DESIGN ESTIMATE FOR RESIDENTIAL BUILDING
SERVICE ENTRANCE
SERVICE ENTRANCE CONDUCTOR = 15 m of 150 mm² THW COPPER WIRE
SERVICE ENTRANCE CONDUIT = 15/3 = 5 pcs – 40mm ø PVC PIPE
NOTE: CEILING HEIGHT = 3m
SWITCH HEIGHT = 1.5m
PANEL BOARD MOUNTING HEIGHT = 2.5m
ACU OUTLET MOUNTING HEIGHT = 2.5m
POWER OUTLET MOUNTING HEIGHT = 0.3m
C1 – LIGHTING OUTLET
Lighting Outlet Conductor: = 2(1.5 + 0.3 + 1.04 + 0.74 + 0.3 + 2.54 + 0.3 + 3.3 + 0.3 + 2.5 +
0.3 + 1.47 + 0.88 + 0.3 + 0.4 + 0.3 + 0.39 + 3.3 + 0.3 + 3.3 + 0.3 + 3.3 + 0.3 + 2.3 + 0.3 + 3.3 +
0.3 + 3.3 + 0.3 + 3.3 + 0.3) + 2(1.63 + 2 + 16 + 0.5 + 0.3)
Lighting Outlet Conductor = 122.98 m of 2.0 mm2 THHN Copper Wire
Lighting Outlet Conduit = 61.49/3 = 20.5 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 14 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V
C2 – LIGHTING OUTLET
Lighting Outlet Conductor: = 2(1.5 + 0.3 + 2.5 + 0.3 + 4 + 1 + 0.3 + 3.11 + 0.3 + 3.11 + 0.3)
+2(20 + 1.5 + 0.5 + 0.3)
Lighting Outlet Conductor = 78.04 m of 2.0 mm2 THHN Copper Wire
Lighting Outlet Conduit = 24.15/3 = 8.5 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 4 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V
C3 – LIGHTING OUTLET
Lighting Outlet Conductor: = 2(1.5 + 0.3 + 2.1 + 1.65 + 0.3 + 2.0 + 0.3 + 2.0 + 0.3) + 2(18 +
5.0 + 0.5 + 0.3)
Lighting Outlet Conductor = 68.5 m of 2.0 mm2 THHN Copper Wire
Lighting Outlet Conduit = 34.25/3 = 11.5 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 4 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V
C4 – LIGHTING OUTLET
Lighting Outlet Conductor: =
3(1.5+0.3+1+0.5+0.3+1+0.3+2.14+0.3+0.5+0.3+2.0+0.3)+4(2.15+0.3)+3(1.5+0.3+2+0.3)+2(1.9
4+0.3)+3(2.76+0.3)+4(2.31+1.4+1.5+0.3)+3(1.56+0.3)+3(3.32+0.3)+2(2.34+0.3+1.55+1.13+0.3
)+2(1+5.25+1.97+0.5+0.3)
Lighting Outlet Conductor = 134.84 m of 2.0 mm2 THHN Copper Wire
Lighting Outlet Conduit = 47.92/3 = 16 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 17 pcs.
No. of Utility Box = 3 pcs.
Circuit Breaker = 15A, 2P, 230V
C5 – LIGHTING OUTLET
Lighting Outlet Conductor:
4(1.5+0.3+1.70+0.3)+3(2+0.3+2.0+0.3)+2(2+0.3+2.0+0.3+1.84+0.3+18.4+0.3)+2(0.5+10+2.13
+0.5+0.3)
Lighting Outlet Conductor = 112.14 m of 2.0 mm2 THHN Copper Wire
Lighting Outlet Conduit = 47.27/3 = 15.8 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 8 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V
C6 – LIGHTING OUTLET
Lighting Outlet Conductor: =
4(1.5+0.3+1.70+0.3)+3(1.62+0.3+1.62+0.3+2.7+0.3+2.7+0.3+1.7+0.3)+2(1.62+0.3)+2(0.5+10+
2.13+0.5+0.3)
Lighting Outlet Conductor = 81.42 m of 2.0 mm2 THHN Copper Wire
Lighting Outlet Conduit = 30.99/3 = 10.4 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 17 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V
C7 – LIGHTING OUTLET
Lighting Outlet Conductor: =
5(1.5+0.3+1.24+1.1+3.0)+4(3+0.3+1.20+1.60+0.3)+2(3.8+1.61+0.3)+3(1.52+1.5+0.3)+3(2.72+
0.3+2.27+0.3+3.3+0.3+2.37+0.3)+2(1.5+1.20+0.3)+2(1.5+1.2+0.3)+2(3.22+0.3+2.34+0.3)+2(1.
