Ds Pgs Pas PGF Paf PGD Pad Pap Pgp100-En G 04.2023 Io Link
Ds Pgs Pas PGF Paf PGD Pad Pap Pgp100-En G 04.2023 Io Link
—
Measurement made easy
Engineered solutions for all applications
Base accuracy
• From ± 0.25 % up to ± 0.075 % of calibrated span
Span limits
• 0.3 – 10000 kPa; 16 inH2O up to 1450 psi
• 0.3 – 10000 kPa abs; 30 mmHg up to 1450 psia
PED compliance
• Category III for PS > 20 MPa, 200 bar
• Sound Engineering Practice (SEP) for PS ≤ 20 MPa, 200 bar
—
General Description
PXS100 PXD100
Model PXS100 is the compact, reliable, essential pressure Model PXD100 is the pressure transmitter from the PXX100
transmitter suitable for liquid, gas or steam applications. It is a series featuring the S26 diaphragm seal line accessories. While
straightforward and robust device designed for rapid delivery having a compact, sturdy stainless-steel housing to grant
and easy installation and use. Thanks to its rugged design robustness, resistance to humidity and vibration, PGD100 is
offering high resistance in even the most demanding leveraging flanges and connections in a variety of geometries.
environments, it is a competitive solution for most The combination of S26 diaphragm seals design according to
applications, including ones in hazardous areas. ASME/EN standards with the unique ABB All-Welded
technology eliminates leakage risks during operation while
ensuring perfect fit to any process.
PXF100
Model PXF100 is designed to fit sanitary, food & beverage Picture 3 - PXD100 with remote diaphragm seal type S26Rx
—
Specification - Physical(1)
Materials
Process isolating diaphragms (2)
AISI 316 L ss, Hastelloy C276,
Diaflex (antiabrasion), H-Shield (against hydrogen
permeation) Additional plate
Self-adhesive label for tag and/or calibration details (up to
Process connection (2) 20 characters). Only by ordering option code "SC" for tag
AISI 316 L ss purposes, tag value will both be transferred in the memory
Hastelloy C276 (Available on request) of the instrument itself and appear on the optional
certificates. Please be aware that display will only show
Filling fluids (3) last 8 digits of tag number.
Silicone oil, inert fill (fluorocarbon), Mineral oil (FDA AISI 316 ss wired-on plate with laser printed customized
approved), Vegetal oil (FDA approved) data (4 lines of 32 characters 4 mm/0.16 in high). By
ordering option code "LEW", custom text has to be
Mounting bracket provided. In case of no text provided, wired-on plate will
AISI 304 ss be delivered blank.
Be aware that if tag is only indicated as part of the custom
Sensor housing, electronics housing and cover text , it will neither be transferred in the memory of the
AISI 316 L ss instrument itself nor appear on the relevant certificate. If
that is required, please order option code "SC".
Filter for atmospheric ventilation
• Filter material: polyamide (PA) Cleaning procedure for oxygen service (code P1)
• Filter housing: plastic (general purpose version), Oxygen service cleaning, (only available with inert oil fill)
stainless steel (Ex certified versions) Pmax =10 MPa for Galden; Tmax=60 °C/140 °F or max.
working pressure
Cover O-ring
EPDM for sensor O-ring and cover O-ring to glass; Certificates (test, design, characteristics, material
EPDM for cover O-ring to housing traceability) (code Cx)
Silicon for cover O-ring to housing Option code "CF" provides an inspection certificate of
calibration 0 to URL but code “SC” should be also selected
Process connection O-ring if the inspection certificate is required for calibration
EPDM for front bonded connection on PXS100 different from 0 to URL.
EPDM, FKM or HNBR for universal connection on PXF100
Approvals (code Gx)
Electrical connections For details refer to section Specification - Certifications
IO-Link connector: Copper Alloy, Nylon, PVC, Rubber and Approvals
(1) Refer to the ordering information for availability of different versions of the relevant
models
(2) Wetted parts of the transmitter.
(3) For PXD refer to OI/DS-S26 datasheet for additional information on available filling fluids
PXS 100, PXF 100, PXP100 AN D PXD100 | PRE SSU RE TR ANSMIT TE RS | DS/PXX100-EN Rev. G 5
—
Functional – specification
—
Specification – Operative limits
Pressure limits
Overpressure limits
Model PXP100 Seal type Pressure limit
Without damage to the transmitter
Sensors
No damage will occur during transmitter operation, if they
1 in. pulp and paper seal with
are used within the specifications and subject to the 4 MPa, 40 bar, 580 psi
ball valve connection
following limits:
1 in. pulp and paper seal -
3 MPa, 30 bar, 435 psi
sealing with gaskets to spud
Sensor code Overpressure limits, 0 abs to:
Sensors L to R 1 in. pulp and paper seal with
C,F 1 MPa, 10 bar, 145 psi 34.5 MPa, 345 bar,
1 in. NPT male threaded
L 3 MPa, 30 bar, 435 psi 5000 psi
connection
D 6 MPa, 60 bar, 870 psi
1 in. pulp and paper seal with
60 MPa, 600 bar, 8700
K 8 MPa, 80 bar, 1160 psi G 1 in. A male threaded
psi
connection
R 20 MPa, 200 bar, 2900 psi
1 1/2 in. pulp and paper seal -
5 MPa, 50 bar, 725 psi
sealing with gasket to spud
The below table shows the maximum pressure limits of
1 1/2 in. pulp and paper seal
the connection when coupled with customer process 34.5 MPa, 345 bar,
with 1 1/2 in. NPT male
interface. It also shows the compatibility of the sensor 5000 psi
threaded connection
ranges. All Sensors 1 1/2 in. pulp and paper seal
60 MPa, 600 bar, 8700
with G 1 1/2 in. A male
psi
Model PXF100 Seal type Pressure limit threaded connection
Sensors
1 1/2 in. pulp and paper seal -
Universal G1" hygienic - AISI sealing with gasket to M44 -
Universal G1" hygienic - HC threaded spud
Storage
Model PGx100, PAx100 Storage temperature limits
Storage temperature range –0 and 85 °C (–58 and 185 °F)
LCD display and IO-Link version –40 and 85 °C (–40 and 185 °F)
IMPORTANT (NOTE)
For Hazardous Atmosphere and Ordinary location applications
see the temperature range specified on the certificate/
approval relevant to the aimed type of protection.
