signal is
applied. Output voltage is zero for this condition.
AC Voltage Controllers
Three-Phase Voltage Controller
❑ Normalized output voltage vs. delay angle is shown in Fig. 5-8. Note that a delay angle of
zero corresponds to the load being connected directly to the three-phase source. The
range of output voltage for the three-phase voltage controller is between full source
voltage and zero.
❑ Harmonic currents in the load and line for the three-phase ac voltage controller are the
odd harmonics of order 6n±1, n=1, 2, 3, . . . (that is, 5th, 7th,11th, 13th). . . . Harmonic
filters may be required in some applications to prevent harmonic currents from
propagating into the ac system.
(18)
The relationship between rms line and delta currents depends on the conduction
angle of the SCRs. For small conduction angles (large ), the delta currents do
not overlap (Fig. 10b), and the rms line currents are
(19)
AC Voltage Controllers
Three-Phase Voltage Controller
Figure 10 (a) Three-phase ac
voltage controller with
a delta-connected resistive
load; (b) Current waveforms
for α=130°; (c) Current
waveforms for α=90°.
AC Voltage Controllers
Three-Phase Voltage Controller
The SCRs are placed in the inductor branch rather than in the capacitor branch
because very high currents could result from switching a capacitor with a SCR.
Static VAR control has the advantage of being able to adjust to changing
load requirements very quickly. Reactive power is continuously adjustable with
static VAR control, rather than having discrete levels as with capacitor banks
which are switched in and out with circuit breakers. Static VAR control is becoming
increasingly prevalent in installations with rapidly varying reactive
power requirements, such as electric arc furnaces. Filters are generally required
to remove the harmonic currents generated by the switched inductance.
Summary
• The delay angle for the thyristors controls the time interval for the switch being on
and thereby controls the effective value of voltage at the load. The range of control
for load voltage is between full ac source voltage and zero.
Summary
• An ac voltage controller can be designed to function in either the fully on or fully
off mode. This application is used as a solid-state relay.
• The load and source current and voltage in ac voltage controller circuits may
contain significant harmonics. For equal delay angles in the positive and negative
half-cycles, the average source current is zero, and only odd harmonics exist.