Energies 15 08026 v2
Energies 15 08026 v2
Review
Fault Ride-Through Operation Analysis of Doubly Fed
Induction Generator-Based Wind Energy Conversion Systems:
A Comparative Review
Aftab Ahmed Ansari * and Giribabu Dyanamina
Department of Electrical Engineering, Maulana Azad National Institute of Technology, Bhopal 462003, India
* Correspondence: [email protected] or [email protected]
Abstract: In present electrical power systems, wind energy conversion systems based on doubly fed
induction generators represent one of the most commonly accepted systems in the global market
due to their excellent performance under different power system operations. The high wind energy
penetration rate makes it challenging for these wind turbines to follow grid code requirements. All
operations of a wind energy system during a dip in voltage require special attention; these operations
are critically known as fault ride-through and low voltage ride-through. In this paper, various fault
ride-through techniques of doubly fed induction generator-based wind energy conversion systems,
such as protective circuitry, reactive power injection, and control methods for transient and steady
state operations, have been presented to improve the performance. During system disturbances,
protective circuitry or control mechanisms are typically used to limit the over-current of the rotor
and the generated inappropriate DC link over-voltage. Simultaneously, the reactive power injection
system overcomes the reactive power scarcity and enhances the transient response, further limiting
the DC bus voltage and rotor current. This review paper compares and suggests appropriate FRT
methods that are driven by external modifications and internal system improvements. Furthermore,
Citation: Ansari, A.A.; Dyanamina, typical case studies are discussed to illustrate and support the FRT system. The impact of each
G. Fault Ride-Through Operation
case study was evaluated and analyzed using the results obtained from the MATLAB/Simulink
Analysis of Doubly Fed Induction
application and the OPAL-RT (OP4500) real time simulator (RTS).
Generator-Based Wind Energy
Conversion Systems: A Comparative
Keywords: doubly fed induction generator (DFIG); fault ride-through; renewable energy system;
Review. Energies 2022, 15, 8026.
wind energy conversion (WEC) system
https://doi.org/10.3390/en15218026
Energies 2022, 15, 8026 Figure 1. The fundamental structure of a wind power generation network. 2 of 33
Figure 1, a WEC system consists of a wind turbine, gearbox/drivetrain, power converter,
and generator or transformer [2].
For windfarms, there are two different operating technologies: one th
speed wind farms and another that uses variable-speed wind farms. Previo
farm could only generate at a fixed rotational speed; thisGridwas called a fixe
Kinetic
Energy Wind Turbine system.
Gearbox
After some time, variable-speed
Generator Power Converter
WEC systems emerged,
Transformer Power Grid
with num
over fixed-speed WEC systems,
(Optional) including the ability to adjust speed i
(Optional)
changes
Mechanical Energyin wind speeds. This reduces wear
Electrical and tear on the tower, gearb
Energy
Figuredrive
1. The
Figure
train
1. The
components
fundamental
fundamental structure
structureof
and alsopower
ofaawind
wind power
increases
generation
generation
the efficiency. In addition, the
network.
network.
crease energy productivity, lowering power variations input to the grid [3].
ForFor
from windfarms,
windfarms,
variable-speed thereare
there aretwotwodifferent
generators different operating
operating
is usually technologies:
fedtechnologies:
to the network oneone that uses
that
via afixed-
uses fixed- ele
power
speed wind farms and another that uses variable-speed
speed wind farms and another that uses variable-speed wind farms. Previously, the wind wind farms. Previously, the wind
(PES),
farm couldwhich not only
only generate at aimproves
fixed rotational dynamic
speed; this and was steady-state
called a fixed-speed performance
WEC bu
farm could only generate at a fixed rotational speed; this was called a fixed-speed WEC
the After
system.
system.
speedAfterof turbines
some and wind generators.
time, variable-speed WEC systems emerged, It can also
some time, variable-speed WEC systems emerged, with numerous benefits
withisolate
numerous thebenefits
generator fr
over fixed-speed WEC systems, including the ability to adjust speed in response to changes
overinnetwork
fixed-speed at the instance ofincluding
a grid fault. thetheThe only adjustdownside of variable-speed
wind speeds.WEC systems,
This reduces wear and tear on ability
tower, to gearbox, and speed
otherindrive response
train to
is that
changes
components they
in wind andmay
also incur
speeds. This additional
increases reduces wear
the efficiency. costs
and and
tear on
In addition, losses in thegearbox,
the tower,
these systems PES
increase [4,5].
and other
energy
drive trainThe
productivity, components and also increases the efficiency.
two most well-known generators used in variable-speed configur
lowering power variations input to the grid [3]. In addition,
Electric power these
from systems
variable- in-
crease
speedenergy
turbines productivity,
generators is usuallylowering
are doubly fed to thepower
fed network
induction variations
via a power
generators input to the grid
electronic
(DFIG) system
and [3].(PES),
Electricwhich
synchronous power ge
fromnot only improvesgenerators
variable-speed dynamic and steady-state
is usually fed to performance
the network but viaalso controls
a power the speedsystem
electronic of
With partial-scale
turbines and wind PES, DFIG-based
generators. It can also isolate wind
the powerfrom
generator systemsthe dominate
power network the
at indu
(PES), which not only improves dynamic and steady-state performance but also controls
system
the
the speed
instance developed
of a grid fault.
of turbines and windbyThe DFIG only has gained
downside
generators. widespread
of variable-speed
It can also
WECacceptance
isolate the generator fromand
systems is that is now th
they
the power
may incur additional costs and losses in the PES [4,5].
usedatconfiguration.
network the instance of a grid Thefault.DFIG Thesystem employs
only downside ofavariable-speed
back-to-back WECconverter,
systems as
The two most well-known generators used in variable-speed configurations of wind
2. they
is that Themay
turbines stator-windings
are incur additional
doubly fed induction of the
costs and DFIG
generators losses are
in the
(DFIG) straightforwardly
and PES [4,5].
synchronous generatorscoupled (SG). to th
The
With two most
partial-scale well-known
PES, DFIG-based generators
wind used
whereas the rotor-windings have two partially rated back-to-back
power in variable-speed
systems dominate theconfigurations
industry. The of power
WEC wind e
turbines
system developed by DFIG has gained widespread acceptance and is now the most widely(SG).
are doubly fed induction generators (DFIG) and synchronous generators
verters (PEC) known as the rotor-side PEC (RSPEC) and the grid-side PEC
Withused
partial-scale
configuration. PES,The DFIG-based
DFIG system wind power
employs systems dominate
a back-to-back converter, theasindustry.
seen in Figure The 2.WEC
system
frequency
The stator-windings
developed
and magnitude
by DFIGof thehas
DFIG areof
gained
current in the
straightforwardly
widespread acceptance
rotortoand
coupled windings
the ispower
nowgrid,
canwhereas
the most
be widely
easily co
this
usedthe configuration,
rotor-windings
configuration. have
The DFIGand
two it also
partially
system allows
rated
employs for a power
back-to-back largeelectronic
a back-to-back range of
converter, changes
converters
as seen (PEC) in rotor
in Figure
known
creased as the rotor-side
wind energy PEC (RSPEC) and the grid-side PEC (GSPEC). The frequency and
2. The stator-windings of theabsorption capability. Thecoupled
DFIG are straightforwardly DFIG’stopower the power output,
grid, rot
magnitude of current in the rotor windings can be easily controlled using this configuration,
whereas
torque the rotor-windings have at two partially rated back-to-back power electronic con- cu
and it alsocanallowsbeforregulated
a large range synchronous
of changes in rotorspeeds speed and byincreased
managing wind the energy rotor
verters
RSPEC.(PEC) capability.
absorption known
The asThe
theDFIG’s
converter’s rotor-side
rated
power PEC
power (RSPEC)
output, and the
is usually
rotor speed, and grid-side
only
torque 30% canPECof (GSPEC).
the
be regulated at The
generator’s
frequency
synchronous and magnitude of current in the rotor windings can be easily controlled using
method isspeeds by managingfrom
advantageous the rotor current
a cost with the RSPEC.
perspective. TheThe converter’s
main rated
disadvantage is
this power
configuration, and 30%
is usually only it also allows
of the for a large
generator’s power, range
so thisofmethod
changes in rotor speed
is advantageous from anda in-
ity perspective.
creased
cost to grid
wind voltage
energy The main disturbances
absorption capability.
disadvantage issuch
The
its as harmonic
DFIG’s
vulnerability power
to grid distortions,
output,
voltagerotor grid and
speed,
disturbances faults
torqueinstability
such canas harmonic [5,6].
be regulated Many
distortions, countries expect
grid faults,speeds
at synchronous and networkbyDFIG WECthe
instability
managing systems
[5,6].
rotor Many to countries
currentbe ablewith tothewith
expect
RSPEC. DFIG
fluctuations, WEC
The converter’s systems
which rated to
has be able
resulted
power to withstand
in a only
is usually voltage
systematic fluctuations,
30% of the plan which
for dealing
generator’s has resulted
power, with DFIG
so this
in a systematic plan for dealing with DFIG disturbances.
method is advantageous from a cost perspective. The main disadvantage is its vulnerabil-
ity to grid voltage disturbances such as harmonic distortions, grid faults, and network
instability [5,6]. Many countries expect DFIG WEC systems to be able to withstand voltage
fluctuations, which has resulted in a systematic plan for dealing with DFIG disturbances.
DFIG Grid
Transformer
Gearbox
Transformer
Gearbox
RSPEC GSPEC
Figure
Figure 2. WEC System
2. WEC with a partial-scale
System converter andconverter
with a partial-scale DFIG. and DFIG.
The critical issue of the DFIG-based WEC systems is the inefficiency when grid voltage
drops due to external short-circuit failures and active power generation decreases, resulting
in a rapid rise in rotor current to compensate for the reduced active power of the RSPEC. As
a result, the PEC boosts the voltage in the rotor windings, which raises the voltage above
its level, causing internal magnetization to decrease according to the voltage reduction.
Demagnetization results in higher output currents on both the rotor and stator circuits,
which exceed the converter ratings. This contributes to the tripping of a WEC system from
the grid. This unexpected change in wind generation units indicates the instability of the
utility system. Some specific criteria have been dictated by the grid code for overcoming the
above scenario, known as FRT systems. These include high-voltage ride-through (HVRT),
low-voltage ride-through (LVRT), and zero-voltage ride-through (ZVRT). The specifications
in the LVRT and ZVRT are generally similar, with grid faults resulting in the voltage of the
grid being zero in the ZVRT profile and the voltage of the grid in the LVRT profile being
15–25% of the nominal value [6]. Grid codes need to address FRT issues to make sure that
turbines and PECs can work safely.
