0% found this document useful (0 votes)
1K views

HPF Ps10b Manual

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views

HPF Ps10b Manual

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 52

Power Products

HPF-PS6(E)(B) & HPF-PS10(E)(B)


Power Supplies
Instruction Manual

Document LS10227-003HP-E Rev: C


2/2/2022 ECN: 00006488
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke IMPORTANT! Smoke detectors must be installed in the same room
detectors, heat detectors, manual pull stations, audible warning as the control panel and in rooms used by the system for the
devices, and a fire alarm control panel (FACP) with remote connection of alarm transmission wiring, communications, signaling,
notification capability—can provide early warning of a developing fire. and/or power. If detectors are not so located, a developing fire may
Such a system, however, does not assure protection against property damage the alarm system, compromising its ability to report a fire.
damage or loss of life resulting from a fire. Audible warning devices such as bells, horns, strobes, speakers
An emergency communication system—typically made up of an and displays may not alert people if these devices are located on the
automatic fire alarm system (as described above) and a life safety other side of closed or partly open doors or are located on another
communication system that may include an autonomous control unit floor of a building. Any warning device may fail to alert people with a
(ACU), local operating console (LOC), voice communication, and disability or those who have recently consumed drugs, alcohol, or
other various interoperable communication methods—can broadcast medication. Please note that:
a mass notification message. Such a system, however, does not • An emergency communication system may take priority over a fire
assure protection against property damage or loss of life resulting alarm system in the event of a life safety emergency.
from a fire or life safety event. • Voice messaging systems must be designed to meet intelligibility
The Manufacturer recommends that smoke and/or heat detectors be requirements as defined by NFPA, local codes, and Authorities
located throughout a protected premises following the Having Jurisdiction (AHJ).
recommendations of the current edition of the National Fire Protection • Language and instructional requirements must be clearly dissemi-
Association Standard 72 (NFPA 72), manufacturer's nated on any local displays.
recommendations, State and local codes, and the recommendations
• Strobes can, under certain circumstances, cause seizures in peo-
contained in the Guide for Proper Use of System Smoke Detectors,
ple with conditions such as epilepsy.
which is made available at no charge to all installing dealers. This
document can be found at http://www.systemsensor.com/appguides/. • Studies have shown that certain people, even when they hear a
A study by the Federal Emergency Management Agency (an agency fire alarm signal, do not respond to or comprehend the meaning of
of the United States government) indicated that smoke detectors may the signal. Audible devices, such as horns and bells, can have dif-
not go off in as many as 35% of all fires. While fire alarm systems are ferent tonal patterns and frequencies. It is the property owner's
designed to provide early warning against fire, they do not guarantee responsibility to conduct fire drills and other training exercises to
warning or protection against fire. A fire alarm system may not make people aware of fire alarm signals and instruct them on the
provide timely or adequate warning, or simply may not function, for a proper reaction to alarm signals.
variety of reasons: • In rare instances, the sounding of a warning device can cause
Smoke detectors may not sense fire where smoke cannot reach the temporary or permanent hearing loss.
detectors such as in chimneys, in or behind walls, on roofs, or on the A life safety system will not operate without any electrical power. If
other side of closed doors. Smoke detectors also may not sense a fire AC power fails, the system will operate from standby batteries only for
on another level or floor of a building. A second-floor detector, for a specified time and only if the batteries have been properly
example, may not sense a first-floor or basement fire. maintained and replaced regularly.
Particles of combustion or “smoke” from a developing fire may not Equipment used in the system may not be technically compatible
reach the sensing chambers of smoke detectors because: with the control panel. It is essential to use only equipment listed for
• Barriers such as closed or partially closed doors, walls, chimneys, service with your control panel.
even wet or humid areas may inhibit particle or smoke flow. Alarm Signaling Communications:
• Smoke particles may become “cold,” stratify, and not reach the • IP connections rely on available bandwidth, which could be lim-
ceiling or upper walls where detectors are located. ited if the network is shared by multiple users or if ISP policies
• Smoke particles may be blown away from detectors by air outlets, impose restrictions on the amount of data transmitted. Service
such as air conditioning vents. packages must be carefully chosen to ensure that alarm signals
will always have available bandwidth. Outages by the ISP for
• Smoke particles may be drawn into air returns before reaching the
maintenance and upgrades may also inhibit alarm signals. For
detector.
added protection, a backup cellular connection is recommended.
The amount of “smoke” present may be insufficient to alarm smoke
• Cellular connections rely on a strong signal. Signal strength can
detectors. Smoke detectors are designed to alarm at various levels of
be adversely affected by the network coverage of the cellular car-
smoke density. If such density levels are not created by a developing
rier, objects and structural barriers at the installation location. Uti-
fire at the location of detectors, the detectors will not go into alarm.
lize a cellular carrier that has reliable network coverage where the
Smoke detectors, even when working properly, have sensing alarm system is installed. For added protection, utilize an external
limitations. Detectors that have photoelectronic sensing chambers antenna to boost the signal.
tend to detect smoldering fires better than flaming fires, which have
• Telephone lines needed to transmit alarm signals from a premise
little visible smoke. Detectors that have ionizing-type sensing
to a central monitoring station may be out of service or temporarily
chambers tend to detect fast-flaming fires better than smoldering
disabled. For added protection against telephone line failure,
fires. Because fires develop in different ways and are often
backup alarm signaling connections are recommended.
unpredictable in their growth, neither type of detector is necessarily
best and a given type of detector may not provide adequate warning The most common cause of life safety system malfunction is
of a fire. inadequate maintenance. To keep the entire life safety system in
excellent working order, ongoing maintenance is required per the
Smoke detectors cannot be expected to provide adequate warning of
manufacturer's recommendations, and UL and NFPA standards. At a
fires caused by arson, children playing with matches (especially in
minimum, the requirements of NFPA 72 shall be followed.
bedrooms), smoking in bed, and violent explosions (caused by
Environments with large amounts of dust, dirt, or high air velocity
escaping gas, improper storage of flammable materials, etc.).
require more frequent maintenance. A maintenance agreement
Heat detectors do not sense particles of combustion and alarm only should be arranged through the local manufacturer's representative.
when heat on their sensors increases at a predetermined rate or Maintenance should be scheduled as required by National and/or
reaches a predetermined level. Rate-of-rise heat detectors may be local fire codes and should be performed by authorized professional
subject to reduced sensitivity over time. For this reason, the rate-of- life safety system installers only. Adequate written records of all
rise feature of each detector should be tested at least once per year inspections should be kept.
by a qualified fire protection specialist. Heat detectors are designed to Limit-F-2020
protect property, not life.

2 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be con- Like all solid state electronic devices, this system may operate
nected to the fire alarm control panel. Disconnect all sources of erratically or can be damaged when subjected to lightning induced
power before servicing. Control unit and associated equipment may transients. Although no system is completely immune from lightning
be damaged by removing and/or inserting cards, modules, or inter- transients and interference, proper grounding will reduce susceptibil-
connecting cables while the unit is energized. Do not attempt to ity. Overhead or outside aerial wiring is not recommended, due to an
install, service, or operate this unit until manuals are read and under- increased susceptibility to nearby lightning strikes. Consult with the
stood. Technical Services Department if any problems are anticipated or
CAUTION - System Re-acceptance Test after Software Changes: encountered.
To ensure proper system operation, this product must be tested in Disconnect AC power and batteries prior to removing or inserting
accordance with NFPA 72 after any programming operation or circuit boards. Failure to do so can damage circuits.
change in site-specific software. Re-acceptance testing is required Remove all electronic assemblies prior to any drilling, filing, ream-
after any change, addition or deletion of system components, or after ing, or punching of the enclosure. When possible, make all cable
any modification, repair or adjustment to system hardware or wiring. entries from the sides or rear. Before making modifications, verify
All components, circuits, system operations, or software functions that they will not interfere with battery, transformer, or printed circuit
known to be affected by a change must be 100% tested. In addition, board location.
to ensure that other operations are not inadvertently affected, at
least 10% of initiating devices that are not directly affected by the Do not tighten screw terminals more than 9 in-lbs. Over-tightening
change, up to a maximum of 50 devices, must also be tested and may damage threads, resulting in reduced terminal contact pressure
proper system operation verified. and difficulty with screw terminal removal.

This system meets NFPA requirements for operation at 0-49º C/32- This system contains static-sensitive components. Always
120º F and at a relative humidity 93% ± 2% RH (non-condensing) at ground yourself with a proper wrist strap before handling any circuits
32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's so that static charges are removed from the body. Use static sup-
standby batteries and the electronic components may be adversely pressive packaging to protect electronic assemblies removed from
affected by extreme temperature ranges and humidity. Therefore, it the unit.
is recommended that this system and its peripherals be installed in Units with a touchscreen display should be cleaned with a dry,
an environment with a normal room temperature of 15-27º C/60-80º clean, lint free/microfiber cloth. If additional cleaning is required,
F. apply a small amount of Isopropyl alcohol to the cloth and wipe
Verify that wire sizes are adequate for all initiating and indicating clean. Do not use detergents, solvents, or water for cleaning. Do not
device loops. Most devices cannot tolerate more than a 10% I.R. spray liquid directly onto the display.
drop from the specified device voltage. Follow the instructions in the installation, operating, and program-
ming manuals. These instructions must be followed to avoid damage
to the control panel and associated equipment. FACP operation and
reliability depend upon proper installation.
Precau-D2-11-2017

FCC Warning
WARNING: This equipment generates, uses, and can radi- Canadian Requirements
ate radio frequency energy and if not installed and used in This digital apparatus does not exceed the Class A limits for
accordance with the instruction manual may cause interfer- radiation noise emissions from digital apparatus set out in
ence to radio communications. It has been tested and found the Radio Interference Regulations of the Canadian Depart-
to comply with the limits for class A computing devices pur- ment of Communications.
suant to Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against such Le present appareil numerique n'emet pas de bruits radio-
interference when devices are operated in a commercial electriques depassant les limites applicables aux appareils
environment. Operation of this equipment in a residential numeriques de la classe A prescrites dans le Reglement sur
area is likely to cause interference, in which case the user le brouillage radioelectrique edicte par le ministere des
will be required to correct the interference at his or her own Communications du Canada.
expense.

HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate®, FlashScan®, Honeywell®. NOTIFIER®, ONYX®, ONYXWorks®, VeriFire®, and VIEW®
are all registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™
are trademarks of Google Inc. Firefox® is a registered trademark of The Mozilla Foundation.
©2022 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 3


Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent
upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly
recommend that you download the most current version of software for each product prior to commissioning any system. Contact
Technical Support with any questions about software and the appropriate version for a specific application.

Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online
Help or printed manuals, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
[email protected]
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.

This symbol (shown left) on the product(s) and / or accompanying documents means that used electrical and electronic products
should not be mixed with general household waste. For proper treatment, recovery and recycling, contact your local authorities or
dealer and ask for the correct method of disposal.

Electrical and electronic equipment contains materials, parts and substances, which can be dangerous to the environment and harmful
to human health if the waste of electrical and electronic equipment (WEEE) is not disposed of correctly.

4 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


Table of Contents
Section 1: System Overview............................................................................................................................................. 8
1.1: General...............................................................................................................................................................................................................8
1.2: Features..............................................................................................................................................................................................................8
1.3: Specifications.....................................................................................................................................................................................................8
1.4: Open/Short/Ground Fault Trip Values in Standby.............................................................................................................................................9
1.5: Switch SW1 - Ground Fault Detection............................................................................................................................................................10
1.6: Applications .....................................................................................................................................................................................................12
1.7: Start-up Procedure ...........................................................................................................................................................................................12
Section 2: Installation ..................................................................................................................................................... 13
2.1: Backbox Mounting ..........................................................................................................................................................................................13
2.2: NAC Circuit Wiring.........................................................................................................................................................................................14
2.2.1: Class B ..................................................................................................................................................................................................14
2.2.2: ZNAC-PS Class A Option Module.......................................................................................................................................................14
2.3: Addressable Module Mounting........................................................................................................................................................................15
2.4: NEC Power-limited (Class 2) Wiring Requirements.......................................................................................................................................16
2.5: FACP with HPF-PS Power Supply in Slave Configuration.............................................................................................................................17
2.6: HPF-PS Power Supply in Master Configuration Connected to FACP ............................................................................................................17
2.7: Connecting to an External Charger..................................................................................................................................................................18
2.7.1: CHG-120...............................................................................................................................................................................................18
2.7.2: CHG-75.................................................................................................................................................................................................18
2.8: Connecting Multiple Power Supplies ..............................................................................................................................................................19
2.8.1: Cascading Multiple Units .....................................................................................................................................................................19
2.8.2: Daisy-chaining Multiple Units .............................................................................................................................................................20
2.9: Ground Fault Detection ...................................................................................................................................................................................20
Section 3: Programming Options .................................................................................................................................. 23
3.1: S1 Global Options DIP Switch ........................................................................................................................................................................24
3.1.1: Global Programmable Features Description.........................................................................................................................................24
Input Debounce/Dejitter/Delay...............................................................................................................................................................24
Command Input #1 .................................................................................................................................................................................25
Charger Enable/Disable ..........................................................................................................................................................................25
AC Loss Door Holder Dropout Timer ....................................................................................................................................................25
AC Fail Indication Delay........................................................................................................................................................................26
Operating Modes.....................................................................................................................................................................................26
3.2: Output Circuit Control DIP Switch Settings....................................................................................................................................................27
3.2.1: Output Circuit Programmable Features Description ............................................................................................................................28
Command Inputs/NAC Circuit Activation .............................................................................................................................................28
Unused Outputs.......................................................................................................................................................................................28
Remote Supply with Resettable and Non-resettable Power ...................................................................................................................28
Door Holder ............................................................................................................................................................................................29
Synchronizing NACs - Master/Slave Configurations.............................................................................................................................29
Master Configuration - Selective Silence ...............................................................................................................................................29
Class A Wiring........................................................................................................................................................................................30
Section 4: LED Indicators ............................................................................................................................................... 31
Section 5: Trouble Supervision...................................................................................................................................... 34
5.1: Trouble Supervision Using Input Circuits .......................................................................................................................................................34
5.2: General Trouble Relay.....................................................................................................................................................................................35
5.3: AC Trouble Relay ............................................................................................................................................................................................36
Section 6: Power Supply Requirements........................................................................................................................ 38
6.1: Overview..........................................................................................................................................................................................................38
6.2: Calculating the AC Branch Circuit ..................................................................................................................................................................38
6.3: Calculating the System Current Draw .............................................................................................................................................................38
6.3.1: Overview...............................................................................................................................................................................................38
6.3.2: How to Calculate System Current Draw ..............................................................................................................................................39
6.4: Selecting and Locating Batteries .....................................................................................................................................................................39
6.4.1: NFPA Battery Requirements ................................................................................................................................................................39
6.4.2: Maximum Battery Standby Load..........................................................................................................................................................40
Section 7: Testing and Maintenance ............................................................................................................................. 41
7.1: Periodic Testing and Service............................................................................................................................................................................41

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 5


Table of Contents

7.2: Battery Checks and Maintenance ....................................................................................................................................................................41


Appendix A: Wire Requirements.................................................................................................................................... 42
Appendix B: Application Examples ............................................................................................................................... 43
B.1: Controlling NACs For Selective Silence Operation Using a Control Module ...............................................................................................43
B.2: Controlling NACs For Sync Follower Operation Using a Control Module (Default Mode Configuration Only).........................................44
B.3: Controlling NACs, Aux Power, or Door Holders Using a Control Module ...................................................................................................45
B.4: Controlling NACs, Aux Power, and Door Holders with NAC Sync ..............................................................................................................46
B.5: Controlling all Three Inputs with One Control Module..................................................................................................................................47
B.6: AC Trouble Reporting with a Conventional FACP.........................................................................................................................................48
Index ................................................................................................................................................................................. 49

6 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards
set forth by the following regulatory agencies:
• Underwriters Laboratories Standards
• NFPA 72 National Fire Alarm Code

Before proceeding, the installer should be familiar with the following documents.