—
...Specification – Operative limits
Refer to the following FILL FLUID CHARACTERISTICS table detailing characteristics of fill fluids when used in transmitters.
Operational limits may vary depending on the materials, gasket and configuration selected.
Absolute viscosity (cP) = Kinematic Viscosity (cSt) x Specific gravity at specified temperature.
The absolute viscosity value is used for response time calculation.
PXS 100, PXF 100, PXP100 AN D PXD100 | PRE SSU RE TR ANSMIT TE RS | DS/PXX100-EN Rev. G 9
The mnemonics will be used as shortest cross references in the S26 data sheet.
Seal Seal type "Seal diaphragm size Direct mount seal Remote seal Mnemonic
model (thickness)
Sensor Sensor
[flange type]"
C F L D K R C F L D K R
Please see more details on S26 remote seals at this link: OI/DS-S26
10 PXS100, PXF 100, PXP100 AN D PXD100 | PRE SSU RE TR ANSMIT TE RS | DS/PXX100-EN Rev. G
—
...Specification – Operative limits
Environmental limits
Electromagnetic compatibility (EMC)
The devices comply with the requirements and tests for
EMC Directive 2014/30/EU to standards EN 61326-1 Table2
(industrial electromagnetic environment) concerning both
emitted interference (CISPR11) and interference immunity.
• Burst test: up to 2 kV at 5 kHz and 100 kHz
• Surge test: up to 1 kV line-line and 2 kV line-ground
Radiated emission: Group 1 - class B according to CISPR11
• FCC 47 CFR part 18.305
• ICES 005 - Issue 4
Conducted emission: group 1 - class A according to
CISPR11 and to CISPR32
• ICES 005 -Issue 4
Humidity
Relative humidity: up to 100 %
Condensation, icing: permissible
Vibration resistance
Acceleration at frequencies of
• 10 – 60 Hz with displacement of 0.7 mm
• 60 – 1000 Hz 5 g (50 m/s2)
(according to IEC 60068-2-6).
Shock resistance
Test Ea Half sine with 3 positive and 3 negative shocks for
each axis
• Acceleration: 50 g
• Duration: 11 ms
Continuous test Ea half sine with 1000 positive and 1000
negative shocks for each axis
• Accelleration: 10 g
• Duration: 10 ms
(according to IEC 60068-2-27)
Wet and dust-laden atmospheres (IP degree of protection)
The transmitter is dust and sand–tight, and is protected
against immersion effects as defined by the following
standards:
• IEC EN60529 to IP66, IP67, IP68
• ISO 20653 to IP69K
• NEMA 4X
Tested ambient
The transmitter is suitable for class D1,
non weather-protected locations, outdoor locations
(according to IEC 60654-1)
PXS 100, PXF 100, PXP100 AN D PXD100 | PRE SSU RE TR ANSMIT TE RS | DS/PXX100-EN Rev. G 11
—
Specification - Performance
Ambient temperature (E∆TZ+E∆TS)
Reference conditions according to IEC 62828-1
Temperature effect according to IEC 62828/1
• Ambient temperature constant in the range 15 – 25 °C
(59 – 77 °F)
For temperature variation between the limits of –40 °C to
• Relative humidity constant in the range 50 – 70 %
+85 °C (-40 °F to +185 °F)
• Ambient pressure constant in the range 860 – 1060 mbar
Sensor for TD up to
• Measuring span based on zero position
All 20:1 ± (0.15 % URL + 0.15 % span)
• Transmitter with AISI 316 L or Hastelloy C276 process
isolating diaphragm
In case of maximum ambient temperature variation of 28K,
• Filling fluid: Silicone oil
then the following expression could be used as it provides a
• Supply voltage: 24 V DC ± 1 %
more accurate interpretation of the effect in that interval.
• Load with HART: 250 Ω
• Transmitter not grounded
For 28K temperature variation between the limits of –40 °C
• Characteristic setting: linear, 4 – 20 mA.
to +85 °C (-40 °F to +185 °F)
Unless otherwise specified, errors are quoted as % of
Sensor for TD up to
calibrated span.
C, F 20:1 ± (0.15 % URL + 0.15 % span)
Some performance referring to the Upper Range Limit are L, D, K, R ± (0.1 % URL + 0.1 % span)
20:1
affected by the actual turndown (TD) as ratio between
Upper Range Limit (URL) and calibrated span.
For PXD100 models, refer to S26 remote seals OI/DS-S26
document for additional error and effects due to ambient
FOR OPTIMUM MEASURING ACCURACY, IT IS RECOMMENDED
temperature changes when in combination with S26x
THAT YOU SELECT THE SENSOR CODE WHICH WILL PROVIDE
diaphragm seal.
THE LOWEST TD VALUE.
—
...Specification - Performance
Power supply
Within the specified limits for the voltage / load, the total
influence is less than 0.005 % of the upper measuring
range limit per volt.
Load
Within the specified load / voltage limits, the total
influence is negligible.
Mounting position
Nominal position: vertical; process connection at bottom.
Mounting positions deviant from the standard position
influence the output due to the filling liquid.
