Technical Questions
Technical Questions
A transformer is a static electrical apparatus, placed into an iron core consisting of thin steel
Polarity is the instantaneous voltage obtained from mode noise transients by providing a barrier, called
the secondary winding in relation to the primary a Faraday Shield, to the capacitive linking of the
winding. primary and secondary windings. The barrier
reduces, or attenuates, the amount of non 60 Hz
While Alternating Current (AC) does not have frequencies passed through the transformer in
polarity in the same sense as Direct Current (DC), either direction. This is accomplished by
polarity is involved whenever circuits or connecting the Faraday Shield to ground,
transformers are connected together. When two effectively reducing transmission of frequencies
wires in AC circuits are of like polarity, the voltage is other than 60 Hz.
rising simultaneously in both, with the current flow
in the same direction. Typical attenuation levels of 50:1 ( 34 DB ) are
achievable with Dongan shielded isolation
Polarity is normally only a consideration when transformers. This attenuation provides noise levels
connecting two or more transformers or windings in generally considered to solve many noise and
series or parallel. For example, the voltages of two transient caused problems. Most Dongan General
windings connected in series will add together if the Purpose transformers are furnished with shields at
start of the second winding is connected to the no additional cost. Shielded transformers are
finish of the first; if the finishes or starts are designated by the suffix SH or the prefix ES.
connected together, the lower voltage will subtract
from the higher. This is the principle upon which
Buck-Boost transformers and transformers with split Regulation:
primaries or secondaries operate. A transformer will generally provide a higher output
voltage when no load is attached to it than when
the transformer is fully loaded at nameplate
Shielding: capacity. Stated differently, under load, a
Most transformer installations today are used to transformers output voltage drops slightly.
power circuits containing solid state devices Regulation is the ratio of the difference between a
sensitive to electrical noise, transients and voltage transformers no load output voltage to its full load
spikes. While the possibility of voltage spikes due output voltage expressed as a percentage.
to lighting strikes on nearby transmission lines
exists, the more frequent threat to electronic For example, suppose a transformer has a no load
equipment comes from conducted electrical noise. voltage of 124 volts and a full load voltage of 120
Noise and transients can enter installations from volts. The transformers regulation is calculated as
distant external sources or from internal sources follows:
such as fluorescent ballasts and switch mode Regulation =
( No Load Voltage - Full Load Voltage )
power supplies. Shielded transformers mitigate the ( No Load Voltage )
harmful effects of certain types of transients.
Transients are high energy, short duration bursts of Regulation =
124 - 120
electrical energy covering a wide range of 120
frequencies other than the nominal domestic 60 Hz
distribution frequency. These bursts range from a Regulation = 3.33%
high of 20 kHz to a low or about 25 Hz. Distribution
systems encounter two types of transient noise:
transverse mode and common mode noise. Temperature and Insulation
Differences in the two are found in their reference to
ground. Ambient Temperature:
Transverse mode noise is noise occurring between The ambient temperature is the average
circuit supply lines. Shielded isolation transformers temperature of the air in the immediate area
have no significant effect in combating transverse surrounding the transformer. The transformer
noise. Generally, though, transverse mode noise dissipates its heat into this ambient air.
transients dissipate when loads are placed across All Dongan transformers are designed to operate in
the lines on which they appear. ambient temperatures of 40°C (104°F) maximum.
Common mode noise, on the other hand, contains Derating of transformers is necessary when
transients appearing between the wires of the ambients exceed 40°C (See Operations Section)
distribution system and ground. Common mode
noise is typically passed to the secondary, or output Temperature Rise:
side of the transformer through a capacitive link Temperature rise refers to the difference in
between the primary and secondary windings. temperature between the ambient air temperature
Circuits containing substantial common mode noise and the actual temperature of the windings or
will eventually cause failure to sensitive enclosure.
92 components.