NFPA Standards
NFPA 72 National Fire Alarm Code
NFPA 70 National Electrical Code

Underwriters Laboratories Documents:


UL 464 Audible Signaling Appliances
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
UL 2572 Standard for Mass Notification Systems

Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)

Other HPP Documents:


Device Compatibility Document Document #54399
SLC Wiring Manual Document #51932
CHG-75 Manual Document #51315
CHG-120 Manual Document #50641

This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems,
UL 864, 10th Edition. Operation of this product with products not tested for UL 864, 9th/10th Edition has not been evaluated. Such operation
requires the approval of the local Authority Having Jurisdiction (AHJ).

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 7


Section 1: System Overview
The HPF-PS6 is a 6 amp and the HPF-PS10 is a 10 amp remote power supply with battery charger. Both models provide ADA compatible
strobe synchronization and a filtered 24 VDC output that can be configured to drive five (6 amp model) or seven (10 amp model) Class B
NACs (Notification Appliance Circuits). NAC circuits can be configured for Class A wiring with the optional ZNAC-PS Class A converter
module. NAC output circuits may be configured as 24 VDC resettable or non-resettable power outputs, or Class D door holder outputs. The
input circuits, which control the power supply operation, are triggered by the reverse polarity of a NAC or by a 12 VDC or 24 VDC power
source. The HPF-PS power supplies are compatible with 12 VDC and 24 VDC control panels.
The HPF-PS6E and HPF-PS10E offer the same features as the HPF-PS6 and HPF-PS10 respectively, but allow connection to 240 VAC.
Unless otherwise specified, the information in this manual applies to both the 120 VAC models and the 240 VAC models.
The HPF-PS6B and HPF-PS10B offer the same features as the HPF-PS6 and HPF-PS10 respectively, but come installed in a black cabinet.

1.1 General
HPF-PS power supplies can be used as remotely mounted power supplies and battery chargers to power non-coded or coded NACs. The
Main FACP (Fire Alarm Control Panel) NAC(s) is connected to the remote power supply input circuit(s). When the command input circuit
activates due to reverse polarity of the NAC from the FACP, the power supply will activate its Notification Appliance Circuits.
During the inactive or non-alarm state, the power supply supervises its NAC field wiring for short and open conditions. In Default Mode,
AC fail, battery, charger and ground fault troubles will also be monitored by the power supply and will activate the AC Fail and General
Trouble relay, respectively. In Retrofit Mode, AC fail, battery, charger, and ground fault troubles will activate the General Trouble relay and
either the Input#1 (If Input#1 is configured as Normal) or Input#2(If Input#1 is configured as Sync Input). The retrofit mode also allows to
further customize the AC fail and ground fault trouble indication, to be reported only at the AC fail relay using S1 Global DIP Switch 8. In
both default and retrofit modes, if a NAC fault is detected, the input end-of-line relay will open to indicate the fault to the main panel. How-
ever, in alarm state all input end-of-line relays are closed to allow input signal daisy-chaining. If an alarm condition occurs and the NAC is
activated, the supervision is disabled and the Notification Appliance Circuit is no longer supervised (except for power-limited conditions).

1.2 Features
• Operates in Default Mode (UL 864 10th Edition compliant) or Retrofit Mode (for use in existing, legacy installations)
• Self-contained in a lockable cabinet
• 24 VDC remote power supply
• Outputs are completely power-limited (Class 2)
• Two (HPF-PS6) or three (HPF-PS10) optically-isolated input/command circuits, compatible with 12 VDC and 24 VDC control panel
NACs
• Five (HPF-PS6) or seven (HPF-PS10) output circuits:
– Fully filtered power
– Five or seven 24 VDC Class B NACs
– Optional ZNAC-PS Class A converter module for conversion to Class A NACs
– Alternatively, all output circuits may be configured as 24 VDC special application power outputs or Class D door holder power
outputs
– Output circuits may be configured as resettable or non-resettable
• Individual NAC Power (red) and Trouble (yellow) LEDs for each output
• Maximum current available:
– HPF-PS6: TB8-TB9 – 1A Regulated, 3A special applications; TB10-TB12 – 0.3A Regulated, 3A special applications
– HPF-PS10: TB8-TB11 – 1.5A Regulated, 3A special applications; TB12-TB14 – 0.3A Regulated, 3A special applications
• Maximum total current available (alarm and standby):
– 6.0 amps for HPF-PS6 alarm; 3.0 amps standby
– 10.0 amps for HPF-PS10 alarm; 3.0 amps standby
• Integral supervised battery charger for lead acid batteries only
• Capable of charging 7.0 AH - 33.0 AH (Amp Hour) batteries (cabinet fits 7 or 18 AH batteries)
• Fully supervised power supply, battery and NACs
• Selectable Strobe Synchronization for NACs (System Sensor, Gentex, Wheelock, and Amseco)
• Coded signal synchronization
• Removable terminal blocks for field wiring capable of accepting 12 - 18 AWG wire
• Selectable Ground Fault detection by switch SW1
• LED trouble diagnostics and history
• Power supply trouble and AC Loss Form-C relay contacts (fail-safe)
• Optional delay of AC loss reporting for 0, 2, 12, or 30 hours
• Mounting location for optional addressable module
• Up to four PS Series units can be cascaded

1.3 Specifications
Refer to Figure 1.1 on page 11 for terminal locations.

NOTE: The HPF-PS6 uses the same PCB layout as the HPF-PS10, however some terminals will be depopulated, leaving the HPF-PS6 with
five output circuits and two input circuits.

8 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


Open/Short/Ground Fault Trip Values in Standby System Overview

Primary AC Power - TB4


• HPF-PS6: 120 VAC, 50/60 Hz, 5.0 amps maximum
• HPF-PS10: 120 VAC, 50/60 Hz, 6.2 amps maximum
• HPF-PS6E: 240 VAC, 50/60 Hz, 2.7 amps maximum
• HPF-PS10E: 240 VAC, 50/60 Hz, 3.5 amps maximum
• Wire size: #12-14 AWG wire with 600V insulation
Command Input Circuits - TB5, TB6, TB7
• Trigger Input Voltage: 9 - 32 VDC
• Input Current Draw in Alarm Polarity: 9 - 32 volts, 14.0 mA maximum per input
Output Circuits - TB8-TB14
• Supervised and power-limited
• Voltage Rating: 24 VDC filtered
• Current:
– HPF-PS6: TB8-TB9 – 1A Regulated, 3A special applications; TB10-TB12 – 0.3A Regulated, 3A special applications (Regulated
power is for industrial horn, strobes, and chimes not included in the Device Compatibility Document. Special application power is
for NAC devices included in Device Compatibility Document, aux power, and door holders.)
– HPF-PS10: TB8-TB11 – 1.5A Regulated, 3A special applications; TB12-TB14 – 0.3A Regulated, 3A special applications
(Regulated power is for industrial horn, strobes, and chimes not included in the Device Compatibility Document. Special application
power is for NAC devices included in Device Compatibility Document, aux power, and door holders.)
– Maximum total alarm current for all output:
HPF-PS6 - 6.0 amps
HPF-PS10 - 10.0 amps
• Output Circuit Types:
– Class B NACs (require 2kΩ - 27kΩ End-of-Line Resistors) and/or Class A NACs using the optional ZNAC-PS Class A converter
module. Use Listed ELRs supplied by the FACP or compatible equipment manufacturer.
– Resettable or non-resettable outputs for 24 VDC power outputs or Class D door holder (max ripple voltage: 780mVRMS)
• Refer to the HPP Device Compatibility Document #54399 for listed compatible devices.
• For wiring requirements, refer to “Wire Requirements” on page 42.
Trouble and AC Loss Relay Contact Rating - TB1-TB2
• Fail-safe Form-C relay (normally energized, transfers with loss of power)
• 4.0 amps @ 30 VDC resistive
Secondary Power (battery) Charging Circuit - TB15
• Supervised, non-power-limited
• Supports lead acid type batteries only
• Float Charge Voltage: 27.6 VDC
• Maximum Peak Charge Current: 2.47A
• Maximum Nominal Charge Current: 1.5 A
• Maximum Battery Capacity: 33.0 AH (with onboard battery charger)
• Minimum Battery Capacity: 7.0 AH
NOTE: The HPF-PS only supports 7AH or 18AH batteries in the cabinet. Other battery capacities up to 33AH will not fit in the cabinet due to
physical dimensions and require a separate battery cabinet.

1.4 Open/Short/Ground Fault Trip Values in Standby


Table 1.1 lists the earth fault resistance detection in standby for each applicable terminal on the FACP.

Output Circuit Terminal Trip Resistance (in ohms)


NAC 1-5/7 + 9.9K or lower
NAC 1-5/7 - 9.2K or lower
ZNAC-PS 1-5/7 + 9.9K or lower
ZNAC-PS 1-5/7 - 9K or lower
Table 1.1 Earth Fault Trip Values

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 9


System Overview Switch SW1 - Ground Fault Detection

Value of the resistance in between any circuit terminal to Earth, which will cause the Ground Fault detection, depends on the ELR chosen for
inputs and output circuits. This resistance will vary from 9.9K down to 0 Ohm.
Table 1.2 lists the open/short trip values and restoral values in standby for the NAC circuits on the FACP.

Circuit Fault Trip Resistance (in ohms) Restore Value


NAC 1-5/7 Short 1.6K or lower 1.7K or higher
NAC 1-5/7 Open 55K or higher 33K or lower
ZNAC-PS 1-5/7 Short 1.6K or lower 1.7K or higher
ZNAC-PS 1-5/7 Open 45K or higher 21K or lower
Table 1.2 NAC Open/Short Trip Values

1.5 Switch SW1 - Ground Fault Detection


The Ground Fault Detection circuit monitors for ground faults. Switch SW1 is located on the lower left section of the power supply circuit
board. Sliding SW1 to the left will disable ground fault detection by the power supply. This should only be done if ground faults are being
monitored by an FACP connected to the HPF-PS power supply or in a cascading application as shown in Section 2.8.1 on page 19.

10 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


Switch SW1 - Ground Fault Detection System Overview

Power-limited (Class 2), Supervised, Special


Note: The HPF-PS6 uses the same PCB Application or Regulated Outputs
layout, however some terminals will be
depopulated, leaving the HPF-PS6 with NAC/Out 7 -
five output circuits and two inputs circuits. NAC/Out 7 +
NAC/Out 6 -
NAC/Out 6 +
NAC/Out 5 -
NAC/Out 5 +
NAC/Out 4 -
TB4 AC Power NAC/Out 4 +
Supervised, NAC/Out 3 -
Non-power-limited NAC/Out 3 +
AC2 (Neutral) Form-C NAC/Out 2 -
Earth Fail-Safe Relays NAC/Out 2 +
AC (Hot) Non-supervised NAC/Out 1 -
(shown energized) NAC/Out 1 +
TB4

AC1 AC2

TB1
TB2

OUT1
OUT6

OUT5

OUT4

OUT3

OUT2
Output Status LEDs
Trouble (yellow)
Power (red)

J8
ZNAC-PS Connector

TB5, TB6, TB7


Command Inputs
Input #1
A+
B-
B+
A-
Input #2
A+
B-
B+
A-
SW1 Ground Fault Input #3
Detection A+
B-
(slide left to disable) B+
(slide right to enable) A-

LEDs
Power (green)

TB15
Batt/Chgr Fault (yellow)
Ground Fault (yellow)

TB15 Supervised Global Output 7 Output 6 Output 5 Output 4 Output 3 Output 2 Output 1
+ Battery Options
- Battery S2-S8
24 VDC S1
Non-power-limited Programming DIP Switches
Programming DIP Switch Activate output DIP switch changes by setting S1
for global options positions 9 and 10 appropriately. Refer to page
page 27 for DIP Switch programming settings.
Each output circuit has its own dedicated
programming DIP switch
Figure 1.1 HPF-PS10 Board Layout

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 11


System Overview Applications

1.6 Applications
The HPF-PS may be used in a number of different applications. It may be used as a remotely-mounted power supply and battery charger
where it can provide up to seven coded or non-coded, synchronized or non-synchronized NACs (Notification Appliance Circuits). Alterna-
tively, any output can be used as a door holder circuit which will provide a steady 24 VDC output until an alarm condition or AC fail condi-
tion causes it to drop to 0 VDC following a selectable delay. See the DIP switch settings for S1 global options on page 24. All outputs can
also provide power.
One possible application for the HPF-PS remote power supply utilizes the NAC repeater feature. In this application, one or two NACs are
connected from the main FACP to the remote power supply command input circuits. When the command input circuits are activated by the
reverse polarity of the NACs, the power supply will activate its corresponding output circuits as programmed by its DIP switch configuration
(refer to Table 3.9 on page 27).
During the inactive state, the remote power supply supervises its NAC field wiring for short and open conditions. If a fault is detected, the
power supply will enter a trouble condition and illuminate the NAC Trouble LED. When the NACs are activated, the supervision is disabled
and the circuits are no longer supervised (except for power-limited conditions). Supervision of other power supply faults such as low battery,
battery charger trouble, ground fault and AC loss will continue and may be monitored via their respective trouble relay.
If an application requires that all outputs activate at the same time, only one NAC is required from the FACP. For this application, the NAC
is connected to command input circuit #1 and the DIP switch is set for this operation.

1.7 Start-up Procedure


1. Configure the power supply switch as described in “Switch SW1 - Ground Fault Detection” on page 10.
2. Install the power supply as described in “Installation” on page 13.
3. Program the power supply as described in “Programming Options” on page 23.
4. Wire the power supply circuits, referring to the options described in “Trouble Supervision” on page 34 and the application examples in
“Application Examples” on page 43.
5. Connect primary power source wiring while observing the following:
– Ensure the AC mains circuit breaker is off before making any wiring connections between the mains and the power supply.
– Make certain primary power source is:
120 VAC, 50/60 Hz, 5.0 (6 amp model) 6.2 amps (10 amp model) or
240 VAC, 50/60 Hz, 2.7 (6 amp model) 3.5 (10 amp model)
– Run a pair of wires (with ground conductor) from the protected premises main breaker box to TB4 of the power supply main circuit
board.
– Use #12-14 AWG gauge wire with 600V insulation.
6. Apply power to the power supply using the following procedure:
– Apply AC power by turning on the AC mains circuit breaker connected to the power supply.
– Connect a properly charged battery to connector TB15 on the power supply main circuit board.
7. Clear trouble history using global DIP switch S1 positions 9 and 10. See DIP switch settings in Table 3.8 on page 27.

12 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


Section 2: Installation
Carefully unpack the system and check for shipping damage. Select a location for the cabinet that is in a clean, dry, vibration-free area where
extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the power
supply. With the hinge mounting on the left, determine the number of conductors required for the devices to be installed and determine the
appropriate knockouts. All wiring must be in accordance with the National and/or Local codes for fire alarm systems and power supplies.

