I2Z
I2Z
If rated burden be PVA at rated secondary current IS amperes, the ohmic impedance of the burden
Zb can be calculated as follows:
P VA
Z b= 2
ohms
Is
If burden power factor is cos ϕ, the values of resistance and reactance of the burden can be
calculated as follows:
Rb =Z b cos ∅
X b=√ Z b2−R b2
The impedance of the relay coil changes with current setting. The values of power consumption
of relays, trip coil etc. are given by their manufacturers. The CT of suitable burden can be
selected after calculating the total burden on the CT.
When the relay is set to operate at current different from the rated secondary current of the CT,
the effective burden of the relay can be calculated as follows:
()
2
Is
Pe =Pr
Ir
Continuity Test
This is a quick audible alarm test using a digital multimeter to determine whether an electrical
circuit or wire is complete or broken.
Follow these steps to complete the continuity test procedure with an autorange digital meter:
1. Make sure all power is off in the circuit you are testing.
2. Set the selector dial to Ω (audible alarm symbol).
3. Connect the test lead and probes on the load terminals as shown (Figure 5). The
audible alarm will indicate continuity without a need for taking your eyes off the work.
4. Touch the probes together to check the leads, connections, and battery life. The audible
alarm should sound. With the leads apart the meter should display OL or I, depending
on the manufacturer.
5. If this is the last test you are doing, turn the meter to “off” and store it in a safe place.
Figure 5: Wiring for a Continuity Test
Previous/next navigation
Previous: Testing Resistance (Ohms) with a Digital Multimeter
Next: Polarity in a Parallel Circuit
BACK TO TOP
LICENSE
Multimeters 101: Basic Operation, Care and Maintenance and Advanced Troubleshooting for the
Skilled Trades by B. Phifer is licensed under a Creative Commons Attribution 4.0 International
License, except where otherwise noted.
SHARE THIS BOOK
1. Temporarily link the line conductor to the CPC in the Consumer Unit.
2. Test between the line and the CPC at each accessory point e.g. a ceiling rose, switch or
socket outlet. The reading obtained at each accessory point should be a low resistance
value. The resistance measured at the extremity of the circuit is the sum of the resistances of
the line conductor and protective conductor (R1 + R2).
When we talk about Continuity Testing within the Inspection and Testing Procedure then
we apply the same principle, but with a bit more detail.
Step 1: Select the circuit to be tested in the distribution board and remove the Line conductor
from the MCB
Step 2: Connect the Line conductor to the Earth conductor (for simplicity, connect it to one of
the spare terminals on the Earth bar). This way you will form a circuit which is half made up of
the Line conductor and half made of the Earth conductor (provided that the terminations within
the electrical accessories such as wall sockets are correct).
Step 3: Select the correct test function on the test equipment, which is the low reading ohm
meter function (Megger 1553).
Step 4:. Do not forget to null the test instrument if required (you can do this by connecting the
two test leads together and pressing the TEST button until the measured value on the display
becomes zero ohm`s)
Step 5: Measure between Line and Earth terminals at each outlet in the circuit. The highest
reading should be recorded on the Schedule of Test Results as the value of (R1+R2).
Step 6:.Return the Line conductor back in to the MCB
Continuity is the presence of a complete path for current flow. A circuit is complete when
its switch is closed.
A digital multimeter’s Continuity Test mode can be used to test switches, fuses, electrical
connections, conductors and other components. A good fuse, for example, should have
continuity.
A DMM emits an audible response (a beep) when it detects a complete path.
The beep, an audible indicator, permits technicians to focus on testing procedures without
looking at the multimeter display.
When testing for continuity, a multimeter beeps based on the resistance of the component
being tested. That resistance is determined by the range setting of the multimeter.
Examples:
If the range is set to 400.0 Ω, a multimeter typically beeps if the component has a resistance
of 40 Ω or less.
If the range is set 4.000 kΩ, a multimeter typically beeps if the component has a resistance
of 200 Ω or less.
The lowest range setting should be used when testing circuit components that should have
low-resistance value such as electrical connections or switch contacts.
Do not forget that with the lighting circuits the intermediate switch should be switched to
all available positions so that all the conductors could be tested for continuity.
Do not forget to link out the dimmer switch on the other lighting circuit, otherwise you will
get wrong test results.
Remember, that by doing these steps you will also confirm the correct polarity of the
conductors, so there is no need to do polarity dead tests again.
Remember to constantly inspect the installation for faults and signs of damages.
Multimeters and ohmmeters are normally used for continuity tests. Specialized continuity testers
are also available which are more basic in nature, inexpensive and have a light bulb which glows
in the case of current flow. The continuity test is performed on an electrical circuit when it is not
powered and with help of the testing device.
Can an electronic circuit which is passing currents be tested by a multi-meter’s continuity
test? Would it be meaningful or harmful? Why?
A continuity test is like a simplified resistance/ohms measurement. A basic method is to apply a
voltage across the resistor and measure the current OR apply a current and measure the voltage.
Then through R = V/I you can calculate the resistance.
Imagine you applied 100 V DC but your meter can only handle 10 V when in the continuity test
mode. Such a test is completely meaningless, and potentially damaging to the meter. If you want
to test continuity or resistance, remove all sources of power, and discharge any stored energy
sources.
The meter is sourcing a (usually low) test voltage. If you connect it to something that is already
powered, you are connecting the two sources together, and the meter isn’t designed to handle
external sources in continuity or resistance (or capacitance, or inductance, or any other passive)
mode..
Return of that investment is a long-term one and it will also save time.
Tests can be done 24/7.
Fewer human resources are required.
Reusability: The scripts are reusable. You don’t need new scripts all the time.
Reliability: It is more reliable and quicker way when running boring repetitive standardized
tests which cannot be skipped.
It not only checks for continuity but also for shorts.
Enquire Now
LATEST UPDATES
References[edit]
1. ^ "How to Test for Continuity with a Digital Multimeter". www.fluke.com. Retrieved 2021-03-
24.
1. Turn the dial to Continuity Test mode. It will likely share a spot
on the dial with one or more functions, usually resistance (Ω).
With the test probes separated, the multimeter’s display may
show OL and Ω.
2. If required, press the continuity button.
1. First insert the black test lead into the COM jack.
2. Then insert the red lead into the VΩ jack. When finished, remove
the leads in reverse order: red first, then black.
3. With the circuit de-energized, connect the test leads across the
component being tested. The position of the test leads is
arbitrary. Note that the component may need to be isolated from
other components in the circuit.
4. The digital multimeter (DMM) beeps if a complete path
(continuity) is detected. If the circuit is open (the switch is in the
OFF position), the DMM will not beep.
5. When finished, turn the multimeter OFF to preserve battery life.
Related resources
How to test diodes with a digital multimeter
How to measure current with a clamp accessory