4 Estimation

This document provides estimates for the electrical design of a residential building, including specifications for 20 circuits (C1-C20). It details the conductor length, conduit requirements, junction boxes, and circuit breakers for lighting and convenience outlets in each circuit. The estimates are based on noted ceiling heights, mounting heights and other dimensions.

Uploaded by

Daryl Balgos
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
38 views14 pages

4 Estimation

This document provides estimates for the electrical design of a residential building, including specifications for 20 circuits (C1-C20). It details the conductor length, conduit requirements, junction boxes, and circuit breakers for lighting and convenience outlets in each circuit. The estimates are based on noted ceiling heights, mounting heights and other dimensions.

Uploaded by

Daryl Balgos
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 14

DESIGN ESTIMATE FOR RESIDENTIAL BUILDING

SERVICE ENTRANCE
SERVICE ENTRANCE CONDUCTOR = 15 m of 150 mm² THW COPPER WIRE
SERVICE ENTRANCE CONDUIT = 15/3 = 5 pcs – 40mm ø PVC PIPE

NOTE: CEILING HEIGHT = 3m


SWITCH HEIGHT = 1.5m
PANEL BOARD MOUNTING HEIGHT = 2.5m
ACU OUTLET MOUNTING HEIGHT = 2.5m
POWER OUTLET MOUNTING HEIGHT = 0.3m

C1 – LIGHTING OUTLET
Lighting Outlet Conductor: = 2(1.5 + 0.3 + 1.04 + 0.74 + 0.3 + 2.54 + 0.3 + 3.3 + 0.3 + 2.5 +
0.3 + 1.47 + 0.88 + 0.3 + 0.4 + 0.3 + 0.39 + 3.3 + 0.3 + 3.3 + 0.3 + 3.3 + 0.3 + 2.3 + 0.3 + 3.3 +
0.3 + 3.3 + 0.3 + 3.3 + 0.3) + 2(1.63 + 2 + 16 + 0.5 + 0.3)

Lighting Outlet Conductor = 122.98 m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 61.49/3 = 20.5 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 14 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V

C2 – LIGHTING OUTLET
Lighting Outlet Conductor: = 2(1.5 + 0.3 + 2.5 + 0.3 + 4 + 1 + 0.3 + 3.11 + 0.3 + 3.11 + 0.3)
+2(20 + 1.5 + 0.5 + 0.3)

Lighting Outlet Conductor = 78.04 m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 24.15/3 = 8.5 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 4 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V

C3 – LIGHTING OUTLET
Lighting Outlet Conductor: = 2(1.5 + 0.3 + 2.1 + 1.65 + 0.3 + 2.0 + 0.3 + 2.0 + 0.3) + 2(18 +
5.0 + 0.5 + 0.3)

Lighting Outlet Conductor = 68.5 m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 34.25/3 = 11.5 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 4 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V
C4 – LIGHTING OUTLET
Lighting Outlet Conductor: =
3(1.5+0.3+1+0.5+0.3+1+0.3+2.14+0.3+0.5+0.3+2.0+0.3)+4(2.15+0.3)+3(1.5+0.3+2+0.3)+2(1.9
4+0.3)+3(2.76+0.3)+4(2.31+1.4+1.5+0.3)+3(1.56+0.3)+3(3.32+0.3)+2(2.34+0.3+1.55+1.13+0.3
)+2(1+5.25+1.97+0.5+0.3)

Lighting Outlet Conductor = 134.84 m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 47.92/3 = 16 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 17 pcs.
No. of Utility Box = 3 pcs.
Circuit Breaker = 15A, 2P, 230V

C5 – LIGHTING OUTLET
Lighting Outlet Conductor:
4(1.5+0.3+1.70+0.3)+3(2+0.3+2.0+0.3)+2(2+0.3+2.0+0.3+1.84+0.3+18.4+0.3)+2(0.5+10+2.13
+0.5+0.3)

Lighting Outlet Conductor = 112.14 m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 47.27/3 = 15.8 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 8 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V