2.1 Backbox Mounting


CAUTION: STATIC SENSITIVE COMPONENTS
! THE CIRCUIT BOARD CONTAINS STATIC-SENSITIVE COMPONENTS. ALWAYS GROUND YOURSELF WITH A PROPER
WRIST STRAP BEFORE HANDLING ANY BOARDS SO THAT STATIC CHARGES ARE REMOVED FROM THE BODY. USE
STATIC SUPPRESSIVE PACKAGING TO PROTECT ELECTRONIC ASSEMBLIES.
1. Mark and pre-drill holes for the top two keyhole mounting bolts.
2. Install two upper fasteners in the wall with the screw heads protruding approximately ¼”.
3. Using the upper keyholes, mount the backbox over the two screws.
4. Mark the lower two holes, remove the backbox from the wall and drill the mounting holes.
5. Mount the backbox, install the remaining fasteners and tighten all screws..

3.424” (8.697cm) Top

Backbox
14.5” (36.8 cm) Depth = 3.424”
(8.697cm)
12.0” (30.48cm)

12.0”
(30.48 cm)

Height = 20.10”
(51.05 cm)

Backbox Mounting Holes

Left Right

1.125” (2.868 cm) Bottom

Figure 2.1 Backbox Mounting Dimensions

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 13


Installation NAC Circuit Wiring

2.2 NAC Circuit Wiring


2.2.1 Class B
The standard configuration for NACs is Class B as shown below. Use Listed ELRs supplied by the FACP or compatible equipment manufac-
turer.
2k-27kΩ ELR

Alarm Polarity Shown


- + Horn Strobe

- + Horn Strobe

- + Horn Strobe

- +

OUT1
OUT6

OUT4

OUT3

OUT2
OUT5

HPF-PS Circuit Board

Figure 2.2 NAC Class B

2.2.2 ZNAC-PS Class A Option Module


The ZNAC-PS is an optional Class A conversion module which mounts to connector J8 on the upper right side of the circuit board. This
module allows the HPF-PS6 or HPF-PS10 to support Class A Notification Appliance Circuits on all outputs. Class A power supervision is
also supported on output circuits #1 and #2 when either of these outputs are configured as resettable or non-resettable auxiliary power.
ZNAC-PS SW1 and SW2 settings must match the HPF-PS output 1 and 2 settings to ensure proper supervision.
Two slide switches are located on the right side of the ZNAC-PS module to properly configure output circuits #1 and #2 for either NAC or
Auxiliary Power operation, as described below. Note that there are no slide switches for the remaining outputs as these outputs do not sup-
port Class A power supervision.
• For output #1, set the upper switch to either “NAC1” or “AUX1” depending on the intended operation.
• For output #2, set the lower switch to either “NAC2” or “AUX2” depending on the intended operation.

NOTE: Class A supervision and the ZNAC-PS module are not intended for use with door holder operation.

- + Alarm
Polarity
Shown
- +
Horn Strobes
- +
- +
OUT1
-NAC1+
TB8

-+
TB2

TB1

OUT1
OUT6

OUT4

OUT3

OUT2
OUT5

NAC1 ZNAC-PS
AUX1
NAC2

AUX2

ZNAC-PS Option Module

HPF-PS Circuit Board

Figure 2.3 Class A NACs using ZNAC-PS Option Module

14 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


Addressable Module Mounting Installation

2.3 Addressable Module Mounting


The HPF-PS has been designed to allow the mounting of an addressable control, relay, or monitor module on the main circuit board inside
the power supply cabinet. This allows power to be fed from an HPF-PS output circuit directly to the module, if needed, without running the
power wires outside the cabinet. Remove mounting screws from the positions indicated below and replace with standoffs (included in hard-
ware kit). Mount the module over the standoffs and secure with screws.
Compatible modules include the XLS-CM-N(CDN), TC810N1013(CDN), XLS-MM-D(CDN), XLS-MM-A(CDN), TC809D1004(CDN),
TC809A1059, TC809A1067CDN, XLS-CM-R(CDN), TC810R1024(CDN), TC822A1010, XP6-C(A), XP6-R(A), and XP10-M(A).
TB1
TB2

TB4

OUT1

OUT1
OUT6

OUT4

OUT3

OUT2
OUT5

OUT6

OUT5

OUT4

OUT3

OUT2
NAC1 NAC1

AUX1 AUX1
NAC2 NAC2

AUX2 AUX2

A+

A+
B-

B-
B+

B+
A-

A-
*If the SLC device does
not match the one in this
A+

A+
Install stacked standoffs
B-

B-
figure, refer to the SLC
B+

B+
(0.5” + 1.093” M/F) manual wiring conver-
A-

A-
sion charts for legacy
A+

A+
and newer versions of
B-

B-
B+

the modules.

B+
A-

A-
TB15

Figure 2.4 Mounting a Single Module in the HPF-PS Cabinet


TB4

AC 1 AC2
TB1
TB2
TB3

OUT1
OUT6

OUT4

OUT3

OUT2
OUT5

OUT1
OUT4

OUT2
OUT6

OUT5

OUT3

BASE ADDRESS +5 BASE ADDRESS +4 BASE ADDRESS +3 BASE ADDRESS +2 BASE ADDRESS +1 BASE ADDRESS +0
6 7 8 9

10
5

2
3
4

SW1
11
12
10

13

J1
0 1514
6 7 8 9

1
5

2
3
4
A+
B-
B+

install 1.093” M/F


A-

standoffs
A+
B-
B+
A-
A+

T16 T11
B-

T10
T15 T14 T13 T12
B+

+5 +4 +3 +2 +1
A-

– + – +
T5 T4 T3 T2 T1
– +
– + – +
– + – + – + – + – + – +
– + +0
T0

TB15

Note: For instructions on mounting a multi-module and a ZNAC-PS module, refer


to the ZNAC-PS Install Sheet #LS10228-000GE-E.
The multi-module must be installed upside down when the ZNAC-PS is installed. If
the ZNAC-PS is not installed, the multi-module may be mounted in either direction.

Figure 2.5 Mounting a Multi-Module in the HPF-PS Cabinet

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 15


Installation NEC Power-limited (Class 2) Wiring Requirements

2.4 NEC Power-limited (Class 2) Wiring Requirements


Power-limited (Class 2) and non-power-limited circuit wiring must remain separated in the cabinet. All power-limited (Class 2) circuit wir-
ing must remain at least 0.25” away from any non-power-limited circuit wiring and all power-limited (Class 2) circuit wiring and non-power-
limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Any conduit
knockouts may be used. For power-limited (Class 2) applications, use of conduit is optional.

AC Power Relay Contacts Output Circuits


Non-power-limited Non-power-limited Circuit Power-limited Circuits (Class 2)

TB11
TB2

TB1

TB13

TB10
TB12

TB9

TB8
TB4

NO NC C NO NC C

NAC1

AUX1
NAC2

AUX2

*If the SLC device

A+
B-
does not match the

B+
A-
one in this figure, Input Circuits

A+
refer to the SLC man- Power-limited Circuit
ual wiring conver- B-
B+
A- (Class 2)
sion charts for legacy
A+

and newer versions of


B-
B+

the modules.
A-

SLC
TB15 Power-limited Circuits
(Class 2)

maintain minimum
0.25” between power-
limited and non-power-
limited wiring

Figure 2.6 Power-limited (Class 2) Wiring Example

16 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


FACP with HPF-PS Power Supply in Slave Configuration Installation

2.5 FACP with HPF-PS Power Supply in Slave Configuration


In this application, the power supply is configured as a Slave unit and connected to a master FACP programmed for synchronized output. .

A+
B-
ELR for

B+
A-
FACP
NAC

A+
B-
NAC programmed for sync

B+
A-
or remote sync output
HPF-PS

A+
B-
B+
A-
FACP
TB15

Figure 2.7 Supervised Master/Slave Connections


The following notes apply to Figure 2.7 on page 17
1. Refer to NFPA 72, Chapter 4-4, Visible Characteristics, Public Mode.
2. Use only devices from the same manufacturer in each system.
3. Set Output DIP Switch: position 3=ON, 4 = OFF, 5 = ON, 6 = OFF.
4. If the FACP has a dedicated sync output connector, wire the remote sync output connector to Input #1 terminals 2 and 3.
5. In this example, the output is mapped to Input#1 in Slave Configuration, but it can programmed to another input using the DIP switches.
6. For NFPA 72 compliance, notification appliances cannot be installed on the FACP control circuit connecting to the HPF-PS input
circuits.

2.6 HPF-PS Power Supply in Master Configuration Connected to FACP


In this application, a master HPF-PS power supply, set for synchronization, is connected to an FACP with non-synchronized output.
A+
B-

ELR for
B+
A-

FACP
NAC
A+
B-

NAC with no synchronization


B+
A-
A+

HPF-PS NAC1
B-
B+
A-

FACP

(also can be triggered by a


TB15 control module or relay module)

Figure 2.8 Supervised FACP to Master Connections (non-synchronized source)


The following notes apply to Figure 2.8.
1. Refer to NFPA 72, Chapter 4-4, Visible Characteristics, Public Mode.
2. Set Output DIP switches to the desired sync protocol as described below. Refer to the Device Compatibility Document for devices.
DIP Switch Position Synchronization Type
3 4 5 6
OFF ON ON OFF Master Configuration - ANSI Temporal (Temporal 3)
ON ON ON OFF Master Configuration - CO Temporal (Temporal 4)
OFF OFF OFF ON Master Configuration - Amseco/Potter
OFF ON OFF ON Master Configuration - Gentex
OFF OFF ON ON Master Configuration - System Sensor
OFF ON ON ON Master Configuration - Wheelock
ON OFF OFF ON Master Configuration, Selective Silence - Amseco/Potter
ON ON OFF ON Master Configuration, Selective Silence - Gentex
ON OFF ON ON Master Configuration, Selective Silence - System Sensor
ON ON ON ON Master Configuration, Selective Silence - Wheelock

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 17


Installation Connecting to an External Charger

3. Use only devices from the same manufacturer in each zone or field of view.
4. In this example, the output is mapped to Input#1 in Master Configuration, but it can programmed to another input using the DIP
switches.
5. For NFPA 72 compliance, notification appliances cannot be installed on the FACP control circuit connecting to the HPF-PS input
circuits.

2.7 Connecting to an External Charger


The HPF-PS Power Supply can be connected to an external charger to charge systems requiring over 33AH batteries. Ensure all power has
been disconnected before wiring. Observe polarity when making connections. Wiring must be in conduit within 20 feet (6.096m) in the same
room.

2.7.1 CHG-120
1. Set S1 position 4 on the HPF-PS Power Supply to the OFF position to disable the onboard battery charger.
2. Connect the battery cables between TB15 (+ and –) on the HPF-PS and the CHG-120 charger output circuit (TB2: Out 1+ and Out 1–)
as shown in Figure 2.9. Be certain to observe polarity.
3. Connect the batteries to the charger.
4. Connect the battery interconnect cable only after AC power is applied and batteries are connected. Refer to the CHG-120 Manual for
more information.
5. Cut and remove Jumper R104 on the CHG-120 to disable ground fault supervision.

TB11 OUT4
TB13 OUT6

TB12 OUT5

TB10 OUT3

TB9 OUT2

TB8 OUT1
TB1
TB2
TB1 TB4

NO NC C NO NC C
R104
TB2
CHG-120 –
+
Cut jumper R104 Charger –
+
– PS Series Power Supply
TB2 +
Note: If batteries are
disconnected at the
CHG-120 terminals,

A+
battery supervision will

B-
B+
be managed by the

A-
CHG-120.

A+
Set S1 position 4 to

B-
B+
A-
the OFF position to

A+
Battery interconnect cable disable charger

B-
B+
A-
– + – +
TB15

12V battery 12V battery

Figure 2.9 Connecting the Power Supply to a CHG-120 Charger

2.7.2 CHG-75
1. Set S1 position 4 on the HPF-PS Power Supply to the OFF position to disable the onboard battery charger.
2. Connect the battery cables between TB15 (+ and –) on the HPF-PS and the CHG-75 charger output circuit (TB2: Out+ and Out–) as
shown in Figure 2.10. Be certain to observe polarity.
3. Connect the batteries to the charger.
4. Connect the battery interconnect cable only after AC power is applied and batteries are connected. Refer to the CHG-75 Manual for
more information.
5. Cut and remove Jumper JP2 on the CHG-75 to disable ground fault detection.
TB11 OUT4
TB13 OUT6

TB10 OUT3
TB12 OUT5

TB9 OUT2

TB8 OUT1
TB1
TB2

JP1 TB4
J4
CUT FOR NO NC C NO NC C
240VAC
AM-1
F1 TB2
+
CHG-75
BAT BAT OUT OUT
+

TENS
11 0 5 7 -
10
TB2
-

8
Charger 14
12 1 +
PS Series Power Supply
+

13 6
TB1
15
9 4 32 ADDRESS
-
-

SW1
HOT NEUT EARTH

11 0 5 7
10 ON OFF
14 8
12 1 JP2
13 6
15 2
9 4 3
ONES
TB3 TB4 J1 J2 J3
A- B+ B- A+

A- B- A+ B+ NC NO C

Cut Jumper JP2 Set S1 position 4 to


A- B+ B- A+

the OFF position to


disable charger
A- B+ B- A+

Battery interconnect cable

- + - + TB15

12V 12V
battery battery -
+

Figure 2.10 Connecting the Power Supply to a CHG-75 Charger

18 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


Connecting Multiple Power Supplies Installation

2.8 Connecting Multiple Power Supplies


2.8.1 Cascading Multiple Units
Up to four HPF-PS power supplies can be cascaded together to provide additional NAC extenders for a system. Maintain separation of
power-limited and non-power-limited wiring as shown in Figure 2.6 on page 16.
Figures 2.11 and 2.12 show the controlling signal connected to Input 1 of HPF-PS1. However, typically any available Input of HPF-PS1 can
be used.
Figures 2.11 and 2.12 show NAC7 of HPF-PS1 - HPF-PS3 as the cascading output. However, any available Output of HPF-PS1 – HPF-PS3
can be used.

NOTE: Any configuration that requires an additional control signal (i.e. a trigger signal), such as Selective Silence or Input #1 Sync
Configuration, will affect which Inputs may be available on PSE1 for use with cascading. (Triggers signals are usually assigned to Input 2.) Refer
to those sections of the manual for specifics.
TB 11 OUT4

TB 11 OUT4

TB11 OUT4

TB11 OUT4
TB13 OUT6

TB13 OUT6

TB13 OUT6

TB13 OUT6
TB12 OUT5

TB10 OUT3

TB12 OUT5

TB10 OUT3

TB12 OUT5

TB10 OUT3

TB12 OUT5

TB10 OUT3
TB 9 OUT2

TB 8 OUT1

TB 9 OUT2

TB 8 OUT1

TB 9 OUT2

TB 8 OUT1

TB 9 OUT2

TB 8 OUT1
TB2

TB1

TB2

TB1

TB2

TB1

TB2

TB1
TB3

TB3

TB3

TB3
TB4 TB4 TB4 TB4

NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C

NAC or remote
sync output

A- B+ B- A+
A- B+ B- A+

A- B+ B- A+

A- B+ B- A+
A- B+ B- A+
A- B+ B- A+

A- B+ B- A+

A- B+ B- A+
A- B+ B- A+
A- B+ B- A+

A- B+ B- A+

A- B+ B- A+
TB15 TB15 TB15 TB15
FACP

HPF-PS4 HPF-PS3 HPF-PS2 HPF-PS1

Figure 2.11 System Sync Connections Triggered by FACP - Cascade

The following notes apply to Figure 2.11.