Several nations have conducted research on the FRT of the WEC systems. These
systems are required to sustain grid connectivity and inject reactive power during outages.
WEC system voltage terminals are frequently vulnerable to voltage sag as a result of a grid
fault. Since the WEC system has been completely disconnected from the grid through the
PEC, the generator will not “see” the voltage drop but will have an indirect effect on it.
As a consequence, the converter tests the system’s FRT functionality. This paper explores
how the DFIG WEC system operates during fault-riding tactics, which includes better
control mechanisms as well as modified hardware solutions. To incorporate the DFIG FRT
techniques, improved control schemes are often implemented using software modifications,
while specialized hardware devices employ additional circuits to support the DFIG WEC
system for tolerating voltages. A basic review of the different methodologies for dealing
with the FRT specifications is illustrated in Section 4. While two kinds of control solutions
for FRT systems are possible, one is an external control solution and the other is an internal
control solution. External solutions are viewed as the implementation of modules that have
been modified to alter the converter’s design. For the latest WEC system implementation,
internal control modification-based FRT options have been selected. They are less costly
and do not require any additional hardware parts, but they add complexity to the system.
One of the most widely used external-based methods for enabling FRT functionality
is the crowbar [7]. It is used to shield the RSPEC from damage by shorting the terminals
of the rotor. This technique, however, converts the DFIG to a Self-Excited Induction
Generator (SEIG), requiring reactive-power support from the grid network and thereby
causing grid voltage stability to suffer. In [8,9], chopper topology and capacitors are used
to stabilize the DC connection voltage. This approach dissipates excess power through
the DC connection, resulting in a smoother voltage profile. A bridge type l fault-current
limiter [10] and dynamic brake resistor [11] are two other strategies suggested for limiting
stator- and rotor-side overcurrent. References [11,12] showed a dynamic voltage restorer
(DVR) and a PEC connected in series as ways to limit the voltage level of the stator
when there is a grid fault. It is also recommended to use FACTS devices as a means to
improve DFIG LVRT capabilities [13]. During grid disturbances, these systems provide
additional reactive power to the power network (grid) and support the restoration of grid
voltage. Ref. [14] addresses the effects of wind energy’s uniqueness by relating to traditional
power generation effectiveness and the reliability of the power grid and suggests simple
strategies for enhancing large-scale wind energy penetration into the electrical system.
In [15], a series grid-side converter handles the voltage output efficiently, allowing it to
successfully cope with distinct conditions of deep voltage drop by discarding DC-transients
and negative magnetic flux elements. A superconducting fault current limiter (SFCL) is a
self-healing mechanism, as no controlling intervention is required in order to move from
super-conducting to non-superconducting states. Internal controls are standard control
systems because they are less expensive and do not need any extra hardware, but they add
Energies 2022, 15, 8026 4 of 33
complexity to DFIG. Pitch control, hysteresis control, modified vector control, and feed
transient control (FTC) are examples of internal controls. Other control approaches that
have been implemented recently include sliding mode control, fuzzy dependent control,
and model predictive control (MPC). In pursuit of the above facts stated, the following are
some notable and contributing features of this paper:
• The technical specifications and restrictions in various nations’ international grid-code
requirements for the WEC system are summarized.
• The present study also includes a precise mathematical model of the DFIG-based
WEC system.
• Different FRT strategies with detailed illustrations and explanations at different op-
erations are noted, presenting the benefits and drawbacks of implementing them to
improve the transient response of wind turbines based on DFIG.
• The paper also presents a comparative study of different FRT schemes and validates
their ability during transient operation.
• Real-time simulator (RTS) and MATLAB/Simulink application results are also used to
assess and investigate a case study.
Furthermore, this article is arranged into the following sections: Section 2 defines the
need for a grid code, while Section 3 discusses the mathematical modelling of DFIG. Section 4
addresses a review of the FRT schemes. Section 5 discusses the simulation study. Section 6
discusses the RTS results. Finally, the conclusions and recommendations are outlined.
1.2
HVRT Limit
Line
1.1
Normal Operation
0.9
Time(ms)
Figure 3. Requirements
Figure for voltage
3. Requirements forride-through in accordance with
voltage ride-through the E. ON regulation.
in accordance with the E. ON regulation.
The specifications of the grid code vary by country/region and system. The level of
penetration of wind energy and the grid’s durability are both affected by these variations
in requirements [17]. Table 1 lists the aforementioned technical specifications and re-
strictions in the International Grid Codes (GCs) of different nations. Table 1 lists the fre-
quency, LVRT, HVRT, and power factor limits of several international nations under the
Energies 2022, 15, 8026 5 of 33
The specifications of the grid code vary by country/region and system. The level of
penetration of wind energy and the grid’s durability are both affected by these variations in
requirements [17]. Table 1 lists the aforementioned technical specifications and restrictions
in the International Grid Codes (GCs) of different nations. Table 1 lists the frequency, LVRT,
HVRT, and power factor limits of several international nations under the fault and after the
fault conditions [18].
LVRT HVRT
Country F (hz) Frequency Limits Max. Time Duration Power Factor
During Fault/Post-Fault During Fault
Vmin. Tmax. Vmin. Tmax. Vmax. Tmax.
Lag Lead
(p.u) (s) (p.u) (s) (p.u) (s)
47.5 < flim < 52.048 Continuous
49.0 < flim < 51.0 10 min
Australia 50 0 0.10 0.7 2.0 1.3 0.06 0.95 0.95
48.0 < flim < 51.0 2 min
47.5 < flim < 52.0 9s
49.0 < flim < 50.5 Continuous
48.5 < flim < 51.5 30 min
Germany 50 0 0.15 0.85 1.0 - - 0.9 0.95
47.5 < flim < 51.5 10 min
46.5 < flim < 53.5 10 s
48.5 < flim < 51.0 Continuous
48.0 < flim < 51.0 25 min
Denmark 50 0.20 0.50 0.90 1.5 1.2 0.1 0.95 0.95
47.5 < flim < 52.0 5 min
47.0 < flim < 52.0 10 s
49.5< flim < 50.5 Continuous
India 50 0.15 0.30 0.85 3.0 1.3 0.2 - -
47.5 < flim < 51.5 WEC system remains connected
59.4 < flim < 60.6 Continuous
58.5 < flim < 61.5 11 min
Canada 60 57.5 < flim < 61.7 1.5 min 0.0 0.15 0.85 1.0 - - 0.90 0.95
56.5 < flim < 61.7 2s
55.5 < flim < 61.7 0.35 s
60.0 < flim < 59.5 Continuous
USA 60 59.5 < flim < 59.3 10 min 0.0 0.15 0.90 1.75 1.20 1 0.95 0.95
59.3 < flim < 58.7 10 s
50 47.5 < flim < 52.0 Continuous
UK 0.15 0.14 0.80 1.21 - - 0.95 0.95
47.0 < flim < 52.0 20 s
49.5 < flim < 50.2 Continuous
China 50 0.2 0.625 0.9 2.0 1.3 0.5 0.95 0.95
47.15 < flim < 51.5 10 min
handle at an average speed. The wind farm’s mechanical energy and the rotor’s torque are
represented by the following expressions [19].
1
Tm = þCt (λ)πVw2 R3 ( Nm) (1)
2
1
Pm = þC p (λ, β)πR2 Vw3 (W ) (2)
2
where R is the radius of the wind turbine rotor, þ is the density of air, and Vw is the wind
velocity. Cp is the power coefficient determined by the wind turbine’s parameters, and it is
provided by Equation (3). It is determined by the tip speed ratio (λ), the pitch angle (β) of
the turbine, and the gamma function (Γ).
1
C p (λ, β) = Γ − 0.02β2 − 5.6 e−0.17Γ (3)
2
2πRnr
λ= (4)
60VW
where nr is the speed at which the turbine rotor is rotating. The relationship between Cp
and Ct is
C (λ, β)
Ct (λ) = P (5)
λ
R(3600)
Γ= (6)
λ(1609)
where Ct is the torque coefficient.
The following is a formulation of the real and reactive power of the stator:
pM
Tem = (i ∅qs − iqr ∅ds ) (17)
Ls dr
From the above discussion, this article summarizes the various FRT strategies for improv-
ing the transient response of the DFIG-based wind energy system. FRT techniques for the
Energies 2022, 15, 8026 8 of 33
DFIG WEC system can be divided into two components, as shown in Figure 4: external
retrofit-based FRT techniques and internal control modification-based control techniques.
Fault CLs
Series Grid-Side
Converter
Figure
Figure 4.
4. FRT
FRT Techniques of DFIG-based
Techniques of DFIG-based WEC
WEC systems.
systems.
4.2. External
Crowbar Retrofit-Based FRT Techniques
activation causes the RSPECfor andDFIG
wind turbine (WT) to lose control over their
ability to control
External active, reactive
retrofit-based FRTpowers
techniquesover are
a period of time.
modules thatThe
haveissue with
been this technique
modified to alter
is that the DFIG-WEC system begins to operate as a reactive power consumption
the converter’s design, and they can be categorized into two sections: protection circuit- unit, such
as an induction motor, resulting in a loss of grid voltage. So,
oriented FRT techniques and reactive power injection-oriented FRT techniques.to overcome the limitations
imposed by the crowbar installation, an improved model of the crowbar arrangement is
proposed, which
Protection will be presented
Circuit-Oriented in the next section, which can ensure the concern of real
FRT Techniques
and reactive
The protection circuit-oriented FRT the
power control. In addition, crowbarare
techniques circuit incorporated
presented as some active and
passive compensators, a crowbar coordination concept with series dynamic resistance, and
(a) Crowbar
a crowbar with Circuit
a DC link chopper. These newer crowbar techniques attempt to reduce
The Crowbar
operating time and Circuit
try toisprevent
one of theDFIG most extensively
from acting asutilized methods
SEIG [25]. The of resolving
research the
in [26]
FRT problemadvancements
investigates [23,24]. As caninbe theseen
LVRT in Figure 5. It involves
effectiveness of DFIGa architecture,
set of resistances
with installed
the rotor
on the slip-ring
crowbar of the
taking grid rotor-sideinto
impedance with the help
account. of semiconductor
In addition to this, theswitches to bypass
mathematical the
concept
RSPEC. Its general basic operation is explained as follows: RSPEC
for the crowbar resistance, taking into account the grid impedance, is also determined. gate signals are
switched
Furthermore,off atTable
the voltage
2 gives adip (for example,
comparative three-phase
analysis faults),
of different and the
crowbar rotor rings
circuitries for are
the
LVRT enhancement of DFIG.
dynamic resistance, and a crowbar with a DC link chopper. These newer crowbar tech-
niques attempt to reduce operating time and try to prevent DFIG from acting as SEIG [25].
