DESIGN OF STRUCTURE
Construction of Community hall in Gollapudi of Vijayawada(R)(M)
SUPPORT REACTIONS
JOINT LOAD FORCE-X FORCE-Y FORCE-Z MOM-X MOM-Y MOM-Z
CASE
1 3 8.6 286.47 12.88 6.46 -0.26 -4.04
2 3 7.52 529.5 23.59 17.23 -0.44 -3.55
3 3 -9.64 1239.06 54.28 118.26 -1.13 15.08
4 3 1.73 1168.88 50.29 109.71 0.81 7.79
5 3 -3.88 475.49 22.51 16.41 0.51 2.07
6 3 -11.08 423.31 12.37 6.53 0.25 5.79
7 3 5.37 415.2 -2.93 -1.36 0.12 -2.15
8 3 61.52 1236.23 -0.32 31.3 -0.52 -29.79
9 3 -57.47 1125.19 -0.78 29.34 0.68 26.95
10 3 -6.49 613.67 -2.36 -0.78 0.19 2.48
11 3 4.15 407.43 -0.41 0.43 0.87 -8.65
12 3 0.65 614.19 0.04 1.23 -0.31 -1.47
13 3 4.24 423.65 0.61 1.18 -0.98 -8.46
14 3 -0.05 617.03 1.07 1.97 -0.08 -0.14
15 3 10.1 444.48 -0.92 0.03 -0.03 -4.99
16 3 -12.31 800.16 -19.09 -43.97 -1.27 7.64
17 3 5.09 424.06 4.18 1.59 -0.23 -2.19
18 3 4.32 1313.5 -38.49 -88.95 0.76 12.35
19 3 -0.69 1320.35 -38.13 -85.88 -1.04 12.42
20 3 -2.08 842.24 -14.8 -34.62 -0.97 1.69
21 3 -10.79 485.19 -6.2 -2.42 -0.21 5.81
22 3 24.35 380.83 -6.11 -2.52 -0.09 -12.22
23 3 -19.29 493.56 -12.69 -8.38 0.45 10.81
24 3 2.68 230.81 -15.56 -12.99 0.3 -0.95
25 3 -1.31 274.22 -14.65 -12.32 -0.16 1.11
26 3 -1.09 216.85 -7.72 -6.08 -0.3 0.93
27 3 -4.15 221.28 -0.66 -0.06 -0.22 2.51
DESIGN OF PILE CAPS----PC1(3,4,8,9,18,19)
I) Design Parametres:-
Concrete mix : M25
Steel : Fe500
Cover to Reinforcement : 50mm
Unit weight of RCC = 25.0KN/cum
Unit weight of Brick masonry = 19.0KN/cum
Characteristic compressive strength of concrete = 25.00N/sqmm
Yield strength of steel = 500N/sqmm
Bredth of column = 0.30m
Depth of column = a = 0.60m
Dia of pile = 0.375m
Factored load on column = P = 1320.25KN
II) Proportioning of pile cap:-
Factored load on the pile cap = 1320.25KN
Add for self weight of pile cap = 66.01KN
Total load = Pu = 1386.26KN
As per soil test report,safe load carrying capacity 375mm dia DUR piles
for 6.00m depth is = 260.00KN
Providing five piles,the load carrying capacity of the pile cap will be 1300.00KN
Hence,ultimate load carrying capacity of the pile cap after accounting for water table and 1462.50KN > Total
group action = load
Hence O.K
As per the above criteria,the proposed pile cap is as shown below:-
PC1
Z
375Ø DUR
3117
1 2
2085
1410
X 3 X
14
Critical Sections 4
10 5
for shear Critical Section
for bending about
X-axis
Critical Section
for bending about
Z-axis Z
III) Calculation of pile reactions:-
2 2
Load on 'i' th pile Pi = Q/n ± Mzxi/∑x ± Mxzi/∑z
where xi = Distance of pile from Z- axis
zi = Distance of pile from x- axis
a)Load Combination 3:-
Q = Ultimate load including self weight = 1386.26KN
∑x2 = Sum of squares of distances of all piles from x- axis = 5.96sqm
∑z2 = Sum of squares of distances of all piles from z- axis = 1.99sqm
Mx = Moment about x- axis 88.59KN-m
Mz = Moment about z- axis 12.59KN-m
Pu = Ultimate load carrying capacity of pile = 390.00KN
S.No Pile No. Q/n xi zi Pile reaction
1 P1 277.25 -1.221 0.705 306.06 SAFE
2 P2 277.25 1.221 0.705 311.21 SAFE
3 P3 277.25 0 0 277.25 SAFE
4 P4 277.25 -1.221 -0.705 243.29 SAFE
5 P5 277.25 1.221 -0.705 248.44 SAFE
All the pile reactions are safe.Hence the design of the pile cap is carried out for the pile cap
dimensions given below:-
The length of pile cap proposed = 3.117m
The width of pile cap proposed = 2.085m
Distance between c/c of piles = L = 1.41m
Shear span av = 0.940m
IV) Design for bending:-
a)For bending action about Z-axis:-
Pile Reactions contributing to bending moment & corresponding lever arm about critical section:-
S.No Pile No Pile reaction Lever arm Moment
1 P1 306.06 1.221 373.70
2 P4 277.25 1.221 338.52
712.22
S.No Pile No Pile reaction Lever arm Moment
1 P2 311.21 1.221 379.99