1. Set all HPF-PS units to Slave (sync follower) Configuration.
2. The debounce/dejitter setting must be set to 1 msec on all cascaded units. See Table 3.3 on page 24.
3. For NFPA 72 2019 compliance, notification appliances cannot be installed on the interconnecting FACP control circuits wired to the
HPF-PS input circuits.
4. The total line impedance for interconnected units cannot be such that it creates a voltage drop > 3.2 VDC.
5. In Default mode, ground fault supervision is provided via the general trouble relay . For ground fault supervision in Retrofit mode, refer
to Table 5.1. Refer to Section 2.9 for different methods of ground fault monitoring for the power supply.
Regulated
24VDC
TB 13 OUT 6

TB 11 OUT 4

TB 13 OUT 6

TB 11 OUT 4

TB 13 OUT 6

TB 11 OUT 4
TB 12 OUT 5

TB 10 O UT 3

TB 12 OUT 5

TB 10 O UT 3

TB 12 OUT 5

TB 10 O UT 3
TB 9 OUT 2

TB 8 OUT 1

TB 9 OUT 2

TB 8 OUT 1

TB 9 OUT 2

TB 8 OUT 1
TB 13 O UT 6

TB 11 O UT 4
TB 12 OUT 5

TB 10 OUT 3

TB 9 O UT2

TB 8 OU T1

TB2

T B1

TB2

T B1

TB2

T B1
TB3

TB3

TB3
TB 1

UL864 listed
TB2
TB3

TB4 TB4 TB4 TB4

NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C

power supply

SLC
A- B+ B- A+
A- B+ B- A+

A- B+ B- A+
A- B+ B- A+

A- B+ B- A+
A- B+ B- A+

A- B+ B- A+
A- B + B- A+

A- B+ B- A+
A- B+ B- A+

A- B+ B- A+
A- B+ B- A+

Control FACP
TB15 TB15 TB15 TB15
Module

HPF-PS4 HPF-PS3 HPF-PS2 HPF-PS1

Figure 2.12 System Sync Connections Triggered by Control Module - Cascade


The following notes apply to Figure 2.12.
1. Set HPF-PS1 to Master configuration, and the desired strobe/horn type. Set remaining HPF-PS units to Slave (sync follower)
configuration.
2. The debounce/dejitter setting must be set to 1 msec on units# HPF-PS2 – HPF-PS4. See Table 3.3 on page 24.
3. Strobe/Horn devices connected to the HPF-PS units are not guaranteed to be in sync with FACP devices when using this configuration
4. For NFPA 72 2019 compliance, notification appliances cannot be installed on the interconnecting FACP control circuits wired to the
HPF-PS input circuits.
5. The total line impedance for interconnected units cannot be such that it creates a voltage drop > 3.2 VDC.
6. In Default mode, ground fault supervision is provided via the general trouble relay . For ground fault supervision in Retrofit mode, refer
to Table 5.1. Refer to Section 2.9 for different methods of ground fault monitoring for the power supply.

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 19


Installation Ground Fault Detection

2.8.2 Daisy-chaining Multiple Units


The number of power supplies which can be daisy-chained is limited by the line resistance and current draw limitations of the upstream mod-
ule or NAC output circuit. Refer to the module, power supply, or fire alarm control panel manual to confirm these circuit specifications.
Maintain separation of power-limited and non-power-limited wiring as shown in Figure 2.6.
Figure 2.13 shows the controlling signal connected to Input 1 of HPF-PS1. However, typically any available Input of HPF-PS1 can be used.

NAC or remote
to next power supplies sync output
in daisy-chain or EOL
(if Class B) or host fire
panel (if Class A).
FACP
HPF-PS3 HPF-PS2 HPF-PS1

Figure 2.13 System Sync Connections Triggered by FACP - Daisy-chaining

The following notes apply to Figure 2.13.


1. The HPF-PS units can be set to work in either Default or Retrofit modes. In standby condition, the input EOL relays are open when they
are used to report troubles, depending on the configured operating mode. Refer to Table 5.1 on page 34. In alarm condition, all inputs
will close their EOL relays to allow the daisy-chaining of input signals.
2. The debounce/dejitter setting must be set to a value that allows the correct detection of input signals. See Table 3.3 on page 24.
3. In Default mode, ground fault supervision is provided via the general trouble relay. For ground fault supervision in Retrofit mode, refer
to Table 5.1. Refer to Section 2.9 for different methods of ground fault monitoring of the power supply. The NAC circuit or remote sync
output is to be monitored by the host FACP.

2.9 Ground Fault Detection


When connected to an FACP, the host FACP must monitor for all ground fault conditions.
There are three ways to monitor for ground faults in the power supply when cascading (up to four) or daisy-chaining power supplies.
1. The negative (-) battery terminal of the HPF-PS power supply must be connected to the negative (-) battery terminal of the host FACP.
Battery wiring is non-power-limited. Power-limited and non-power-limited wiring must be wired with a minimum of 0.25” spacing in
between and enter/exit through different knockouts. When cascading multiple power supply units, continue connecting the negative

20 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


Ground Fault Detection Installation

battery terminals, including FACP battery terminal. Ground faults must then be detected by the first HPF-PS in the chain. Disable
ground fault detection on other HPF-PS units by sliding SW1 to the left. Ensure ground fault detection is enabled on HPF-PS1, the first
power supply from the FACP, by sliding SW1 to the right. 18 AWG wire minimum must be used.
to next
negative
battery wire nut, ground Power Supply Host FACP
terminal cables, and
ground stud

TB11
TB2

TB1

TB13
TB3

TB10
TB12

TB9

TB8
TB4

NO NC C NO NC C NO NC C

optional NAC1

AUX1

ZNAC-PS
NAC2

AUX2

converter
card

A+
B-
B+
SW1 ground fault

A-
detection switch

A+
B-
B+
A-
A+
B-
B+
A-
TB15

Battery - Battery -

Figure 2.14 Ground Fault Detection Option 1


2. Ground fault monitoring may be accomplished by mapping an annunciator point on a UL 864-listed FACP as ground fault. The
annunciator shall be wired adjacent to the FACP so all displays are grouped for viewing and operation by one person.
Addressable FACP: The FACP must be programmed to turn on the common trouble LED, trouble tone, and a separate yellow
annunciator point when the monitor module connected to the HPF-PS ground fault relay is initiated. The annunciator point must also be
labeled as “XXX Ground Fault” where “XXX” describes ground fault origin.

to next
monitor
module
TB11

TB11
TB1

TB1
TB2

TB13

TB2

TB13
TB3

TB3
TB10

TB10
TB12

TB12
TB9

TB8

TB9

TB8

TB4 TB4

NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C
UL 864-listed
NAC1

A UX1
NAC2
NAC1

A UX1
NAC2
annunciator
A UX2 A UX2

UL 864-listed
A- B+ B- A+

A- B+ B- A+

addressable control
A- B+ B- A+

A- B+ B- A+

panel
A- B+ B- A+

A- B+ B- A+

- SLC
TB15 TB15

Maintain 0.25” spacing


between power-limited and
non-power-limited wiring.

Figure 2.15 Ground Fault Detection Option 2 - Addressable FACP

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 21


Installation Ground Fault Detection

3. Conventional FACP: The FACP must be programmed to turn on the common trouble LED, trouble tone, and a separate yellow
annunciator point when the input connected to the HPF-PS ground fault relay is initiated. Use one input per HPF-PS power supply.

Input 1 Input 2
TB2

TB1

TB2

TB1
TB13

TB11

TB13

TB11
TB3

TB3
TB10

TB10
TB12

TB9

TB12

TB9
TB8

TB8
TB4 TB4

NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C

NAC1 NAC1

AUX1 AUX1
N AC2 N AC2

UL 864-listed
AUX2 AUX2

conventional
control panel
A- B+ B- A+

A- B+ B- A+
A- B+ B- A+

A- B+ B- A+
A- B+ B- A+

A- B+ B- A+
UL 864-listed
TB15 TB15
annunciator

Maintain 0.25” spacing


between power-limited and
non-power-limited wiring.

Figure 2.16 Ground Fault Detection Option 3 - Conventional FACP

22 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


Section 3: Programming Options
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below:
Permitted in Settings permitted in
Program feature or option Possible settings
UL864 / UL2572? (Y/N) UL 864 / UL2572
Door Holder Dropout Delay Y Refer to “AC Loss Door Holder Dropout Timer” on • Does not drop
page 25. • 15 seconds
• Does not drop • 60 seconds
• 15 seconds • 5 minutes
• 5 minutes
• 60 seconds
AC Loss Delay Timer Y Refer to “AC Fail Indication Delay” on page 26. • 2 hours1
• 30 hours • none
• 12 hours
• 2 hours
• none
Operating Mode Y Refer to “Operating Modes” on page 26. • Default Mode2
• Retrofit Mode
• Change Output Circuit Configurations
• Display Trouble History
• Default Mode
Table 3.1 Agency-Permitted Programming Settings
1 A two hour delay is only permitted on an addressable FACP.
2 For site compliance to UL864 10th Edition, all power supplies must be configured for Default Mode.
This section describes the programming options available via DIP switch settings. The HPF-PS can be field programmed using DIP switches
S1-S8 which are located at the bottom of the circuit board. S1 controls the global options of the power supply and S2-S8 control the functions
of each output circuit, respectively. Refer to the following illustration for switch locations and DIP switch placement in the ON and OFF
positions.
Important: Activate output DIP switch changes by setting S1 positions 9 and 10 appropriately. Refer to Table 3.8 on page 27 for DIP Switch
programming settings.

TB15

S1 S2-S8

ON ON

1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8
Switches 1 through 9 shown Switches 1 through 7 shown
in OFF (Open) position in OFF (Open) position
Switch 10 shown in
Switch 8 shown in
ON (Closed) position
ON (Closed) position

Figure 3.1 Field Programming DIP Switches

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 23


Programming Options S1 Global Options DIP Switch

3.1 S1 Global Options DIP Switch


The following table lists the global control options for the HPF-PS programmable features and the switch settings required to select a partic-
ular feature. A detailed description of each feature is presented in the following pages. Refer to Table 3.1 for UL-compliant settings.
S1 DIP Switch Function
1, 2 These switches determine the command input debounce/dejitter setting (Setting applies to ALL inputs)1.
1 OFF, 2 OFF = Temporal (for ANSI temporal signals)
1 ON, 2 OFF = 50Hz (20 msec, for full wave rectified signals)
1 OFF, 2 ON = 6 msec (for strobe sync signals, control/relay modules)
1 ON, 2 ON = 1 msec (for strobe sync signals, control/relay modules)
3 This switch determines the function for Command Input #1.2
3 OFF = Command Input #1 as Sync Configuration3
3 ON = Command Input #1 as Normal Configuration
4 This switch controls the battery charger.
4 OFF = Internal battery charger disabled
4 ON = Internal battery charger enabled
5, 6 These switches determine door holder dropout delay after AC power loss
5 OFF, 6 OFF= Power does not drop out
5 ON, 6 OFF = 5 minutes
5 OFF, 6 ON = 60 seconds
5 ON, 6 ON = 15 seconds
7, 8 In DEFAULT MODE: (S1 DIP Switch 9 In RETROFIT MODE: (S1 DIP Switch 9 OFF, 10 OFF)
ON, 10 ON) DIP switch 7 determines the AC loss delay timer
These switches determine the AC loss 7 OFF = 2 hours
delay timer 7 ON = none
7 OFF, 8 OFF = 30 hours DIP switch 8 determines which trouble relays will report the AC and ground faults
7 ON, 8 OFF = 12 hours 8 OFF = AC fault and ground fault reported by the Input #1/
7 OFF, 8 ON = 2 hours Input #2 trouble relay and the General Trouble relay
7 ON, 8 ON = none 8 ON = AC fault is reported only by the AC trouble relay.

9, 10 These switches determine the operating mode of the power supply.


Return switches to Retrofit or Default Mode to exit change output circuit configurations and display trouble history modes!
9 OFF, 10 OFF = Retrofit Mode (existing, legacy installations)
9 ON, 10 OFF = change output circuit configurations
9 OFF, 10 ON = display trouble history
9 ON, 10 ON = Default Mode (UL 864 10th Edition compliant)
Table 3.2 S1 Global Options DIP Switch Settings
1 Debounce/dejitter provides settling time for input signals to avoid false triggers.
2 Strobe synchronization only works with non-coded NACs.
3 Output circuit(s) must be set to activate on Input #2 or Input #3, if applicable. See, "Command Input #1" below.

3.1.1 Global Programmable Features Description


Input Debounce/Dejitter/Delay
Signals from electronic circuits or relay contacts can have a small unstable time when changing state (OFF to ON, or ON to OFF). This
means the signal can briefly “bounce” between states before stabilizing to the desired state, causing signal “jitter” during this time. The
HPF-PS provides four “debounce/dejitter” settings, as shown in the table below. These settings provide time for a NAC Input signal to stabi-
lize before that NAC Input will recognize it as a valid signal, and not just “noise”, so as to prevent false activation of Output circuits. Input
debounce settings can be used as needed. Unless the system experiences input “noise” issues, apply 1ms setting for general use.
Position 1 Position 2 Setting Notes
OFF OFF Temporal Debounces ANSI temporal signals. Allows for a 0.5 second ON signal with an almost 2
second OFF signal to trigger a continuous ON input signal. Do not use for strobe sync
signals.
ON OFF 50Hz (20msec) Debounces FWR (full wave rectified signals). Allows an input signal with 50Hz, 33% duty
cycle to trigger a continuous (i.e. filters FWR input signal to appear constantly on) ON input
signal. May apply to legacy panels. Do not use for strobe sync signals.
OFF ON 6 msec Input delay for strobe sync signals (i.e. Slave Configuration using sync input), or
control/relay modules (i.e. Master or Aux. power Configuration using trigger input).
ON ON 1 msec Input delay for strobe sync signals (i.e. Slave Configuration using sync input), or
control/relay modules (i.e. Master or Aux. power Configuration using trigger input). Must be
the only one used when cascading power supplies. Refer to Section 2.8.1 on page 19.
Table 3.3 Debounce/Dejitter Settings

24 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


S1 Global Options DIP Switch Programming Options

Command Input #1
Power supply Output circuits can be configured to “follow” a sync pattern that is input to Command Input #1 (TB5), either immediately
(Input#1 Normal Configuration), or only after a trigger signal (Input #1 Sync Configuration) is applied at Command Input #2 (TB6) or Com-
mand Input #3 (TB7), if applicable. In Input #1 Sync Configuration, an output circuit will only output the Command Input #1 sync pattern
when Command Input #2 (or Command Input #3 on the HPF-PS10) is receiving a valid (9V - 32V) trigger signal.
• Input #1 is dedicated as the follower input for any synchronization signal received into this input. Do not apply the trigger signal to this
input.
• Input #2 is used for the trigger input for either the 6 amp or 10 amp models. Do not apply the synchronization signal to this input.
• Input #3 can also be used for the trigger input, but is only available on the 10 amp model. Do not apply the synchronization signal to
this input.
• Use only one input (Input #2 or #3) at any one time for the trigger input. When using the Global DIP switch S1 #1 and #2 = ON,ON,
both Input#2 and Input#3 will be used as the trigger input.
• A trigger signal between 9-32VDC is required for proper operation.