22+1.37+1.45+1.5+0.3)
Lighting Outlet Conductor = 154.26 m of 2.0 mm2 THHN Copper Wire
Lighting Outlet Conduit = 52.43/3 = 17.5 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 16 pcs.
No. of Utility Box = 2 pcs.
Circuit Breaker = 15A, 2P, 230V
C8 – LIGHTING OUTLET
Lighting Outlet Conductor: =
3(1.26+1.24+1.5+0.3)+2(2+1+0.3)+2(2+0.3+2+0.3)+3(2+0.3+2+0.3)+3(2.4+0.3+2+0.3+2+0.3)+
2(2+0.3)+5(2+0.3)+4(1+0.3+1.5)+2(2.6+2.6+0.6+1.4+1.1+2.85+0.5+0.3)
Lighting Outlet Conductor = 115.6 m of 2.0 mm2 THHN Copper Wire
Lighting Outlet Conduit = 43.45/3 = 14.5 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 15 pcs.
No. of Utility Box = 2 pcs.
Circuit Breaker = 15A, 2P, 230V
C9 – LIGHTING OUTLET
Lighting Outlet Conductor: =
5(1.63+2.18+1.5+0.3)+3(1.63+0.3+2+1+0.3+2.7+0.3+1.7+0.3)+2(2.6+0.3+2.6+2.6+0.6+1.7+0.3
)+2(1+2.34+0.5+0.3)
Lighting Outlet Conductor = 88.42 m of 2.0 mm2 THHN Copper Wire
Lighting Outlet Conduit = 30.68/3 = 10.3 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 10 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V
C10 – LIGHTING OUTLET
Lighting Outlet Conductor: =
2(1.74+1.5+0.3+1+0.3+2.16+0.3+19+0.5+0.3)+2(7.17+0.9)+2(12.84+1.8)
Lighting Outlet Conductor = 99.62 m of 2.0 mm2 THHN Copper Wire
Lighting Outlet Conduit = 49.81/3 = 16.6 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 10 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V
C11 – LIGHTING OUTLET
Lighting Outlet Conductor: =
2(0.4+1.5+1.24+0.3)+2(5.91+0.9)+2(14.75+1.5)+2(3.3+0.96+9.44+1+0.5+0.3)
Lighting Outlet Conductor = 84 m of 2.0 mm2 THHN Copper Wire
Lighting Outlet Conduit = 42/3 = 14.1 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 9 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V
C12 – LIGHTING OUTLET
Lighting Outlet Conductor: =
2(1.5+0.3+0.95+2.32+0.3+1.37+3.73+4.27+0.3+0.5)+2(4+0.6)+2(13.7+1.5)
Lighting Outlet Conductor = 70.68 m of 2.0 mm2 THHN Copper Wire
Lighting Outlet Conduit = 35.34/3 = 11.8 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 8 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V
C13 – LIGHTING OUTLET
Lighting Outlet Conductor: = 2(4.48+9+1.36+0+0.5+0.3+2(1.2+0.3+2(11.45+1.5)
Lighting Outlet Conductor = 140.88 m of 2.0 mm2 THHN Copp1er Wire
Lighting Outlet Conduit = 30.09/3 = 10.1 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 6 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V
C14 – LIGHTING OUTLET
Lighting Outlet Conductor: = 2(0.8+1.56+0.5+0.3)+2(1.23+5.56+5.71+0.3+0.5)+2(14.7+1.8)
Lighting Outlet Conductor = 65.92 m of 2.0 mm2 THHN Copp1er Wire
Lighting Outlet Conduit = 32.96/3 = 11 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 8 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V
C15- CONVENIENCE OUTLET
C.O CONDUCTOR = 2(0.5+0.3)+2(18.94+10+1.59+2.7+0.3+1.34+1.79+0.3)
C.O CONDUCTOR = 75.52 m of 3.5 mm² THHN COPPER WIRE