C6 – LIGHTING OUTLET
Lighting Outlet Conductor: =
4(1.5+0.3+1.70+0.3)+3(1.62+0.3+1.62+0.3+2.7+0.3+2.7+0.3+1.7+0.3)+2(1.62+0.3)+2(0.5+10+
2.13+0.5+0.3)

Lighting Outlet Conductor = 81.42 m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 30.99/3 = 10.4 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 17 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V

C7 – LIGHTING OUTLET
Lighting Outlet Conductor: =
5(1.5+0.3+1.24+1.1+3.0)+4(3+0.3+1.20+1.60+0.3)+2(3.8+1.61+0.3)+3(1.52+1.5+0.3)+3(2.72+
0.3+2.27+0.3+3.3+0.3+2.37+0.3)+2(1.5+1.20+0.3)+2(1.5+1.2+0.3)+2(3.22+0.3+2.34+0.3)+2(1.
22+1.37+1.45+1.5+0.3)

Lighting Outlet Conductor = 154.26 m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 52.43/3 = 17.5 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 16 pcs.
No. of Utility Box = 2 pcs.
Circuit Breaker = 15A, 2P, 230V

C8 – LIGHTING OUTLET
Lighting Outlet Conductor: =
3(1.26+1.24+1.5+0.3)+2(2+1+0.3)+2(2+0.3+2+0.3)+3(2+0.3+2+0.3)+3(2.4+0.3+2+0.3+2+0.3)+
2(2+0.3)+5(2+0.3)+4(1+0.3+1.5)+2(2.6+2.6+0.6+1.4+1.1+2.85+0.5+0.3)

Lighting Outlet Conductor = 115.6 m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 43.45/3 = 14.5 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 15 pcs.
No. of Utility Box = 2 pcs.
Circuit Breaker = 15A, 2P, 230V

C9 – LIGHTING OUTLET
Lighting Outlet Conductor: =
5(1.63+2.18+1.5+0.3)+3(1.63+0.3+2+1+0.3+2.7+0.3+1.7+0.3)+2(2.6+0.3+2.6+2.6+0.6+1.7+0.3
)+2(1+2.34+0.5+0.3)

Lighting Outlet Conductor = 88.42 m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 30.68/3 = 10.3 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 10 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V

C10 – LIGHTING OUTLET


Lighting Outlet Conductor: =
2(1.74+1.5+0.3+1+0.3+2.16+0.3+19+0.5+0.3)+2(7.17+0.9)+2(12.84+1.8)

Lighting Outlet Conductor = 99.62 m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 49.81/3 = 16.6 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 10 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V

C11 – LIGHTING OUTLET


Lighting Outlet Conductor: =
2(0.4+1.5+1.24+0.3)+2(5.91+0.9)+2(14.75+1.5)+2(3.3+0.96+9.44+1+0.5+0.3)

Lighting Outlet Conductor = 84 m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 42/3 = 14.1 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 9 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V

C12 – LIGHTING OUTLET


Lighting Outlet Conductor: =
2(1.5+0.3+0.95+2.32+0.3+1.37+3.73+4.27+0.3+0.5)+2(4+0.6)+2(13.7+1.5)

Lighting Outlet Conductor = 70.68 m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 35.34/3 = 11.8 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 8 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V

C13 – LIGHTING OUTLET


Lighting Outlet Conductor: = 2(4.48+9+1.36+0+0.5+0.3+2(1.2+0.3+2(11.45+1.5)

Lighting Outlet Conductor = 140.88 m of 2.0 mm2 THHN Copp1er Wire


Lighting Outlet Conduit = 30.09/3 = 10.1 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 6 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V

C14 – LIGHTING OUTLET


Lighting Outlet Conductor: = 2(0.8+1.56+0.5+0.3)+2(1.23+5.56+5.71+0.3+0.5)+2(14.7+1.8)

Lighting Outlet Conductor = 65.92 m of 2.0 mm2 THHN Copp1er Wire


Lighting Outlet Conduit = 32.96/3 = 11 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 8 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V

C15- CONVENIENCE OUTLET


C.O CONDUCTOR = 2(0.5+0.3)+2(18.94+10+1.59+2.7+0.3+1.34+1.79+0.3)

