Troubleshooting Wonderware Application Server Bootstrap Communications
Troubleshooting Wonderware Application Server Bootstrap Communications
Doc Id TN482
876
SUMMARY
This Tech Note outlines general troubleshooting steps to address communication issues between a remote node and an Wonderware Application Server Galaxy.
This Tech Note augments TN 461 Troubleshooting Industrial Application Server Bootstrap Communications.
SITUATION
Application Versions
Wonderware Application Server 3.5 (2012). Please check the compatability matrix at the Wonderware Tech Support site for supported operating systems.
This Tech Note uses Windows Server 2008 for the examples.
Note: If you are having trouble opening the SMC logger from a client node or the Server node, please see Tech Note 437: Unable to Open Logger Under Windows XP SP2 and Windows 2003
SP1.
Ensure that the ArchestrA Network Admin Account is the same on all machines in the Galaxy (or wish to interact with nodes in the Galaxy).
1. Launch the Change Network Account utility from Start/All Programs/Wonderware/Common/Change Network Account.
Use the OS Configuration Utility to add TCP/UDP ports and application authorization to the Windows Firewall exclusion list, in order to allow Wonderware products to operate as designed on
Windows XP SP2 , Windows 2003 SP1 or greater, Windows Vista, Windows 2008, and Windows 7.
You can also download the utility from the GCS support site.
For a list of what the utility does, please refer to the Tech Article Security Settings for Wonderware Products.
3. Reboot the machine after running the O/S Configuration Utility.
The Schneider Electric industrial software business and AVEVA have merged to trade as AVEVA Group plc, a UK listed company. The Schneider Electric and Life
Is On trademarks are owned by Schneider Electric and are being licensed to AVEVA by Schneider Electric.
Ensure that the version of Wonderware Application Server installed on the remote node is the same as the version of the Wonderware Application Server Galaxy.
1. Verify the version by going to Control Panel / Programs / Programs and Features. Verify the Wonderware Application Server 2012 version on the Galaxy Repository (GR) Node and
on the remote nodes.
Note: If the Version column is not visible, right click on a column name then click More. You can then see the Version column.
Figure 2 (above) shows Wonderware Application Server 2012 -- 3.5 Patch 01.
Port 135
Port 139
Port 445
Ports 1024 to 65535
http://support.microsoft.com/kb/832017
http://www.linklogger.com/TCP135.htm
http://www.linklogger.com/TCP139.htm
http://www.linklogger.com/TCP445.htm
This is the editor you use to make local DCOM changes to DCOM security levels on the computer.
2. Expand the branches as follows:
The Schneider Electric industrial software business and AVEVA have merged to trade as AVEVA Group plc, a UK listed company. The Schneider Electric and Life
Is On trademarks are owned by Schneider Electric and are being licensed to AVEVA by Schneider Electric.
Click the Location tab and make sure the Run application on this computer box is checked.
Note: On x64 operating systems this option may be grayed out/disabled. The workaround is to use the 32-bit version of DCOMCNFG by using the following command line:
C:\WINDOWS\SysWOW64>mmc comexp.msc /32.
Under each Security grouping, ensure that the security settings are set similar to those shown in the following graphics. These are the minimum settings needed.
The Schneider Electric industrial software business and AVEVA have merged to trade as AVEVA Group plc, a UK listed company. The Schneider Electric and Life
Is On trademarks are owned by Schneider Electric and are being licensed to AVEVA by Schneider Electric.
The Schneider Electric industrial software business and AVEVA have merged to trade as AVEVA Group plc, a UK listed company. The Schneider Electric and Life
Is On trademarks are owned by Schneider Electric and are being licensed to AVEVA by Schneider Electric.
The This user option shown below should be the ArchestrA Network Admin account defined using the Wonderware Change Network Account Utility.
The Endpoints tab panel should look similar to the following graphic (Figure 11 below).
The Schneider Electric industrial software business and AVEVA have merged to trade as AVEVA Group plc, a UK listed company. The Schneider Electric and Life
Is On trademarks are owned by Schneider Electric and are being licensed to AVEVA by Schneider Electric.
Ensure the Enable Distributed COM on this computer option is checked (Figure 13 below).
The Schneider Electric industrial software business and AVEVA have merged to trade as AVEVA Group plc, a UK listed company. The Schneider Electric and Life
Is On trademarks are owned by Schneider Electric and are being licensed to AVEVA by Schneider Electric.
4. Ensure that the selected option is Classic and not Guest only.
7. Ensure that the ArchestrA Network Admin account is listed here. In Figure 18 (below), it is wwuser.
The Schneider Electric industrial software business and AVEVA have merged to trade as AVEVA Group plc, a UK listed company. The Schneider Electric and Life
Is On trademarks are owned by Schneider Electric and are being licensed to AVEVA by Schneider Electric.
8. Similarly check if the Archestra Network Admin Account is added in the following policies:
Log on as a batch job
Deny log on locally
Deny log on through Remote Desktop Services
Act as part of the operating system. (While it is not generally required, in some specific cases adding the ArchestrA Network admin account to this policy may resolve
communication issues. Click the following link for information on Act as part of the operating system property.)
9. Double-click Deny logon as a service.
10. Ensure that the ArchestrA Network Admin account (referenced above) is not listed here (Figure 20 below).
The Schneider Electric industrial software business and AVEVA have merged to trade as AVEVA Group plc, a UK listed company. The Schneider Electric and Life
Is On trademarks are owned by Schneider Electric and are being licensed to AVEVA by Schneider Electric.
Make sure the ArchestrA Network Admin account is a member of the Administrators group on the local machine, regardless if it is a local or domain account.
Note: The user logged on to the desktop of the remote machine that is trying to launch an IDE for remote GR access must be an Administrator of the remote machine. Administrator
permissions are necessary to allow proper DCOM and similar communication.
Make sure the following folders are shared on the local machine and that the ArchestrA Network Admin account has permissions to read and write to the folders.
aaFileRepository
aaSF$
ArchestrA Galaxy Data
Wonderware$
Note: If the Tools menu is not visible, press F10 to see the menu.
The Schneider Electric industrial software business and AVEVA have merged to trade as AVEVA Group plc, a UK listed company. The Schneider Electric and Life
Is On trademarks are owned by Schneider Electric and are being licensed to AVEVA by Schneider Electric.
The Schneider Electric industrial software business and AVEVA have merged to trade as AVEVA Group plc, a UK listed company. The Schneider Electric and Life
Is On trademarks are owned by Schneider Electric and are being licensed to AVEVA by Schneider Electric.