The research in [26] investigates advancements in the LVRT effectiveness of DFIG archi-
tecture, with the rotor crowbar taking grid impedance into account. In addition to this,
the mathematical concept for the crowbar resistance, taking into account the grid imped-
Energies 2022, 15, 8026 9 of 33
ance, is also determined. Furthermore, Table 2 gives a comparative analysis of different
crowbar circuitries for the LVRT enhancement of DFIG.
To
The Grid
Rotor
DFIG
Shaft
Ifrotor
X
Ifrotor
Irotor
s RSPEC DC- Link
F +
S2 S1 Cdc To The
Irspec GSPEC
-
Icrw Rcrw
To
The Grid
Rotor
DFIG
Shaft
Ifr X
Icrw Irotor
N
RSPEC DC- Link
C
+
Zseries s
S2 S1 Cdc To The
GSPEC
Irsc -
Icrw Rnpscrw
Stator
Rotor Generator Bus Coupling Transformer
DFIG
RSPEC Vdc GSPEC PCC Grid
Shaft DC
AC
DC AC Grid filter
Rotor filter
Figure
Figure 7.7.Conventional
Conventional DC chopper
DC chopper protectionprotection circuit for
circuit for DFIG-based WECDFIG-based
systems. WEC systems.
(d) Series dynamic braking resistor (SDBR) control scheme
(d) Series dynamic braking resistor (SDBR) control scheme
A series connection of power electronic switches and series dynamic resistors con-
nergies 2022, 15, x FOR PEER REVIEW
A toseries
nected connection
the stator of power
or rotor terminal electronic
forms SDBR. SDBR is switches and series
a series topology dynamic r
that is asso-
ciated with the stator terminal. The circuit depicted in Figure 8 is ideal for extreme fault
nected to the stator or rotor terminal forms SDBR. SDBR is a series topology
situations due to its high-power output and low residual voltage.
ciated with the stator terminal. The circuit depicted in Figure 8 is ideal for e
situations Bypass Switch
Stator dueGenerator
to its high-power
Bus
output andCoupling
low residual voltage.
Transformer
Rotor
DFIG
SDBR
PCC
Shaft RSPEC Vdc GSPEC
AC
DC
DC AC
Grid filter
8.SDBR
Figure 8.
Figure SDBRProtection CircuitCircuit
Protection for DFIG-based WEC systems.WEC systems.
for DFIG-based
SDBR is distinguished from the crowbar by its circuitry structure. Although SDBR
SDBR
has the is distinguished
advantage from magnitude,
of regulating current the crowbar by its circuitry
the DCLINK structure.
chopper/crowbar is Alth
shunt-connected and controls voltage. Furthermore, the high
has the advantage of regulating current magnitude, the DCLINK choppe voltage in the SDBR method
is shared by resistance due to its structure of the series. As a result, the induced overvoltage
shunt-connected
cannot result in a loss andof controls
control over voltage. Furthermore,
the converter. The SDBR the highregulates
not only voltagethein the S
isovervoltage
shared by resistance
of the rotor, whichdue to result
might its structure
in the RSPECof losing
the series.
control, As a also
but it result, the induc
strongly
restricts the high current of the rotor. Additionally, by restricting
age cannot result in a loss of control over the converter. The SDBR not only the rotor current, the
charging current of the DC bus capacitor can also be brought down. Furthermore, the
overvoltage
SBDR could manage of thetherotor,
DFIG’swhich might
real power, resultthe
improving inwind
the generator’s
RSPEC losing stabilitycontro
strongly restricts
in the event theAdditionally,
of a fault. high current of the
during rotor.drop,
a voltage Additionally, by restricting
the SDBR improves the t
generator output, decreasing its increased speed. This impact will
rent, the charging current of the DC bus capacitor can also be brought down. F enhance the DFIG
system’s and wind farm’s post-fault recovery, as the SDBR regulates and improves the
the SBDR could manage the DFIG’s real power, improving the wind generat
in the event of a fault. Additionally, during a voltage drop, the SDBR impro
erator output, decreasing its increased speed. This impact will enhance the D
and wind farm’s post-fault recovery, as the SDBR regulates and improves the
in the event of a fault. Additionally, during a voltage drop, the SDBR improves th
erator output, decreasing its increased speed. This impact will enhance the DFIG sy
and wind farm’s post-fault recovery, as the SDBR regulates and improves the accele
Energies 2022, 15, 8026 speed of the rotor during grid disturbance [31]. The mathematical formulation 11 of 33 of th
current is developed in [32] using the SDBR and constant converter current regulati
analytical analysis of the LVRT transient is conducted in order to characterize the
effect. Focusing
acceleration speedon anrotor
of the index integrating
during the DFIG’s
grid disturbance capacities
[31]. The to offer
mathematical active power
formulation
of the fault current is developed in [32] using the SDBR and constant converter current
tance and reduce electromagnetic torque oscillation, the resistance of the SDBR is opti
regulation. An analytical analysis of the LVRT transient is conducted in order to characterize
(e) Modulated
the LVRT series DBR
effect. Focusing (MSDBR)
on an index integrating the DFIG’s capacities to offer active
powerInassistance and reduce
[33], a braking electromagnetic
resistor torque oscillation,
that is comparable the resistance
to both single- of the multi-step
and SDBR b
is optimized.
resistors is described. It is based on modulated series DBR (MSDBR) technology. Th
(e) Modulated series DBR (MSDBR)
trol scheme is applied to maintain the desired terminal voltage to be consistent
presenceIn [33],
ofaboth
braking resistor that
balanced andis unbalanced
comparable to voltage
both single- and multi-step
drops. Restoring braking
the stator v
resistors is described. It is based on modulated series DBR (MSDBR) technology. This
helps GSPEC and RSPEC maintain controllability to avoid DC bus overvoltage, rot
control scheme is applied to maintain the desired terminal voltage to be consistent in the
tor short-circuit
presence current,
of both balanced andand DC busvoltage
unbalanced capacitor
drops.overload.
Restoring theAsstator
a result,
voltageno extra pro
helps
devices,
GSPEC and such as a maintain
RSPEC DC-chopper, crowbar,
controllability or rotor
to avoid DC busbraking resistance,
overvoltage, are require
rotor/stator
short-circuit operation
continuous current, and ofDC bus capacitor
a generator overload.
facility As a result,
improves no extraresponse
the voltage protectiveduring
devices,period.
covery such asThe
a DC-chopper,
MSDBR module, crowbar, asor rotor
shown braking resistance,
in Figure are required.
9, is made The antise
up of two
continuous operation of a generator facility improves the voltage response during the
sulated
recoverybipolar
period. gate transistors
The MSDBR module,thatasare
shownconnected
in Figure in each
9, is madephase
up of parallel to the brak
two antiseries
sistor. Thebipolar
insulated statorgate
voltage controller’s
transistors that are PWM
connectedsignals independently
in each phase parallel toregulate the voltage
the braking-
stator. Restoring
resistor. The statorthe stator’s
voltage voltage
controller’s causes
PWM theindependently
signals GSPEC and regulate
RSPECthe components
voltage of of the
the stator. Restoring the stator’s voltage causes the GSPEC and
to compensate for the voltage and current overload caused by the direct RSPEC components of current
the lin
circuit to compensate for the voltage and current overload caused by the direct current link.
MSDBR
Stator Generator Bus Coupling Transformer
Rotor
DFIG
RSPEC Vdc GSPEC PCC
AC DC
DC AC Grid filter
Rotor filter
9. MSDBR
Figure 9.
Figure MSDBRprotection circuit
protection for DFIG-based
circuit WEC systems.
for DFIG-based WEC systems.
(f) Fault CLs
Another type of protective approach employed for boosting the FRT capabilities of
DFIG-oriented WEC systems is the use of Fault Current Limiters (FCLs). The fault current
level is limited by a three-phase FCL, which includes an isolation transformer and a high-
DC inductance with bypass-resistance situated on the DFIG stator-side [34]. To improve
the transient stability of the DFIG, a number of fault current limiter variations have been
developed, and future research is ongoing on these limiters. However, FCLs are superior
to the crowbar and dynamic braking resistor concept in terms of performance. Figure 10
illustrates all of the FCLs that were used to improve the FRT capacity of the DFIG.
FCL arrangements can be classified into two groups based on their impedance type and
component arrangement. There are four types of FCLs based on their impedance: resistive,
inductive, resistive-inductive, and resonance. Another classification exists depending on
whether a superconductor is employed or not. The FCLs can be classified as either solid-
state or saturated core transformers based on their component type. The FCL is located in
different positions of the DFIG to increase the FRT capacity of the DFIG. In each position,
the impact on the key-parameters of the DFIG is related to the FCL impedance type. From
the perspective of positioning, the FCL is mainly located at the terminal and stator ends of
the DFIG. There are some FCLs on the end of the rotor and some other configurations on
the DC link. Further, from the perspective of impedance, the FCL is mainly resistive, as
seen in Figure 10 [35].
either solid-state or saturated core transformers based on their component type. The FCL
is located in different positions of the DFIG to increase the FRT capacity of the DFIG. In
each position, the impact on the key-parameters of the DFIG is related to the FCL imped-
ance type. From the perspective of positioning, the FCL is mainly located at the terminal
and stator ends of the DFIG. There are some FCLs on the end of the rotor and some other
Energies 2022, 15, 8026 12 of 33
configurations on the DC link. Further, from the perspective of impedance, the FCL is
mainly resistive, as seen in Figure 10 [35].
Fault Current
Limiting Device
Non Superconducting
Superconducting FCL
FCL
Inductive-Resistive Type
FCL: Optimized Located Inductive Type FCL: Active SFCL
with Reactive Power Injection
Figure 10.10.
Figure FCL classification
FCL forfor
classification DFIG-based WEC
DFIG-based systems.