This effect can be compensated by carrying out zero
signal adjustment.
Long-term stability
± 0.25 % of URL over a 10 years period
Total performance
For a temperature change from -40° to 85°C (-40° to
+185°F) with TD 1:1 and considering IEC 62828-1
expression:
• 0.39 % of calibrated span for standard accuracy models
• 0.32 % of calibrated span for E9 extended accuracy
models
• 0.31 % of calibrated span for E7 extended accuracy
models
Eperf=√(E∆TZ+E∆TS)2+ELin2
Eperf=√(E∆TZ+E∆TS)2+ELin2 +E∆TR2
—
Specification - Certifications and Approvals
Hazardous atmospheres Other Approvals
INTRINSIC SAFETY Ex ia: Ministerial decree DM174/2004
ATEX Europe approval (code HAM) Wetted parts in AISI 316 L for PxS100
II 1 G Ex ia IIC T4 Ga are approved under ministerial
II 1/2 D Ex ia IIIC T 135°C Da/Db decree nr. DM174/2004 and
II 1/2 D Ex ta/tb IIIC T 135°C Da/Db hence are suitable for drinking
water applications.
IECEx approval (code HJM)
Ex ia IIC T4 Ga
Ex ia IIIC T 135°C Da/Db Water Regulation Approval Scheme (WRAS)
Ex ta/tb IIIC T 135°C Da/Db PxS100 with wetted parts in AISI 316 L
is WRAS approved and hence
CSA Approvals (code HCM) suitable fordrinking water
• For US applications when installed
Class I, Zone 0, AEx ia IIC T4 Ga and used correctly.
IS Class I Div 1 Gr A, B, C, D T4
IS Class II, Div 1 Gr E, F, G 120° C Hygienic Equipment Design of the EHEDG (PxF100)
Zone 20/21 AEx ia IIIC T135° C Da/Db PxF100 process connections have
Zone 20/21 AEx ta/tb IIIC T135° C Da/Db been certified according to the
Class I, Div. 2 Gr A, B, C, D T4 EHEDG guidelines and hence are
Class III, Div 1 suitable, with appropriate filling
• For Canada fluids, gaskets and installation
Ex ia IIC T4 Ga guidance, for Food and Beverage
IS Class I Div 1 Gr A, B, C, D T4 applications.
IS Class II, Div 1 Gr E, F, G 120° C
Ex ia IIIC T135°C Da/Db Conforming to 3-A Sanitary Standards (PxF100)
Ex ta/tb IIIC T135°C Da/Db PxF100 process connections
Class I, Div. 2 Gr A, B, C, D T4 (with both diaphragm materials
Class III, Div 1 AISI 316 L and Hastelloy® C-276)
have been certified according to the
Combined ATEX Europe, IECEx and CSA (US and Canada) 3-A guidelines and hence are
approvals (code HMM) suitable, with appropriate filling
fluids, gaskets and installation
Without integral display guidance, for Food and Beverage
NEPSI China approval (code HMN) applications. ABB is authorised to
Without integral display display the 3-A Symbol.
• INTRINSIC SAFETY Ex ia:
Ex ia IIC T4 Ga European Regulation (EC) No. 1935/2004
Ex iaD 20/21 T135°C Pxx100 uses wetted parts which are in compliance with
Ex tD A20/A21 IP6X T135°C (EC) No. 1935/2004, see available declaration on www.abb.
com/pressure
With integral display
NEPSI China approval (code HMN)
With integral display
• INTRINSIC SAFETY Ex ia:
Ex ia IIC T4 Ga
IMPORTANT (NOTE)
REFER TO CERTIFICATES FOR PROTECTION CONCEPT,
PROCESS TEMPERATURE RANGES AND MAX AMBIENT
TEMPERATURE.
14 PXS100, PXF 100, PXP100 AN D PXD100 | PRE SSU RE TR ANSMIT TE RS | DS/PXX100-EN Rev. G
—
Specification - Electrical data and options
HART digital communication and 4 to 20 mA output
Power supply Output signal
The transmitter operates from 10.5 to 42 V DC with no 4 to 20 mA analog version
load and is protected against reversed polarity (additional • Two–wire, 4 to 20 mA analog output signal
loads enable operation above 42 V DC). HART/4 to 20 mA version
Minimum operating voltage increases to 14.5 V DC with • Two–wire, 4 to 20 mA analog output signal and digital
optional backlit LCD display. process variables (%, mA or engineering units)
For Ex ia and other intrinsically safe approval power superimposed on the 4 to 20 mA signal with protocol
supply must not exceed 30 V DC. based to Bell 202 FSK standard H.
LCD display (optional) NAMUR NE 43 defines as alarm limits the lower ≤ 3.6 mA
and the upper ≥ 21 mA.
2 versions available- Risk connected to any deviation from NAMUR NE43
• D3: Glass touch LCD display with 2-button keypad thresholds of the alarm current limits falls under
• D4: Backlit glass touch LCD display with 2-button Customers' responsibility.
keypad
HART release
Digital, graphic LCD display with 2-button keypad for Revision 7.
customized visualization and configuration
VISUALISATION Analog version HART version
(4-20 mA) (4-20 mA + HART)
PV value (in Pressure units) - Y
(1)
Freely assigned start/end values and unit
(2)
Optional through SD digit code
(3)
Applied pressure is required
(4)
Optional through SE digit code
PXS 100, PXF 100, PXP100 AN D PXD100 | PRE SSU RE TR ANSMIT TE RS | DS/PXX100-EN Rev. G 15
Power supply
The transmitter operates following the parameters of the
table below.