2 P5 248.44 1.221 303.35
683.34
The design bending moment about Z-axis = Muz = 712.22KN-m
Adopting Limit state method of design M u = 0.133 fckbd2
The effective depth of footing required = d = [Mu/(0.133fckb)]0.5
262.15mm
Over all depth required assuming 16mm dia bars = = 320.15mm
However assume 750mm over all depth,then effective depth comes to 690.00mm
The actual depth of neutral axis = 56.98mm
Area of steel required = 2458.14sqmm
No.of 20mm dia bars required = 7.83Nos
However No.of 20mm bars provided = 15Nos
Then the area of reinforcement provided = 4710.00sqmm
Percentage of reinforcement provided = 0.327
b)For bending action about x-axis:-
Pile Reactions contributing to bending moment & corresponding lever arm about critical section:-
S.No Pile No Pile reaction Lever arm Moment
1 P1 306.06 0.705 215.77
2 P2 311.21 0.705 219.40
435.17
S.No Pile No Pile reaction Lever arm Moment
1 P4 243.29 0.705 171.52
2 P5 248.44 0.705 175.15
346.67
The design bending moment about Z-axis = Muz = 435.17KN-m
Adopting Limit state method of design M u = 0.133 fckbd2
The effective depth of footing required = d = [Mu/(0.133fckb)]0.5
250.54mm
Over all depth required assuming 16mm dia bars = = 310.54mm
However assume 750mm over all depth,then effective depth comes to 690.00mm
The actual depth of neutral axis = 34.33mm
Area of steel required = 1480.79sqmm
No.of 16mm dia bars required = 7.37Nos
However No.of 16mm bars provided = 15Nos
Then the area of reinforcement provided = 3014.40sqmm
Percentage of reinforcement provided = 0.21
V) Design for Shear:-
a)Check for two way shear:-
The critical section for punching shear is located at d/2 from the face of the column.
Hence,perimetre of the punching area is = 4560.00mm
Punching shear stress = 0.42N/sqmm
Permissible punching shear stress = 0.25√fck = 1.25N/sqmm >0.42N/sqmm Hence safe.
b)Check for one-way shear:-
The critical section of one way shear is at a distance of 'd' from the face of the column
The Clause 34.2.4.2 of IS 456 – 2000 states the following:-
In computing the external shear or any section through a footing supported on
Piles, the entire reaction from any pile of diameter Dp whose centre is located
Dp/2 or more outside the section shall be assumed as producing shear on the
section; the reaction from any Pile whose centre is located Dp/2 or more inside
the section shall be assumed as producing no shear on the section. For
intermediate positions of the pile centre, the position of pile reaction to be
assumed as producing shear on the section shall be based on straight line
interpolation between full value at Dp/2 outside the section and zero value at
Dp/2 inside the section
Pile reactions contributing to one-way shear for the sections located at a distance 'd' from the face of column
Section Pile No Pile reaction
1 P1 306.06
P4 243.29
549.35
2 P2 311.21
P5 248.44
559.65
3 P1 55.0908
P2 56.0178
111.1086
4 P4 43.7922
P5 44.7192
88.5114
The critical shear force on the section = 559.65KN
Hence,the factored design shear force VFd = 559.65KN
Nominal shear stress Tv = 0.389N/sqmm <2.8 N/sqmm
(As per Table 20 of 1S 456)
Hence,the section is safe from shear point of view
The percentage area of the tensile reinforcement provided = 0.327%
The design shear strength of concrete for the above steel percentage from
Table 19 of IS 456 is 0.400 N/sqmm
As per clause 40.5.1 of IS 456:2000,the shear strength can be increased by 2d/a v times for the sections located
at a distance closer than 2d from concentrated load or face of support,where a v is the shear span
2d/av = 1.47
Hence,increased shear strength = 0.588 N/sqmm Hence Vuc = 845.93KN
0.588 >0.389
Hence,no shear reinforcement is required.