WEC systems.
ESS
Figure 11. ESS protection circuit for DFIG-based WEC systems.
ESS
(h) Series Grid-Side Converter
Figure 11. ESS protection circuit for DFIG-based WEC systems.
Figure 11. ESS protection circuit for DFIG-based WEC systems.
The Series Grid-Side Converter (SGSC), seen in Figure 12, is a two-way power
(h) Series Grid-Side Converter
conductor
(h) Seriesconverter
Grid-Sidelinked across the DC link. The SGSC controls the voltage by d
Converter
ing or The Series
consuming Grid-Side Converter
real power in(SGSC), seento
an effort in manage
Figure 12,the
is a two-way
DC12, link power semi-
The
conductor Series Grid-Side
converter Converter
linked across (SGSC),
the DC link. The SGSCseen in Figure
controls the voltage avoltage.
isby two-way The
delivering
SGS
power
another
conductor function
or consuming
that compensates
converter
real powerlinked across
in an effort
stator
the
to manageDC harmonic
thelink.
voltages
Thevoltage.
DC link SGSC by harvesting
controls
The SGSC has theanother
voltagethebyhar
d
voltage
function content.
that SGSC
compensates injects
stator series
harmoniccompensation
voltages by voltage
harvesting to
the
ing or consuming real power in an effort to manage the DC link voltage. The SGS compensate
harmonic for
voltage the inf
of negative
content.
another sequence
SGSC
function thatgrid
injects series voltage bystator
compensation
compensates balancing
voltage tothe
harmonicvoltage
compensate for
voltages of by
the
the stator.
influence
harvestingAdditional
of
the har
negative
flux of sequence
the stator grid
can voltage
also beby balancing
regulated the
or voltage of
controlled the stator.
by SGSCAdditionally, the
serial-voltage flux injectio
voltage content. SGSC injects series compensation voltage to compensate for the inf
of the stator can also be regulated or controlled by SGSC serial-voltage injection [41].
of negative sequence grid voltage by balancing the voltage of the stator. Additiona
Stator Generator Bus be regulated or controlled
flux of the stator
Rotor can also by SGSC serial-voltage injectio
Coupling Transformer
DFIG
Stator Generator Bus
Pstator
Rotor SGSC Coupling Transformer
PCC
Shaft
DFIG
Protor
RSPEC GSPEC
Vdc Ptotal
DC PGSC
AC
DC AC
Rotor filter RSPEC Vdc GSPEC
DC PGSC
AC
Figure 12. SGSC Protection Circuit for DFIG-based WEC
AC systems.
DC
Rotor filter
To improve the utilization of SGSC, [41] proposes a resonant adaptive controller.
Even in the presence of voltage imbalances throughout the switch network grid, hybrid
controllers maintain a constant voltage on the stator. The DFIG-single WT’s parallel-group-
side corrector (PGSR) and SGSC architectural features are demonstrated in [42]. These
technologies have been integrated and are attempting to share the same DC bus. PGSR
supplies power to the circuit of the rotor during synchronous operation. To ensure the
generator voltage never exceeds the nominal value, the SGSC maintains the optimal range
of the stator flux. Table 2 concludes with a comparative analysis of FRT techniques based
on protection circuits.
Energies 2022, 15, 8026 14 of 33
• Enhances the transitional dynamics and transient • Battery system performance and
power network stability of the generator maintenance challenges
g. ESS [37–40] • Controls the active output power at the • Self-discharge is a waste of stored energy, as it is
steady-state mode. inactive during operation.
DFIG
Shaft Pstator Grid
RSPEC GSPEC
Vdc
AC DC Vdc
DC AC
Rotor Grid filter Vdc
filter
DVR
Figure 13.DVR
Figure 13. DVR circuit
circuit for DFIG-based
for DFIG-based WEC systems.
WEC systems.
In [44], distinct DVR configurations are evaluated in terms of voltage and power
In [44],
ratings. distinct
The control DVRcentered
systems configurations arecontrollers
on resonant evaluated areinaddressed
terms ofinvoltage
[45,46] inand pow
ings.
order The control systems
to compensate centeredvoltages.
for non-symmetric on resonant
Ref. [47]controllers areuse
investigates the addressed
of a DVR to in [45,46
der to compensate for non-symmetric voltages. Ref. [47] investigates the use of a D
enable the uninterrupted fault ride-through of voltage sags that meet GC requirements. [40]
describes
enable theuninterrupted
the development of afaultbuilt-in DVR with an energy
ride-through storagesags
of voltage system (ESS)
that meetfor wind
GC require
farms based on DFIG. A Vanadium Redox Flow battery (VRF) is integrated into the DFIG
[40] describes the development of a built-in DVR with an energy storage system (E
back-to-back PWM converter in parallel with the DC connection capacitor. Through the
wind farms DC-DC
bidirectional based converter,
on DFIG.the A ESS
Vanadium Redox
output charges theFlow battery
DC link (VRF)
capacitor. is integrated i
In addition,
DFIG
the DVRback-to-back
receives powerPWM fromconverter in parallel
the same capacitor. Thewith the DCconverter
DC-TO-DC connection capacitor. Th
maintains
a constant voltage on the DC link. A further solution for optimizing
the bidirectional DC-DC converter, the ESS output charges the DC link capacitor. the efficiency and I
performance of the DVR is explored in [48]. It uses a new asymmetrical multilevel inverter
tion, the DVR receives power from the same capacitor. The DC-TO-DC converter
(MLI) centered on a Level Creator and an H-bridge inverter: an improved configuration
tains
of theaFCL
constant
DVR forvoltage
grid andon DFIGthesupport
DC link. A further
during solution
fault currents for by
induced optimizing
significant the eff
and performance of the DVR is explored in [48]. It uses a new
voltage sags. The appropriate parameters for the construction of a fault current-limitingasymmetrical mu
inverter
dynamic (MLI)
voltage centered
restorer foron
DFIGa Level
systemsCreator and an examined
are thoroughly H-bridgeininverter:
[49]. an improved
(b) Static VAR Compensator (SVC)
Since the early 1970s, the SVC has been the most important component of FACTS
devices. It is made up of traditional thyristors, which operate at a faster rate than me-
chanically switched conventional devices and necessitate more sophisticated controllers.
Shunt-connected SVC stands for reactive power generators or absorbers. By providing a
controlled capacitive current or inductive current output, it can ensure the voltage level
stability of the associated bus. The SVC DFIG is shown in Figure 14. SVC is a combination
of a Thyristor Controlled Reactor (TCR) and a Thyristor Switched Capacitor (TSC). The TCR
uses the control of the firing angle to continually decrease or increase inductive-current,
although, in TSR, the attached inductors can be cut in and out step-by-step, eliminating the
need to continuously control the firing angle [50]. Improving dynamic voltage manage-
ment, thereby improving system load capacity and dampening system oscillations, may
be one of the key reasons for installing SVC [51]. SVC will also be able to increase power
transfer in the event of faults by holding the generator acceleration down and vice versa.
This decreases the effect of the operational failure on the capacity of the generator to remain
synchronous. The current SVCs are of varying susceptibility characteristics [52]. The
traditional technology of SVCs is losing its effectiveness because of a low surge capability,
a poor dynamic efficiency, poor response speeds, etc.
crease power transfer in the event of faults by holding the generator
and vice versa. This decreases the effect of the operational failure on
generator to remain synchronous. The current SVCs are of varying sus
teristics [52]. The traditional technology of SVCs is losing its effectivene
Energies 2022, 15, 8026 16 of 33
surge capability, a poor dynamic efficiency, poor response speeds, etc.
TCR TSC
Figure 14.
Figure 14. SVC
SVC circuit
circuit for DFIG-based
for DFIG-based WEC systems.WEC systems.
DFIG
Vdc
VSI
4.4. Future Research Ideas on WEC System Transient Stability Employing External Retrofitting
The aforementioned protection-based strategies focus on either LVRT enhancement
or reactive power adjustment. The employment of PECs in WEC systems leads to the
decoupling of sources from loads, which exacerbates inertia issues in the power system. It
is the imbalance in power that occurs as a result of grid disturbances that is responsible for
the quickening or slowing of the rotor speed. Most of the studies that have been conducted
in this field have followed one of two main lines of thought: the first line of thought
concentrates on improving the LVRT in order to prevent the destruction or disconnection
of the WEC system by limiting the amount of inrush current that occurs during a fault,
and the second line of thought is predicated on the idea that frequency stability can be
improved either during or after a fault. Virtual Synchronous Generator (VSG) and virtual
impedance approaches are utilized to ensure the system’s stability [58]. These two strategies
need to be developed collaboratively. Consequently, the increase in FRT capabilities by
the introduction of virtual inertia is an exciting research topic. As a result, an emerging
research approach in the field of DFIG WEC systems is an improved inertia control strategy
with external retrofits for LVRT improvement. This combinational strategy can meet the
kinetic energy needs in inadequate conditions. In a similar way, FACTS devices can also
effectively enhance LVRT by introducing or absorbing reactive power into the network. At
the same time, this should also be about improving frequency stability during emergencies
and frequency management when things are running normally.
control loop, thus improving the ability to control the transient current and minimize the
ripple in torque caused by faults at the grid. The DQ transformation angle is given by a
three-phase phase lock loop (PLL) based on a synchronous reference frame with the q-axis
tied to the positive sequence stator voltage. Two FFTC functional blocks are added to the
traditional vector control technique to improve it.
(b) Model predictive control
Model predictive control (MPC) has grown in popularity as a potential alternative
to modern control technology because it is centered on a system model to forecast the
controlled variables’ future behavior, follows optimization standards and implementation
plans at each sampling moment, and achieves the optimal control response. There are two
main factors that classify the prediction algorithms of all AC drives: the pre-calculated
duration (called the prediction range) and the method used to generate the reference signal.
Some controllers take the inverter’s discrete function, which is considered to compute the
switching states directly without employing pulse width modulation (PWM); this is known
as a finite control set (FCS). Other schemes route control signals through some modulator,
such as PWM, and are referred to as continuous control set topologies (CCS). The FCS MPC
selects switching states by considering the discrete operation of the inverters and thus does
not employ any modulation scheme. This control analyzes all possible switching scenarios
and chooses the first one that meets the specified convergence criterion. As a result, the
optimization approach is significantly easier than the one used in the CCS-MPC. The CCS-
MPC optimizes the inverter by considering its average model, with the goal of reducing
the error between the predicted signal and the reference signal. The controller’s output in
this case is the reference duty cycles, which are fed to the modulation technique [60,61].