POWER SUPPLY
Minimum power supply voltage 9Vdc
Configuration of
• Language, TAG, PV Unit, PV Lower Range Value, PV
Upper Range Value, Linearization Type, Damping,
Display Line 1 View, Backlight, Contrast
• Output 1 Mode (Switching point 1, Reset Point 1)
• Output 2 Mode (Switching point 2, Reset Point 2)
• Set PV to Zero or Reset PV Bias
—
Configuration
Transmitter with HART communication Transmitter with IO-Link digital communication
and 4 – 20 mA and 4 – 20 mA
Standard configuration Standard configuration
Transmitters can be ordered optionally factory calibrated Transmitters can be ordered optionally factory calibrated
to customers specific range. The required calibrated range to customers specific range. The required calibrated range
and tag will be printed on an additional tag plate. and tag will be printed on an additional tag plate.
If a calibration range and tag is not required, the If a calibration range and tag is not required, the
transmitter will be supplies as follows: transmitter will be supplies as follows:
Engineering Unit kPa Output 1 Threshold NO
4 mA Zero Output 2 Disabled
20 mA Upper Range Limit (URL) Pressure unit kPa
Output Linear Temperature unit Celsius
Damping 1s Damping 1s
Transmitter failure mode Upscale Analogue fail safe type Down
Tag Blank (up to 20 alphanumeric Lower range value 0 kPa
characters - long; Upper range value Upper sensor limit (USR)
only last 8 visible on display - Short Tag Blank
short) Backlight On
Optional display 2 line display view: Display view 1 line - PV in kPA
- PV in kPa for HART version, Advanced diagnostic Disabled
in mA for 4 to 20 mA version;
- output in mA and in percent Any or all the above configurable parameters, including
as bargraph lower and upper range values which must be the same unit
Write protection Disabled of measure, can be easily changed using a IO-link device
tool using the relative IODD.
Any or all the above configurable parameters, including lower
and upper range values which must be the same unit of Tag and Calibration
measure, can be easily changed using a HART hand–held Tag and/or specific calibrated span shall be ordered using
communicator or by a PC running the configuration software option code "SC".
with DD or FDI In case a calibration report is needed on a full range
device, option code "SC" has to be ordered and full span
Tag and Calibration has to be provided as calibrated span.
Tag and/or specific calibrated span shall be ordered using In case option "SC" is ordered for tag purposes, two tag
option code "SC". types are available: Short Tag and Application Specific Tag.
In case a calibration report is needed on a full range See below table for details about tag type applicability /
device, option code "SC" has to be ordered and full span presence:
has to be provided as calibrated span.
In case option "SC" is ordered for tag purposes, two tag Max
Type On Display On CertificationOn Device Label
types are available: Short Tag and Long Tag. Length
See below table for details about tag type applicability / Short Tag 8 digits YES YES NO
presence: Application
Specific 32 digits NO YES YES
Tag
Type Max Length On Display On CertificationOn Device Label
Short Tag 8 digits YES YES NO
In order to set up Tag (either Application Specific / Short
Long Tag 32 digits NO YES YES
or both) option in production, SC is mandatory in the
code.
In order to enable Tag (either Long / Short or both) option
In case no specific indication will be given about the tag
SC is mandatory in the code.
type, data will be considered as Application Specific Tag by
In case no specific indication will be given about the tag
default.
type, data will be considered as Long Tag by default.
In case tag is required on the optional wired-on customer
In case tag is required on the optional wired-on customer
data plate (optional digit LEW) specific indication needs to
data plate (optional digit LEW) specific indication needs to
be given.
be given.
PXS 100, PXF 100, PXP100 AN D PXD100 | PRE SSU RE TR ANSMIT TE RS | DS/PXX100-EN Rev. G 17
—
Mounting dimensions
(not design data) - dimensions in mm (inch)
Ø 80 (3.15)
Nameplate,
certification,
tag plates area
100.8 (3.97)
Ventilation
port
Electrical
connection
External ground
termination point
37.5 (1.48)
Figure 1 PXS100 with 1/2 in NPT female connection (Option code "A")
100.8 (3.97)
34.5 (1.36)
Figure 2 PXS100 with 1/2 in NPT male / ¼ in NPT female connection and LCD digital display (Option code "B")