c) Check for Truss action:-
The shear span to depth ratio = av /d = 1.36 >0.60
Though,the truss action is not pre-dominant,the tensile reinforcement should be checked for horizontal tensile
force ' H ' resulting from truss action,because av /d ratio is not more than 2.
Hd=(Pu/2)[L/2-a/4]
H = Pu/8d[2L-a] = 557.52KN
Area of steel required to resist the above above tensile force A st = 1281.66sqmm
The tensile reinforcement provided is more than the above value.Hence O.K
d) Bursting steel:-
Generally 0.2 times tensile steel will be provided as bursting steel.
Hence,the bursting steel required = 942.00sqmm
Adopting 16mm rings,No.of rings required = 4.69
However,provide 5 Nos of 16mm dia rings as bursting steel.
DESIGN OF PILE CAPS----PC2(16,20)
I) Design Parametres:-
Concrete mix : M25
Steel : Fe500
Cover to Reinforcement : 75mm
Unit weight of RCC = 25.0KN/cum
Unit weight of Brick masonry = 19.0KN/cum
Characteristic compressive strength of concrete = 25.00N/sqmm
Yield strength of steel = 500N/sqmm
Bredth of column = b = 0.30m
Depth of column = a = 0.600m
Dia of pile = 0.375m
Factored load on column = P = 842.24KN
II) Proportioning of pile cap:-
Factored load on the pile cap = 842.24KN
Add self weight 84.22KN
Total load = Pu = 926.46KN
As per soil test report,safe load carrying capacity 375mm dia DUR piles
for 5.00m depth is = 230.00KN
As per clause 5.2.7.2 of IS:2911(Part III)-1980,the minimum spacing between the centre to centre of bored DUR
piles should not be less than 1.5Du.
Providing four piles,load carrying capacity of the pile cap after accounting for water table will be 690.00KN
690.00KN
Hence,ultimate load carrying capacity of the pile cap = 1035.00KN > Total load
Hence O.K
As per the above criteria,the proposed pile cap is as shown below:-
1.41
1.41
X X
Y
As such,the dimensions of the pile cap of as given below:-
The length of pile cap proposed = 2.085m
The width of pile cap proposed = 2.085m
Distance between c/c of piles = L = 1.410m
Depth of pile cap assumed = D = 0.650m
Effective depth = d = 0.565m
Shear span av = 0.405m
III) Depth of pile cap:-
a)For bending action about Y--Y direction:-
The ultimate bending moment on the pile cap = Mu = 2x(Pu/4)x[L/2-a/4] = 257.09KN-m
Adopting Limit state method of design Mu = 0.133 fckbd2
The effective depth of footing required = d = [Mu/(0.133fckb)]0.5
192.57mm
Over all depth required assuming 16mm dia bars = = 275.57mm
However assume 650mm overall depth,then the effective depth comes to 567.00mm
The actual depth of neutral axis = 24.61mm
Area of steel required = 1061.70sqmm
No.of 16mm dia bars required = 5.28Nos
Hence No.of 16mm dia bars to be provided within pile diametre = 13Nos
Then the area of reinforcement provided = 2612.48sqmm
Percentage of reinforcement provided = 0.221
b)For bending action about X--X direction:-
The ultimate bending moment on the pile cap = Mu = 2x(Pu/4)x[L/2-b/4] = 291.84KN-m
Adopting Limit state method of design Mu = 0.133 fckbd2
The effective depth of footing required = d = [Mu/(0.133fckb)]0.5
201.42mm
Over all depth required assuming 16mm dia bars = = 284.42mm
However assume 650mm overall depth,then the effective depth comes to 567.00mm
The actual depth of neutral axis = 28.01mm
Area of steel required = 1208.31sqmm
No.of 16mm dia bars required = 6.01Nos
Hence No.of 16mm dia bars to be provided within pile diametre = 13Nos
Then the area of reinforcement provided = 2612.48sqmm
Percentage of reinforcement provided = 0.221
c)Check for shear:-
The critical section of one way shear is at a distance of 'd' from the face of the column
Hence,the factored design shear force VFd = 463.23KN
Nominal shear stress Tv = 0.392N/sqmm <3.1 N/sqmm
(As per Table 20 of 1S 456)
Hence,the section is safe from shear point of view
The percentage area of the tensile reinforcement provided = 0.221%
The design shear strength of concrete for the above steel percentage from
Table 19 of IS 456 is 0.337 N/sqmm
As per clause 40.5.1 of IS 456:2000,the shear strength can be increased by 2d/a v times for the sections located
at a distance closer than 2d from concentrated load or face of support,where a v is the shear span
2d/av = 2.8
Hence,increased shear strength = 0.944 N/sqmm Hence Vuc = 1115.52KN
0.944 >0.392
Hence,no shear reinforcement is required.
