0% found this document useful (0 votes)
26 views

Three Phase Transformer Deltadelta Connection PDF

The document discusses a delta-delta transformer connection. It has three phases with each winding in a delta configuration. The phase and line voltages are equal and the transformation ratios are the same. The phase shift between primary and secondary voltages is either 0 or 180 degrees depending on how the secondary leads are connected.

Uploaded by

karesanikas2004
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
26 views

Three Phase Transformer Deltadelta Connection PDF

The document discusses a delta-delta transformer connection. It has three phases with each winding in a delta configuration. The phase and line voltages are equal and the transformation ratios are the same. The phase shift between primary and secondary voltages is either 0 or 180 degrees depending on how the secondary leads are connected.

Uploaded by

karesanikas2004
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Three Phase Transformer:

Delta-Delta Connection
By : Dr. Atul R. Phadke
Associate Professor in Electrical Engineering
Government College of Engineering, Karad (Maharashtra)
DELTA-DELTA CONNECTION:
In delta connection, the finishing end of one winding is connected to A
𝐴2 𝑎2
a
the starting end of the next winding to form a closed loop.
𝑉 𝑉 𝐾𝑉 𝐾𝑉
For example, 𝐴1 is connected to 𝐵2 , 𝐵1 to 𝐶2 and 𝐶1 to 𝐴2 to form a 𝐴1 𝑎1
closed loop.
B b
Three lines are taken out from the three nodes, i.e. from 𝐴2 , 𝐵2 and 𝐵2 𝑏2
𝐶2 .
Let the line voltage on primary side 𝑉1𝐿 = 𝑉 𝐵1 𝑏1

 The phase voltage on primary side 𝑉1𝑝ℎ = 𝑉 C c


𝐶2 𝑐2
𝑉2𝑝ℎ
The phase transformation ratio, =𝐾
𝑉1𝑝ℎ
𝐶1 𝑐1
 The phase voltage on secondary side 𝑉2𝑝ℎ = 𝐾 × 𝑉1𝑝ℎ = 𝐾𝑉
 The line voltage on secondary side 𝑉2𝐿 = 𝑉2𝑝ℎ = 𝐾𝑉
𝑉2𝐿 𝐾𝑉
The line transformation ratio, = =𝐾
𝑉1𝐿 𝑉

 In  −  connection, phase transformation ratio = line


transformation ratio = K 2
DELTA-DELTA CONNECTION (𝐷𝑑0):

A a C1 c1
A2 A1 a1 a2 A2 (A) a2 (a)
C2 (C) c2 (c)
B b
B2 B1 b1 b2 B1 b1
A1 a1
B2 (B) b2 (b)
C c
C2 C1 c1 c2
12
11 1
From phasor diagrams it can be seen that the primary and
10 2
secondary line voltages (and therefore the corresponding phase
voltages) are in phase. 9 3
8 4
The phase shift between the primary and secondary voltages is
7 5
00 . 6

The vector group is 𝐷𝑑0


DELTA-DELTA CONNECTION (𝐷𝑑6):

C1 c1 (c)
A a A2 (A) a2
A2 A1 a2 a1
C2 (C) c2

B b B1 b1 (b)
B2 B1 b2 b1
A1 a1 (a)
B2 (B) b2
C c
C2 C1 c2 c1
12
11 1
10 2
If the secondary leads are taken out from delta nodes a1-b2,
b1c2, and c1a2, the secondary voltages are in phase opposition 9 3
to the primary voltages. 8 4
From phasor diagrams it can be seen that the the phase shift 7 6 5
between primary and secondary voltages is 1800.
The vector group is 𝐷𝑑6
FEATURES OF DELTA-DELTA CONNECTION:
/ connection is suitable for large low voltage transformers. A
𝐴2 𝑎2
a

Even if the load is unbalanced, the three phase load voltages remain 𝑉 𝑉 𝐾𝑉 𝐾𝑉
almost constant. 𝐴1 𝑎1

The phase voltage is same as line voltage. Hence, delta connected B b


𝐵2 𝑏2
windings require more insulation than star connected windings of the
same rating.
𝐵1 𝑏1
No neutral connection is available on either side.
C c
𝐶2 𝑐2
This connection can operate as open delta with reduced capacity to
maintain the continuity of service.
𝐶1 𝑐1

You might also like