In [62], the FCS-MPC algorithm used to increase the potential of DFIG LVRT in variable
speed WEC systems is discussed. This algorithm uses the inertia of the doubly fed induction
generator’s rotor to maintain the excess energy during a sag in the grid’s voltage. The
simulation results show that the operational control scheme is suitable for ensuring the safe
LVRT of the DFIG-based WEC system and an active and reactive power generation unit
while also meeting grid code standards. Because of the simplicity of the suggested control
scheme, which requires no additional hardware, it outperforms traditional approaches in
terms of performance and grid reliability enhancements, such as typical crowbar protection.
In [63], a time-effective FCS-MPC strategy for DFIG systems has been presented. The
switching state of the RSPEC is used directly as a control input in this strategy. This enables
the converter to carry out optimized control actions directly. Additionally, MPC-based
studies for LVRT potential in DFIGs have not yet been explored.
(c) Sliding mode control
Sliding mode control (SMC) is a powerful, stable, and highly nonlinear system control
mechanism. SMC is characterized by its robust performance, quick convergence speed, and
easy implementation characteristics [64]. The SMC design concepts and their applications
for drive systems were first suggested in [65]. It offers quick implementation, the rejection
of disruption, robustness, and a quick response, but the controlled condition may exhibit
undesired chattering. Due to their robust external disturbances and non-linear dynamics
of WEC systems and generators, several second-order SMC methods in aerodynamic
control and power converter control in renewable energy applications have been proposed
in [66,67]. In [66], a robust control sliding mode was proposed in order to regulate power
generation in wind generators at variable speeds. This can ensure the consistency and
stability of the two operating areas, including high-speed and low-speed areas. The sliding
mode control algorithms proposed in [68] for converters on the rotor end and on the grid
end can let the WT run and operate effectively during uneven grid voltage conditions. They
are also easy to use and do not require positive and negative voltage or current sequences
for decomposition. Weakening high frequency chattering has always been a key problem
in conventional sliding mode monitoring which needs to be studied and resolved. By
Energies 2022, 15, 8026 20 of 33
using this method, the efficiency of the control strategy has been established. However, the
scenario with an unknown control direction remains unexplored.
(d) Fuzzy logic controller
The wind turbine converter topologies are conventionally controlled by PI controllers.
PI controllers, however, provide less robustness and require precise knowledge of the
dynamic model parameters for tuning. To tackle this limitation, a Fuzzy Logic Controller
(FLC) is introduced. In a variety of ways, fuzzy logic is being used effectively to control
DFIGs-based WTs. Fuzzy logic is used in [69] to manage both active and reactive energy
production. A fuzzy-logic gain modulator was employed in [70] to properly regulate
the speed of the generator in order to maximize the overall power production while also
controlling real and reactive power generation via rotor side control schemes. In [71],
a neuro fuzzy PI-gain scheduler with a VC technique is introduced to make the system
respond faster, settle down faster, and not make steady-state errors. Furthermore, it
compares the efficiency and effectiveness of the DFIG system to that of a traditional PI
controller. In [72], the introduction of an effective control scheme for the grid-connected
DFIG with interval type-2 fuzzy sets (DFIG) with a vector control technique is presented;
the DFIG is suitable for dealing with irregularities in the operating conditions of distributed
systems, such as the fault, load variations, and wind velocity. The controller’s output
is evaluated by integrating it to an IEEE 34-bus test sample and accounting for multiple
uncertainties. While the type-1 FLC can handle nonlinearity in the system, the type-2 FLC is
far more efficient at dealing with system uncertainties. As a conclusion, these concepts open
up a new field of application for the use of fuzzy control to enhance the FRT capabilities of
DFIG using both active and passive techniques.
(e) Other advanced control
Numerous new advanced techniques and modelling methodologies have been sug-
gested to investigate and address DFIG’s LVRT capacity. Newly proposed approaches
include the SMES based on FLC in [73] and the series-linked current source converter-
dependent SMES in [74], which enhances the DFIG’s LVRT performance. An adaptive
learning control approach for WEC systems with DFIGs is presented in [75]. The DFIG-
LVRT WT’s performance will also be improved with heightened state-feedback predictive
control, as presented in [76]. In [77], a novel controlled DFIG-WT crowbar is presented for
fault-level mitigation using an adaptive neurofuzzy inference system. The study in [78]
introduces a fuzzy-based technique for wind velocity prediction in Maximum Power Point
Tracking (MPPT) configurations within normal circumstances and a coordinated Genetic
Algorithm-based Active-Reactive (GA-PQ) controller incorporating a DC chopper in the
FRT technique during grid failures. A transient reconfiguring approach for the DFIG
is presented and studied in [79] in order to improve its LVRT capacity. It is based on a
modified rotor-voltage-reference technique. Ref. [80] provides an enhanced FRT system
for a WEC system equipped with a DFIG that is based on proper stator voltage regulation
and is capable of addressing symmetrical, unsymmetrical, and unbalanced grid voltage
drops. This is achieved by using a correctly adapted topology of the standard WEC system
with the DFIG, which allows the stator voltage to be regulated through the rotor power
converters system.
A new robust fractional-order supertwisting sliding mode control was developed and
suggested in [81] for supercapacitor-based power supplies in order to maintain a constant
and smooth DC voltage and to rapidly improve the FRT and PQ capabilities of DFIG-based
wind turbines. The frequency variation induced by the voltage dip is addressed in [82]
using a P-Q coordination-based LVRT control technique for wind farms. By using an offline
look-up table technique, the suggested strategy may adaptively deliver the active and
reactive reference currents, thereby reducing the absence of active power generation and
speeding up active power recovery during the LVRT interval. The study in [83] proposes a
cooperative strategy using Virtual Inertia Control (VIC) and a redesigned GSPEC for Low-
Voltage Ride-Through (LVRT) in order to meet Grid Code Requirements while also offering
Energies 2022, 15, 8026 21 of 33
frequency support to the grid via synthetic inertia. Table 4 concludes with a comparative
analysis of FRT techniques based on internal control modification-based control techniques
for DFIGs.
Table 4. Comparative analysis of internal control modification-based control techniques for DFIGs.
• Complex control.
• The torque pulsation produced by the negative sequence current
a. FFTCC [59] • Input voltage sensor is required.
is reduced by the effective control of the transient current.
• Sluggish response.
• Costly.
• Complicated.
d. Fuzzy-basedcontrol [70] • Trifling transient overshoot using fuzzy methods.
• More power consumption.
• Poor time response.
4.6. Future Research Ideas on WEC System Transient Stability Employing Control Mechanisms
This subsection focuses on modern or advanced control methods for LVRT system
improvement. Concerning the DFIG WEC system, strategies must also concentrate on low-
inertia challenges. Incorporating a traditional Virtual Synchronous Generator (VSG) loop into
an RSPEC topology can improve the system’s frequency stability, but combining this with a
strategy to limit the current can enhance the voltage while keeping the frequency stable.
5. Simulation Study
In this section, a case study was conducted using the specialized power system analysis
tool named Matlab/Simulink application to strengthen the credibility of the aforementioned
analysis. This section develops a comprehensive DFIG mechanism model to demonstrate
the protection system’s performance and reviews the insights with the help of a control
strategy field-oriented control to simulate the behavior of a doubly fed generator in the
context of a three-phase grid voltage drop. In addition to the theoretical study presented, a
simulation study of a 9 MW WEC system comprised of six 1.5 MW wind turbines integrated
into a 25 kV distribution network exports power to 120 kV wind turbines equipped with
a DFIG which are composed of a wound rotor induction generator and an AC/DC/AC
PWM converter based on an IGBT module. While the stator winding is directly connected
to the 60 Hz grid, the rotor is fed at a variable frequency via the AC/DC/AC converter.
set in the following manner. Whenever the current of the rotor surpasses 1.5 times the
rated current, the RSPEC is short-circuited and is subsequently rendered ineffective. The
DFIG mechanism with rotor crowbar protectors is shown in Figure 16b. At time t = 3 s, the
structure identifies stator-voltage losses, which triggers the crowbar protection and stops
the RSPEC. Figure 16b shows the current of the crowbar resistance, which goes up sharply
and then quickly goes down as time passes. The higher the resistance of the crowbar,
the faster the current of the crowbar attenuation. The crowbar resistor has a significant
inhibitory impact on the rotor and stator fault currents, which are now limited within
the DFIG system’s permissible limits. In comparison to the scenario without protection,
the circuit with crowbar safety can rapidly resume stable functioning again when the
voltage returns to normal. Figure 16b also shows that the DC link voltage was significantly
decreased with crowbar shielding, particularly in comparison to Figure 16a.
5.3. DFIG Performance Analysis with Rotor Series Dynamic Breaking Resistance
(RSDBR) Protection
In this method, the dynamic resistance is connected in series with the rotor, and its
structure is similar to the SDBR used to limit the stator and rotor over the current at the
stator end of the generator set. It is controlled by a power semiconductor switch. Under
normal operating conditions, the switch is activated, and the resistance is bypassed. During
a system disturbance, the switch is disabled, and a resistor is inserted in the rotor winding
in series. The RSDBR has the peculiar benefit of being able to directly control the current.
In addition, due to the series configuration of the RSDBR, the high voltage is shared by the
resistance, so the induced excessive voltage will not cause the failure of RSPEC control,
and it will also limit excessive rotor current. Figure 16c shows the simulation results of the
DFIG with rotor resistance protection. At time t = 3 s, the RSDBR configuration recognizes
the stator voltage loss, thus activating the resistance protection system without stopping
the RSPEC. The three-phase current of the rotor is greater than 2 p.u. when there is no
protection system. Figure 16c shows that the RSDBR method effectively suppresses the
rotor’s three-phase current within 2 pu, indicating that the fault ride-through capability
is significantly better than that of no protection. The simulation results in Figure 16c also
demonstrate the efficacy of the RSDBR method by limiting the stator three-phase current
and limiting the variability of the DC bus voltage to less than 1.2 times the rated value,
ensuring that the converter is not harmed.
Table 5 of this report also provides a comparative analysis of several circuits for the
DFIG’s LVRT improvement.
