0% found this document useful (0 votes)
24 views

Data Sheet CM PTP

The CM PTP communication module provides serial communication connections via RS422, RS485, and RS232 interfaces. It supports protocols like Freeport, 3964R, Modbus RTU master and slave, and has a maximum transmission rate of 115.2 Kbit/s. The module can be configured and integrated in STEP 7 as of version V12 and draws a maximum of 29mA current. It has diagnostic LEDs, 4KB of telegram buffer, and supports decentralized operation in SIMATIC S7 systems.

Uploaded by

iotation.service
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
24 views

Data Sheet CM PTP

The CM PTP communication module provides serial communication connections via RS422, RS485, and RS232 interfaces. It supports protocols like Freeport, 3964R, Modbus RTU master and slave, and has a maximum transmission rate of 115.2 Kbit/s. The module can be configured and integrated in STEP 7 as of version V12 and draws a maximum of 29mA current. It has diagnostic LEDs, 4KB of telegram buffer, and supports decentralized operation in SIMATIC S7 systems.

Uploaded by

iotation.service
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Data sheet 6ES7137-6AA00-0BA0

SIMATIC ET 200SP, CM PTP communication module for serial


connection RS422, RS485 and RS232, Freeport, 3964 (R), USS,
MODBUS RTU Master, Slave, 115200 Kbit/s

General information
Product type designation CM PtP
Firmware version
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
Engineering with
● STEP 7 TIA Portal configurable/integrated as of V12 / V12
version
● STEP 7 configurable/integrated as of version V5.5 SP2 with GSD file
● PROFIBUS as of GSD version/GSD revision GSD as of Revision 5
● PROFINET as of GSD version/GSD revision GSDML V2.3

Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes

Input current

6ES7137-6AA00-0BA0 Subject to change without notice


Page 1/4 05/21/2020 © Copyright Siemens
Current consumption (rated value) 29 mA

Power loss
Power loss, typ. 0.7 W

Address area
Address space per module
● Inputs 8 byte

1. Interface
Interface types
● RS 485 Yes
● RS 422 Yes
● RS 232 Yes

Interface types
RS 232
● Transmission rate, max. 115.2 kbit/s
● Cable length, max. 15 m
● RS 232 auxiliary signals RTS, CTS, DTR, DSR, RI, DCD
RS 485
● Transmission rate, max. 115.2 kbit/s
● Cable length, max. 1 200 m
RS 422
● Transmission rate, max. 115.2 kbit/s
● Cable length, max. 1 200 m
● 4-wire full duplex connection Yes
● 4-wire multipoint connection Yes

Protocols
Integrated protocols
Freeport
— Telegram length, max. 2 kbyte
— Bits per character 7 or 8
— Number of stop bits 1 or 2 bit
— Parity None, even, odd, always 1, always 0, any
3964 (R)
— Telegram length, max. 2 kbyte
— Bits per character 7 or 8
— Number of stop bits 1 or 2 bit
— Parity None, even, odd, always 1, always 0, any
Modbus RTU master
— Address area 1 to 247, extended 1 to 65535
— Number of slaves, max. 32
MODBUS RTU slave

6ES7137-6AA00-0BA0 Subject to change without notice


Page 2/4 05/21/2020 © Copyright Siemens
— Address area 1 to 247, extended 1 to 65535
Telegram buffer
● Buffer memory for telegrams 4 kbyte
● Number of telegrams which can be buffered 255

Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
● Hardware interrupt No
Diagnostic messages
● Wire-break Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
● for module diagnostics Yes; green/red DIAG LED
● Receive RxD Yes; green LED
● Transmit TxD Yes; green LED

Potential separation
between backplane bus and interface Yes

Isolation
Isolation tested with 707 V DC (type test)

Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -30 °C; From FS03
● horizontal installation, max. 60 °C
● vertical installation, min. -30 °C; From FS03
● vertical installation, max. 50 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 2 000 m; On request: Installation altitudes greater than 2 000 m

Decentralized operation
to SIMATIC S7-300 Yes
to SIMATIC S7-400 Yes
to SIMATIC S7-1200 Yes
to SIMATIC S7-1500 Yes
to standard PROFINET controller Yes

Dimensions
Width 15 mm
Height 73 mm
Depth 58 mm

Weights
Weight, approx. 30 g

6ES7137-6AA00-0BA0 Subject to change without notice


Page 3/4 05/21/2020 © Copyright Siemens
last modified: 05/09/2020

6ES7137-6AA00-0BA0 Subject to change without notice


Page 4/4 05/21/2020 © Copyright Siemens