C.O CONDUCTOR = 75.52 m of 3.5 mm² THHN COPPER WIRE


C.O CONDUIT = 37.76/3 = 12.6 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 3 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V

C16- CONVENIENCE OUTLET


C.O CONDUCTOR = 2(0.5+0.3)+2(13.28+4.78+1.16+2.7+0.3)+2(0.64+1.24+0.3)+2(5.4+0.3)
C.O CONDUCTOR = 61.8 m of 3.5 mm² THHN COPPER WIRE
C.O CONDUIT = 30.9/3 = 10.3 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 4 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V

C17- CONVENIENCE OUTLET


C.O CONDUCTOR = 2(0.5+0.3+4.83+10)+2(2.7+0.3+1+1.82+0.3)

C.O CONDUCTOR = 43.5 m of 3.5 mm² THHN COPPER WIRE


C.O CONDUIT = 21.75/3 = 7.3 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 2 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V

C18- CONVENIENCE OUTLET


C.O CONDUCTOR =
2(0.5+0.3+2.84+7.06+1.35+2.7+0.3)+2(2.7+2.7+0.3+1+2.7+2.7+2.7+0.3)

C.O CONDUCTOR = 60.3 m of 3.5 mm² THHN COPPER WIRE


C.O CONDUIT = 30.15/3 = 10.1 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 4 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V

C19- CONVENIENCE OUTLET


C.O CONDUCTOR =
2(0.5+0.3+2.84+7.06+1.35+2.7+0.3)+2(2.7+2+1.35+2.7+0.3)+2(2.23+0.3+1.73+0.3+5.4+1.51+
0.56+0.3)

C.O CONDUCTOR = 72.86 m of 3.5 mm² THHN COPPER WIRE


C.O CONDUIT = 36.43/3 = 12.2 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 6 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V

C20- CONVENIENCE OUTLET


C.O CONDUCTOR = 2(0.5+0.3+3.72+3.14+0.3+1.61+2.7)+2(5.4+3.38+0.3)+2(1.78+0.3)

C.O CONDUCTOR = 46.86 m of 3.5 mm² THHN COPPER WIRE


C.O CONDUIT = 23.43/3 = 7.8 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 4 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V
C21- CONVENIENCE OUTLET
C.O CONDUCTOR = 2(0.5+0.3+12+2.7+1.14+0.3+2.93+0.3)

C.O CONDUCTOR = 40.34 m of 3.5 mm² THHN COPPER WIRE


C.O CONDUIT = 20.17/3 = 6.7 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 2 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V

C22- CONVENIENCE OUTLET


C.O CONDUCTOR = 2(0.5+0.3+2.7+14.28+5+0.3+1.87+0.3)

C.O CONDUCTOR = 50.5 m of 3.5 mm² THHN COPPER WIRE


C.O CONDUIT = 25.25/3 = 8.4 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 2 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V

C23- CONVENIENCE OUTLET


C.O CONDUCTOR = 2(0.5+0.3+2.7+7.38+0.36+0.3)+2(5.4+0.3+1.05+2.67+0.3)

C.O CONDUCTOR = 42.52 m of 3.5 mm² THHN COPPER WIRE


C.O CONDUIT = 21.26/3 = 7.1 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 3 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V

C24- AIR CONDITIONING UNIT


ACU CONDUCTOR = 2(0.5+0.3+4.16+3.44+1.28+0.5+0.3)

ACU CONDUCTOR = 20.96 m of 5.5 mm² THHN COPPER WIRE


ACU CONDUIT = 10.48/3 = 3.5 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V

C25- AIR CONDITIONING UNIT


ACU CONDUCTOR = = 2(0.5+0.3+11.6+2.37+0.5+0.3)

ACU CONDUCTOR = 31.14 m of 5.5 mm² THHN COPPER WIRE


ACU CONDUIT = 15.57/3 = 5.2 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V
C26- AIR CONDITIONING UNIT
ACU CONDUCTOR = 2(0.5+0.3+0.3+0.5+11.46+2.8)

ACU CONDUCTOR = 31.72 m of 5.5 mm² THHN COPPER WIRE


ACU CONDUIT = 15.86/3 = 5.3 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V