C.O CONDUIT = 37.76/3 = 12.6 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 3 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V
C16- CONVENIENCE OUTLET
C.O CONDUCTOR = 2(0.5+0.3)+2(13.28+4.78+1.16+2.7+0.3)+2(0.64+1.24+0.3)+2(5.4+0.3)
C.O CONDUCTOR = 61.8 m of 3.5 mm² THHN COPPER WIRE
C.O CONDUIT = 30.9/3 = 10.3 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 4 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V
C17- CONVENIENCE OUTLET
C.O CONDUCTOR = 2(0.5+0.3+4.83+10)+2(2.7+0.3+1+1.82+0.3)
C.O CONDUCTOR = 43.5 m of 3.5 mm² THHN COPPER WIRE
C.O CONDUIT = 21.75/3 = 7.3 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 2 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V
C18- CONVENIENCE OUTLET
C.O CONDUCTOR =
2(0.5+0.3+2.84+7.06+1.35+2.7+0.3)+2(2.7+2.7+0.3+1+2.7+2.7+2.7+0.3)
C.O CONDUCTOR = 60.3 m of 3.5 mm² THHN COPPER WIRE
C.O CONDUIT = 30.15/3 = 10.1 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 4 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V
C19- CONVENIENCE OUTLET
C.O CONDUCTOR =
2(0.5+0.3+2.84+7.06+1.35+2.7+0.3)+2(2.7+2+1.35+2.7+0.3)+2(2.23+0.3+1.73+0.3+5.4+1.51+
0.56+0.3)
C.O CONDUCTOR = 72.86 m of 3.5 mm² THHN COPPER WIRE
C.O CONDUIT = 36.43/3 = 12.2 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 6 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V
C20- CONVENIENCE OUTLET
C.O CONDUCTOR = 2(0.5+0.3+3.72+3.14+0.3+1.61+2.7)+2(5.4+3.38+0.3)+2(1.78+0.3)
C.O CONDUCTOR = 46.86 m of 3.5 mm² THHN COPPER WIRE
C.O CONDUIT = 23.43/3 = 7.8 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 4 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V
C21- CONVENIENCE OUTLET
C.O CONDUCTOR = 2(0.5+0.3+12+2.7+1.14+0.3+2.93+0.3)
C.O CONDUCTOR = 40.34 m of 3.5 mm² THHN COPPER WIRE
C.O CONDUIT = 20.17/3 = 6.7 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 2 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V
C22- CONVENIENCE OUTLET
C.O CONDUCTOR = 2(0.5+0.3+2.7+14.28+5+0.3+1.87+0.3)
C.O CONDUCTOR = 50.5 m of 3.5 mm² THHN COPPER WIRE
C.O CONDUIT = 25.25/3 = 8.4 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 2 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V
C23- CONVENIENCE OUTLET
C.O CONDUCTOR = 2(0.5+0.3+2.7+7.38+0.36+0.3)+2(5.4+0.3+1.05+2.67+0.3)
C.O CONDUCTOR = 42.52 m of 3.5 mm² THHN COPPER WIRE
C.O CONDUIT = 21.26/3 = 7.1 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 3 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V
C24- AIR CONDITIONING UNIT
ACU CONDUCTOR = 2(0.5+0.3+4.16+3.44+1.28+0.5+0.3)
ACU CONDUCTOR = 20.96 m of 5.5 mm² THHN COPPER WIRE
ACU CONDUIT = 10.48/3 = 3.5 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V
C25- AIR CONDITIONING UNIT
ACU CONDUCTOR = = 2(0.5+0.3+11.6+2.37+0.5+0.3)
ACU CONDUCTOR = 31.14 m of 5.5 mm² THHN COPPER WIRE
ACU CONDUIT = 15.57/3 = 5.2 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V
