Generator Protection
Generator Protection
OBJECTIVE:
Generation
Overload protection
Overcurrent protection
Overvoltage protection
Unbalanced loading
Rotor faults
Reverse power
Loss of excitation
Loss of synchronization
Parallel operation with grid
DISCUSSION:
GENERATION
ELECTRICAL
MECHANICAL
The neutral point of a generator is usually earthed to facilitate the protection of the
stator winding and associated system. Earthing also prevents damaging transient
overvoltage’s in the event of an arcing earth fault or ferro resonance.
The stator insulation failure can lead to earth fault in the system. Severe arcing to the
machine core could burn the iron at the point of fault and weld laminations together.
In the worst case, it could be necessary to rebuild the core down to the fault
necessitating a major strip-down. Practice, as to the degree of limitation of the earth
fault current varies from rated load current to low values such as 5 A.
Generators connected direct to the distribution network are usually earthed through a
resistor. However, the larger generator–transformer unit (which can be regarded as
isolated from the EHV transmission system) is normally earthed through the primary
winding of a voltage transformer, the secondary winding being loaded with a low
ohmic value resistor. Its reflected resistance is very high (proportional to the turns
ratio squared) and it prevents high transient overvoltage’s being produced as a result
of an arcing earth fault.
For HV generators, impedance is usually inserted in the stator earthing connection to
limit the magnitude of the earth fault current.
When connected directly through impedance, overcurrent relays of both
instantaneous and time-delayed type are used. A setting of 10% of the maximum
earth fault current is considered the safest setting, which normally is enough to avoid
spurious operations due to the transient surge currents transmitted through the
system capacitance. The time delay relay is applied a value of 5%.
Earth fault protection must be applied where impedance earthing is employed that
limits the earth fault current to less than the pick-up threshold of the overcurrent
and/or differential protection for a fault located down to the bottom 5% of the stator
winding from the star-point.
In the voltage-operated type, a standard induction disk type overvoltage relay is
used. It is also to be noted that the relay is connected across the secondary winding
of the transformer and the relay shall be suitably rated for the higher continuous
operating voltage. Further, the relay is to be insensitive for third harmonic current.
Phase-to-phase faults clear of earth are less common. They may occur on the end
coils or on adjacent conductors in the same slot. In the latter case, the fault would
involve earth in a very short time.
OVERLOAD PROTECTION
Generators are very rarely troubled by overload, as the amount of power they can
deliver is a function of the prime mover, which is being continuously monitored by its
governors and regulator. Where overload protection is provided, it usually takes the
form of a thermocouple or thermistor embedded in the stator winding. The rotor
winding is checked by measuring the resistance of the field winding.