S.No LVRT Strategy Rotor Current RSPEC Status DC Link Voltage Remark(S)
Crowbar Circuit [24,84]
a. Limited To < 2.0 Blocked Limits To < 1. 35p.U Effective For Symmetrical Faults
(Figure 16)
b. DC Link Chopper [8] No Change Maintained Limits To < 1. 05p.U Effective For All Types of Faults
Crowbar Integrated with DC
c. Reduced To < 2.0 Blocked Limits To < 1. 35p.u Effective For All Types of Faults
Link Chopper [84]
d. RSDBR Circuit (Figure 16) [85] Reduced To < 1.59 Maintained Limits To < 1. 15p.u Effective For All Types of Faults
Crowbar Integrated with Series
e. Reduced To < 2.0 Partially Maintained Limits To < 1. 35p.u Effective For All Types of Faults
R–L [27]
f. DVR [47] Reduced To < 2.0 Partially Maintained Limits To < 1. 25p.u Effective For All Types of Faults
GWinstek GDS-1104B
OPAL-RT 4500 DSO
Communications Host PC
Lines
This technique (RSDBR) utilizes a dynamic resistor in series with the rotor to decrease
the rotor and stator overcurrent in a DFIG-based WEC system. Figure 20 shows the RTS
findings for the DFIG with rotor resistance protection. The RSDBR configuration detects a
stator voltage decrease and activates the resistance security mechanism without interfering
with the RSPEC. As shown in Figure 20c, the RSDBR technique effectively reduces the
stator and rotor’s three-phase current within 2 pu, indicating that the fault ride-through
capability is significantly greater than that without protection. RSDBR also eliminates the
significant torque variation associated with fault initiation. The simulation results and RTS
results further show that the RSDBR technique is effective in reducing converter damage
findings for the DFIG with rotor resistance protection. The RSDBR configuration detects
a stator voltage decrease and activates the resistance security mechanism without inter-
fering with the RSPEC. As shown in Figure 20c, the RSDBR technique effectively reduces
the stator and rotor’s three-phase current within 2 pu, indicating that the fault ride-
Energies 2022, 15, 8026 through capability is significantly greater than that without protection. RSDBR also25elim- of 33
inates the significant torque variation associated with fault initiation. The simulation re-
sults and RTS results further show that the RSDBR technique is effective in reducing con-
verter
by damage
regulating bystator
the regulating the stator
three-phase three-phase
current current
and limiting the and limiting
DC bus thevariability
voltage DC bus volt-to
age variability to less than 1.2
less than 1.2 times the rated value.times the rated value.
(a) (b)
(c) (d)
Pre-Fault During Fault Post-Fault
Pre-Fault During Fault Post-Fault
(e) (f)
(g)
Figure18.
Figure 18. Real-time
Real-time simulator
simulator (RTS)
(RTS) results
results demonstrating
demonstrating the
the performance
performanceof ofDFIG-based
DFIG-basedWECWEC
systems without protection: (a) stator voltage; (b) stator current; (c) rotor current; (d) DC link volt-
systems without protection: (a) stator voltage; (b) stator current; (c) rotor current; (d) DC link voltage;
age; (e) active power; (f) reactive power; (g) torque.
(e) active power; (f) reactive power; (g) torque.
(g)
Energies 2022, 15, 8026 Figure 18. Real-time simulator (RTS) results demonstrating the performance of DFIG-based26 WEC
of 33
systems without protection: (a) stator voltage; (b) stator current; (c) rotor current; (d) DC link volt-
age; (e) active power; (f) reactive power; (g) torque.
(a) (b)
Pre-Fault Post-Fault
Pre-Fault During Fault Post-Fault
During Fault
(c) (d)
(e) (f)
(g)
Figure 19. Real-time simulator (RTS) results demonstrating the performance of DFIG-based WEC
Figure 19. Real-time simulator (RTS) results demonstrating the performance of DFIG-based WEC
systems with crowbar protection: (a) crowbar current; (b) stator current; (c) rotor current; (d) DC
systems with crowbar protection: (a) crowbar current; (b) stator current; (c) rotor current; (d) DC link
link voltage; (e) active power; (f) reactive power; (g) torque.
voltage; (e) active power; (f) reactive power; (g) torque.
Energies 2022, 15, 8026 Figure 19. Real-time simulator (RTS) results demonstrating the performance of DFIG-based27 WEC
of 33
systems with crowbar protection: (a) crowbar current; (b) stator current; (c) rotor current; (d) DC
link voltage; (e) active power; (f) reactive power; (g) torque.
(a) (b)
(c) (d)
Pre-Fault During Fault Post-Fault
(e) (f)
(g)
Figure20.
Figure 20. Real-time
Real-time simulator
simulator (RTS)
(RTS)results
resultsdemonstrating
demonstrating the
theperformance
performance ofofDFIG-based
DFIG-basedWEC
WEC
systems with RSDBR protection; (a) stator voltage; (b) stator current; (c) rotor current; (d) DC
systems with RSDBR protection; (a) stator voltage; (b) stator current; (c) rotor current; (d) DC link
link voltage; (e) active power; (f) reactive power;
voltage; (e) active power; (f) reactive power; (g) torque. (g) torque.
7.7.Comparison
Comparisonof ofthe
thePerformance
PerformanceofofSimulated
SimulatedTechniques
Techniques
The
Thecrowbar
crowbarandandRSDBR
RSDBRprotection
protectiontechniques
techniquesare
arecompared
comparedininterms
termsofof
their simula-
their simu-
tion and
lation andreal-time
real-timesimulator results.
simulator results.InInorder
ordertotoensure
ensurethe
thecomparability
comparabilityof ofthe
theresearch
research
results, the crowbar protection circuit and RSDBR are connected and withdrawn at the
same time. Figures 13–20 respectively illustrate the transient response of a DFIG with
RSDBR and crowbar protection under fault conditions. The reactive power consumed by
the crowbar protection mechanism is greater than the reactive power consumed by the
Energies 2022, 15, 8026 28 of 33
results, the crowbar protection circuit and RSDBR are connected and withdrawn at the
same time. Figures 13–20 respectively illustrate the transient response of a DFIG with
RSDBR and crowbar protection under fault conditions. The reactive power consumed by
the crowbar protection mechanism is greater than the reactive power consumed by the
rotor series resistance mechanism. This is due to the fact that the DFIG remains control-
lable and capable of generating reactive power with RSDBR. As a result, it appears that
RSDBR protection has a significant advantage in terms of grid voltage restoration. When
the crowbar is switched on, its peak torque is significantly greater than the RSDBR, but
when it is switched off, its peak torque is less than the RSDBR. This can cause large torque
fluctuations in the crowbar, as shown in Figures 13 and 20.
Figures 13–20 also illustrates that the peak of the rotor and the stator transient current
waveforms in the crowbar during fault initiation are significantly bigger than those of
the RSDBR. As a result, the effect of the RSDBR is significantly smaller than that of the
crowbar, particularly during start-up. It is possible to conclude that RSDBR scheme is
slightly superior to the other scheme.
Author Contributions: The authors confirm contribution to the paper as follows: study conception
and design: A.A.A., G.D.; data collection: A.A.A.; analysis and interpretation of results: A.A.A., G.D.;
draft manuscript preparation: A.A.A. All authors have read and agreed to the published version of
the manuscript.
Funding: This research received no external funding.
Institutional Review Board Statement: Not applicable.
Informed Consent Statement: Not applicable.
Data Availability Statement: Not applicable.
Acknowledgments: This research did not receive any specific grant from funding agencies in the
public, commercial, or not-for-profit sectors.
Conflicts of Interest: The authors declare no conflict of interest.
Nomenclature
Vw Wind speed (m/s) ids: iqs d–q components of the stator current
R Radius of the rotor in meters ∅ds ,∅qs d–q components of the stator flux
þ Air density in kg/m3 vdr , vqr d–q components of the rotor voltage
Cp (λ, β) Power coefficient idr , iqr d–q components of the rotor current
λ Tip speed ratio of the turbine blade ∅dr , ∅qr d–q components of the rotor flux
β Pitch angle in degrees R s , Rr Stator and rotor resistance
Γ Gamma function Ls , Lr Stator and rotor inductance
Pm Mechanical active power in watts M Mutual inductance
Tm Mechanical torque Tem Electrical torque
nr Rotational speed of the turbine rotor s Slip
ωs Synchronous electrical speed p Pole pairs
ω re Rotor’s electrical speed Ps Stator real power.
vds , vqs d–q components of the stator voltage Qs Stator reactive power.
Energies 2022, 15, 8026 30 of 33
References
1. Global Wind Report 2021—Global Wind Energy Council. Available online: https://gwec.net/global-wind-report-2021/ (accessed
on 18 May 2022).
2. Bhowmik, S.; Spee, R.; Enslin, J. Performance optimization for doubly fed wind power generation systems. IEEE Trans. Ind. Appl.
1999, 35, 949–958. [CrossRef]
3. Carrasco, J.M.; Franquelo, L.G.; Bialasiewicz, J.T.; Galvan, E.; PortilloGuisado, R.; Prats, M.A.M.; Leon, J.I.; Moreno-Alfonso, N.