C27- AIR CONDITIONING UNIT


ACU CONDUCTOR = 2(0.5+0.6+0.5+6.42+7.20)

ACU CONDUCTOR = 30.44 m of 5.5 mm² THHN COPPER WIRE


ACU CONDUIT = 15.22/3 = 5.1 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V

C28- AIR CONDITIONING UNIT


ACU CONDUCTOR = 2(1+0.6+13+6.35)

ACU CONDUCTOR = 41.9 m of 5.5 mm² THHN COPPER WIRE


ACU CONDUIT = 20.95/3 = 7 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V

C29- REF OUTLET CONDUCTOR


REF OUTLET CONDUCTOR = 2(1+0.6+0.85+5.87)

REF OUTLET CONDUCTOR = 16.64 m of 5.5 mm² THHN COPPER WIRE


REF OUTLET CONDUIT = 8.32/3 = 2.8 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V

C30- WASTE DISPOSER OUTLET CONDUCTOR


WASTE DISPOSER OUTLET CONDUCTOR = 2(1+0.6+5.87)

WD OUTLET CONDUCTOR = 14.94 m of 5.5 mm² THHN COPPER WIRE


WD OUTLET CONDUIT = 7.47/3 = 2.5 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V

C31- MICROWAVE OVEN OUTLET CONDUCTOR


MO OUTLET CONDUCTOR = 2(1+0.6+5.87+0.78+3.2)

MO OUTLET CONDUCTOR = 22.9 m of 5.5 mm² THHN COPPER WIRE


MO OUTLET CONDUIT = 11.45/3 = 3.8 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V

C32- WATER HEATER OUTLET CONDUCTOR


WH OUTLET CONDUCTOR = 2(1+0.6+5.87+1.6+3.2)

WH OUTLET CONDUCTOR = 24.54 m of 5.5 mm² THHN COPPER WIRE


WH OUTLET CONDUIT = 12.27/3 = 4.1 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V

C33- WATER PUMP OUTLET CONDUCTOR


WP OUTLET CONDUCTOR = 2(1.6+2.96+1.29+3.2)

WP OUTLET CONDUCTOR = 18.1 m of 5.5 mm² THHN COPPER WIRE


WP OUTLET CONDUIT = 9.05/3 = 3 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V

C34- DISH WASHER OUTLET CONDUCTOR


DW OUTLET CONDUCTOR = 2(2.7+1.31+1.6+3.2)

DW OUTLET CONDUCTOR = 17.62 m of 5.5 mm² THHN COPPER WIRE


DW OUTLET CONDUIT = 8.81/3 = 3 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V

C35- WASHING MACHINE OUTLET CONDUCTOR


WM OUTLET CONDUCTOR = 2(0.4+0.39+1.6+3.2)

WM OUTLET CONDUCTOR = 11.18 m of 5.5 mm² THHN COPPER WIRE


WM OUTLET CONDUIT = 5.59/3 = 1.9 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V

C36- SPARE OUTLET CONDUCTOR


SPARE OUTLET CONDUCTOR = 2(1.76+1.48+1.6+3.2)

SPARE OUTLET CONDUCTOR = 16.08 m of 5.5 mm² THHN COPPER WIRE


SPARE OUTLET CONDUIT = 8.04/3= 2.7 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V

C37- SPARE OUTLET CONDUCTOR


SPARE OUTLET CONDUCTOR = 2(1.6+3.2+1.48+1)

SPARE OUTLET CONDUCTOR = 14.56 m of 5.5 mm² THHN COPPER WIRE


SPARE OUTLET CONDUIT = 7.28/3 = 2.5 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V

C38 – LIGHTING OUTLET


Lighting Outlet Conductor: =
2(1.5+0.3+1+0.5+0.78+0.3+3.3+0.3)+2(26.4+1.8+26.4+1.8)+2(7.11+0.9)+2(1.91+0.3+17.45+2.
04+0.3+0.5)

Lighting Outlet Conductor = 189.78 m of 2.0 mm2 THHN Copp1er Wire


Lighting Outlet Conduit = 94.89/3 = 31.6 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 14 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V

