Computer Aided Load Estimation Algorithm
Computer Aided Load Estimation Algorithm
2015)
Abstract
This study collected existing mathematical formulae that are essential for load
estimation in residential and non-residential buildings, combined the formulae collected
and wrote a computer algorithm that would effectively support load estimation in
residential and non-residential buildings. The algorithm was used to develop interactive
and user-friendly software for load estimation in residential and non-residential
buildings. The software was developed using C# Programming Language and it is
named Air-conditioner Load Estimator (ALE). The ALE has been evaluated and
validated. Hence, using the air-conditioner loads for various buildings, both residential
and non-residential cooling loads can be determined on the quickly without going
through standard tables.
I. Non-Residential Buildings Cooling Load for the Wall ( ) and 4.6W for 12mm
Estimation thick Glass window ( ), (ASHRAE, 2011).
Generally, the load components for Hence, the Summation of the sensible loads for
estimating load capacity in air-conditioning the wall, roof and the glass window could be
system for a building are identified as follow: obtained.
External Loads: External loads consist of the b. Partitions, Ceiling & Floors: The equation
following:- to calculate the cooling load due to
a. Sensible loads through opaque envelope partitions, ceiling and floors is as given in
assemblies (i.e. due to roofs, walls, floors) (2)
b. Sensible loads through transparent or (2)
translucent envelope assemblies (i.e. due to U Thermal Transmittance for roof or wall or
skylights, windows, glazed openings) glass (ASHRAE, 2001).
c. Sensible loads through ventilation and A area of partition, ceiling or floor calculated
infiltration (i.e. due to air leakage) from building plans
d. Latent loads through ventilation and Outside design temperature
infiltration. Inside design temperature of conditioned
Sensible Heat Gain is the heat flowing into the space (assumed constant)
building by conduction through exterior walls, The U-values used in this research work
floors, ceilings, doors and windows due to the according to ASHRAE, (2011) include:
temperature difference on their two sides; heat 1.47 W for partitions, 0.62 W for
received from solar radiation directly through ceiling for floor
glass of windows, ventilators or doors and the and are measured using a thermometer.
heat absorbed by walls and roofs; he heat given c. Ventilation & Infiltration Air: Ventilation
off by lights; the heat liberated by the and Infiltration air is the amount of outdoor
occupants and the heat carried by the outside air required to maintain Indoor Air Quality
air as result of infiltration and ventilation for the occupants (ASHRAE, 2001) and
through the cracks in doors, windows, chairs, makeup for air leaving the space due to
book-shelves etc and through their frequent equipment exhaust, ex-filtration and
openings. pressurization while Infiltration air is the
Latent Heat Gain is the heat gain due to amount of unconditioned air entering the
moisture in the outside air entering by conditioned space due to opening of some
infiltration and ventilation and the heat gain space. The equation to calculate the cooling
due to condensation of moisture from load due to ventilation and infiltration air is
occupants. as given in (3)
In respect of the external load mentioned above (3)
the sensible load could be calculated in term of where:
various components of non-residential building ACH Ventilation airflow rate/Volumetric air
as follows: flow rate calculated as air change per hour
a. Roofs, External Walls & Conduction d. Solar Load Through Glass: The equation to
through Glass: The equation to calculate calculate the cooling load due to radiant
the cooling load due roofs, walls and the sensible loads from the
conductions through glass is as given in (1) transparent/translucent elements such as
(1) window glass, skylights and plastic sheets
where: is as given in (4)
U is the thermal Transmittance for roof or wall (4)
or glass, A is the area of roof, wall or glass where:
calculated from building plans, CLTD is the A = area of roof, wall or glass calculated from
Cooling Load Temperature Difference for roof, building plans
walls, or glass, (ASHRAE, 2011). SHGC Solar Heat Gain Coefficient.
The Thermal Transmittance used in this work CLF Solar Cooling Load Factor.
is 0.62W for the Roof ( ),
163 Technical Report
AU J. T. 18(4): 161-172 (Apr. 2015)
Table 1: Sensible Heat Gain (SHG) and Latent Heat Gain (LHG) in respect of human activities
S/N Activities SHG (Watt) LHG (Watt)
1 Seated at rest 60 40
2 Seated, very light work, writing 65 55
3 Seated , eating 75 95
4 Seated, light work, typing 75 75
5 Standing, light work, walking, slowly. 90 95
6 Light bench work 100 130
7 Light machine work 100 205
8 Heavy work 165 305
9 Moderate dancing 120 255
10 Athletics 185 340
Source: ASHRAE, 2011.
Since the space temperature is not maintained number of light presently installed. The Blast
constant during the 24 hours period, then the factor allowance (FBF) is 1 for compact
Cooling Load Factor (CLF) is 1. fluorescent Light (CFL) and 1.2 for ordinary
b. Electric `Lights: The equation to calculate fluorescent tube.
the cooling load due to Electric lights is c. Appliances: The equation to calculate the
given as in (7): cooling load due to appliances is given as
(7) in (8):
W Installed lamp watts input from electrical (8)
lighting plan or lighting load data W Installed rating of appliances in watts
FUT Lighting utilization factor according to the manufacturer’s data.