18 PXS100, PXF 100, PXP100 AN D PXD100 | PRE SSU RE TR ANSMIT TE RS | DS/PXX100-EN Rev. G
—
...Mounting dimensions
min. 14 (0.55)
85 (3.35)
Ø 80 (3.15)
95.8 (3.77)
34.5 (1.36)
G 1/2 B
87 (3.43)
85 (3.35)
∅80 (3.15)
100.8 (3.97)
16/19 (0.63/0.75)
∅50 (1.97)
15 (0.59)
21 (0.83)
G 1/2 inch
Wr. 24 (0.95)
Figure 4 PXS100 with front bonded diaphragm connection (Option code "P")
PXS 100, PXF 100, PXP100 AN D PXD100 | PRE SSU RE TR ANSMIT TE RS | DS/PXX100-EN Rev. G 19
47 (1.85)
72.3 (2.85)
103 (4.06)
70 (2.76)
90 (3.55)
53 (2.09)
83 (3.27) 45 (1.77)
Figure 5 PXS100 with 1/2 in NPT male / 1/4 in NPT female connection on bracket (Option code "B")
20 PXS100, PXF 100, PXP100 AN D PXD100 | PRE SSU RE TR ANSMIT TE RS | DS/PXX100-EN Rev. G
—
...Mounting dimensions
87 (3.43)
20.3 (0.80)
∅80 (3.15)
132 (5.20)
∅B
∅A
H
∅A
Rd
C
∅D
87 (3.43)
∅80 (3.15)
20.3 (0.80)
132 (5.20)
O-Ring
∅B
∅A
H
C
K
∅A
Rd
∅D
—
...Mounting dimensions
87 (3.43)
∅80 (3.15)
20.3 (0.80)
132 (5.20)
∅A
∅C
∅B
H
∅A
87 (3.43)
20.3 (0.80)
∅80 (3.15)
132 (5.20)
∅B
∅A
H
C
H
∅A
Rd
∅D
—
...Mounting dimensions
87 (3.43)
20.3 (0.80)
∅80 (3.15)
154/135 (6.07/5.31)
∅B
∅A
C 12.3 (0.48)
∅A
∅D
87 (3.43)
20.3 (0.80)
∅80 (3.15)
154/135 (6.07/5.31)
∅E
∅A
10 (0.39)
∅C 17 (0.67)
∅B
∅D
—
...Mounting dimensions
87 (3.43)
20.3 (0.80)
∅80 (3.15)
N04 ∅11.5
132 (5.20)
∅65 (2.56)
∅48 (1.89)
28 (1.10)
∅105 (4.14)
∅65 (2.56)
87 (3.43)
15.3 (0.60)
87 (3.43)
∅80 (3.15) ∅80 (3.15)
132 (5.20)
132 (5.20)
19 (0.75)
Universal
19 (0.75)
Hole to check
connection G1
leakage
O-Ring
28.5 (1.12)
28.5 (1.12)
Adapter
Wr. 46 (1.81) Wr. 41 (1.62) Wr. 46 (1.81) ∅24 (0.95)
Figure 13 PXF100 with Universal connection and hygenic adapter (Option code "U")
PXS 100, PXF 100, PXP100 AN D PXD100 | PRE SSU RE TR ANSMIT TE RS | DS/PXX100-EN Rev. G 27
87 (3.43)
85 (3.35)
∅80 (∅3.15)
20 (0.80)
85/88 (3.35/3.46)
M44 THREADED SPUD GASKET TO SPUD
G MALE THREADED
NPT MALE THREADED
BALL VALVE
Wr. 36
∅54 (2.13)
37 (1.46)
46 (1.80)
21 (0.82)
30 (1.18)
∅35 (1.38)
M44 x 1.25
∅20 (0.79)
∅25 (0.99)
G 1 inch B
Figure 15 PXP100 with Ball Valve (Option code "E") Figure 16 PXP100 with M44 Threaded Spud (Option code "G")
28 PXS100, PXF 100, PXP100 AN D PXD100 | PRE SSU RE TR ANSMIT TE RS | DS/PXX100-EN Rev. G
—
...Mounting dimensions
Wr. Wr.
B
B
∅A
NPT ∅A
G
Option
NPT MWP (bar) ØA B Wr. Option
code G (ISO 228) MWP (bar) A (dia) B Wrench
1 in. C 345 26 (1,02) 65 (2,56) 41 code
G 1 in. A 600 26 (1.02) 61(2.4) 41
1 1/2 in. D 345 39 (1,54) 66 (2,6) 55
G 1 1/2 in. B 600 39 (1.54) 63 (2.48) 55
∅E
∅D
N° C holes N° C
5/16-18 UNC
45 (1.77)
25.4 (1.00)
1 or 2 Viton gaskets
∅A
D (dia) E (dia)
Size/ Rating Option code MWP (Bar) A (dia) C No. of Gaskets 1st O-ring 2nd O-ring
Welding Spud Welding Spud
—
Electrical connections
HART version
communication board
power supply and
signal terminals
-
connector for LCD
+
external earth resistor +
terminal (not visible) line load
JK L
1
D E F
M N O
GH I
3
P QR ground
- write protection
4 5 6
S T U V W X Y Z#
7 8 9
handheld
terminal receiver unit
HAZARDOUS AREA SAFE AREA
Figure 22 Connections
HART communication requires a minimum loop resistance of 250 ohm. If this is less than 250 ohm, additional resistance should be added.
IO-Link version
The IO-link device uses a M12-4 connector and requires the following connection to the external system:
Figure 23 Connections
Transistor functions
Output 1 IO-Link or Transistor
Output 2 4-20mA or Transistor
Transistor mode PNP, NPN,PP
Maximum current for each transistor 250mA
Max transistors power dissipation 2W
Max load for each transistor 8W
High level voltage drop <2V @ 250mA
Low level voltage drop <1V @ 250mA
Transistors dead time <10ms
Delay function 10ms to 60s
Short circuit resistance Yes
Current limiter Disable, 50, 100, 200, 250 mA
Leakage current NPN 20uA Max
Leakage current PNP 40uA Max
PXS 100, PXF 100, PXP100 AN D PXD100 | PRE SSU RE TR ANSMIT TE RS | DS/PXX100-EN Rev. G 31
—
Ordering Information
Basic ordering information PGS100 Gauge Pressure Transmitters and PAS100 Absolute Pressure Transmitters
Select one character or set of characters from each category and specify complete catalog number.
Refer to additional ordering information and specify one or more codes for each transmitter if additional options are required.
Additional ordering information model PGS100 Gauge Pressure Transmitters and PAS100 Absolute Pressure Transmitters
Add one or more options code after the basic ordering information to select all required options.