C39 – LIGHTING OUTLET


Lighting Outlet Conductor: = 2(17.44+0.3+0.5+1.5+0.3+2.34+0.3+3.95+1+0.3)+2(6.24+0.9)

Lighting Outlet Conductor = 70.14 m of 2.0 mm2 THHN Copp1er Wire


Lighting Outlet Conduit = 35.07/3 = 11.7 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 5 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V
C40 – LIGHTING OUTLET
Lighting Outlet Conductor: = 2(2.06+1.5+0.3)+2(4+0.9)+2(1.34+18+4.5+0.5+0.3)

Lighting Outlet Conductor = 66.8 m of 2.0 mm2 THHN Copp1er Wire


Lighting Outlet Conduit = 33.4/3 = 11 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 4 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V

C41 – LIGHTING OUTLET


Lighting Outlet Conductor: = 2(1.5+0.3+1.85+0.3+0.96+26.19+2.7+14+1.5+7.53+4+0.5+03)

Lighting Outlet Conductor = 128.66 m of 2.0 mm2 THHN Copp1er Wire


Lighting Outlet Conduit = 64.33/3 = 21.5 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 15 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V

C42 – LIGHTING OUTLET


Lighting Outlet Conductor: =
2(0.42+1.5+0.3+3.18+0.3+2.91+0.3+12+1.2+0.3+7.53+4.35+0.5+0.3)

Lighting Outlet Conductor = 70.18 m of 2.0 mm2 THHN Copp1er Wire


Lighting Outlet Conduit = 55.09/3 = 18.5 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 6 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V

C43 – LIGHTING OUTLET


Lighting Outlet Conductor: =
3(1+1.5+0.3+1.23+2+0.3)+2(3.15+0.3)+3(2.87+0.3)+4(1.3+1+1.5+0.3+2.3+0.3)+3(3.21+0.3)+2
(2.4+1.48+0.9)+2(6.12+2.45+0.5+0.3)

Lighting Outlet Conductor = 101.03 m of 2.0 mm2 THHN Copp1er Wire


Lighting Outlet Conduit = 37.31/3 = 12.5 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 10 pcs.
No. of Utility Box = 2 pcs.
Circuit Breaker = 15A, 2P, 230V
C44 – LIGHTING OUTLET
Lighting Outlet Conductor: =
2(0.5+0.3+2.8+1.2)+4(1.83+1.5+0.3+3+1.65+0.3)+3(3.32+1.2)+2(2.30+5.18+0.9+3.3+0.3)+3(6.
6+0.9)

Lighting Outlet Conductor = 103.94 m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 37.38/3 = 12.5 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 17 pcs.
No. of Utility Box = 2 pcs.
Circuit Breaker = 15A, 2P, 230V

C45 – LIGHTING OUTLET


Lighting Outlet Conductor: =
4(1.17+2.2+1.5+0.3)+3(5.08+0.9)+2(15.24+1.8)+5(1.65+0.3)+2(1.65+0.3)+2(1+0.3+2.34+0.5)

Lighting Outlet Conductor = 94.63 m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 36.23 /3 = 12.1 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 13 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V

C46 – LIGHTING OUTLET


Lighting Outlet Conductor: =
4(5.5+0.3+1+2.68+0.3)+3(10.38+1.8)+2(1.73+0.3+1.09+4.54+0.5+0.3)

Lighting Outlet Conductor = 92.58 m of 2.0 mm2 THHN Copp1er Wire


Lighting Outlet Conduit = 30.42/3 = 10.2 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 10 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V

C47 – LIGHTING OUTLET


Lighting Outlet Conductor: = 2(1.63+1.5+0.3)+2(9.75+1.5)+2(5.52+0.9)+2(1+1.64+0.5+0.3)

Lighting Outlet Conductor = 49.08 m of 2.0 mm2 THHN Copp1er Wire


Lighting Outlet Conduit = 24.54/3 = 8.2 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 10 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V

C48- CONVENIENCE OUTLET


C.O CONDUCTOR = 2(0.5+0.3+1.23+3.44+2.7+0.3+1.42+1.28+0.3)
C.O CONDUCTOR = 22.94 m of 3.5 mm² THHN COPPER WIRE
C.O CONDUIT = 11.47/3 = 3.8 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 2 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V