c) Check for Truss action:-
The shear span to depth ratio = av/d = 0.71 >0.60
Though,the truss action is not pre-dominant,the tensile reinforcement should be checked for horizontal tensile force ' H '
resulting from truss action,because av/d ratio is not more than 2.
H = Pu/24Ld[3L2-b2] = 181.29KN
Area of steel required to resist the above above tensile force A st = 416.76sqmm
The tensile reinforcement provided is more than the above value.Hence O.K
d) Bursting steel:-
Generally 0.2 times tensile steel will be provided as bursting steel.
Hence,the bursting steel required = 522.50sqmm
Adopting 12mm rings,No.of rings required = 4.62
However,provide 5 Nos of 12mm dia rings as bursting steel.
DESIGN OF PILE CAPS----PC3(2,5,10,11,12,13,14,21)
I) Design Parametres:-
Concrete mix : M25
Steel : Fe500
Cover to Reinforcement : 75mm
Unit weight of RCC = 25.0KN/cum
Unit weight of Brick masonry = 19.0KN/cum
Characteristic compressive strength of concrete = 25.00N/sqmm
Yield strength of steel = 500N/sqmm
Bredth of column = b = 0.23m
Depth of column = a = 0.450m
Dia of pile = 0.375m
Factored load on column = P = 617.00KN
II) Proportioning of pile cap:-
Factored load on the pile cap = 617.00KN
Add for self weight of pile cap = 30.85KN
Total load = Pu = 647.85KN
As per soil test report,safe load carrying capacity 375mm dia DUR piles
for 5.00m depth is = 230.00KN
Hence,ultimate load carrying capacity of the 3 pile cap after accounting for water table = 776.25KN > Total load
Hence O.K
As per the above criteria,the proposed pile cap is as shown below:-
0.70
375mm Ø DUR
1
1.4
X X
2.09
As such,the dimensions of the pile cap of as given below:-
The length of pile cap proposed = 2.090m
The width of pile cap proposed = 1.910m
Distance between c/c of piles = L = 1.410m
Depth of pile cap assumed = D = 0.650m
Effective depth = d = 0.565m
Shear span av = 0.710m
III) Depth of pile cap:-
a)For bending action about Y--Y direction:-
The ultimate bending moment on the pile cap = Mu = (Pu/3)x0.71 = 153.32KN-m
Adopting Limit state method of design Mu = 0.133 fckbd2
The effective depth of footing required = d = [Mu/(0.133fckb)]0.5
155.38mm
Over all depth required assuming 16mm dia bars = = 238.38mm
However assume 650mm overall depth,then the effective depth comes to 567.00mm
The actual depth of neutral axis = 15.92mm
Area of steel required = 629.04sqmm
No.of 16mm dia bars required = 3.13Nos
Hence No.of 16mm dia bars to be provided within pile diametre = 10Nos
Then the area of reinforcement provided = 2009.60sqmm
Percentage of reinforcement provided = 0.186
b)For bending action about X--X direction:-
The ultimate bending moment on the pile cap = Mu = 2*(Pu/3)x0.41 = 177.08KN-m
The ultimate bending moment on the pile cap = Mu = (Pu/3)x0.71 = 153.32KN-m
Adopting Limit state method of design Mu = 0.133 fckbd2
The effective depth of footing required = d = [Mu/(0.133fckb)]0.5
155.38mm
Over all depth required assuming 16mm dia bars = = 238.38mm
However assume 750mm overall depth,then the effective depth comes to 567.00mm
The actual depth of neutral axis = 15.92mm
Area of steel required = 629.04sqmm
No.of 16mm dia bars required = 3.13Nos
Hence No.of 16mm dia bars to be provided within pile diametre = 10Nos
Then the area of reinforcement provided = 2009.60sqmm
Percentage of reinforcement provided = 0.186
c)Check for shear:-
The critical section of one way shear is at a distance of 'd' from the face of the column
Hence,the factored design shear force VFd = 431.90KN
Nominal shear stress Tv = 0.364N/sqmm <3.1 N/sqmm
(As per Table 20 of 1S 456)
Hence,the section is safe from shear point of view
The percentage area of the tensile reinforcement provided = 0.186%
The design shear strength of concrete for the above steel percentage from
Table 19 of IS 456 is 0.315 N/sqmm
As per clause 40.5.1 of IS 456:2000,the shear strength can be increased by 2d/a v times for the sections located
at a distance closer than 2d from concentrated load or face of support,where a v is the shear span
2d/av = 1.6
Hence,increased shear strength = 0.504 N/sqmm Hence Vuc = 545.82KN
0.504 >0.364
Hence,no shear reinforcement is required.