C26- AIR CONDITIONING UNIT
ACU CONDUCTOR = 2(0.5+0.3+0.3+0.5+11.46+2.8)
ACU CONDUCTOR = 31.72 m of 5.5 mm² THHN COPPER WIRE
ACU CONDUIT = 15.86/3 = 5.3 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V
C27- AIR CONDITIONING UNIT
ACU CONDUCTOR = 2(0.5+0.6+0.5+6.42+7.20)
ACU CONDUCTOR = 30.44 m of 5.5 mm² THHN COPPER WIRE
ACU CONDUIT = 15.22/3 = 5.1 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V
C28- AIR CONDITIONING UNIT
ACU CONDUCTOR = 2(1+0.6+13+6.35)
ACU CONDUCTOR = 41.9 m of 5.5 mm² THHN COPPER WIRE
ACU CONDUIT = 20.95/3 = 7 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V
C29- REF OUTLET CONDUCTOR
REF OUTLET CONDUCTOR = 2(1+0.6+0.85+5.87)
REF OUTLET CONDUCTOR = 16.64 m of 5.5 mm² THHN COPPER WIRE
REF OUTLET CONDUIT = 8.32/3 = 2.8 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V
C30- WASTE DISPOSER OUTLET CONDUCTOR
WASTE DISPOSER OUTLET CONDUCTOR = 2(1+0.6+5.87)
WD OUTLET CONDUCTOR = 14.94 m of 5.5 mm² THHN COPPER WIRE
WD OUTLET CONDUIT = 7.47/3 = 2.5 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V
C31- MICROWAVE OVEN OUTLET CONDUCTOR
MO OUTLET CONDUCTOR = 2(1+0.6+5.87+0.78+3.2)
MO OUTLET CONDUCTOR = 22.9 m of 5.5 mm² THHN COPPER WIRE
MO OUTLET CONDUIT = 11.45/3 = 3.8 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V
C32- WATER HEATER OUTLET CONDUCTOR
WH OUTLET CONDUCTOR = 2(1+0.6+5.87+1.6+3.2)
WH OUTLET CONDUCTOR = 24.54 m of 5.5 mm² THHN COPPER WIRE
WH OUTLET CONDUIT = 12.27/3 = 4.1 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V
C33- WATER PUMP OUTLET CONDUCTOR
WP OUTLET CONDUCTOR = 2(1.6+2.96+1.29+3.2)
WP OUTLET CONDUCTOR = 18.1 m of 5.5 mm² THHN COPPER WIRE
WP OUTLET CONDUIT = 9.05/3 = 3 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V
C34- DISH WASHER OUTLET CONDUCTOR
DW OUTLET CONDUCTOR = 2(2.7+1.31+1.6+3.2)
DW OUTLET CONDUCTOR = 17.62 m of 5.5 mm² THHN COPPER WIRE
DW OUTLET CONDUIT = 8.81/3 = 3 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V
C35- WASHING MACHINE OUTLET CONDUCTOR
WM OUTLET CONDUCTOR = 2(0.4+0.39+1.6+3.2)
WM OUTLET CONDUCTOR = 11.18 m of 5.5 mm² THHN COPPER WIRE
WM OUTLET CONDUIT = 5.59/3 = 1.9 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V
C36- SPARE OUTLET CONDUCTOR
SPARE OUTLET CONDUCTOR = 2(1.76+1.48+1.6+3.2)
SPARE OUTLET CONDUCTOR = 16.08 m of 5.5 mm² THHN COPPER WIRE
SPARE OUTLET CONDUIT = 8.04/3= 2.7 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V
C37- SPARE OUTLET CONDUCTOR
SPARE OUTLET CONDUCTOR = 2(1.6+3.2+1.48+1)
SPARE OUTLET CONDUCTOR = 14.56 m of 5.5 mm² THHN COPPER WIRE
SPARE OUTLET CONDUIT = 7.28/3 = 2.5 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOX = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V
C38 – LIGHTING OUTLET
Lighting Outlet Conductor: =
2(1.5+0.3+1+0.5+0.78+0.3+3.3+0.3)+2(26.4+1.8+26.4+1.8)+2(7.11+0.9)+2(1.91+0.3+17.45+2.