Transformer Terms and Definitions
93
Transformer Terms and Definitions
In epoxy encapsulated transformers, the Nameplate kVA
800.428.2626 • 313.567.8500 • FAX 313.567.8828 • www.dongan.com
DONGAN ELECTRIC MANUFACTURING CO. • 2987 FRANKLIN • DETROIT, MI 48207
% Efficiency= x 100
transformers heat is conducted by the epoxy to the Nameplate kVA + Total Losses
enclosure. Because the surface area of the
enclosure is greater than that of the transformer, the In a typical enclosed, ventilated, dry-type
temperature at the enclosure surface tends to be transformer, air flow through and around the
significantly less than that found on the surface of enclosure transfers and dissipates the heat from the
the transformer element inside. core and windings. This assures that enclosure
UL and CSA standards strictly regulate the highest temperatures will remain well below internal
temperature which the case can reach. The winding temperatures.
enclosure temperature rise shall not exceed 50°C in
a 40°C ambient at full rated current. While these Inrush Current:
temperatures are quite warm to the touch, they are All transformers consume a higher amount of amps
completely within the allowed parameters of the than rated current for a very short duration when
insulation system, UL and NEMA standards. All first energized. This inrush current is highest when
Dongan transformers comply with these standards.
Excitation Current, Losses NEMA 4X Same as NEMA 4 plus corrosion resistant Indoor / Outdoor
= 601.3 Amps
Full Load Amps (FLA):
This calculation confirms that the minimum
Nameplate kVA x 1000 interrupting capacity of the fuse or circuit breaker
FLA =
Primary Supply Voltage must be no less than 601.3 amps at 480 volts.
15 x 1000
FLA =
480 Transformer Operations
FLA = 31.25 Amps Overloading Transformers:
The life of a transformer is dependent on the life of
Next Determine: its insulation. Transformers loaded in excess of
nameplate rated kVA develop excessive heat.
Excessive heat will lead to degradation of the
Maximum Short Circuit Current
insulation system and premature failure of the
transformer. For this reason, transformers should
Full Load Amps
= not be overloaded. Transformers should be sized
Impedance with future loads in mind to reduce the possibility of
overloading and consequently reducing service life.
31.25
=
5% Operation of transformers in ambient
31.25
temperatures exceeding 40°C:
= Operating transformers in ambient air exceeding
.05 40°C will reduce operational life unless the
transformer is allowed to operate under conditions
= 625 Amps of reduced maximum load. The chart below
indicates recommended derating for various
This calculation confirms that the minimum ambient temperatures. While special designs for
interrupting capacity of the fuse or circuit breaker high ambient temperatures can be supplied,
must be no less than 625 amps at 480 volts. standard transformers derated are both more
Now suppose you are required to determine the economical and more readily available. Consult the
interrupting capacity of a three phase, 30 kVA factory for ambient temperatures exceeding 60°C.
transformer with 6% impedance connected to a 480
volt supply. Maximum Maximum
Ambient Percentage
Determine: Temperature of Loading
Duty Cycle:
Transformers produce heat during the course of
normal operations. Some of the heat produced is
directly related to the amount of load amps drawn
on the transformer. Duty cycle refers to the
percentage of time the transformer is loaded to its
maximum capacity as opposed to not supplying a
load.
Incorrect - Phase B has a total
load of 11 kVA when the maximum
Duty cycle is usually expressed over a period of an
allowed is 10 kVA hour, not including continuous shutdown periods
(overnight, weekends, etc.). Therefore, the duty
cycle refers to the amount of time the transformer is
producing maximum heat output vs. the amount of
time it has to cool off again. The most severe duty
cycle is, of course, 100%. In some cases,
transformers must be oversized in severe duty
cycle applications, and in a few cases they can be
down sized for light duty cycles.
The most important application of duty cycle is in
motor operation, where duty cycle must be
considered along with motor starting cycles. A
situation where a motor runs almost continuously,
(say, 85%) but starts several times per hour will
require an oversized transformer. This is because
the starting current will cause a momentary
overload, with attendant heat buildup, which cannot
Correct - Phase A Load = 9 kVA, be cleared from the transformer due to the high
Phase B Load = 9 kVA, and duty cycle percentage.
Phase C Load = 8 kVA Dongans technical and customer service staff can
advise you on proper transformer sizing where
Balanced Loading of a Three Phase severe duty cycle and/or frequent motor starts are
involved.