XX XX XXX XX XX XX XX XX
LCD Display (see FOOTNOTE)
Glass touch LCD display with 2-button keypad (Note 14) D3
Backlit glass touch LCD display with 2-button keypad D4
Extended performances
± 0.075% extended Base accuracy E7
± 0.10 % extended base accuracy E9
Hazardous area certifications (see relevant paragraph for complete detailed markings)
ATEX Ex ia and Ex ta/tb (Note 4, 14) HAM
CSA approvals (USA and Canada) IS (Gas and Dust) (Note 4, 14) HCM
IECEX Ex ia and Ex ta/tb (Note 4, 14) HJM
Combined ATEX, CSA approvals (USA and Canada) and IECEx (Gas and Dust) (Note 4, 14) HMM
NEPSI China (Ex ia and Ex iaD / Ex tD) (Note 14) HMN
INMETRO (Brazil) Ex ia and Ex ta/tb (Note 14) HMB
EAC Ex ia and Ex ta/tb (Note 14) HME
Approvals
CSA ordinary location (USA and Canada) (Note 4) GO
DM174 water approval (Note 5) GD
WRAS water approval (Tmax = 85 °C for Process connection size code P and 100 °C for codes A, B, C) (Note 5) GW
Combined water approvals (Note 5) GA
Physical application
Oxygen service cleaning, (only available with inert oil fill) (Note 6) P1
Pmax =10 MPa for Galden; Tmax=60 °C/140 °F or max. working pressure
Accessories
External grounding terminal (fitted as standard if hazardous area certification code Hxx is selected) AG
Manifold assembly (Note 7, 8) AM
Mounting bracket
Local configuration (Easy Set Up) for 4..20mA Version (Note 10) SE
—
...Ordering Information
... Additional ordering information model PGS100 Gauge Pressure Transmitters and PAS100 Absolute Pressure Transmitters
XX XXX XX
Inspection/compliance certificates
Inspection certificate EN 10204–3.1 of calibration (5-point) (Note 11) CF
Inspection Certificate UNI EN 10204 3.1 (9 points calibration) (Note 12) CN
Inspection certificate EN 10204–3.1 of cleanliness stage CC
Inspection certificate EN 10204–3.1 of helium leakage test of the sensor module CL
Inspection certificate EN 10204–3.1 of the pressure test CH
Certificate of compliance with the order EN 10204–2.1 of instrument design CD
Inspection certificate EN 10204–3.1 of process wetted parts CM
Certificate of compliance with the order EN 10204–2.1 of pressure bearing and wetted parts CW
Labels
Label and display visualization in imperial units (Pressure = inH2O/ psi at 68 °F; Temperature = deg. F) LTU
Supplemental wired–on stainless steel plate (4 lines, 32 characters each) LEW
Label and display visualization in Chinese (Note 13) LTS
Manuals
German M1
Italian (PENDING) M2
Spanish (PENDING) M3
French (PENDING) M4
English M5
Chinese (PENDING) M6
Portuguese (PENDING) MA
Russian (PENDING) MB
Note 1: Only available with Front bonded G 1/2 in process connection code P
Note 2: For 10000 kPa/100 bar/1450 psi sensor code R, H-Shield is only available with front bonded G 1/2 in process connection code P
Note 3: Not available with 40 kPa/400 mbar/160 inH2O/300 mmHg sensor code F
Note 4: Hazardous area certification and CSA ordinary location options are mutually exclusive
Note 5: Available only with Diaphragm material code A
Note 6: Not available with DIN EN 837-1 G 1/2 B process connection code C
Note 7: Not available with any Ex certificates.
Note 8: Not available with Physical application code P1
Note 9: Option code SC has to be ordered if 0 to URL calibration record is required
Note 10: Available only with Output code A
Note 11: Option code CF provides an inspection certificate of calibration 0 to URL
Option code SC should be also selected if the inspection certificate is required for calibration different from 0 to URL
Note 12: Mutually exclusive with Inspection certificate code CF
Note 13: Only available with Housing code U
Note 14: Not available with Protocol/Output code L
—
Ordering Information
Basic ordering information PGF100 Gauge Pressure Transmitters and PAF100 Absolute Pressure Transmitters
Select one character or set of characters from each category and specify complete catalog number.
Refer to additional ordering information and specify one or more codes for each transmitter if additional options are required.
—
...Ordering Information
...Basic ordering information PGF100 Gauge Pressure Transmitters and PAF100 Absolute Pressure Transmitters
X X X X
Additional ordering information model PGF100 Gauge Pressure Transmitters and PAF100 Absolute Pressure Transmitters
Add one or more options code after the basic ordering information to select all required options.
XX XX XXX XX XX XX XX
LCD Display (see FOOTNOTE)
Glass touch LCD display with 2-button keypad (Note 23) D3
Backlit glass touch LCD display with 2-button keypad D4
Extended performances
± 0.075 % extended base accuracy E7
Hazardous area certifications (see relevant paragraph for complete detailed markings)
ATEX Ex ia and Ex ta/tb (Note 10, 23) HAM
CSA approvals (USA and Canada) IS (Gas and Dust) (Note 10, 23) HCM
IECEX Ex ia and Ex ta/tb (Note 10, 23) HJM
Combined ATEX, CSA approvals (USA and Canada) and IECEx (Gas and Dust) (Note 10, 23) HMM
Approvals
CSA ordinary location (USA and Canada) (Note 10) GO
Combined 3A & EHEDG approvals (Note 9, 11) GF
Physical application
Vacuum-proof design P8
Accessories
External grounding terminal AG
(fitted as standard if hazardous area certification code Hxx is selected)
Software application
Calibration to specified measuring span and/or tag number (and printed on plastic label) (Note 12) SC
—
...Ordering Information
... Additional ordering information model PGF100 Gauge Pressure Transmitters and PAF100 Absolute Pressure Transmitters
XX XXX XX XX
Inspection/compliance certificates
Inspection certificate EN 10204–3.1 of calibration (5-point) (Note 14) CF
Inspection Certificate UNI EN 10204 3.1 (9 points calibration) (PENDING) (Note 15) CN
Inspection certificate EN 10204–3.1 of cleanliness stage CC
Inspection certificate EN 10204–3.1 of helium leakage test of the sensor module CL
Inspection certificate EN 10204–3.1 of the pressure test CH
Certificate of compliance with the order EN 10204–2.1 of instrument design CD
Inspection certificate EN 10204–3.1 of process wetted parts CM
Certificate of compliance with the order EN 10204–2.1 of pressure bearing and wetted parts CW
Labels
Label and display visualization in imperial units (Pressure = inH2O/ psi at 68 °F; Temperature = deg. F) LTU
Supplemental wired–on stainless steel plate (4 lines, 32 characters each) LEW
Label and display visualization in Chinese (Note 22) LTS
Manuals
German M1
Italian (PENDING) M2
Spanish (PENDING) M3
French (PENDING) M4
English M5
Chinese (PENDING) M6
Portuguese (PENDING) MA
Russian (PENDING) MB
Other Accessories
Gasket for Front bonded G 1 - EPDM for F&B (FDA, EC 1935/2004) (Note 16) RF
Gasket for Front bonded G 1 - FKM for F&B (FDA, EC 1935/2004) (Note 16) RK
Gasket for Front bonded G 1 - HNBR for F&B (FDA, EC 1935/2004) (Note 16) RN
Note 1: Not available with Diaphragm material F,C & Process connection size code U
Note 2: Only available with process connection code U
Note 3: All ABB adapters used with the Front Bonded G1 in hygienic connection have a leak detect port of 2.4 mm, which must be positioned at the lowest
point for the installation.