04+0.3+0.5)
Lighting Outlet Conductor = 189.78 m of 2.0 mm2 THHN Copp1er Wire
Lighting Outlet Conduit = 94.89/3 = 31.6 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 14 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V
C39 – LIGHTING OUTLET
Lighting Outlet Conductor: = 2(17.44+0.3+0.5+1.5+0.3+2.34+0.3+3.95+1+0.3)+2(6.24+0.9)
Lighting Outlet Conductor = 70.14 m of 2.0 mm2 THHN Copp1er Wire
Lighting Outlet Conduit = 35.07/3 = 11.7 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 5 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V
C40 – LIGHTING OUTLET
Lighting Outlet Conductor: = 2(2.06+1.5+0.3)+2(4+0.9)+2(1.34+18+4.5+0.5+0.3)
Lighting Outlet Conductor = 66.8 m of 2.0 mm2 THHN Copp1er Wire
Lighting Outlet Conduit = 33.4/3 = 11 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 4 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V
C41 – LIGHTING OUTLET
Lighting Outlet Conductor: = 2(1.5+0.3+1.85+0.3+0.96+26.19+2.7+14+1.5+7.53+4+0.5+03)
Lighting Outlet Conductor = 128.66 m of 2.0 mm2 THHN Copp1er Wire
Lighting Outlet Conduit = 64.33/3 = 21.5 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 15 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V
C42 – LIGHTING OUTLET
Lighting Outlet Conductor: =
2(0.42+1.5+0.3+3.18+0.3+2.91+0.3+12+1.2+0.3+7.53+4.35+0.5+0.3)
Lighting Outlet Conductor = 70.18 m of 2.0 mm2 THHN Copp1er Wire
Lighting Outlet Conduit = 55.09/3 = 18.5 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 6 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V
C43 – LIGHTING OUTLET
Lighting Outlet Conductor: =
3(1+1.5+0.3+1.23+2+0.3)+2(3.15+0.3)+3(2.87+0.3)+4(1.3+1+1.5+0.3+2.3+0.3)+3(3.21+0.3)+2
(2.4+1.48+0.9)+2(6.12+2.45+0.5+0.3)
Lighting Outlet Conductor = 101.03 m of 2.0 mm2 THHN Copp1er Wire
Lighting Outlet Conduit = 37.31/3 = 12.5 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 10 pcs.
No. of Utility Box = 2 pcs.
Circuit Breaker = 15A, 2P, 230V
C44 – LIGHTING OUTLET
Lighting Outlet Conductor: =
2(0.5+0.3+2.8+1.2)+4(1.83+1.5+0.3+3+1.65+0.3)+3(3.32+1.2)+2(2.30+5.18+0.9+3.3+0.3)+3(6.
6+0.9)
Lighting Outlet Conductor = 103.94 m of 2.0 mm2 THHN Copper Wire
Lighting Outlet Conduit = 37.38/3 = 12.5 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 17 pcs.
No. of Utility Box = 2 pcs.
Circuit Breaker = 15A, 2P, 230V
C45 – LIGHTING OUTLET
Lighting Outlet Conductor: =
4(1.17+2.2+1.5+0.3)+3(5.08+0.9)+2(15.24+1.8)+5(1.65+0.3)+2(1.65+0.3)+2(1+0.3+2.34+0.5)
Lighting Outlet Conductor = 94.63 m of 2.0 mm2 THHN Copper Wire
Lighting Outlet Conduit = 36.23 /3 = 12.1 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 13 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V
C46 – LIGHTING OUTLET
Lighting Outlet Conductor: =
4(5.5+0.3+1+2.68+0.3)+3(10.38+1.8)+2(1.73+0.3+1.09+4.54+0.5+0.3)
Lighting Outlet Conductor = 92.58 m of 2.0 mm2 THHN Copp1er Wire
Lighting Outlet Conduit = 30.42/3 = 10.2 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 10 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V
C47 – LIGHTING OUTLET
Lighting Outlet Conductor: = 2(1.63+1.5+0.3)+2(9.75+1.5)+2(5.52+0.9)+2(1+1.64+0.5+0.3)
Lighting Outlet Conductor = 49.08 m of 2.0 mm2 THHN Copp1er Wire
Lighting Outlet Conduit = 24.54/3 = 8.2 pcs. – 15mm Ø PVC Pipe