If the sync signal is lost in Input#1 Normal Configuration or only the trigger signal is present at Input#2 or #3 in Input#1 Sync Configuration,
the output circuit behavior will depend on the operating mode configuration:
• In Default Mode (Input#1 Normal Configuration, S1 DIP switch 3 ON, 9 ON, 10 ON):
– If the there is no sync signal, the NAC output circuits will be turned OFF immediately.
– If the sync signal is suddenly lost (due to wiring failure), the power supply will turn NACs OFF immediately until a sync signal
appears.
– If the sync signal becomes active after being previously lost (while the trigger signal is ON), the outputs will immediately follow the
Sync signal and NAC configurations.
• In Default Mode (Input#1 Sync Configuration, S1 DIP switch 3 OFF, 9 ON, 10 ON):
– If the there is no sync signal at Input #1, the NAC output circuits will be turned OFF immediately, even if there is a trigger signal at
input #2 or Input#3.
– If the sync signal is suddenly lost at Input #1 (due to wiring failure), the power supply will turn NACs OFF immediately, even if
there is a trigger signal at input #2 or Input#3, until a sync signal appears.
– If the sync signal becomes active after being previously lost, the outputs will immediately follow the Sync signal (provided the
trigger is present at Input#2 or Input#3) and NAC configurations.
• In Retrofit Mode (Input#1 Normal configuration, S1 DIP switch 3 ON, 9 OFF, 10 OFF):
– If there is no sync signal, the NAC circuits will be turned off immediately.
– If the sync signal is suddenly lost (due to wiring failure), the power supply will turn NACs off immediately until a sync signal
appears.
– If the sync signal becomes active after being previously lost (while the trigger signal is on), the outputs will immediately follow the
sync signal and NAC configurations.
• In Retrofit Mode (Input#1 Sync Configuration, S1 DIP switch 3 OFF, 9 OFF, 10 OFF):
– The sync signal is monitored continuously and is declared lost if the signal is off for 3 consecutive seconds. The sync signal is
declared restored (after being previously lost) after it is back on.
– If the trigger signal is activated while the sync signal is in lost state, the power supply will turn NACs on steady with no sync until
the sync signal is restored. The NACs will turn off when the trigger input becomes inactive.
– If the sync signal goes missing while the trigger signal is active, the power supply will turn NACs off until the sync goes into Sync
Lost state (3 sec). After the three seconds, the power supply will turn NACs on steady with no sync.
– If the sync signal goes into the restore state after being previously lost while the trigger signal is active, the outputs will follow the
sync signal and NAC configurations.
Charger Enable/Disable
The HPF-PS battery charger can be disabled to accommodate an external battery charger, such as the CHG-75 or CHG-120. Setting DIP
switch position 4 to the OFF position will disable the charger. Setting DIP switch position 4 to the ON position will enable the charger. It
should only be disabled if an external battery charger is being used for the HPF-PS.
AC Loss Door Holder Dropout Timer
Any output can be configured as a NAC, aux power, or door closer circuit. Configuring an output circuit as a door closer circuit will provide
a steady 24 VDC to door holders until an alarm condition or an AC fail condition. Upon an alarm condition, power to door holder circuits
will be removed, causing doors to close immediately. During an AC fail condition, the door holder will remain energized until the pro-
grammed AC fail indication delay expires. Programmed delays are only applicable to AC loss conditions. Refer to Table 3.1 for UL-compli-
ant settings.
DIP switch positions 5 and 6 are used to select the door holder dropout timer as listed below:
Position 5 Position 6 Door holder dropout delay after AC loss
OFF OFF Power does not drop out with AC loss
ON OFF 5 minutes
OFF ON 60 seconds
ON ON 15 seconds
Table 3.4 Door Holder Dropout Settings

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 25


Programming Options S1 Global Options DIP Switch

AC Fail Indication Delay


The AC Fail Indication Delay feature provides the option to delay generation of a trouble signal upon the loss of AC power. Refer to
Table 3.1 for UL-compliant settings.
 Default Mode
When using the power supply in Default Mode: DIP switch positions 7 and 8 are used to select the AC Fail Indication Delay as listed below:
Position 7 Position 8 AC Fail Indication Delay
OFF OFF 30 hours
ON OFF 12 hours
OFF ON 2 hours
ON ON none
Table 3.5 AC Loss Delay Settings: Default Mode
 Retrofit Mode
When using the power supply in Retrofit Mode: DIP switch position 7 is used to select the AC Fail Indication Delay as listed below:
Position 7 AC Fail Indication Delay
OFF 2 hours
ON none
Table 3.6 AC Loss Delay Settings: Retrofit Mode
DIP switch position 8 is used to select which trouble relays will report any AC and ground faults.
Position 8 AC Fail/Ground Fault Indication
OFF AC faults and ground faults are reported either by the Input #1 EOL relay or Input #2 EOL relay (if Input#1
is configured as sync) and by the General Trouble relay
ON AC faults are reported only by the AC Trouble relay.

Table 3.7 AC Fail/Ground Fault Indication: Retrofit Mode


Refer to “AC Trouble Relay” on page 36, for operation of internal NAC trouble relay in response to AC loss.
Operating Modes
The power supply operates primarily in Default Mode or Retrofit Mode, depending on the installation. While in either mode, the power sup-
ply can be placed in two special, temporary operating modes per settings described in Table 3.8. These modes are Change Output Circuit
Configurations and Display Trouble History. Upon completion of either of these two modes, the system must be placed back in Default or
Retrofit operating mode. Note that the current operation of all outputs will not be affected or disturbed while in either of these two special
operating modes.

NOTE: When switching between Default and Retrofit modes, go to Change Output Circuit Configurations mode first (and remain there for at
least 1 second) and then move to the desired new mode (even if nothing is changed in the DIP switch settings). This will ensure that the
operating mode is updated.

 Default Mode
This is default operating mode of the power supply (the mode configured when the unit is shipped), and is compliant with UL 864 10th Edi-
tion standards. Operation of the power supply will be detailed in Default Mode unless otherwise specified.
 Retrofit Mode
This mode is an alternative to Default Mode, to be used for legacy/existing installations
Note that when the power supply is configured for use in Retrofit Mode, the FACP should be monitoring either Input #1/Input #2 end-of-line
relay or the General Trouble relay, but not both.
In Retrofit Mode, output 1 will blink as visual indication that the panel is operating in Retrofit Mode. Refer to Section 4 for details on LED
patterns.
 Change Output Circuit Configurations Mode

NOTE: DIP switch settings may be changed to the desired configuration either before or after entering Change Output Circuit Configurations
Mode.

1. Enter this mode via the setting shown in Table 3.8. Once entered, the Output trouble LEDs will continually flash from right to left to
confirm the HPF-PS is in Change Output Configuration Mode.
2. Configure settings on the Output DIP switches as needed (see Note above).
3. Return to Default or Retrofit Mode via DIP switches settings for 9 and 10 as shown in Table 3.8 below. The output trouble LEDs will
stop the flash pattern described above to confirm Default or Retrofit Mode has been restored.

26 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


Output Circuit Control DIP Switch Settings Programming Options

 Display Trouble History Mode


To see past troubles on the system, place position 9 to OFF and position 10 to ON. Refer to Section 4 for descriptions of troubles. Trouble
history will be erased upon exiting the Display Trouble History operating mode.
The behavior of the Display Trouble History Mode with regard to the Sync Input Configuration and Trouble reporting will depend on which
was the last active (minimum 5 minutes) operating mode, Default or Retrofit, before entering Display Trouble History Mode.
DIP switch positions 9 and 10 are used to select the type of operating mode as listed below:
Position 9 Position 10 Operating Mode
OFF OFF Retrofit Mode
ON OFF Change output circuit configurations
OFF ON Display Trouble History
ON ON Default Mode
Table 3.8 Operating Mode

3.2 Output Circuit Control DIP Switch Settings


Each output circuit has its own programming DIP switch. DIP switches S2-S8 are labeled on the PCB to indicate which output circuit it is
controlling. Output circuits are labeled at the top of the PCB, TB8-TB14.The following table applies to DIP Switches S2-S8.
Important! If an output circuit is overloaded, the output will shut off and generate a trouble signal. If this happens, the HPF-PS will need to
be reset manually. Either reset circuit configurations by toggling switch S1 position 10 to the OFF position for a minimum of five seconds or
turn off primary and secondary power and reapply to the HPF-PS.

DIP Switch Position


Output Control Setting/Operation
1 2
OFF OFF NAC output will activate when Command Input #1 is activated.
Do not use this setting when Input#1 is set to Sync Configuration.
ON OFF NAC output will activate when Command Input #2 is activated.
(Exception: this Input controls Horn silencing during Selective Silence operation.)
OFF ON NAC output will activate when Command Input #3 is activated, if available. (If
accidentally programmed on a HPF-PS6, the system will default to Input #2.)
ON ON NAC output will activate when ANY Command Input is activated.
If Input #1 is set to Sync Configuration (Global DIP switch 3 = OFF), this setting applies
to Input#2 and Input#3 only.
3 4 5 6 Output Control Setting/Operation
OFF OFF OFF OFF Unused/Unsupervised. Outputs will not activate. Factory default setting.
ON OFF OFF OFF Reserved- Outputs will not activate
OFF ON OFF OFF Non-resettable auxiliary power
OFF OFF ON OFF Resettable aux power
ON ON OFF OFF Door holder auxiliary power
ON OFF ON OFF Slave Configuration (NAC follower)
OFF ON ON OFF Master Configuration - ANSI Temporal (Temporal 3)
ON ON ON OFF Master Configuration - CO Temporal (Temporal 4)
OFF OFF OFF ON Master Configuration - Amseco/Potter
OFF ON OFF ON Master Configuration - Gentex
OFF OFF ON ON Master Configuration - System Sensor
OFF ON ON ON Master Configuration - Wheelock
ON OFF OFF ON Master Configuration, Selective Silence - Amseco/Potter
ON ON OFF ON Master Configuration, Selective Silence - Gentex
ON OFF ON ON Master Configuration, Selective Silence - System Sensor
ON ON ON ON Master Configuration, Selective Silence - Wheelock
7 Output Control Setting/Operation (Only applies when ZNAC-PS is installed)
OFF Class B
ON Class A
8 Output Control Setting/Operation (Unused)
OFF Unused/Unassigned
ON Unused/Unassigned
Table 3.9 S2-S8 Output Circuit DIP Switch Settings

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 27


Programming Options Output Circuit Control DIP Switch Settings

3.2.1 Output Circuit Programmable Features Description


Command Inputs/NAC Circuit Activation
The HPF-PS allows for individual NAC circuit programming. Each NAC can be configured to activate based on the settings selected for up
to 3 command inputs.
Set DIP switch positions 1 and 2 according to which input circuit is used as the trigger input for the coordinating configuration as shown
below.
Position 1 Position 2 Default Normal Default Sync Retrofit Normal Retrofit Sync
OFF OFF NAC will activate when Input N/A NAC will activate when Input N/A
#1 activates. #1 activates.
ON OFF NAC will activate when input NAC will activate when NAC will activate when input NAC will activate when Input
#2 activates. Input #2 activates provided #2 activates. #2 is active regardless of
(Exception: this Input controls the sync signal is present at (Exception: this Input controls sync input at Input #1.
Horn silencing during Input #1. Horn silencing during If Sync signal is present at
Selective Silence operation.) Selective Silence operation.) Input #1, the output follows
the sync. If the sync signal at
Input #1 is deemed LOST,
the outputs will turn on
steady.
OFF ON NAC will activate when Input NAC will activate when Input NAC will activate when Input NAC will activate when Input
#3 activates (Input #3 is only #3 activates, provided the #3 activates (Input #3 is only #3 is active regardless of
available on the HPF-PS10 sync signal is present at available on the HPF-PS10 sync input at Input #1.
model. If selected on HPF- Input #1 (Input #3 is only model. If selected on HPF- If Sync signal is present at
PS6, this setting will default available on the HPF-PS10 PS6, this setting will default Input #1, the output follows
to input #2.) model. If selected on HPF- to input #2.) the sync. If the sync signal at
PS6, this setting will default Input #1 is deemed LOST,
to input #2.) the outputs will turn on
steady.
ON ON NAC will activate when any NAC will activate when input NAC will activate when any NAC will activate when Input
input (1, 2, or 3) activates. #2 or input #3 activate input (1, 2, or 3) activates. #2 OR Input #3 is active
provided sync signal is regardless of sync input at
present at Input #1. Input #1.
If Sync signal is present at
Input #1, the output follows
the sync.
If the sync signal at Input #1
is deemed LOST, the outputs
are turned on steady.
Table 3.10 Output to Command Input Assignment
See Section 5 for an explanation of trouble reporting for each mode of operation.
Unused Outputs
The factory default setting for all output circuits is “unused/unsupervised” where positions 3, 4, 5, and 6 are set to the OFF position. Any
unused or disabled outputs in the system configuration must be set to OFF as shown below.
Position 3 Position 4 Position 5 Position 6 Auxiliary Power Type
OFF OFF OFF OFF Unused/Unsupervised. Outputs will not activate.
Factory default setting.
ON OFF OFF OFF Reserved- Outputs will not activate
Table 3.11 Auxiliary Power Settings
Remote Supply with Resettable and Non-resettable Power
Each output circuit on the HPF-PS can be used as a remote stand-alone power supply to provide power to any devices that require filtered,
resettable or non-resettable power. The HPF-PS can provide up to 3 amps of continuous current. Non-resettable power is suitable for power-
ing annunciators and other peripheral equipment. Resettable power is suitable for four-wire smoke detectors. Resettable outputs reset when
the mapped input receives a negative pulse trigger signal from FACP or control module. There will be a three second delay prior to output
reset. The output reset will last 10 seconds. Set DIP switches positions indicated in Table 3.12 below to select auxiliary power type.
Position 3 Position 4 Position 5 Position 6 Auxiliary Power Type
OFF ON OFF OFF Non-resettable (constant) aux power
OFF OFF ON OFF Resettable aux power
Table 3.12 Auxiliary Power Settings

28 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


Output Circuit Control DIP Switch Settings Programming Options

Door Holder
Each output circuit can be configured as a door holder circuit. Setting DIP switch positions according to Table 3.13 will configure the
selected output circuit as a door holder circuit which will provide a steady 24 VDC to door holders until a mapped input activates an alarm or
when an AC fail condition removes the power following a programmable delay. See “AC Loss Door Holder Dropout Timer” on page 25 for
more information.
Position 3 Position 4 Position 5 Position 6 Door Holder
ON ON OFF OFF Set as door holder circuit
Table 3.13 Door Holder Power
Synchronizing NACs - Master/Slave Configurations
Each of the HPF-PS power supply outputs can be independently configured for Master or Slave Synchronization by setting DIP switches
according to Table 3.14. Synchronization is a feature that controls the activation of notification appliances in such a way that all devices will
turn on and off at exactly the same time. This is particularly critical when activating strobes which must be synchronized to avoid random
activation and a potential hazard or confusion.
In some installations, it is necessary to synchronize the flash timing of all strobes in the system for ADA compliance. Strobes accomplish
this by monitoring very short timing pulses on the NAC power which are created by an FACP with synchronization capability. If a NAC wire
run from the host FACP or power supply is repurposed as a control circuit to the input of a HPF-PS, the HPF-PS NAC output circuits can
track (follow) the strobe synchronization timing pulses. This maintains the overall system flash timing of the additional strobes attached to
this power supply. Note that strobe synchronization works only with non-coded NACs.
When the output circuit is configured as a sync generator (Master Synchronization Configuration), the sync input circuit will only be used to
trigger the output. The power supply is the originator of the strobe synchronization pulse on the NAC output. Refer to Table 3.14 to select the
desired Master Configuration sync type.
When the output circuit is configured as a sync follower (Slave Synchronization Configuration), the power supply’s NAC outputs track the
strobe synchronization pulses present at the supply’s Input terminals (based on the settings selected from Table 3.10). The pulses originate
from an upstream FACP or other power supply. Some FACPs provide synchronization timing pulses from a dedicated sync output connector.
Connect the HPF-PS input terminals to the FACP sync output connector instead of the FACP NAC.
If circuits are configured for both Master and Slave Configuration, devices must be installed in different zones or field of view on a circuit
basis.
Position 3 Position 4 Position 5 Position 6 Synchronization Type
ON OFF ON OFF Slave Configuration (NAC follower) - NAC outputs track Command Input
Circuits
OFF ON ON OFF Master Configuration - ANSI Temporal (Temporal 3)
ON ON ON OFF Master Configuration - CO Temporal (Temporal 4)
OFF OFF OFF ON Master Configuration - Amseco/Potter
OFF ON OFF ON Master Configuration - Gentex
OFF OFF ON ON Master Configuration - System Sensor
OFF ON ON ON Master Configuration - Wheelock
Table 3.14 Input#1 Sync Configuration - Master/Slave Configuration Settings
Master Configuration - Selective Silence
Selective Silence allows the silencing of the sounder portion of a horn/strobe combination device without turning off the strobe. Selective
Silence is only supported while in Master Configuration setting for Amseco, Gentex, System Sensor, and Wheelock. Refer to Table 3.15 to
select the desired Master Configuration, Selective Silence sync type.

