Samalkha SLD-22.04.2023

The document provides a single line diagram of a power substation. It shows transformers stepping down voltages from a high voltage compartment to a lower voltage section. Circuit breakers, fuses, and monitoring equipment are included to protect components and monitor operations. Wiring and components are labeled according to their functions.

Uploaded by

Darshit Vyas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views1 page

Samalkha SLD-22.04.2023

The document provides a single line diagram of a power substation. It shows transformers stepping down voltages from a high voltage compartment to a lower voltage section. Circuit breakers, fuses, and monitoring equipment are included to protect components and monitor operations. Wiring and components are labeled according to their functions.

Uploaded by

Darshit Vyas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

RELAYING:

No.

3:100/50/5+5A
V MFM A

UV/OV
CORE-1
CL-0.5,10VA

PT
100VA,CL:0.5
PTR: 11kV
F11
R

MCB Q01 F10


630A
WIRE BUS WTI OTI DS
A01
HV COMPARTMENT
MFM
COMPACT
Q81
51+51N
50+50N
INCOMING
CABLE

SUBSTATION Q11
630A

A01

100/50/1+1A
5P10/2.5VA

3RX1CX95Sq.mm
XLPE AL.CABLE

50X60mm GI STRIP
OLTC RTCC AVRR
For body earthing
1600KVA
50x6mm CU STRIP
For Neutral earthing

S1
EP
T/F COMPARTMENT
CTR ------ TO WTI
S2
H
S1
CTR-2500/5A
1xCL: 1.0 TO APFCR
VA: 15 S2 MFM
S1

ELR

METER
TO LT COMPARTMENT

TIMER

CTR-2500/5A
CL-1.0,15VA MFM

MCB
6A,SP

R Y B EM.

M
H1 H2

SPD
UV/OV

CTR-2500/5A NOTE:

32
PLC
CL-5P10 46

-TECHNICAL SPECIFICATIONS FOR TRANSFORMER,HT METER,RMU,LT PANELS


Q1
SHALL BE AS PER BENGALORE ELECTRICITY (BESCOM) RULES AND
2500A,4P
50KA,M/F ACB REGULATIONS & COMPLY WITH CEA GUIDLINES,
THIS SINGLE LINE DIAGRAM MAY VARY ACCORDINGLY.
-THIS IS TENTATIVE SINGLE LINE DIAGRAM.
2500A,Aluminium Busbar

800A,TP 800A,TP 800A,TP 800A,TP 800A,TP


MCCB MCCB MCCB MCCB MCCB

H1 H2 H3 H1 H2 H3 H1 H2 H3

APFC

1.1kV x2R x 4C X 300 Sq.mm 1.1kV x2R x 4C X 300 Sq.mm 1.1kV x2R x 4C X 300 Sq.mm 1.1kV x2R x 4C X 300 Sq.mm
ALU.Armoured XLPE FRLS Cable ALU.Armoured XLPE FRLS Cable ALU.Armoured XLPE FRLS Cable ALU.Armoured XLPE FRLS Cable

CHARGER CHARGER CHARGER CHARGER


DISTRIBUTION PANEL-1 DISTRIBUTION PANEL-2 DISTRIBUTION PANEL-3 DISTRIBUTION PANEL-4
PHASE IND. PHASE IND. PHASE IND. PHASE IND.
CT CT CT CT
MFM WITH RS-485 800/5A MFM WITH RS-485 800/5A MFM WITH RS-485 800/5A MFM WITH RS-485 800/5A
ON OFF TRIP MFM ON OFF TRIP MFM ON OFF TRIP MFM ON OFF TRIP MFM
CL-0.5S,15VA CL-0.5S,15VA CL-0.5S,15VA CL-0.5S,15VA

EMERGENCY EMERGENCY EMERGENCY EMERGENCY


SWITCH SWITCH SWITCH SWITCH
4P,800A,36kA MCCB 4P,800A,36kA MCCB 4P,800A,36kA MCCB 4P,800A,36kA MCCB
WITH O/C,S/C,E/F WITH O/C,S/C,E/F WITH O/C,S/C,E/F WITH O/C,S/C,E/F
PROTECTION PROTECTION PROTECTION PROTECTION
MFM

MFM

MFM

MFM

MFM

MFM

MFM

MFM
3P, 4W, 400V, 800A 50HZ , 50KA, AL BUS BAR 3P, 4W, 400V, 800A 50HZ , 50KA, AL BUS BAR 3P, 4W, 400V, 800A 50HZ , 50KA, AL BUS BAR 3P, 4W, 400V, 800A 50HZ , 50KA, AL BUS BAR
PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION
4P,160A,25kA MCCB