c) Check for Truss action:-
The shear span to depth ratio = av/d = 1.25 >0.60
Though,the truss action is not pre-dominant,the tensile reinforcement should be checked for horizontal tensile force ' H '
resulting from truss action,because av/d ratio is not more than 2.
H = Pu/24Ld[3L2-b2] = 127.57KN
Area of steel required to resist the above above tensile force A st = 293.26sqmm
The tensile reinforcement provided is more than the above value.Hence O.K
d) Bursting steel:-
Generally 0.2 times tensile steel will be provided as bursting steel.
Hence,the bursting steel required = 401.92sqmm
Adopting 12mm rings,No.of rings required = 3.56
However,provide 4 Nos of 12mm dia rings as bursting steel.
DESIGN OF PILE CAPS----PC4(6,15,22,23)
I) Design Parametres:-
Concrete mix : M25
Steel : Fe500
Cover to Reinforcement : 50mm
Unit weight of RCC = 25.0KN/cum
Unit weight of Brick masonry = 19.0KN/cum
Characteristic compressive strength of concrete = 25.00N/sqmm
Yield strength of steel = 500N/sqmm
Bredth of column = 0.23m
Depth of column = a = 0.38m
Dia of pile = 0.375m
Factored load on column = P = 493.56KN
II) Proportioning of pile cap:-
Factored load on the pile cap = 493.56KN
Add for self weight of pile cap = 24.68KN
Total load = Pu = 518.24KN
As per soil test report,safe load carrying capacity 375mm dia DUR piles
for 5.00m depth is = 230.00KN
Ultimate load carrying capacity of the pile cap after accounting for water table = 524.40KN > Total load
Hence O.K
As per the above criteria,the proposed pile cap is as shown below:-
375Ø DUR Piles
2.09
0.70
1.41
As such,the dimensions of the pile cap of as given below:-
The length of pile cap proposed = 2.09m
The width of pile cap proposed = 0.70m
Distance between c/c of piles = L = 1.41m
Shear span av = 0.710m
III) Depth of pile cap:-
a)For bending action:-
The ultimate bending moment on the pile cap = Mu = (Pu/2)x[L/2-a/4] = 150.84KN-m
Adopting Limit state method of design Mu = 0.133 fckbd2
The effective depth of footing required = d = [Mu/(0.133fckb)]0.5
254.57mm
Over all depth required assuming 16mm dia bars = = 314.57mm
However assume 750mm overall depth,then the effective depth comes to 690.00mm
The actual depth of neutral axis = 35.47mm
Area of steel required = 513.64sqmm
No.of 16mm dia bars required = 2.56Nos
Hence No.of 16mm dia bars to be provided within pile diametre = 6Nos
Then the area of reinforcement provided = 1205.76sqmm
Percentage of reinforcement provided = 0.25
b)Check for shear:-
The critical section of one way shear is at a distance of 'd' from the face of the column
Hence,the factored design shear force VFd = 246.78KN
Nominal shear stress Tv = 0.511N/sqmm <2.8 N/sqmm
(As per Table 20 of 1S 456)
Hence,the section is safe from shear point of view
The percentage area of the tensile reinforcement provided = 0.250%
The design shear strength of concrete for the above steel percentage from
Table 19 of IS 456 is 0.360 N/sqmm
As per clause 40.5.1 of IS 456:2000,the shear strength can be increased by 2d/a v times for the sections located
at a distance closer than 2d from concentrated load or face of support,where a v is the shear span
2d/av = 1.94
Hence,increased shear strength = 0.698 N/sqmm Hence Vuc = 337.33KN
0.698 >0.511
Hence,no shear reinforcement is required.
c) Check for Truss action:-
The shear span to depth ratio = av/d = 1.03 >0.60
Though,the truss action is not pre-dominant,the tensile reinforcement should be checked for horizontal tensile force ' H '
resulting from truss action,because av/d ratio is not more than 2.