Power-electronic systems for the grid integration of renewable energy sources: A survey. IEEE Trans. Ind. Electron. 2004, 53,
1002–1016. [CrossRef]
4. Ansari, A.A.; Dyanamina, G. Comparative analysis of controlling methods for doubly fed induction generator based wind energy
system. Lect. Notes Electr. Eng. 2022, 852, 493–507. [CrossRef]
5. Ekanayake, J.; Jenkins, N. Comparison of the response of doubly fed and fixed-speed induction generator wind turbines to
changes in network frequency. IEEE Trans. Energy Convers. 2004, 19, 800–802. [CrossRef]
6. Yaramasu, V.; Wu, B.; Sen, P.C.; Kouro, S.; Narimani, M. High-power wind energy conversion systems: State-of-the-art and
emerging technologies. Proc. IEEE 2015, 103, 740–788. [CrossRef]
7. Pannell, G.; Atkinson, D.J.; Zahawi, B. Minimum-threshold crowbar for a fault-ride-through grid-code-compliant DFIG wind
turbine. IEEE Trans. Energy Convers. 2010, 25, 750–759. [CrossRef]
8. Pannell, G.; Zahawi, B.; Atkinson, D.J.; Missailidis, P. Evaluation of the performance of a DC-link brake chopper as a DFIG
low-voltage fault-ride-through device. IEEE Trans. Energy Convers. 2013, 28, 535–542. [CrossRef]
9. Huchel, L.; El Moursi, M.S.; Zeineldin, H.H. A parallel capacitor control strategy for enhanced FRT capability of DFIG. IEEE
Trans. Sustain. Energy 2014, 6, 303–312. [CrossRef]
10. Guo, W.; Xiao, L.; Dai, S.; Xu, X.; Li, Y.; Wang, Y. Evaluation of the performance of BTFCLs for enhancing LVRT capability of
DFIG. IEEE Trans. Power Electron. 2014, 30, 3623–3637. [CrossRef]
11. Ibrahim, A.O.; Nguyen, T.H.; Lee, D.-C.; Kim, S.-C. A fault ride-through technique of DFIG wind turbine systems using dynamic
voltage restorers. IEEE Trans. Energy Convers. 2011, 26, 871–882. [CrossRef]
12. Zhang, S.; Tseng, K.-J.; Choi, S.S.; Nguyen, T.D.; Yao, D.L. Advanced control of series voltage compensation to enhance wind
turbine ride through. IEEE Trans. Power Electron. 2011, 27, 763–772. [CrossRef]
13. Amaris, H.; Alonso, M. Coordinated reactive power management in power networks with wind turbines and FACTS devices.
Energy Convers. Manag. 2011, 52, 2575–2586. [CrossRef]
14. Yuan, X. Overview of problems in large-scale wind integrations. J. Mod. Power Syst. Clean Energy 2013, 18, 22–25. [CrossRef]
15. Flannery, P.S.; Venkataramanan, G. A fault tolerant doubly fed induction generator wind turbine using a parallel grid side rectifier
and series grid side converter. IEEE Trans. Power Electron. 2008, 23, 1126–1135. [CrossRef]
16. Mahela, O.P.; Gupta, N.; Khosravy, M.; Patel, N. Comprehensive Overview of Low Voltage Ride through Methods of Grid
Integrated Wind Generator. IEEE Access 2019, 7, 99299–99326. [CrossRef]
17. Tsili, M.; Papathanassiou, S. A review of grid code technical requirements for wind farms. IET Renew. Power Gener. 2009, 3,
308–332. [CrossRef]
18. Attya, A.; Domínguez-García, J.L.; Anaya-Lara, O. A review on frequency support provision by wind power plants: Current and
future challenges. Renew. Sustain. Energy Rev. 2018, 81, 2071–2087. [CrossRef]
19. Abad, G.; López, J.; Rodríguez, M.A.; Marroyo, L.; Iwanski, G. Dynamic modeling of the doubly fed induction machine. Doubly
Fed Induction Mach. 2011, 209–239. [CrossRef]
20. Justo, J.J.; Mwasilu, F.; Jung, J.-W. Doubly-fed induction generator based wind turbines: A comprehensive review of fault
ride-through strategies. Renew. Sustain. Energy Rev. 2015, 45, 447–467. [CrossRef]
21. Kayikci, M.; Milanovic, J.V. Assessing transient response of DFIG-based wind plants—The influence of model simplifications and
parameters. IEEE Trans. Power Syst. 2008, 23, 545–554. [CrossRef]
22. Mwasilu, F.; Jung, J.-W.; Ro, K.-S.; Justo, J. Improvement of dynamic performance of doubly fed induction generator-based wind
turbine power system under an unbalanced grid voltage condition. IET Renew. Power Gener. 2012, 6, 424–434. [CrossRef]
23. Lima, F.K.A.; Luna, A.; Rodriguez, P.; Watanabe, E.H.; Blaabjerg, F. Rotor voltage dynamics in the doubly fed induction generator
during grid faults. IEEE Trans. Power Electron. 2009, 25, 118–130. [CrossRef]
24. Rahimi, M.; Azizi, A. Transient Behavior Representation, Contribution to Fault Current Assessment, and Transient Response
Improvement in DFIG-Based Wind Turbines Assisted with Crowbar Hardware. Int. Trans. Electr. Energy Syst. 2019, 29, e2698.
[CrossRef]
25. Haidar, A.M.A.; Muttaqi, K.M.; Hagh, M.T. A Coordinated control approach for DC link and rotor crowbars to improve fault
ride-through of DFIG-based wind turbine. IEEE Trans. Ind. Appl. 2017, 53, 4073–4086. [CrossRef]
26. Din, Z.; Zhang, J.; Zhu, Y.; Xu, Z.; El-Naggar, A. Impact of grid impedance on LVRT performance of DFIG system with rotor
crowbar technology. IEEE Access 2019, 7, 127999–128008. [CrossRef]
27. Justo, J.; Bansal, R. Parallel R-L configuration crowbar with series R-L circuit protection for LVRT strategy of DFIG under
transient-state. Electr. Power Syst. Res. 2018, 154, 299–310. [CrossRef]
28. Shi, J.; Tang, Y.; Xia, Y.; Ren, L.; Li, J. SMES based excitation system for doubly-fed induction generator in wind power application.
IEEE Trans. Appl. Supercond. 2011, 21, 1105–1108. [CrossRef]
Energies 2022, 15, 8026 31 of 33
29. Guo, W.; Xiao, L.; Dai, S. Enhancing low-voltage ride-through capability and smoothing output power of DFIG with a supercon-
ducting fault-current limiter–magnetic energy storage system. IEEE Trans. Energy Convers. 2012, 27, 277–295. [CrossRef]
30. Naderi, S.B.; Negnevitsky, M.; Muttaqi, K.M. A Modified DC chopper for limiting the fault current and controlling the DC-link
voltage to enhance fault ride-through capability of doubly-fed induction-generator-based wind turbine. IEEE Trans. Ind. Appl.
2018, 55, 2021–2032. [CrossRef]
31. Yang, J.; Fletcher, J.E.; O’Reilly, J. A series-dynamic-resistor-based converter protection scheme for doubly-fed induction generator
during various fault conditions. IEEE Trans. Energy Convers. 2010, 25, 422–432. [CrossRef]
32. Huang, J.; Zhang, L.; Sang, S.; Xue, X.; Zhang, X.; Sun, T.; Wu, W.; Gao, N. Optimized series dynamic braking resistor for LVRT of
doubly-fed induction generator with uncertain fault scenarios. IEEE Access 2022, 10, 22533–22546. [CrossRef]
33. Huang, P.-H.; El Moursi, M.S.; Hasen, S.A. Novel fault ride-through scheme and control strategy for doubly fed induction
generator-based wind turbine. IEEE Trans. Energy Convers. 2014, 30, 635–645. [CrossRef]
34. Guo, W.; Xiao, L.; Dai, S.; Li, Y.; Xu, X.; Zhou, W.; Li, L. LVRT capability enhancement of DFIG with switch-type fault current
limiter. IEEE Trans. Ind. Electron. 2014, 62, 332–342. [CrossRef]
35. Naderi, S.B.; Davari, P.; Zhou, D.; Negnevitsky, M.; Blaabjerg, F. A review on fault current limiting devices to enhance the fault
ride-through capability of the doubly-fed induction generator based wind turbine. Appl. Sci. 2018, 8, 2059. [CrossRef]
36. Puchalapalli, S.; Singh, B. A novel control scheme for wind turbine driven DFIG interfaced to utility grid. IEEE Trans. Ind. Appl.
2020, 56, 2925–2937. [CrossRef]
37. Qu, L.; Qiao, W. Constant power control of DFIG wind turbines with supercapacitor energy storage. IEEE Trans. Ind. Appl. 2011,
47, 359–367. [CrossRef]
38. Jayasinghe, S.D.G.; Vilathgamuwa, D.M. Flying supercapacitors as power smoothing elements in wind generation. IEEE Trans.
Ind. Electron. 2012, 60, 2909–2918. [CrossRef]
39. Shen, Y.W.; Ke, D.P.; Qiao, W.; Sun, Y.Z.; Kirschen, D.S.; Wei, C. Transient reconfiguration and co-ordinated control for power
converters to enhance the LVRT of a DFIG wind turbine with an energy storage device. IEEE Trans. Energy Convers. 2015, 30,
1679–1690. [CrossRef]
40. Chen, X.; Yan, L.; Zhou, X.; Sun, H. A novel DVR-ESS-embedded wind-energy conversion system. IEEE Trans. Sustain. Energy
2018, 9, 1265–1274. Available online: https://ieeexplore.ieee.org/document/8170301/ (accessed on 19 May 2022). [CrossRef]
41. Gontijo, G.; Tricarico, T.; Krejci, D.; França, B.; Aredes, M. A novel stator voltage distortion and unbalance compensation of a
DFIG with series grid side converter using adaptive resonant controllers. In Proceedings of the 2017 Brazilian Power Electronics
Conference (COBEP), Juiz de Fora, Brazil, 19–22 November 2017; pp. 1–6.
42. Omar, S.; Helal, A.; Elarabawy, I. Stator voltage sensorless DFIG with low voltage ride-through capability using series and parallel
grid side converters. In Proceedings of the 2016 7th International Renewable Energy Congress (IREC), Hammamet, Tunisia, 22–24
March 2016; pp. 1–6. [CrossRef]
43. Meyer, C.; De Doncker, R.W.; Li, Y.W.; Blaabjerg, F. Optimized control strategy for a medium-voltage DVR—Theoretical
investigations and experimental results. IEEE Trans. Power Electron. 2008, 23, 2746–2754. [CrossRef]
44. Nielsen, J.; Blaabjerg, F. A detailed comparison of system topologies for dynamic voltage restorers. IEEE Trans. Ind. Appl. 2005, 41,
1272–1280. [CrossRef]
45. Li, Y.W.; Blaabjerg, F.; Vilathgamuwa, D.M.; Loh, P.C. Design and comparison of high performance stationary-frame controllers
for DVR implementation. IEEE Trans. Power Electron. 2007, 22, 602–612. [CrossRef]
46. Marafao, F.; Colon, D.; Jardini, J.; Komatsu, W.; Matakas, L.; Galassi, M.; Ahn, S.; Bormio, E.; Camargo, J.; Monteiro, T.; et al.