NOTE: Do not apply synchronization signals to Command Input #1 and 2. Only trigger signals are allowed (i.e. constant 9-32 VDC).
Synchronization signal is internally generated by the system when in Master Configuration.

Only Command Inputs #1 and #2 are used to control the Selective Silence operation. (Command Input #3 on HPF-PS10 does not support
Selective Silence.) Input #1 is for activating the horn/strobe devices, while Input 2 only controls sounding of the horns. Input #1 must be
active for Input #2 to have any effect on NAC outputs set for Selective Silence. The list below provides additional detail.
• If only Command Input #1 is active, only the strobes will be activated .
• If both Command Input #1 and #2 are active, strobes and horns will be activated.
• If only Command Input #2 is active, NAC outputs will not be activated.
• If neither Command Input #1 nor #2 is active, NAC outputs will not be activated.
Position 3 Position 4 Position 5 Position 6 Synchronization Type
ON OFF OFF ON Master Configuration, Selective Silence - Amseco/Potter
ON ON OFF ON Master Configuration, Selective Silence - Gentex
ON OFF ON ON Master Configuration, Selective Silence - System Sensor
ON ON ON ON Master Configuration, Selective Silence - Wheelock
Table 3.15 Master Configuration - Selective Silence Settings

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 29


Programming Options Output Circuit Control DIP Switch Settings

Class A Wiring
NAC circuits (all outputs) and aux power circuits (outputs 1 and 2) can be converted to Class A wiring using the ZNAC-PS option card. Set-
ting DIP switch position 7=ON when a selected output circuit is configured for Class A wiring. The default setting is OFF for Class B wir-
ing.
 Maximum Number of Strobes for Synchronization
The total current draw for each Notification Appliance Circuit cannot exceed 3.0 amps special application, 1A (6 amp model) or 1.5A (10
amp model) regulated. Refer to the manufacturer’s documentation supplied with the strobe to determine the maximum current draw for each
strobe and ensure that the circuit maximum is not exceeded.
To ensure proper strobe and circuit operation, there is also a limit to the number of strobes that can be attached to each circuit. Following is a
table of the strobes that have been tested with the power supply and the maximum number that can be connected to each NAC when using
the lowest candela settings. Make sure that the NAC maximum current is not exceeded:
Manufacturer max. number of strobes1
System Sensor 69
Gentex 42
Wheelock 50
Amseco/Potter 34
Table 3.16 Maximum Number of Strobes
1 These values are for strobe-only devices at the minimum
candela setting. Values will be different for strobe/horn and
horn-only devices. Refer to the manufacturer’s installation
documents for values on these devices.

30 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


Section 4: LED Indicators
The HPF-PS power supply has 3 system LED indicators for Power, Batt/Chgr Fault, and Ground Fault. In addition, each available output cir-
cuit also has 2 status LEDs. Refer to Figure 1.1 on page 11 for LED locations. A description of each HPF-PS LED indication is given below.

Ground Fault LED (yellow)


No Fault LED is OFF

Fault Condition: LED is ON constant


ground fault

Power LED (green)


No Fault LED is ON constant

Fault Condition: Repeating LED blink pattern (non-diagnostic phase and diagnostic phase)
AC power loss (or brownout)
1 short blink (250ms) Retrofit Mode* pause

250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms 1000ms 1000ms
*Retrofit Mode will be indicated by an LED blink on the NAC1 Trouble LED only.

Battery fault LED (yellow)


No Fault LED is OFF

Fault Condition: Repeating LED blink pattern (non-diagnostic phase and diagnostic phase)
Charging path (FETs) failure
1 short blink (250ms) Retrofit Mode* pause

250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms 1000ms 1000ms

Fault Condition: Repeating LED blink pattern (non-diagnostic phase and diagnostic phase)
Charger voltage too low or
Charger Diode Fault Retrofit Mode* pause
2 short blinks (250ms)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms 1000ms 1000ms

Fault Condition: Repeating LED blink pattern (non-diagnostic phase and diagnostic phase)
Battery
discharged/overcharged
Retrofit Mode* pause
3 short blinks (250ms)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms 1000ms 1000ms

Fault Condition: Repeating LED blink pattern (non-diagnostic phase and diagnostic phase)
Battery disconnected/fully
discharged Retrofit Mode* pause
4 short blinks (250ms)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms 1000ms 1000ms

*Retrofit Mode will be indicated by an LED blink on the NAC1 Trouble LED only.

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 31


LED Indicators

Output Circuit Status LEDs (red)


Output inactive LED is OFF

Output active LED is ON constant

Output Circuit Trouble LEDs (yellow)


No Fault LED is OFF

Fault Condition: Repeating LED blink pattern (non-diagnostic phase and diagnostic phase)
Wire Supervision
Class A or B Open circuit Retrofit pause
1 short blink (250ms) Mode*
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms 1000ms 1000ms

*Retrofit Mode will be indicated by an LED blink on the NAC1 Trouble LED only
Fault Condition: Repeating LED blink pattern (non-diagnostic phase and diagnostic phase)
Wire Supervision
Class A or B Short Circuit Retrofit pause
2 short blinks (250ms) Mode*
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms 1000ms 1000ms

*Retrofit Mode will be indicated by an LED blink on the NAC1 Trouble LED only
Fault Condition: Repeating LED blink pattern (non-diagnostic phase and diagnostic phase)
Aux Power Supervision
Class A Open circuit Retrofit pause
(ZNAC-PS Circuit #1 and #2 only) Mode*
3 short blinks (250ms) 250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms 1000ms 1000ms

*Retrofit Mode will be indicated by an LED blink on the NAC1 Trouble LED only
Fault Condition: Repeating LED blink pattern (non-diagnostic phase and diagnostic phase)
Power limit condition (individual ckt overload)
4 short blinks per individual circuit (250ms) Retrofit pause
Fault Condition: Mode*
Power limit condition (panel overload) 250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms 1000ms 1000ms
4 short blinks on all output circuits (250ms)
*Retrofit Mode will be indicated by an LED blink on the NAC1 Trouble LED only
Operating Mode Fault: Repeating LED blink pattern (non-diagnostic phase)
Power Supply Change Output Config. Mode
Set positions 9 and 10 on S1 to the correct Output circuit Trouble LEDs blink from right to left across all output circuits for 500ms.
position. Refer to “Operating Modes” on
page 26.

Retrofit Mode Indication (yellow)


Retrofit Mode will be Repeating LED blink pattern (non-diagnostic phase and diagnostic phase)
indicated by an LED blink on
the NAC1 Trouble LED only. Retrofit Mode pause
NAC outputs fault conditions
will still be indicated by short 250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms 1000ms 1000ms
250ms blinks (where
applicable).

32 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


Notes

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 33


Section 5: Trouble Supervision
The FACP will detect HPF-PS power supply faults. Any of the following conditions will cause the trouble contact to open, provided the
FACP Notification Appliance Circuit is not in alarm.
5.1 Trouble Supervision Using Input Circuits
The FACP (Fire Alarm Control Panel) supervises the connection between itself and the HPF-PS via the control panel’s NAC End-of-Line
Resistor (ELR). To supervise the HPF-PS, an ELR must be installed across terminals 1 & 4 (A+ & A-) of Command Inputs #1 and #2 (and
#3 for the 10 amp models). A field wiring fault on the NAC output of the HPF-PS will trigger a disconnection of the ELR at the related
Command Input, causing a general NAC trouble at the FACP provided the FACP’s NAC is not in alarm. All inputs in an alarm state will
close their EOL relays to allow the daisy-chaining of input signals (both in Default Mode or Retrofit Mode). Refer to Section 3.2, “Output
Circuit Control DIP Switch Settings”, on page 27 for input/output configuration assignment. The following are exceptions.
1. Resettable Aux Power, Non-Resettable Aux Power, and Door Holder Aux Power outputs will trigger the General Trouble relay only
during an output trouble regardless of the output to input relationship (i.e. mapping) when the Power supply is configured in the Default
Mode. When configured in Retrofit Mode, they will be reported by either the Input#1 or Input#2 (if Input #1 is in Sync Configuration)
EOL relay, and in addition by the General Trouble relay Refer to 5.2, "General Trouble Relay" below.
2. Faults are only reported by Command Input #1 when Selective Silence Output Configuration is controlled by Command Input #1 and
#2.
3. Faults are only reported by the trigger input when Command Input #1 is configured for Sync Configuration operation controlled by a
sync and trigger input.
If the HPF-PS is in alarm, only a power-limiting condition on the NAC will be detected as a trouble.
If other trouble monitoring is required when the power supply is in alarm, the Trouble Relay at TB1 and AC Trouble at TB2 can be used for
this purpose.
The following table summarizes the trouble supervision using the input end-of-line relays in both Default Mode and Retrofit Mode.
Note that when the power supply is configured for Retrofit Mode, the FACP should be monitoring either Input #1/Input #2 end-of-line relay
or the General trouble relay, not both.

Panel Status Default Mode Retrofit Mode


Input #x end-of- • Any new open, short, ZNAC faults, or If Input #1 is configured as Normal (S1 DIP switch 3 =ON):
line relays in existing power-limiting conditions of • Any new open, short, ZNAC faults, or existing power-limiting conditions of Slave or
standby Slave or Master (non-selective silence) Master (non-selective silence) NAC outputs are reported at the Input #1 EOL relay
NAC outputs are reported at the mapped (for any outputs mapped to either Input #1, Input #2, Input #3, or mapped to ALL
command input EOL relay (or Input #1 in inputs)
case of outputs mapped to ALL inputs). • Any new open, short, ZNAC faults, or existing power-limiting conditions of Master
• If Input #1 is configured as a sync input, selective silence NAC outputs are reported at the Input #1 EOL relay.
outputs can be mapped only to trigger • Any new or existing fault conditions of resettable aux power, non-resettable aux
Inputs #2 or Input #3 or either. If there is power, or door holder outputs are reported at the Input #1 EOL relay.
a trouble on any output circuits, the Input • Any new or existing battery, charger, panel overload, or AC fuse trouble conditions
#1 EOL relay is unaffected. Any new are reported at the Input #1 EOL relay.
open, short, ZNAC faults, or existing If S1 Global DIP switch 8 = OFF
power-limiting conditions of Slave or • Any new or existing AC trouble or ground fault trouble are reported at Input #1 EOL
Master (non-selective silence) NAC Relay (with 0 or 2h AC trouble delay depending on S1 Global DIP switch 7
outputs are, however, reported at Configuration).
respective mapped Command Input #2 If S1 Global DIP switch 8=ON
or Input #3 EOL Relay or at Command • Any new or existing ground fault trouble will be reported at Input #1 EOL Relay.
Input #2 if outputs are mapped to either. If Input #1 is configured as Sync (S1 DIP switch 3 =OFF):
• Any new open, short, ZNAC faults, or • Any new open, short, ZNAC faults, or existing power-limiting conditions of Slave or
existing power-limiting conditions of Master (non-selective silence) NAC outputs are reported at the Input #2 EOL relay
Master selective silence NAC outputs (for any outputs mapped to either Input #2, Input #3, or mapped to ALL inputs).
are reported at the Input #1 EOL relay. • Any new or existing fault conditions of resettable aux power, non-resettable aux
power, or door holder outputs are reported at the Input #2 EOL relay.
• Any new or existing battery, charger, panel overload, or AC fuse trouble conditions
are reported at the Input #2 EOL relay.
If S1 Global DIP switch 8 = OFF
• Any new or existing AC trouble or ground fault trouble are reported at Input #2 EOL
Relay (with 0 or 2h AC trouble delay depending on S1 Global DIP switch 7
Configuration)
If S1 Global DIP switch 8=ON
• Any new or existing ground fault troubles will be reported at Input #2 EOL Relay.
Input #x end-of- • All inputs in alarm state will close their • All inputs in alarm state will close their EOL relays to allow the daisy-chaining of
line relays in EOL relays to allow the daisy-chaining of input signals
alarm input signals.

Table 5.1 Operating Mode Behavior for Trouble Supervision Using Input Circuits

34 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


General Trouble Relay Trouble Supervision

5.2 General Trouble Relay


The HPF-PS power supply has a fail-safe Form-C trouble relay located at TB1. The contacts can be monitored by an FACP input circuit or
an addressable monitor module as illustrated in Figure 5.1. Note that any faults reported by Command Inputs are not repeated by the trouble
relay in Default Mode, offering limited trouble reporting. For Retrofit Mode trouble reporting, refer to Table 5.1 above and Table 5.2 below.
When the power supply is configured for Retrofit Mode, the FACP should be monitoring either Input #1/Input #2 end-of-line relay or the
General Trouble Relay, but not both.
Trouble conditions that will cause the normally energized trouble relay to change states regardless of whether the panel is in alarm or standby:
• A battery fail condition at the power supply
• A battery charger fail on the power supply
• A ground fault condition on the power supply (in Retrofit Mode if S1 Global DIP switch 8 = OFF)
• An AC fail condition (only in Retrofit Mode, if S1 Global DIP switch 8 = OFF)
• A field wiring fault on the HPF-PS outputs configured as resettable aux power, non-resettable aux power, or door holder aux power
• A total panel overload fault
• A blown AC fuse
• A field wiring fault on the NAC output configured as Slave, Master, or Master Selective Silence Outputs (only in Retrofit Mode)
The following table summarizes the trouble supervision using the General trouble relay in both Default Mode and Retrofit Mode.
Note that when the power supply is configured in Retrofit Mode, the FACP should be monitoring either Input #1/Input #2 end-of-line relay
or the Internal trouble relay, but not both.