FBF Blast factor allowance, as appropriate Usage factor.
CLF Cooling Load Factor, by hour of Radiation factor.
occupancy. For this research, the Cooling Load CLF Cooling Load Factor, by hour of
Factor is 1. occupancy.
The Wattage is determined by looking at the For the sake of this research work, the Cooling
current rating of the lamp and multiplying that load factor for heavy equipment is taken as
with the standard voltage (240 V). The Light 0.16 while for light equipment is taken as 0.12,
Utilization factor (FUT) is calculated as the (ASHRAE, 2011).
ratio of the light current in use to the total
Table 3: Cooling Load Temperature Difference for Different Sources for SFU Building and MDU
Walls and Doors Walls and Doors Roofs & Ceilings Roofs & Ceiling Exposed Floors
(SFU) (MDU) (Single family ) (Multi-family)
North-13 N-18 31 43 11
NE & NW-16 NE-20
E & W-18 E-26
SE &SW-17 SE-26
S-14 S-24
SW-32
W-35
NW-28
Source: ASHRAE, 2011.
Table 3 present the CLTD for different sections I and II were implemented through
components of the different types of residential software developed herein. The software called
building, NE and NW represents North-East air-conditioner load estimator was developed
and North-West respectively, E and W using visual C# 2012 integrated development
represents East and the West respectively, SE emolument (IDE)
and SW represents South-East and South-West When the software is triggered a welcome
respectively and S represents South. audio sound and a graphical user interface
(GUI) showing several buttons textboxes and
Software Implementation pictures explaining the functions of each
window in the tab panel is launched. Fig. 2
The formulae needed for determining shows the main features of the login and home
the cooling load for non-residential and page of the software.
residential building compile discussed in
Basically, the software is divided into two cooling loads. There are five input interfaces
major interfaces windows according to its for non-residential building cooling load
functionality: These are the non-residential and estimation namely: Roof, External Walls and
the residential building cooling load estimation Glass Panel GUI, Building occupancy GUI,
input interfaces. Both interfaces contain details Ventilation, Partition, Ceiling and Floor GUI,
of the input to be supplied by the user to Light and Equipment GUI and Solar GUI.
facilitate determination of the respective
Fig. 4: Ventilation, Partition, Ceiling and Floor GUI for non-residential building CLC.
167 Technical Report
AU J. T. 18(4): 161-172 (Apr. 2015)
Also, for residential building cooling load Externals Walls GUI, Partitions of
estimation, there are eight input interfaces Unconditioned Space GUI, Ceiling and Roofs
namely: Glass and Windows GUI, Doors GUI, GUI, Exposed Roof GUI, Infiltrations GUI and
Building Occupancy GUI.
As an example, see Figures 3 and 4 for the input information relating to the loads starting
building occupancy GUI and Ventilation, from the roof, external wall and conduction
Partition, Ceiling and Floor GUI for non- through glass are entered by the user and the
residential building cooling load calculation computation is done after the user must have
(CLC) respectively. clicked the compute key, i.e. the corresponding
Also, Figures 5 and 6 show the building load is computed.
occupancy GUI and Ceiling and Roofs GUI for If there are other information relating to the
residential building CLC respectively. load due to occupancy, ventilation, partition
Generally, the air-conditioner cooling load and ceiling floors etc and the user enters this
estimator prompted the user for a password. information, then the total load due to these
Immediately, the user launched it and if the sources are computed and displayed in the grid
user enters the correct password the home page layout (see Fig. 7). Some values will be
of the software opens. Thereafter, the relevant provided by the user and entered into the
168 Technical Report
AU J. T. 18(4): 161-172 (Apr. 2015)
appropriate fields and the total load will be calculating the loads manually.
computed and compared with the results of
West-Facing 12 4 12 6.5 12 12
South-Facing 12 4 12 6 12 12
East-Facing 12 3 12 7.5 12 12
Partitions Area = 3
Ceiling Area = 12
Expose Floor Area = 12
Light and Equipment Apartment = Heavy e.g. Conference, CFL: Total = 8,
in use = 4, Total Wattage = 9600W.
Total Number of Equipment = 4, heavy = 2 (washing
machine and fridge), medium = 2 (bread toaster and
grinder).
Solar(North) Area = 12 , Glass State = Closed
Solar(South) Area = 12 , Glass State = Closed
Table 7: Data set for case 3- School of Engineering Building Conference Room.
The value of the total load obtained in case 1 is capacity of the air-conditioning system for case
11258.54 Watts, case 2 is 19538.718 Watts and 1 is 15 hp, case 2 is 25 hp and case 3 is 10 hp.
also in case 3 is 8493.02388 Watts. The actual