Note 4: Pipe couplings ISO 2852, DIN 32676, BS 4825 Part 3 are according to EHEDG only in combination with Tri-Clamps seals Combifit International B.V.,
The Netherlans.
Note 5: Not availbale with sensor range R
Note 6: Pipe couplings DIN 11851 are according to EHEDG, 3A only in combination with ASEPTO-STAR k-flex upgrade gaskets Kieselmann GmbH, Germany.
Note 7: Not available with Diaphragm material codes H,F and C
Note 8: Not available with Diaphragm material codes F,C
Note 9: 3A approved. 3A approval works for 1 in. G universal connection only in combination with relevant gaskets (digit RF,RK,RN) and accessories
(ordering code PZH)
Note 10: Hazardous area certification and CSA ordinary location options are mutually exclusive
Note 11: Not applicable with process connections digits C,D,E,H,L,P,Q,U
Note 12: Option code SC has to be ordered if 0 to URL calibration record is required
Note 13: Available only with Output code A
Note 14: Option code CF provides an inspection certificate of calibration 0 to URL
Option code SC should be also selected if the inspection certificate is required for calibration different from 0 to URL
Note 15: Mutually exclusive with Inspection certificate code CF
Note 16: Only with Process connection code U
Note 17: Gauge couplings SMS SS1145 are according to 3A (CIP) only if special conditions for use are followed (please see the Operating manual for more
details)
Note 18: Pipe couplings Neumo Biocontrol® are according to 3A (CIP) only if special conditions for use are followed (please see the Operating manual for
more details).
Note 19: Varinline® type F process connection is according to EHEDG only on the Varinline® tank flange type T and P with EPDM o-ring. Varinline® GEA
Tuchenhagen GmbH, Germany.
Note 20: Varinline® type N process connection is according to EHEDG only on the Varinline® tank flange type T and P and Varinline® System housing with
EPDM o-ring. Varinline® GEA Tuchenhagen GmbH, Germany.
Note 21: Not available with sensor codes C & F
Note 22: Only available with Housing code U
Note 23: Not available with Protocol/Output code L
38 PXS100, PXF 100, PXP100 AN D PXD100 | PRE SSU RE TR ANSMIT TE RS | DS/PXX100-EN Rev. G
—
Ordering Information
Basic ordering information PGP100 Gauge Pressure Transmitters and PAP100 Absolute Pressure Transmitters
Select one character or set of characters from each category and specify complete catalog number.
Refer to additional ordering information and specify one or more codes for each transmitter if additional options are required.
—
…Ordering information
Additional ordering information model PGP100 Gauge Pressure Transmitters and PAP100 Absolute Pressure Transmitters
Add one or more options code after the basic ordering information to select all required options.
XX XX XXX XX XX XX XX XX
LCD Display (see FOOTNOTE)
Glass touch LCD display with 2-button keypad (Note 8) D3
Backlit glass touch LCD display with 2-button keypad D4
Extended performances
± 0.075 % extended base accuracy E7
Hazardous area certifications (see relevant paragraph for complete detailed markings)
ATEX Ex ia and Ex ta/tb (PENDING) (Note 2, 8) HAM
CSA approvals (USA and Canada) IS (Gas and Dust) (PENDING) (Note 2, 8) HCM
IECEX Ex ia and Ex ta/tb (PENDING) (Note 2, 8) HJM
Combined ATEX, CSA approvals (USA and Canada) and IECEx (Gas and Dust) (PENDING) (Note 2, 8) HMM
Approvals
CSA ordinary location (USA and Canada) (PENDING) (Note 2) GO
Accessories
External grounding terminal AG
(fitted as standard if hazardous area certification code Hxx is selected)
Mounting bracket
Universal for pipe or wall mounting / AISI 304 ss (1.4301) BU
OUTPUT CONFIGURATION
SIL2 (PENDING) (Note 3) NL
Software application
Calibration to specified measuring span and/or tag number (and printed on plastic label) (Note 4) SC
XX XXX XX
Inspection/compliance certificates
Inspection certificate EN 10204–3.1 of calibration (5-point) (Note 5) CF
Inspection certificate EN 10204–3.1 of cleanliness stage CC
Inspection certificate EN 10204–3.1 of helium leakage test of the sensor module CL
Inspection certificate EN 10204–3.1 of the pressure test CH
Certificate of compliance with the order EN 10204–2.1 of instrument design CD
Inspection certificate EN 10204–3.1 of process wetted parts CM
Certificate of compliance with the order EN 10204–2.1 of pressure bearing and wetted parts CW
Inspection Certificate UNI EN 10204 3.1 (9 points calibration) (PENDING) (Note 6) CN
Labels
Label and display visualization in imperial units (Pressure = inH2O/ psi at 68 °F; Temperature = deg. F) LTU
Supplemental wired–on stainless steel plate (4 lines, 32 characters each) LEW
Label and display visualization in Chinese (Note 7) LTS
Manuals
German M1
Italian (PENDING) M2
Spanish (PENDING) M3
French (PENDING) M4
English M5
Chinese (PENDING) M6
Note 1:
Note 2: Hazardous area certification and CSA ordinary location options are mutually exclusive
Note 3: Available only with Display D3, D4
Note 4: Option code SC has to be ordered if 0 to URL calibration record is required
Note 5: Option code CF provides an inspection certificate of calibration 0 to URL
Option code SC should be also selected if the inspection certificate is required for calibration different from 0 to URL
Note 6: Mutually exclusive with Inspection certificate code CF
Note 7: Only available with Housing code U
Note 8: Not available with Protocol/Output code L
—
Ordering Information
Basic ordering information PGD100 Gauge Pressure Transmitters and PAD100 Absolute Pressure Transmitters
Select one character or set of characters from each category and specify complete catalog number.