No. of Junction Box = 10 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V
C48- CONVENIENCE OUTLET
C.O CONDUCTOR = 2(0.5+0.3+1.23+3.44+2.7+0.3+1.42+1.28+0.3)
C.O CONDUCTOR = 22.94 m of 3.5 mm² THHN COPPER WIRE
C.O CONDUIT = 11.47/3 = 3.8 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 2 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V
C49- CONVENIENCE OUTLET
C.O CONDUCTOR = 2(9+1.7+0.5+0.3+2.7+0.3+2.91+0.3)
C.O CONDUCTOR = 35.42 m of 3.5 mm² THHN COPPER WIRE
C.O CONDUIT = 17.71/3 = 6 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 2 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V
C50- CONVENIENCE OUTLET
C.O CONDUCTOR =
2(0.5+0.3+4.34+2.7+0.30)+2(2.7+0.3+3.43+1.1+2+0.3)+2(5.4+0.5+2.37+0.3+5.4+0.37+0.3)
C.O CONDUCTOR = 65.22 m of 3.5 mm² THHN COPPER WIRE
C.O CONDUIT = 32.61/3 = 10.9 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 6 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V
C51- CONVENIENCE OUTLET
C.O CONDUCTOR = 2(0.5+0.3+2.7+5.08+0.64)+2(0.3+1.87)
C.O CONDUCTOR = 22.78 m of 3.5 mm² THHN COPPER WIRE
C.O CONDUIT = 11.39/3 = 3.8 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 2 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V
C52- CONVENIENCE OUTLET
C.O CONDUCTOR = 2(0.5+0.3+2.7+5.53+5.39+0.3+5.4+0.3+1.17)
C.O CONDUCTOR = 43.18 m of 3.5 mm² THHN COPPER WIRE
C.O CONDUIT = 21.59/3 = 7.2 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 2 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V
C53- CONVENIENCE OUTLET
C.O CONDUCTOR = 2(0.5+0.3+2.7+7+6.78+0.3)+2(5.4+1.14+0.3)+2(0.75+2+0.3)+2(2+0.3)
C.O CONDUCTOR = 59.54 m of 3.5 mm² THHN COPPER WIRE
C.O CONDUIT = 29.77/3 = 10 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 4 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V
C54- CONVENIENCE OUTLET
C.O CONDUCTOR = 2(0.45+0.3)+2(0.47+17.3+0.6+2.7+0.5+0.3)
C.O CONDUCTOR = 59.54 m of 3.5 mm² THHN COPPER WIRE
C.O CONDUIT = 29.77/3 = 10 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 2 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V
C55- CONVENIENCE OUTLET
C.O CONDUCTOR = 2(0.5+0.3+2.7+8.6+5.4+0.3)+2(2.46+1.96+1.02+0.6)
C.O CONDUCTOR = 47.68 m of 3.5 mm² THHN COPPER WIRE
C.O CONDUIT = 23.84/3 = 8 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 3 pcs.
CIRCUIT BREAKER = 15A, 2P, 230V
C56- AIR CONDITIONING UNIT
ACU CONDUCTOR = 2(1.6+5.25+17.04)
ACU CONDUCTOR = 47.78 m of 5.5 mm² THHN COPPER WIRE
ACU CONDUIT = 23.89/3 = 8 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V
C57- AIR CONDITIONING UNIT
ACU CONDUCTOR = 2(1.6+2.76+0.65)
ACU CONDUCTOR = 10.02 m of 5.5 mm² THHN COPPER WIRE
ACU CONDUIT = 5.01/3 = 1.8 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V
C58- AIR CONDITIONING UNIT
ACU CONDUCTOR = 2(1.6+2.80+6.08)
ACU CONDUCTOR = 20.96 m of 5.5 mm² THHN COPPER WIRE
ACU CONDUIT = 10.48/3 = 3.5 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V
C59- AIR CONDITIONING UNIT
ACU CONDUCTOR = 2(5.36+22.07+1.6)
ACU CONDUCTOR = 58.06 m of 5.5 mm² THHN COPPER WIRE
ACU CONDUIT = 29.03/3 = 9.7 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V
C60- AIR CONDITIONING UNIT
ACU CONDUCTOR = 2(1.6+12.24+5.41)
ACU CONDUCTOR = 38.5 m of 5.5 mm² THHN COPPER WIRE
ACU CONDUIT = 19.25/3 = 6.5 pcs. of 20mm ø PVC PIPE
NUMBER OF UTILITY BOXES = 1 pc.
CIRCUIT BREAKER = 30A, 2P, 230V