C49- CONVENIENCE OUTLET


C.O CONDUCTOR = 2(9+1.7+0.5+0.3+2.7+0.3+2.91+0.3)

C.O CONDUCTOR = 35.42 m of 3.5 mm² THHN COPPER WIRE


C.O CONDUIT = 17.71/3 = 6 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 2 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V

C50- CONVENIENCE OUTLET


C.O CONDUCTOR =
2(0.5+0.3+4.34+2.7+0.30)+2(2.7+0.3+3.43+1.1+2+0.3)+2(5.4+0.5+2.37+0.3+5.4+0.37+0.3)

C.O CONDUCTOR = 65.22 m of 3.5 mm² THHN COPPER WIRE


C.O CONDUIT = 32.61/3 = 10.9 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 6 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V

C51- CONVENIENCE OUTLET


C.O CONDUCTOR = 2(0.5+0.3+2.7+5.08+0.64)+2(0.3+1.87)

C.O CONDUCTOR = 22.78 m of 3.5 mm² THHN COPPER WIRE


C.O CONDUIT = 11.39/3 = 3.8 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 2 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V

C52- CONVENIENCE OUTLET


C.O CONDUCTOR = 2(0.5+0.3+2.7+5.53+5.39+0.3+5.4+0.3+1.17)

C.O CONDUCTOR = 43.18 m of 3.5 mm² THHN COPPER WIRE


C.O CONDUIT = 21.59/3 = 7.2 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 2 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V
C53- CONVENIENCE OUTLET
C.O CONDUCTOR = 2(0.5+0.3+2.7+7+6.78+0.3)+2(5.4+1.14+0.3)+2(0.75+2+0.3)+2(2+0.3)

C.O CONDUCTOR = 59.54 m of 3.5 mm² THHN COPPER WIRE


C.O CONDUIT = 29.77/3 = 10 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 4 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V

C54- CONVENIENCE OUTLET


C.O CONDUCTOR = 2(0.45+0.3)+2(0.47+17.3+0.6+2.7+0.5+0.3)

C.O CONDUCTOR = 59.54 m of 3.5 mm² THHN COPPER WIRE


C.O CONDUIT = 29.77/3 = 10 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 2 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V

C55- CONVENIENCE OUTLET


C.O CONDUCTOR = 2(0.5+0.3+2.7+8.6+5.4+0.3)+2(2.46+1.96+1.02+0.6)

C.O CONDUCTOR = 47.68 m of 3.5 mm² THHN COPPER WIRE


C.O CONDUIT = 23.84/3 = 8 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 3 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V

C56- AIR CONDITIONING UNIT


ACU CONDUCTOR = 2(1.6+5.25+17.04)

ACU CONDUCTOR = 47.78 m of 5.5 mm² THHN COPPER WIRE


ACU CONDUIT = 23.89/3 = 8 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V

C57- AIR CONDITIONING UNIT


ACU CONDUCTOR = 2(1.6+2.76+0.65)

ACU CONDUCTOR = 10.02 m of 5.5 mm² THHN COPPER WIRE


ACU CONDUIT = 5.01/3 = 1.8 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V
C58- AIR CONDITIONING UNIT
ACU CONDUCTOR = 2(1.6+2.80+6.08)

ACU CONDUCTOR = 20.96 m of 5.5 mm² THHN COPPER WIRE


ACU CONDUIT = 10.48/3 = 3.5 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V

C59- AIR CONDITIONING UNIT


ACU CONDUCTOR = 2(5.36+22.07+1.6)

ACU CONDUCTOR = 58.06 m of 5.5 mm² THHN COPPER WIRE


ACU CONDUIT = 29.03/3 = 9.7 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V

C60- AIR CONDITIONING UNIT


ACU CONDUCTOR = 2(1.6+12.24+5.41)

ACU CONDUCTOR = 38.5 m of 5.5 mm² THHN COPPER WIRE


ACU CONDUIT = 19.25/3 = 6.5 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V