Refer to additional ordering information and specify one or more codes for each transmitter if additional options are required.
Additional ordering information model PGD100 Gauge Pressure Transmitters and PAD100 Absolute Pressure Transmitters
Add one or more options code after the basic ordering information to select all required options.
XX XX XXX XX XX XX XX
LCD Display (see FOOTNOTE)
Glass touch LCD display with 2-button keypad (Note 8) D3
Backlit glass touch LCD display with 2-button keypad D4
Extended performances*
± 0.075 % extended base accuracy E7
± 0.1 % extended base accuracy E9
Hazardous area certifications (see relevant paragraph for complete detailed markings)
ATEX Ex ia and Ex ta/tb (Note 1, 8) HAM
CSA approvals (USA and Canada) IS (Gas and Dust) (Note 1, 8) HCM
IECEX Ex ia and Ex ta/tb (Note 1, 8) HJM
Combined ATEX, CSA approvals (USA and Canada) and IECEx (Gas and Dust) (Note 1, 8) HMM
Approvals
CSA ordinary location (USA and Canada) (Note 1) GO
Accessories
External grounding terminal AG
(fitted as standard if hazardous area certification code Hxx is selected)
Mounting bracket
Universal for pipe or wall mounting / AISI 304 ss (1.4301) (Note 2) BU
Software application
Calibration to specified measuring span and/or tag number (and printed on plastic label) (Note 3) SC
—
...Ordering Information
...Additional ordering information model PGD100 Gauge Pressure Transmitters and PAD100 Absolute Pressure Transmitters
XX XXX XX
Inspection/compliance certificates
Inspection certificate EN 10204–3.1 of calibration (5-point) (Note 5) CF
Inspection Certificate UNI EN 10204 3.1 (9 points calibration) (PENDING) (Note 6) CN
Inspection certificate EN 10204–3.1 of cleanliness stage CC
Inspection certificate EN 10204–3.1 of helium leakage test of the sensor module CL
Inspection certificate EN 10204–3.1 of the pressure test CH
Certificate of compliance with the order EN 10204–2.1 of instrument design CD
Inspection certificate EN 10204–3.1 of process wetted parts CM
Certificate of compliance with the order EN 10204–2.1 of pressure bearing and wetted parts CW
Labels
Label and display visualization in imperial units (Pressure = inH2O/ psi at 68 °F; Temperature = deg. F) LTU
Supplemental wired–on stainless steel plate (4 lines, 32 characters each) LEW
Label and display visualization in Chinese (Note 7) LTS
Manuals
German M1
Italian (PENDING) M2
Spanish (PENDING) M3
French (PENDING) M4
English M5
Chinese (PENDING) M6
Portuguese (PENDING) MA
Russian (PENDING) MB
Note 1: Hazardous area certification and CSA ordinary location options are mutually exclusive
Note 2: Available only when coupled with S26 remote mount
Note 3: Option code SC has to be ordered if 0 to URL calibration record is required
Note 4: Available only with Output code A
Note 5: Option code CF provides an inspection certificate of calibration 0 to URL
Option code SC should be also selected if the inspection certificate is required for calibration different from 0 to URL
Note 6: Mutually exclusive with Inspection certificate code CF
Note 7: Only available with Housing code U
Note 8: Not available with Protocol/Output code L
Trademarks
™ Galden is a Montefluos trademark
® HART is a registered trademark of FieldComm Group, Austin, Texas, USA
® Hastelloy is a registered trademark of Haynes International, Inc.
® IO-Link is a registered trademark of PROFIBUS Nutzerorganisation e.V. (PNO), Karlsruhe, Germany
® Neumo Biocontrol is a registered trademark of NEUMO-Ehrenberg Group
® VARINLINE is a registered trademark of GEA Tuchenhagen GmbH
44 PXS100, PXF 100, PXP100 AN D PXD100 | PRE SSU RE TR ANSMIT TE RS | DS/PXX100-EN Rev. G
—
ABB Measurement & Analytics
We reserve the right to make technical changes or modify the contents of this document without
prior notice. With regard to purchase orders, the agreed particulars shall prevail.
ABB does not accept any responsibility whatsoever for potential errors or possible lack
of information in this document.
We reserve all rights in this document and in the subject matter and illustrations contained therein.
DS/PXX100-EN