Hd=(Pu/2)[L/2-a/4]
H = Pu/8d[2L-a] = 229.55KN
Area of steel required to resist the above above tensile force A st = 527.70sqmm
The tensile reinforcement provided is more than the above value.Hence O.K
d) Bursting steel:-
Generally 0.2 times tensile steel will be provided as bursting steel.
Hence,the bursting steel required = 241.15sqmm
Adopting 12mm rings,No.of rings required = 2.13
However,provide 4 Nos of 12mm dia rings as bursting steel.
DESIGN OF PILE CAPS----PC5(1,24,25,26,27)
I) Design Parametres:-
Concrete mix : M25
Steel : Fe500
Cover to Reinforcement : 50mm
Unit weight of RCC = 25.0KN/cum
Unit weight of Brick masonry = 19.0KN/cum
Characteristic compressive strength of concrete = 25.00N/sqmm
Yield strength of steel = 500N/sqmm
Bredth of column = 0.23m
Depth of column = a = 0.45m
Dia of pile = 0.300m
Factored load on column = P = 286.47KN
II) Proportioning of pile cap:-
Factored load on the pile cap = 286.47KN
Add for self weight of pile cap = 28.65KN
Total load = Pu = 315.12KN
As per soil test report,safe load carrying capacity 300mm dia DUR piles
for 5.00m depth is = 170.00KN
Hence,ultimate load carrying capacity of the pile cap after accounting for water table = 382.50KN > Total load
Hence O.K
As per the above criteria,the proposed pile cap is as shown below:-
300Ø DUR Piles
1.73
0.60
1.13
As such,the dimensions of the pile cap of as given below:-
The length of pile cap proposed = 1.73m
The width of pile cap proposed = 0.60m
Distance between c/c of piles = L = 1.13m
Shear span av = 0.560m
III) Depth of pile cap:-
a)For bending action:-
The ultimate bending moment on the pile cap = Mu = (Pu/2)x[L/2-a/4] = 64.81KN-m
Adopting Limit state method of design Mu = 0.133 fckbd2
The effective depth of footing required = d = [Mu/(0.133fckb)]0.5
180.24mm
Over all depth required assuming 16mm dia bars = = 240.24mm
However assume 600mm overall depth,then the effective depth comes to 540.00mm
The actual depth of neutral axis = 22.62mm
Area of steel required = 280.85sqmm
No.of 16mm dia bars required = 1.40Nos
Hence No.of 16mm dia bars to be provided within pile diametre = 5Nos
Then the area of reinforcement provided = 1004.80sqmm
Percentage of reinforcement provided = 0.31
b)Check for shear:-
The critical section of one way shear is at a distance of 'd' from the face of the column
Hence,the factored design shear force VFd = 143.24KN
Nominal shear stress Tv = 0.442N/sqmm <2.8 N/sqmm
(As per Table 20 of 1S 456)
Hence,the section is safe from shear point of view
The percentage area of the tensile reinforcement provided = 0.310%
The design shear strength of concrete for the above steel percentage from
Table 19 of IS 456 is 0.391 N/sqmm
As per clause 40.5.1 of IS 456:2000,the shear strength can be increased by 2d/a v times for the sections located
at a distance closer than 2d from concentrated load or face of support,where a v is the shear span
2d/av = 1.93
Hence,increased shear strength = 0.755 N/sqmm Hence Vuc = 244.50KN
0.755 >0.442
Hence,no shear reinforcement is required.
c) Check for Truss action:-
The shear span to depth ratio = av/d = 1.04 >0.60
Though,the truss action is not pre-dominant,the tensile reinforcement should be checked for horizontal tensile force ' H '
resulting from truss action,because av/d ratio is not more than 2.