Transformer with a Center Tapped 240
Volt Delta Winding: Operating Transformers
A common application for three phase transformers with Motor Loads:
with a 240 volt Delta, center tapped winding is to
Transformers are well suited for providing power for
provide power for three phase 240 volt loads and
motor load applications provided a few sizing
single phase 120 volt lighting loads at the same
considerations are followed.
time. Balanced loading is essential to assure
transformer life is not compromised. Typical motors have inrush loads of 5 to 10 times
their running load requirements. Momentary inrush
For example, suppose a 45 kVA, three phase
loads of this magnitude will cause a similar
transformer is to have 36 kVA of three phase load.
momentary transformer output voltage drop.
We know that each phase can carry one-third of the
total nameplate kVA (15 kVA), and that the three Lower transformer output voltage results in lower
phase load splits one-third per phase. In this torque and lower horsepower output of the motor
example, each phase would see one- third of 36 proportionate to the square of the voltage drop. For
kVA, or 12 kVA per phase. This means that no more example, if the voltage drops to 90% of normal,
than 3 kVA of single phase load can be applied to torque and horsepower would be 81% of normal
the center tapped leg. (90%² = 81%)
Additionally, the single phase load must be equally Should the output voltage seen by the motor fall
divided on either side of the center tap so that 1.5 below 50% of nameplate requirements, overheating
and even failure of both motor and/or transformer
kVA is connected between X0 and X2 and 1.5 kVA
is connected between X0 and X3.
97
Transformer Terms and Definitions
could result. Overheating and failure can occur single phase kVA ratings. For example, three single
800.428.2626 • 313.567.8500 • FAX 313.567.8828 • www.dongan.com
DONGAN ELECTRIC MANUFACTURING CO. • 2987 FRANKLIN • DETROIT, MI 48207
even in cases where correctly sized overcurrent phase 10 kVA transformers connected in this
devices employed in the circuit do not trip. manner will have a capacity of 3 x 10 kVA - or 30
For this reason, transformers should be sized with a kVA, three phase.
few rules in mind. Conversely, two transformer banks are connected
For applications where one transformer is powering almost solely in an Open Delta (Delta Primary and
one motor, size the transformer so that the motors Delta Secondary) configuration. The capacity of the
running amps do not exceed 66% of the 2 unit, three phase bank is equal to the sum of the
transformers maximum full load amps. individual single phase kVA ratings multiplied by
For applications of more than one motor being 86.6% (.866). For example, two single phase 10
powered by the same transformer, motor start up kVA transformers connected in this manner will
should be sequenced so that the motors do not have a capacity of 2 x 10 kVA x .866 - or 17.3 kVA,
start at the same time. If sequencing is not practical, three phase.
size the transformer so that the combined running
amps of all motors do not exceed 66% of the Three Phase to Single Phase:
transformers maximum full load amps. Transformers will not convert three phase to
Increase transformer kVA by 20% when motors are single phase.
started more than once per hour. A single phase transformer may be connected to a
Derate transformer kVA by .3% for each 330 feet three phase source to furnish single phase power.
over 3300 feet above sea level. The primary of the single phase transformer is
connected to any two of the three phase lines, or in
Parallel Operation: the case of a wye service, to any phase line and the
Transformers may be operated in parallel banks to neutral. Primary voltage of the single phase
achieve higher ampacities under the following transformer must be chosen appropriately to match
circumstances: phase-to-phase or phase-to-neutral voltages of the
Transformer winding voltages must be exactly three phase source.
equal. If there is an imbalance in voltage, excessive Caution must be exercised to avoid unbalanced
current caused by the voltage imbalance will loading of the three phase system supplying power
circulate through the transformer bank, creating to these types of circuits. Examine all connected
heat which will quickly destroy the transformer loads at the three phase source before proceeding.
bank.
Transformer impedances must be the same.
Internal and external polarity must be identical on all Single Phase to Three Phase:
connections. Three phase power requires a three phase source.
Ampacities of the transformers add arithmetically: You cannot use any combination of transformer
two 3 kVA transformers in parallel give a 6 kVA magic to produce three phase power from a
capacity. single phase source. When this is required, a
In addition to the above, three phase transformers rotating phase adder or a special inductive/
must have the same angular displacement and capacitive device called a phase converter must be
phasing. used. This is a highly specialized area, and
In short, the safest way to achieve parallel operation equipment for this purpose should be specified with
is to use identical transformers of the same the advice of firms supplying the phase change
manufacturer. equipment.