Panel Status Default Mode Retrofit Mode


General Trouble • Any new or existing battery, charger, panel • Any new or existing battery, charger, panel overload, or AC fuse trouble conditions
relay in Standby overload, AC fuse, or ground trouble are reported.
and Alarm conditions are reported. • Any new or existing fault conditions of resettable aux power, non-resettable aux
• Any new or existing fault conditions of power, or door holder outputs are reported.
resettable aux power, non-resettable aux • Any new open, short, ZNAC faults, or power-limiting conditions of Slave or Master
power, or door holder outputs are reported. (non-selective silence) NAC outputs which are mapped to command Input 1, Input
2, Input 3, or mapped to ALL inputs are reported.
• Any new open, short, ZNAC faults, or existing power-limiting conditions of Master
selective silence NAC outputs are reported.
If S1 Global DIP switch 8= OFF
• Any new or existing AC trouble or ground fault trouble are reported (with 0 or 2h
AC trouble delay depending on S1 Global DIP switch 7 Configuration).
If S1 Global DIP switch 8=ON
• Any new or existing ground fault trouble will be reported.
Table 5.2 Operating Mode Behavior for the General Trouble Relay
If trouble monitoring is required when the power supply is in alarm, the General Trouble Relay at TB1 can be used for this purpose. Refer to
Figure 5.1 below.

NOTE: The individual NAC Trouble LED will indicate which NAC circuit is in trouble.

Monitor Module ELR

NO
T11
T10 T1
NC T9 T2
T8 T3
T7
T7 T4
TB1
TB2

T6 T5
TB4
T6
NO NC C NO NC C
AC Trouble
Trouble Trouble Relay Monitor Module*

*If the SLC device does not


HPF-PS match the one in this figure, refer
to the SLC manual wiring con-
version charts for legacy and SLC
newer versions of the modules.

Figure 5.1 Monitoring the Trouble Relay

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 35


Trouble Supervision AC Trouble Relay

5.3 AC Trouble Relay


The HPF-PS power supply has a fail-safe Form-C trouble relay located at TB2. The contacts can be monitored by an FACP input circuit or
an addressable monitor module similar to the drawing illustrated in Figure 5.1. The AC Trouble Relay responds to an AC fail condition on
the HPF-PS immediately, or after a programmed delay time, depending on the setting of S1 switches 7 and 8.
The reporting of AC loss to a central station is usually delayed in order to prevent multiple transmissions of AC loss and restoral, allowing
AC power to stabilize. When a host FACP is programmed to delay AC loss reporting, the HPF-PS must be configured to delay the reporting
of AC fail. This is accomplished by setting S1 positions 7 and 8. Refer to the DIP switch setting chart in Table 3.5 on page 26. This will pre-
vent AC loss from being reported as a trouble condition for 30, 12, 2, or 0 hours. (Only the 2 and 0 hours options are available in Retrofit
Mode.) Note that only no delay and the 2 hour delay are acceptable per UL 864 and UL 2572.
Note that when the power supply is configured for Retrofit Mode, the S1 Global DIP switch 8 setting will determine how an AC power loss
trouble condition is reported
• If S1 Global DIP switch 8 = OFF, an AC power loss trouble condition is reported by either Input #1 or Input #2 EOL relay and by the
General Trouble relay.
• If S1 Global DIP switch 8 = ON, an AC power loss trouble condition is reported by the AC trouble relay only.
The following table summarizes the trouble supervision using the AC trouble relay in both Default Mode and Retrofit Mode.

Panel Status Default Mode Retrofit Mode


AC Trouble relay • Any new or existing AC trouble conditions are reported (with 0, • IF S1 Global DIP switch 8 = ON, any new or existing AC
in Standby and 2, 12, or 30 hour delay depending on S1 Global DIP switch 7 trouble conditions are reported (with 0 or 2 hour delay
Alarm and 8 configuration). depending on S1 Global DIP switch 7 configuration.)

36 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


Notes

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 37


Section 6: Power Supply Requirements
6.1 Overview
This section contains instructions and tables for calculating power supply currents in alarm and standby conditions. This is a four-step pro-
cess, consisting of the following:
1. Calculating the total amount of AC branch circuit current required to operate the system
2. Calculating the power supply load current for secondary non-fire and fire alarm conditions
3. Calculating the size of batteries required to support the system if an AC power loss occurs
4. Selecting the proper batteries for your system

6.2 Calculating the AC Branch Circuit


The power supply requires connection to a separate, dedicated AC branch circuit, which must be labeled FIRE ALARM. This branch cir-
cuit must connect to the line side of the main power feed of the protected premises. No other non-fire alarm equipment may be powered from
the fire alarm branch circuit. The branch circuit wire must run continuously, without any disconnect devices, from the power source to the
power supply. Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Codes as well as local codes.
Use a minimum of 14 AWG (2.00 mm2) wire with 600 volt insulation for this branch circuit.
Use Table 6.1 to determine the total amount of current, in AC amperes, that must be supplied to the system.

Number of Current Draw Total Current


Device Type
Devices (AC amps) per Device
HPF-PS6(B) 5.0
or or
HPF-PS10(B) 6.2
or 1 x or =
HPF-PS6E 2.7
or or
HPF-PS10E 3.5
[ ] [ ] x [ ] =
[ ] [ ] x [ ] =
Sum Column for AC Branch Current Required =
Table 6.1 120/240 VAC Branch Circuit Requirements

6.3 Calculating the System Current Draw


6.3.1 Overview
The power supply must be able to power all internal and external devices continuously during a fire alarm condition. The secondary power
source (batteries) must be able to power the system during a primary power loss.To calculate the non-fire alarm load on the power supply
when secondary power is applied, use Calculation Column 1 in Table 6.3 on page 39. The power supply must support a larger load current
during a fire alarm condition. To calculate the fire alarm load on the power supply as secondary power, use Calculation Column 2 in
Table 6.3 on page 39.
When calculating current draw and the battery size, note the following:
• Primary refers to the main power source for the power supply.
• Secondary refers to the power supply’s backup batteries.
• All currents are given in amperes (A). Table 6.2 shows how to convert milliamperes and microamperes to full amperes.

To convert... Multiply Example


Milliamperes (mA) to amperes (A) mA x 0.001 3 mA x 0.001 = 0.003 A
Microamperes (μA) to amperes (A) μA x 0.000001 300 μA x 0.000001 = 0.0003 A
Table 6.2 Converting to Full Amperes

38 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


Selecting and Locating Batteries Power Supply Requirements

6.3.2 How to Calculate System Current Draw


Use Table 6.3 to calculate current draws as follows and refer to the battery calculation tool on the ESD website.
1. Enter the quantity of devices in both columns.
2. Enter the current draw where required. Refer to the HPP Device Compatibility Document for compatible devices and their current
draws.
3. Calculate the current draws for each in both columns.
4. Sum the total current for each column.
Following are the types of current that can be entered into Table 6.3.
 Calculation Column 1 - The secondary supply current load that the power supply must support during a non-fire alarm condition,
with DC power applied
 Calculation Column 2 - The secondary supply current load the power supply must support during a fire alarm condition, with DC
power applied
Table 6.3 contains two columns for calculating current draws. For each column, calculate the current and enter the total (in amperes) in the
bottom row. When finished, use the data to select the proper size batteries in Tables 6.4 and 6.5.

Calculation Column 1 Calculation Column 2


Secondary, Non-Fire Alarm Current Secondary, Fire Alarm Current
Device Type (amps) (amps)
Qty X (current draw) = Total Qty X (current draw) = Total
Main Circuit Board - HPF-PS6 with all outputs 2k EOL 1 X [0.154] = 1 X [0.192] =
Main Circuit Board - HPF-PS6 with 4.7k EOL 1 X [0.139] = 1 X [0.157] =
Main Circuit Board - HPF-PS6 with 27k EOL 1 X [0.124] = 1 X [0.137] =
Main Circuit Board - HPF-PS6 with all Outputs Aux Power Class 1 X [0.132] = 1 X [0.132] =
B
Main Circuit Board - HPF-PS6 with ZNAC-PS Class A option card 1 X [0.142] = 1 X [0.142] =
with all outputs Aux Power
Main Circuit Board - HPF-PS10 with all outputs 2k EOL 1 X [0.178] = 1 X [0.232] =
Main Circuit Board - HPF-PS10 with 4.7k EOL 1 X [0.156] = 1 X [0.185] =
Main Circuit Board - HPF-PS10 with 27k EOL 1 X [0.135] = 1 X [0.154] =
Main Circuit Board - HPF-PS10 with all Outputs Aux Power Class 1 X [0.149] = 1 X [0.149] =
B
Main Circuit Board - HPF-PS10 with ZNAC-PS Class A option 1 X [0.160] = 1 X [0.160] =
card with all outputs Aux Power
NAC/Output #1 [ ] X[ ]= [ ] X[ ]=
NAC/Output #2 [ ] X[ ]= [ ] X[ ]=
NAC/Output #3 [ ] X[ ]= [ ] X[ ]=
NAC/Output #4 [ ] X[ ]= [ ] X[ ]=
NAC/Output #5 [ ] X[ ]= [ ] X[ ]=
NAC/Output #6 [ ] X[ ]= [ ] X[ ]=
NAC/Output #7 [ ] X[ ]= [ ] X[ ]=
EOLR-1 Power Supervision Relay [ ] X [0.020] = [ ] X [0.020] =
Sum each column for totals Secondary Non-Alarm = Secondary Alarm =

Table 6.3 System Current Draw Calculations

6.4 Selecting and Locating Batteries


Select batteries that meet or exceed the total ampere hours determined in Tables 6.4 and 6.5. The power supply can charge batteries from 7
AH to 33 AH range. The power supply cabinet is capable of housing industry standard 7 AH or 18 AH batteries. Other ampere batteries (e.g.
12AH, 26AH, 33AH) will not fit physically inside the HPF-PS cabinet and require a separate battery box.

6.4.1 NFPA Battery Requirements


NFPA 72 Local and Proprietary Fire Alarm Systems require 24 hours of standby power followed by 5 minutes in alarm for normal operations
or 15 minutes for mass notification systems.

NOTE: When using carbon monoxide detection, the system must be monitored by a Supervising Station meeting the Standard for the
Installation of Carbon Monoxide (CO) Detection and Warning Equipment, NFPA 720.

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 39


Power Supply Requirements Selecting and Locating Batteries

6.4.2 Maximum Battery Standby Load


Tables 6.4 and 6.5 show the standby load calculations for the power supply based on 24 hours of standby. The standby load calculations in
the Table 6.3 must be less than the number shown in Tables 6.4 and 6.5 for the selected battery size, standby hour and alarm time. The num-
bers below have a built in 20% derating factor for the battery ampere capacity.

Alarm Time (min)


Battery
Capacity
(AH) 5 10 15 20 30

7 0.212 A 0.190 A 0.169 A 0.147 A N/A


12 0.379 A 0.357 A 0.336 A 0.314 A 0.271 A
18 0.579 A 0.557 A 0.536 A 0.514 A 0.471 A
33 1.079 A 1.057 A 1.036 A 1.014 A 0.971 A
75 2.479 A 2.457 A 2.436 A 2.414 A 2.371 A
120 3.000 A 3.000 A 3.000 A 3.000 A 3.000 A

Table 6.4 Maximum Battery Standby Loads for 24 Hour Standby on the HPF-PS6

Alarm Time (min)


Battery
Capacity
(AH) 5 10 15 20 30

7 0.198 A 0.162 A N/A N/A N/A


12 0.364 A 0.329 A 0.293 A 0.258 A 0.187 A
18 0.564 A 0.529 A 0.493 A 0.458 A 0.387 A
33 1.064 A 1.029 A 0.993 A 0.958 A 0.887 A
75 2.464 A 2.429 A 2.393 A 2.358 A 2.287 A
120 3.000 A 3.000 A 3.000 A 3.000 A 3.000 A

Table 6.5 Maximum Battery Standby Loads for 24 Hour Standby on the HPF-PS10

40 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


Section 7: Testing and Maintenance
7.1 Periodic Testing and Service
Periodic testing and servicing of equipment is essential to ensure proper and reliable operation. Test and service the power supply according
to the schedules and procedures outlined in the following documents:
• NFPA Standard 72’s section on Inspection, Testing and Maintenance

7.2 Battery Checks and Maintenance


Maintenance-free sealed lead-acid batteries used in the system do not require the addition of water or electrolyte. These batteries are charged
and maintained in a fully charged state by the main power supply’s charger during normal system operation. A discharged battery typically
reaches the voltage of 27.6 VDC within 48 hours;. Sealed lead-acid batteries must be replaced within at most 5 years from their date of man-
ufacture. Minimal replacement battery capacity appears on the control panel marking label. Immediately replace a leaking or damaged bat-
tery. Replacement batteries are available from the manufacturer.

WARNING: SULFURIC ACID


! BATTERIES CONTAIN SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN AND EYES AND DAMAGE TO
FABRICS.

F1 Fuse Replacement Not Allowed


Rechargeable Battery Replacement Recommended Part Numbers:
• BAT-1270 (12V,7AH)
• BAT-12120 (12V, 12AH)
• BAT-12180 (12V 18AH)
• BAT-12260 (12V, 26AH)
• BAT-12330 (12V, 33AH)

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 41


Appendix A: Wire Requirements
Connecting external system accessories to the main circuits must be carefully considered to ensure proper operation. It is important to use
the correct type of wire, gauge and run length for each circuit. The following table lists NAC wiring requirements for the HPF-PS6 and HPF-
PS10 Power Supply.
The numbers documented in this chart are worst case numbers, based on the conditions listed below. The maximum voltage drop, maximum
loop resistance, and wire length ratings can be increased with lower system current loading.
1. The HPF-PS6/10 is full capacity loaded at 6A/10A.
2. The HPF-PS6/10 is running at the Low Battery voltage of 20.4VDC (at Battery Connector TB15).
Wire lengths apply to Class B wiring, and to Class A wiring returned to the ZNAC-PS card.

Max Load Max Loop Resistance


AWG 12 (Solid) AWG 14 (Solid) AWG 16 (Solid) AWG 18 (Solid)
(Amps) (Ohms)
0.25 12.804 3320 2087 1310 823
0.50 6.402 1660 1044 655 412
0.75 4.268 1107 696 437 274
1.00 3.201 830 522 327 206
1.25 2.561 664 417 262 165
1.50 2.134 553 348 218 137
1.75 1.829 474 298 187 118
2.00 1.601 415 261 164 103
2.25 1.423 369 232 146 91
2.50 1.280 332 209 131 82
2.75 1.164 302 190 119 75
3.00 1.067 277 174 109 69

Table A.1 Wiring Requirements for Power Supply

NOTE: Calculations are based on Direct-Current Resistance data for uncoated copper wire, per National Electrical Code (2005 Edition) Table
8, Conductor Properties.

NOTE: These distances reflect the worst case scenario and are based on the correct draw of the highest candela strobes at the low end of the
supported NAC voltage with the entire load at the end of the circuit. Further distances can be achieved by performing a point to point voltage
calculation that more accurately reflects the specific devices used and how they are dispersed on the circuit.

