REVISIONS
REV. DATE ECN # DESCRIPTION BY APPROVED
ADDED SPECIFICATION #3; REMOVED CP
1 8/31/2009 JH JFS
POCKET DIMENSION.
7.00 177.75
5.30 134.62
1.12 28.45
.56 14.22 X .75" SLOTS 6.41 162.81
7.00 177.92
5.30 134.70
7.50 190.50 4.94 125.48
BOLT CIRCLE
.19 4.83 BUSHING TO ROOF GASKET
ROOF MOUNTING FLANGE ONE REQUIRED PER ASSEMBLY
TWO PIECES REQUIRED PER ASSEMBLY MATERIAL: .19" .020" VITON
MATERIAL: ALUMINUM
63.89 1622.86 (REFERENCE ONLY)
7.73 196.34
25.21±.06 640.44±1.52 30.00±.03 762±0.76
(10 SKIRTS)
2.50 63.50 VITON GASKET 5.25 133.35
MINIMUM
1.125 28.58
DAG 213
TYPICAL
.56 14.30
(4 PLACES)
1.75 44.45
4.00 101.60
TYPICAL
4.75 120.65 VITON GASKET 1.75 44.45
TYPICAL
6.62 168.15 ALUMINUM WASHER
2" - 12 UN - 2A THREADS MYLAR TUBE
1.52 38.61 1.38 34.93 .75 19.05
31.52±.25 800.60±6.35
(REF. ONLY) TYPICAL (REF. ONLY)
SPECIFICATIONS:
1. RATED VOLTAGE......................38kV
2. BASIC IMPULSE LEVEL...............250kV
1 3. NOMINAL CURRENT RATING....3500A
4. STRIKE DISTANCE.......................22.00 [558.80] TOP & BOTTOM
5. CREEP DISTANCE (MIN.)...........46.38 [1177.93] TOP & BOTTOM
6. CANTILEVER STRENGTH............200 LBS
7. APPROXIMATE WEIGHT............135.3 LBS
TOLERANCES H-J ENTERPRISES, INC.
MATERIAL: (EXCEPT AS NOTED) 3010 HIGH RIDGE BLVD. HIGH RIDGE, MO. 63049 USA
1. SPADE - COPPER C11000 - TIN PLATED PHONE 1-636-677-3421 FAX 1-636-376-1915
2. STUD - COPPER C11000 - TIN PLATED DECIMAL
3. CLAMP - ALUMINUM 356-T6 OR TENZALLOY PROPRIETARY AND CONFIDENTIAL 38kV 250kV BIL BUSHING ASSEMBLY
+/- .032"/.8mm
4. CAP & WASHER - 6061-T6511 ALUMINUM THE INFORMATION CONTAINED IN THIS
FRACTIONAL
2" - 12 COPPER CONDUCTOR
DRAWING IS THE SOLE PROPERTY OF
PORCELAIN NOTES: H-J ENTERPRISES, INC. ANY
MATERIAL
(SEE DRAWING)
1. WET PROCESS ELECTRICAL PORCELAIN. REPRODUCTION IN PART OR AS A WHOLE +/-
CHK'D APP'D DRAWING NO.
2. GRAY GLAZE MUNSELL 5BG 7.0/0.4
AS1454-003
WITHOUT THE WRITTEN PERMISSION OF ANGULAR
3. TOLERANCE 3% WITH NOTHING LESS THAT .03", UNLESS OTHERWISE NOTED ON DRAWING. H-J ENTERPRISES, INC. IS DRAWN BY DATE SCALE
PROHIBITED. +/- 2 Degrees JH 8/28/2009 N.T.S.