4P,160A,25kA MCCB

4P,160A,25kA MCCB

4P,160A,25kA MCCB

4P,63A,25kA MCB

4P,63A,25kA MCB

4P,63A,25kA MCB

4P,63A,25kA MCB

4P,160A,25kA MCCB

4P,160A,25kA MCCB

4P,160A,25kA MCCB

4P,160A,25kA MCCB

4P,63A,25kA MCB

4P,63A,25kA MCB

4P,63A,25kA MCB

4P,63A,25kA MCB

4P,160A,25kA MCCB

4P,160A,25kA MCCB

4P,160A,25kA MCCB

4P,160A,25kA MCCB

4P,63A,25kA MCB

4P,63A,25kA MCB

4P,63A,25kA MCB

4P,63A,25kA MCB

4P,160A,25kA MCCB

4P,160A,25kA MCCB

4P,160A,25kA MCCB

4P,63A,25kA MCB

4P,63A,25kA MCB

4P,63A,25kA MCB

4P,63A,25kA MCB
WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C


4P,160A,25kA MCCB

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C

WITH O/C & S/C


PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION
WITH O/C & S/C
4P,100A,25kA MCCB

WITH O/C & S/C


4P,100A,25kA MCCB

WITH O/C & S/C


4P,100A,25kA MCCB

WITH O/C & S/C


4P,100A,25kA MCCB

WITH O/C & S/C


4P,160A,25kA MCCB

WITH O/C & S/C


4P,160A,25kA MCCB

WITH O/C & S/C


4P,160A,25kA MCCB

WITH O/C & S/C


4P,160A,25kA MCCB

WITH O/C & S/C


4P,160A,25kA MCCB

WITH O/C & S/C


4P,160A,25kA MCCB

WITH O/C & S/C


4P,160A,25kA MCCB

WITH O/C & S/C


4P,160A,25kA MCCB

WITH O/C & S/C


4P,100A,25kA MCCB

WITH O/C & S/C


4P,100A,25kA MCCB

WITH O/C & S/C


4P,100A,25kA MCCB

WITH O/C & S/C


4P,100A,25kA MCCB
PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION
WITH O/C & S/C
4P,63A,25kA MCB

WITH O/C & S/C


4P,63A,25kA MCB

WITH O/C & S/C


4P,63A,25kA MCB

WITH O/C & S/C


4P,63A,25kA MCB

WITH O/C & S/C


4P,63A,25kA MCB

WITH O/C & S/C


4P,63A,25kA MCB

WITH O/C & S/C


4P,63A,25kA MCB

WITH O/C & S/C


4P,63A,25kA MCB

WITH O/C & S/C


4P,63A,25kA MCB

WITH O/C & S/C


4P,63A,25kA MCB

WITH O/C & S/C


4P,63A,25kA MCB

WITH O/C & S/C


4P,63A,25kA MCB

WITH O/C & S/C


4P,63A,25kA MCB

WITH O/C & S/C


4P,63A,25kA MCB

WITH O/C & S/C


4P,63A,25kA MCB

WITH O/C & S/C


4P,63A,25kA MCB
FAST FAST FAST FAST SLOW SLOW SLOW SLOW FAST FAST FAST FAST SLOW SLOW SLOW SLOW FAST FAST FAST FAST SLOW SLOW SLOW SLOW FAST FAST FAST FAST SLOW SLOW SLOW SLOW
CHARGER-1 CHARGER-2 CHARGER-3 CHARGER-9 CHARGER-1 CHARGER-2 CHARGER-12 CHARGER-13 CHARGER-1 CHARGER-2 CHARGER-3 CHARGER-4 CHARGER-1 CHARGER-2 CHARGER-13 CHARGER-14 CHARGER-1 CHARGER-2 CHARGER-3 CHARGER-4 CHARGER-1 CHARGER-2 CHARGER-11 CHARGER-12 CHARGER-1 CHARGER-2 CHARGER-3 CHARGER-4 CHARGER-1 CHARGER-2 CHARGER-12 CHARGER-13
25KW 25KW 25KW 25KW KANDI KANDI KANDI KANDI 60KW 60KW 60KW 60KW KANDI KANDI KANDI KANDI 60KW 60KW 60KW 60KW KANDI KANDI KANDI KANDI GBT-30KW GBT-30KW GBT-30KW GBT-30KW KANDI KANDI KANDI KANDI
DELTA DELTA DELTA DELTA EXICOM EXICOM EXICOM EXICOM EXICOM EXICOM EXICOM EXICOM MINDRA MINDRA MINDRA MINDRA

PROJECT :- SAMALKA

CLIENT: - BLU SMART MOBILITY PVT. LTD. GURGAON


NAME SIGN. DATE

BLU SMART CHARGE


DRN. PUNEET 22.04.23
C:\Users\harshilthakor\Desktop\Blusmart_Logo 2.png

PVT LTD. DGN. ANIL 22.04.23 SCALE


CKD. HT 22.04.23 N.T.S

APPD. GJ 22.04.23
TITLE:
DWG. NO: REV.
TENTATIVE SINGLE LINE DIAGRAM
SHT. No. 01 No. OF SHT. 01