42 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


Appendix B: Application Examples
B.1 Controlling NACs For Selective Silence Operation Using a Control Module
In this application, the power supply has been set as a master with synchronized outputs and selective silence (see DIP switch settings and
Selective Silence Operation information in Section 3). This application requires Input #1 to be controlled by the FACP. Input #2 is required
for controlling selective silence via a control/relay module, programmed as an alarm output and a silenceable point. Only Mass Notification,
Fire, or combo Mass Notification/Fire NACs are allowed in this configuration. The control module can be powered by one of the HPF-PS
output circuits, configured as aux power (24VDC).

NAC Output Circuits

24VDC power output

TB11
TB1
TB2

TB13

TB10
TB12

TB9

TB8
TB4

NO NC C NO NC C

FACP

A+
B-
NAC
T11
T6
T7
T8
T9
T10

B+
A-
Control Module*
*If the SLC device does not match
A+

SLC
B-

the one in this figure, refer to the


B+

SLC manual wiring conversion


A-

charts for legacy and newer ver-


sions of the modules.
A+
B-
T5
T4
T3
T2
T1

B+
A-

TB15

Figure B.1 Controlling Multiple Outputs with One Input

The following notes apply to Figure B.1.


When the HPF-PS power supply is in an inactive state (FACP NAC not active), a trouble on the NAC circuit will result in an open circuit
condition on the FACP (monitored by End-of-Line Resistor across TB5, Terminals 1 and 4). As an alternative, the trouble contacts at TB1 of
the power supply can also be used for limited trouble monitoring excluding Selective Silence output faults. Refer to Section 5 for more infor-
mation.
• Refer to Section 3 for instructions on setting the DIP switches.
• Selective Silence output faults are only reported via Command Input #1 (not Command Input #2).
• Wire NACs as shown on page 14.
• Do not loop wires under screw terminals. Break wires to maintain proper supervision.
• An End-of-Line Resistor must be installed across all input circuits, Terminals 1 and 4, for control module wiring supervision (the ELR
value is dependent on the module/FACP employed).
• For a list of compatible devices, refer to the HPP Device Compatibility Document #54399.
• Refer to the SLC Wiring Manual for more information.

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 43


Application Examples Controlling NACs For Sync Follower Operation Using a Control Module (Default Mode Configuration Only)

B.2 Controlling NACs For Sync Follower Operation Using a Control Module (Default
Mode Configuration Only)
In this application, the power supply has been set to operate in Slave Configuration and will follow the sync signal from the FACP. This
application requires Input #1 to be controlled by the FACP sync output. Input #1 may be wired to the next HPF-PS or terminate in and ELR.
Input #2 (or Input #3, if available) will act as the trigger signal for the output circuits. The control module can be powered by one of the HPF-
PS output circuits, configured as aux power (24VDC). See Table 3.14 on page 29 for DIP switch settings.

NAC Output Circuits

24VDC power output

TB11
TB1
TB2

TB13

TB10
TB12

TB9

TB8
TB4

NO NC C NO NC C

to next PS Series
Power Supply or ELR

FACP

A+
B-
NAC Sync
T11
T6
T7
T8
T9
T10

B+
A-
Control Module*
*If the SLC device does not match A+
B-
SLC
the one in this figure, refer to the
B+
A-

SLC manual wiring conversion


charts for legacy and newer ver-
A+

sions of the modules.


B-
T5
T4
T3
T2
T1

B+
A-

TB15

Figure B.2 Controlling Multiple Outputs with One Input as Sync Follower

The following notes apply to Figure B.2.


• When the HPF-PS power supply is in an inactive state (control module not active), a trouble on the NAC circuits mapped to TB6 will
result in an open circuit condition on the control module output circuit (monitored by End-of-Line Resistor across TB6, Terminals 1 and
4). As an alternative, the trouble contacts at TB1 of the power supply can also be used for limited trouble monitoring excluding faults
reported by Command Input #2 related to Command Input#1 configured for Sync Input Configuration. Refer to Section 5 for more
information.
• Refer to Section 3 for instructions on setting the DIP switches.
• Output faults are reported via Command Input#2 with Command Input#1 configured for Sync Input Configuration operation.
• Refer to the FACP manual for load restrictions and line length limitations when wiring multiple power supplies at the input.
• Wire NACs as shown on page 14.
• Do not loop wires under screw terminals. Break wires to maintain proper supervision.
• An End-of-Line Resistor must be installed across all input circuits, Terminals 1 and 4, for control module wiring supervision (the ELR
value is dependent on the module/FACP employed).
• For a list of compatible devices, refer to the HPP Device Compatibility Document #54399.
• Refer to the SLC Wiring Manual for more information.

44 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


Controlling NACs, Aux Power, or Door Holders Using a Control Module Application Examples

B.3 Controlling NACs, Aux Power, or Door Holders Using a Control Module
All output circuits, NACs, aux power (non-resettable power – active regardless of control module state), or door holders, can be controlled
from one input such as an addressable control module as illustrated in Figure B.3. The control module can be powered from one of the HPF-
PS output circuits, as 24 VDC power. In this example, Output #1 will be configured as 24VDC non-resettable aux power.
The control module is shown to demonstrate the use of an internally mounted device associated with an addressable fire alarm control panel.
The module could be replaced with any circuit capable of polarity reversal, such as an FACP Notification Appliance Circuit.

24VDC power output

TB11
TB1
TB2

TB13

TB10
TB12

TB9

TB8
TB4

NO NC C NO NC C

A+
B-
B+
T11
T6
T7
T8
T9
T10

A-
Control Module*

A+
*If the SLC device does not match

B-
the one in this figure, refer to the

B+
SLC manual wiring conversion

A-
charts for legacy and newer ver-
sions of the modules.

A+
B-
B+
T5
T4
T3
T2
T1

A-

TB15 SLC

Figure B.3 Controlling NACs, Aux Power, and Door Holders with One Input
The following notes apply to Figure B.3.
• Any output circuit can be configured as NAC, door holder, or 24VDC power.
• Wire NACs as shown on page 14.
• Refer to Section 3 for instructions on setting the DIP switches.
• When the HPF-PS power supply is in an inactive state (control module not active), a trouble on the NAC circuits mapped to TB5 will
result in an open circuit condition on the control module output circuit (monitored by an End-of-Line Resistor across Terminals 1 and
4). Additionally, the trouble contacts at TB1 of the power supply can also be used for limited trouble monitoring excluding output faults
reporting to Command Input #1. Refer to Section 5 for more information.
• Do not loop wires under screw terminals. Break wires to maintain proper supervision.
• An End-of-Line Resistor must be installed between terminals 1 and 4 for control module wiring supervision (the ELR value is
dependent on the module/FACP employed).
• For a list of compatible devices, refer to the HPP Device Compatibility Document #54399.
• Refer to the SLC Wiring Manual for more information.

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 45


Application Examples Controlling NACs, Aux Power, and Door Holders with NAC Sync

B.4 Controlling NACs, Aux Power, and Door Holders with NAC Sync
In this application, use of a single TC822A1010 mounted inside the cabinet can monitor the two power supply trouble relays and trigger two
independent inputs via relay circuits. HPF-PS outputs #1 and #2 are being used for 24 VDC aux power triggered by the module’s relay cir-
cuits. Any HPF-PS output circuit can be configured to follow any input circuit.

End-of-Line Resistors 24VDC Aux Power


supplied with Module

TB11
TB1
TB2

TB13

TB10
TB12

TB9

TB8
TB4

NO NC C NO NC C
AC Trouble
Trouble

FACP

NAC or Remote
Sync Output

A+
B-
T7 NO

T8 C

T9 NC

T10 NO

T11 C

T12 NC

B+
A-
SLC

A+
B-
B+
A-
TC822A101
A+
B-
B+
T6

T5

T4

T3

T2

T1

A-

TB15

Figure B.4 Controlling NACs, Aux Power, and Door Holders with One Input and NAC Sync

The following notes apply to Figure B.4.


• Any output circuit can be configured as NAC, door holder, or 24VDC power.
• Refer to Section 3 for instructions on setting the DIP switches.
• Do not loop wires under screw terminals. Break wires to maintain proper supervision.
• An End-of-Line Resistor must be installed between terminals 1 and 4 for module wiring supervision (the ELR value is dependent on the
module/FACP employed).
• An End-of-line Resistor on input circuits#1-2 (TB5-6) are optional for this particular application.
• Ensure that the TC822A1010 is programmed appropriately at the FACP where the inputs are not mapped to the same zone as its
outputs.
• For a list of compatible devices, refer to the HPP Device Compatibility Document #54399.
• Refer to the SLC Wiring Manual for more information.

46 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


Controlling all Three Inputs with One Control Module Application Examples

B.5 Controlling all Three Inputs with One Control Module


In this application, all three command inputs are being controlled by one multi-module, the XP6-C mounted inside the cabinet. Output #1 is
being used for 24 VDC aux power. Any output circuit may be configured to any input.

24V Aux
Power

TB11 OUT4
TB13 OUT6

TB10 OUT3
TB12 OUT5

TB9 OUT2

TB8 OUT1
TB2

TB1
TB4

NO NC C NO NC C

NAC1

AUX1
NAC2

ZNAC-PS BASE ADDRESS +5 BASE ADDRESS +4 BASE ADDRESS +3 BASE ADDRESS +2 BASE ADDRESS +1 BASE ADDRESS +0
AUX2

Class A Converter
Option Module

6 7 8 9

0
1
5

2
3
4
SW1

12
11
10

13
J1

15 14
6 7 8 9

10
5

2
3
4

XP6-C

T16 T11 T10


T15 T14 T13 T12
+5 +4 +3 +2 +1

– + – +
T5 T4 T3 T2 T1
– +
– + – +
– + – +
– + – + – + – +
– + +0
SLC
T0

TB15

Figure B.5 Controlling Three Inputs with One Module


The following notes apply to Figure B.5.
• An End-of-Line Resistor must be installed between terminals 1 and 4 for control module wiring supervision (the ELR value is
dependent on the module/FACP employed).
• Either disable the unused addresses or install ELRs across unused outputs on the XP6-C.
• Refer to Section 3 for instructions on setting the DIP switches.
• Do not loop wires under screw terminals. Break wires to maintain proper supervision.
• For a list of compatible devices, refer to the HPP Device Compatibility Document #54399.
• Refer to the SLC Wiring Manual for more information.

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 47


Application Examples AC Trouble Reporting with a Conventional FACP

B.6 AC Trouble Reporting with a Conventional FACP


In this application, the HPF-PS is being used with a conventional FACP that does not have a type-coded input zone for AC Power loss with
a delay. AC Trouble Delay on the HPF-PS must be set to none (S1-7 ON, 8 ON). AC Fail delay timers must be set on the DACT. The DACT
must be installed in close proximity to the conventional FACP so the audible and visual signaling can be given locally at the FACP as
required by UL 864.

ELR

TB11 OUT4
TB13 OUT6

TB10 OUT3
TB12 OUT5

TB9 OUT2

TB8 OUT1
AC1 AC2
UL 864
TB1
TB2

TB4

NO NC C NO NC C 10th Edition
Listed DACT

HPF-PS Channel 1
Channel 2
Channel 3
ELR Channel 4

NAC

A+
B-
B+
A-
24VDC non-resettable power

A+
B-
B+
A-
A+
B-
B+
A-

+ - + - ELRs
TB15
TB1

TB2
+ - + - B+ B- B+ B- B+ B- B+ B- B+ B- B+ B- C NO NC C NC NO C NC NO
Nonreset Reset NAC 1 NAC 2 ZONE 1 ZONE 2 ZONE 3 ZONE 4 TROUBLE ALARM SUPV

UL 864 Listed Regulated 24 VDC


Conventional FACP

Figure B.6 AC Trouble Reporting with a Conventional FACP

The following notes apply to Figure B.6.


• Wiring from the power supply to the DACT must be in metal conduit within 20 feet of the FACP.
• Refer to Section 3 for instructions on setting the DIP switches.
• Do not loop wires under screw terminals. Break wires to maintain proper supervision.
• An End-of-Line Resistor must be installed between terminals 1 and 4 on the input circuits that require wiring supervision. (The ELR
value is dependent on the FACP employed).
• Refer to panel/DACT documentation for programming information.

48 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


Index
A maximum short term 8 N
AC power 9 standby 9 NAC
calculations 38 total continuous 9 activation 8
current 9 total short term 9 circuit wiring 14
fail 26 Class
fail delay 26 D see also NFPA Class 8
loss 8 daisy-chain 20 coding 8
loss relay 9 debounce/dejitter 24 output
loss reporting delay 8, 36 default mode 8, 24, 26 see also output circuit 9
loss timer 24 dimensions see also Notification Appliance Circuit 8
voltage 9 backbox 13 NEC power-limited wiring requirements 16
activation DIP switch non-alarm state 8
reverse polarity 8 settings 24, 27 non-resettable power 27, 28
alarm condition 8 disable outputs 28 notification appliance circuit
applications 8 door holder 29 see also NAC 8
aux power 27 dropout delay 24
aux power control O
see also resettable or non-resettable power E operating mode 24, 26
28
ELR 9, 14, 34, 43, 44, 45, 46, 47, 48 output
disable 28
B F unused 28
backbox dimensions 13 output circuit 9
factory default 28
battery 20 Class 9
faults 34
capacity 9 current 9
features 8
charge current 9 maximum current 8, 9
filtered power 8
charger capacity 8 see also NAC output 9
float charge voltage 9
float charge voltage 9 types 9
form-C
lead acid 8, 9 voltage rating 9
see also relay 8
maximum capacity 8 output power 8
see also secondary power 9
trouble 8 G P
ground fault 8, 19, 21
power
ground fault detection 8, 10
C non-resettable 8
switch SW1 10
cabinet resettable 8
see also backbox 13 power supply 38
capacity H board layout drawing 11
battery 9 HPF-PS10 8 connectors and switches 11
cascading 19, 20 HPF-PS6 8 power-limited outputs 8
charge current power-limited wiring 16
maximum 9 I
nominal 9 input 25 R
charger current 9 relay
enable/disable 25 settings 27, 28 general trouble 35
charger trouble 8 voltage 9 trouble 8, 9
circuit board input #1 sync configuration 25 reporting delay
layout 11 input circuit 8 AC loss 36
Class A Converter Module 14 activation 8 requirements 38
see also ZNAC-PS 8 compatibility 8 resettable power 27, 28
Class B 8 see also control 9 retrofit mode 8, 24, 26, 31, 32
coding installation 13
NAC 8
command circuit 8 S
M secondary power
current 9
master configuration 29 see also battery 9
see also input circuit 9
module selective silence 29
voltage 9
mounting 15 slave configuration 27, 29
command input 25
mounting special operating mode 26
compatibility
see also installation 13 specifications 8
input circuit 8
multi-module startup procedure 10
current
mounting 15 strobe synchronization 8
maximum continuous 8

HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 49


Index

supervision 8
trouble 34
SW1
ground fault detection 10
switch
SW1 ground fault detection 8, 10
sync 29
sync configuration 25
sync type 17, 29
synchronization
ADA compatible 8
selectable 8

T
trouble 35
power supply 8
supervision 34
trouble relay 8, 9, 35
contact rating 9
trouble supervision 8

W
wiring 8
AC power 9
power-limited 16

Z
ZNAC-PS 14, 15
see also Class A Converter Module 8

50 HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022


HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022 51
Honeywell Power Products
12 Clintonville Road
Northford, CT 06472-1610
877.HPP.POWR
LS10227-003HP-E | C | 02-22
www.honeywellpower.com ©2022 Honeywell International Inc.

You might also like