98 phase bank is equal to the sum of the individual incompatible with the others.
Transformer Terms and Definitions
Upon receipt of shipment, dry type transformers installations is essential in increasing the safety of
should be thoroughly inspected for any external or personnel.
hidden damage. In the event a product is found to Grounding conductors are sized in accordance with
be damaged, contact the delivering carrier to file a the above cited codes. All ground connections
claim and notify your local Dongan Representative. must be free of paint and nonconductive materials
Save all shipping cartons, crates, and/or skids for including rust, dust and corrosion. In addition,
inspection by the delivering carrier. connections must be tight at all points in order to
Transformers may be extremely heavy. Care must maintain adequate bonds throughout.
be taken when moving, lifting, and handling to
avoid damage to either the transformer or the lifting Installing to minimize Hum:
apparatus. Ventilated, cabinet style transformers
must not be tipped over during movement. Lift truck All energized transformers hum due to the
forks should be placed under the skid provided to alternating magnetic field in the transformers core.
avoid enclosure damage. Dongan transformers are designed to minimize this
noise. While transformer noise is not avoidable,
Lifting provisions are provided on many certain installation techniques will reduce noise
transformers. In some cases, the enclosure top complaints.
cover must be removed to access lifting provisions
provided on the core brackets. A transformer should be installed where it will be
the least objectionable. This is generally away from
quiet areas of a facility. If the ambient sound levels
Installation: are required to be quieter than the transformers
Dry-type transformer installations must comply with all rated sound output, move the transformer to a
applicable national and local codes for overcurrent remote or noisier area. In addition, transformers
protection, enclosure bonding, grounding, etc. should be installed where sound will not reflect
Particular attention must be given to assure all from close surfaces such as nearby walls, ceilings
installations are provided with adequate clearance or floors.
from walls and ceilings, and ventilation is sufficient to Installations should not be chosen that will resonate
provide for free air circulation in and around each
sound. This might occur on thin walls or structures
transformer. Transformers installed in rooms must on which the transformer is mounted or from rigid
have enough ventilation to maintain ambient air
conduit connections. The best installations are
temperatures within established insulation those that most effectively isolate the transformer
temperature limits when measured at or near the
from its surrounding support structures and
transformer ventilation openings or enclosure. connections.
Accessibility to the transformer must be considered
Dongan
when locations for transformers are selected. transformers comply Transformer Average
Whenever possible, installation should be away
with ANSI and NEMA kVA Sound Level
from high traffic areas. Placement must allow standards for sound Range (Decibels)
unrestricted access to covers and panels for
requirements. These
inspection, maintenance, and testing. In addition, standards establish
0-9 40
area must be provided to allow installation of 10 - 50 45
maximum sound
guards for maintenance personnel and, if levels for various
51 - 150 50
necessary, for the removal of the transformer 151 - 300 55
transformer kVA
without major disassembly of other components. ratings as listed in
301 - 500 60
Outdoor applications should be in areas where the chart.
water will not pond or flood into or around the
enclosure or connections. Enclosure ratings must Maintenance:
be appropriate for outdoor use.
Periodic maintenance should be performed by
qualified personnel only. Ventilated openings and
Grounding: transformer enclosures must be kept free of dust
The National Electric Code® , Articles 250 and 450, and debris so as not to restrict the free flow of air
NEMA ST 20 and local electrical codes mandate throughout the transformer. Periodically the unit
methods and practices for providing adequate and should be de-energized and checked for loose
appropriate conductor grounds and enclosure connections and internal collections of dust and
bonds. dirt. Dust may be removed with the use of
Grounding is important because it increases the compressed air or with a vacuum cleaner.
safety of the installation by permitting a path to In addition, when de-energized, the transformer
ground should the transformers coil make contact may be periodically checked for terminal alignment,
with the transformer core or enclosure and for pitted or corroded terminals or wires, and tightness
100 passing accumulated static charge buildup to and condition of ground connections, mounting
bolts and all other hardware.