Hd=(Pu/2)[L/2-a/4]
H = Pu/8d[2L-a] = 132.03KN
Area of steel required to resist the above above tensile force A st = 303.52sqmm
The tensile reinforcement provided is more than the above value.Hence O.K
d) Bursting steel:-
Generally 0.2 times tensile steel will be provided as bursting steel.
Hence,the bursting steel required = 200.96sqmm
Adopting 12mm rings,No.of rings required = 1.78
However,provide 4 Nos of 12mm dia rings as bursting steel.
DESIGN OF ONE WAY SLAB:-
Design Parametres:-
Unit weight of RCC = 25KN/cum
Concrete mix : M25
Steel : Fe500
Cover to Reinforcement : 25mm
Characteristic compressive strength of concrete = 25N/sqmm
Yield strength of steel = 500N/sqmm
Item Slab panel Description
S1
Length of slab panel ly in m 14.75
Width of slab panel lx in m 2.44
ly/lx 6.05
Overall depth required in mm 94
Width of slab panel considered 'b' in 1.00
'm'
Depth provided 'D' in 'm' 0.135
Dia.of bars assumed 8mm
Dead load in KN/sqm 4.375
Live load in KN/sqm 4.00
Floor finishes in KN/sqm 1.00
Total Load in KN/sqm 9.375
Design Moment Me1(-)ve in KN-m 8.37
Effective depth for balanced section 55.08
in 'mm'
Effective depth provided 'd' in 'mm' 106
Actual depth of neutral axis 'xu' in 9.1
'mm'
Maximum depth of neutral axis 'xumax' 50.88
in 'mm'
Area of steel required Ast in 'mm2' 188.36
Main Steel provided at continuous 8mm@175
edge mm c/c
Area of steel provided in mm2 287.09
Dist. Steel provided at continuous 8mm@200
edge mm c/c
Area of steel provided in mm2 251.2
DESIGN OF TWO WAY SLAB:-
Design Parametres:-
Unit weight of RCC = 25KN/cum
Concrete mix M25
Steel Fe500
Cover to Reinforcement 25mm
Characteristic compressive strength of concrete = 25N/sqmm
Yield strength of steel = 500N/sqmm
Item Slab panel Description
S2(End Panel)--
Two adjacent
edges
discontinuous
Length of slab panel ly in m 4.59
Width of slab panel lx in m 3.36
ly/lx 1.37
Overall depth required in mm 105
Width of slab panel considered 'b' in 'm' 1.00
Depth provided 'D' in 'm' 0.135
Dia.of bars assumed 8mm
Dead load in KN/sqm 4.375
Live load in KN/sqm 4.00
Floor finishes in KN/sqm 1.00
Total Load in KN/sqm 9.38
Short span(-) moment coefficient at continuous edge 0.071
Short span(-) moment at continuous edge 7.51
Short span(+) moment coefficient at mid span 0.053
Short span(+) moment at mid span 5.61
Long span(-) moment coefficient at continuous edge 0.047
Long span(-) moment at continuous edge 4.97
Long span(+) moment coefficient at mid span 0.035
Long span(+) moment at mid span 3.70
Design Moment Me1(-)ve in KN-m 11.27
Effective depth for balanced section in 'mm' 58.18
Effective depth provided 'd' in 'mm' 106
Actual depth of neutral axis 'xu' in 'mm' 12.43
Maximum depth of neutral axis 'xumax' in 'mm' 48.76
Area of steel required Ast in 'mm2' 257.12
Main Steel provided at continuous edge 8mm@150mm c/c
Area of steel provided in mm2 334.93
Design Moment Me1(+)ve in KN-m 8.41
Effective depth for balanced section in 'mm' 50.27
Actual depth of neutral axis 'xu' in 'mm' 9.15
Maximum depth of neutral axis 'xumax' in 'mm' 48.76
Area of steel required Ast in 'mm2' 189.35
Main Steel provided at mid span 8mm@150mm c/c
Area of steel provided in mm2 334.93
Design Moment Me1(-)ve in KN-m(Long span) 7.46
Effective depth for balanced section in 'mm' 47.34
Actual depth of neutral axis 'xu' in 'mm' 8.08
Maximum depth of neutral axis 'xumax' in 'mm' 48.76
Area of steel required Ast in 'mm2' 167.18
Dist. Steel provided at continuous edge 8mm@175mm c/c
Area of steel provided in mm2 287.09
Dist.steel at mid span 8mm@175mm c/c