Multiloop controller and reference generator for a Dynamic Voltage Restorer implementation. In Proceedings of the ICHQP 2008:
13th International Conference on Harmonics and Quality of Power, Wollongong, NSW, Australia, 28 September–1 October 2008;
pp. 1–6. [CrossRef]
47. Wessels, C.; Gebhardt, F.; Fuchs, F.W. Fault ride-through of a dfig wind turbine using a dynamic voltage restorer during
symmetrical and asymmetrical grid faults. IEEE Trans. Power Electron. 2010, 26, 807–815. [CrossRef]
48. Falehi, A.D.; Rafiee, M. Maximum efficiency of wind energy using novel dynamic voltage restorer for DFIG based wind turbine.
Energy Rep. 2018, 4, 308–322. [CrossRef]
49. Latif, S.; Savier, J. Design and implementation of DVR as fault current limiter in DFIG during grid faults. Int. J. Eng. Syst. Model.
Simul. 2021, 12, 38–53. [CrossRef]
50. Singh, B. Introduction to FACTS controllers in wind power farms: A technological review. Int. J. Adv. Renew. Energy Res. (IJARER)
2012, 1.
51. Mithulananthan, N.; Canizares, C.; Reeve, J.; Rogers, G. Comparison of PSS, SVC, and STATCOM controllers for damping power
system oscillations. IEEE Trans. Power Syst. 2003, 18, 786–792. [CrossRef]
52. Hemeida, M.G.; Hussien, H.R.; Wahab, M.A.A. Stabilization of a wind farm using static VAR compensators (SVC) based fuzzy
logic controller. Adv. Energy Power 2015, 3, 61–74. [CrossRef]
53. Molinas, M.; Suul, J.A.; Undeland, T. Low voltage ride through of wind farms with cage generators: STATCOM versus SVC. IEEE
Trans. Power Electron. 2008, 23, 1104–1117. [CrossRef]
54. Muyeen, S.M. A combined approach of using an SDBR and a STATCOM to enhance the stability of a wind farm. IEEE Syst. J.
2015, 9, 922–932. [CrossRef]
Energies 2022, 15, 8026 32 of 33
55. Narushima, J.; Inoue, K.; Takaku, T.; Isobe, T.; Kitahara, T.; Shimada, R. Application of magnetic energy recovery switch for power
factor correction. In Proceedings of the IPEC 2005: The 7th International Power Engineering Conference, Marina Mandarin Hotel,
Singapore, 29 November–2 December 2005; pp. 737–743.
56. Wiik, J.A.; Wijaya, F.D.; Shimada, R. Characteristics of the magnetic energy recovery switch (MERS) as a series FACTS controller.
IEEE Trans. Power Deliv. 2009, 24, 828–836. [CrossRef]
57. Alharbi, Y.M.; Abu-Siada, A. Application of UPFC to Improve the Low-Voltage-Ride-Through Capability of DFIG. 2015,
pp. 665–668. Available online: https://ieeexplore.ieee.org/document/7281548/ (accessed on 20 May 2022).
58. Choopani, M.; Hosseinian, S.H.; Vahidi, B. New transient stability and LVRT improvement of multi-VSG grids using the frequency
of the center of inertia. IEEE Trans. Power Syst. 2020, 35, 527–538. [CrossRef]
59. Liang, J.; Howard, D.F.; Restrepo, J.A.; Harley, R.G. Feedforward transient compensation control for DFIG wind turbines during
both balanced and unbalanced grid disturbances. IEEE Trans. Ind. Appl. 2013, 49, 1452–1463. [CrossRef]
60. Abdelrahem, M.; Mobarak, M.H.; Kennel, R. Model predictive control for low-voltage ride through capability enhancement of
DFIGs in variable-speed wind turbine systems. In Proceedings of the 9th International Conference on Electrical and Computer
Engineering, ICECE, Dhaka, Bangladesh, 20–22 December 2016; pp. 70–73. [CrossRef]
61. Kou, P.; Liang, D.; Li, J.; Gao, L.; Ze, Q. Finite-control-set model predictive control for DFIG wind turbines. IEEE Trans. Autom. Sci.
Eng. 2018, 15, 1004–1013. [CrossRef]
62. Rafiee, Z.; Heydari, R.; Rafiee, M.; Aghamohammadi, M.R.; Rodriguez, J.; Blaabjerg, F. Adaptive model predictive control of
DFIG-based wind farm: A model-free control approach. In Proceedings of the 2020 IEEE 21st Workshop on Control and Modeling
for Power Electronics (COMPEL 2020), Aalborg, Denmark, 9–12 November 2020; pp. 1–6. [CrossRef]
63. Mossa, M.A.; Do, T.D.; Al-Sumaiti, A.S.; Quynh, N.V.; Diab, A.A.Z. Effective model predictive voltage control for a sensorless
doubly fed induction generator. IEEE Can. J. Electr. Comput. Eng. 2021, 44, 50–64. [CrossRef]
64. Utkin, V.I. Sliding mode control design principles and applications to electric drives. IEEE Trans. Ind. Electron. 1993, 40, 23–36.
[CrossRef]
65. Beltran, B.; Ahmed-Ali, T.; El Hachemi Benbouzid, M. Sliding mode power control of variable-speed wind energy conversion
systems. IEEE Trans. Energy Convers. 2008, 23, 551–558. [CrossRef]
66. Ben Elghali, S.; Benbouzid, M.; Ahmed-Ali, T.; Charpentier, J.; Mekri, F. High-order sliding mode control of DFIG-based marine
current turbine. In Proceedings of the 2008 34th Annual Conference of IEEE Industrial Electronics, Orlando, FL, USA, 10–13
November 2008; pp. 1228–1233. [CrossRef]
67. Martinez, M.I.; Tapia, G.; Susperregui, A.; Camblong, H. Sliding-mode control for DFIG rotor- and grid-side converters under
unbalanced and harmonically distorted grid voltage. IEEE Trans. Energy Convers. 2012, 27, 328–339. [CrossRef]
68. Zhang, H.-X.; Fan, J.-S.; Meng, F.; Huang, J.-F. A new double power reaching law for sliding mode control. Control. Decis. 2013,
28, 289–293.
69. Kim, E.-H.; Kim, J.-H.; Lee, G.-S. Power factor control of a doubly fed induction machine using fuzzy logic. In Proceedings
of the ICEMS 2001—Proceedings of the 5th International Conference on Electrical Machines and Systems, Shenyang, China,
18–20 August 2001; Volume 2, pp. 747–750. [CrossRef]
70. Soloumah, H.M.; Kar, N.C. Fuzzy logic based vector control of a doubly-fed induction generator in wind power application.
Wind Eng. 2006, 30, 201–224. [CrossRef]
71. Jabr, H.M.; Lu, D.; Kar, N.C. Design and implementation of neuro-fuzzy vector control for wind-driven doubly-fed induction
generator. IEEE Trans. Sustain. Energy 2011, 2, 404–413. [CrossRef]
72. Raju, S.K.; Pillai, G.N. Design and implementation of type-2 fuzzy logic controller for DFIG-based wind energy systems in
distribution networks. IEEE Trans. Sustain. Energy 2016, 7, 345–353. [CrossRef]
73. Yunus, A.M.S.; Abu-Siada, A.; Mosaad, M.I.; Albalawi, H.; Aljohani, M.; Jin, J.X. Application of SMES technology in improving
the performance of a DFIG-WECS connected to a weak grid. IEEE Access 2021, 9, 124541–124548. [CrossRef]
74. Ren, J.; Xiao, X.; Zheng, Z.; Ma, Z. A SMES-based dynamic current limiter to improve the LVRT capability of DFIG-based WECS.
IEEE Trans. Appl. Supercond. 2021, 31, 5401805. [CrossRef]
75. Abouheaf, M.; Gueaieb, W.; Sharaf, A. Model-free adaptive learning control scheme for wind turbines with doubly fed induction
generators. IET Renew. Power Gener. 2018, 12, 1675–1686. [CrossRef]
76. Taveiros, F.; Barros, L.; Costa, F. Heightened state-feedback predictive control for DFIG-based wind turbines to enhance its LVRT
performance. Int. J. Electr. Power Energy Syst. 2019, 104, 943–956. [CrossRef]
77. Noureldeen, O.; Hamdan, I. A novel controllable crowbar based on fault type protection technique for DFIG wind energy
conversion system using adaptive neuro-fuzzy inference system. Prot. Control Mod. Power Syst. 2018, 3, 35. [CrossRef]
78. Raghavendran, C.; Roselyn, J.P.; Devaraj, D. Development and performance analysis of intelligent fault ride through control
scheme in the dynamic behaviour of grid connected DFIG based wind systems. Energy Rep. 2020, 6, 2560–2576. [CrossRef]
79. Ali, M.A.S.; Mehmood, K.K.; Baloch, S.; Kim, C.-H. Modified rotor-side converter control design for improving the LVRT
capability of a DFIG-based WECS. Electr. Power Syst. Res. 2020, 186, 106403. [CrossRef]
80. A Highly Effective Fault-Ride-Through Strategy for a Wind Energy Conversion System With a Doubly Fed Induction Generator.
IEEE Trans. Power Electron. 2020, 35, 8154–8164. [CrossRef]
Energies 2022, 15, 8026 33 of 33
81. Falehi, A.D.; Torkaman, H. Promoted supercapacitor control scheme based on robust fractional-order super-twisting sliding
mode control for dynamic voltage restorer to enhance FRT and PQ capabilities of DFIG-based wind turbine. J. Energy Storage
2021, 42, 102983. [CrossRef]
82. Shan, J.; Wang, Z.; Zhou, C.; Zhang, Z.; Fan, Y. A P-Q coordination method for wind farm to mitigate system frequency deviation
during LVRT period. In Proceedings of the 2021 IEEE 4th International Electrical and Energy Conference (CIEEC 2021), Wuhan,
China, 28–30 May 2021; pp. 1–6. [CrossRef]
83. A Cooperative Approach of Frequency Regulation through Virtual Inertia Control and Enhancement of Low Voltage Ride-Through
in DFIG-Based Wind Farm. J. Modern Power Syst. Clean Energy 2021, 1–12. [CrossRef]
84. Okedu, K.E.; Muyeen, S.M.; Takahashi, R.; Tamura, J. Wind farms fault ride through using DFIG with new protection scheme.
IEEE Trans. Sustain. Energy 2012, 3, 242–254. [CrossRef]
85. Ansari, A.A.; Dyanamina, G. MATLAB simulation of FRT techniques for DFIG-based wind farms. In Proceedings of the 2021
International Conference on Control, Automation, Power and Signal Processing (CAPS), Jabalpur, India, 10–12 December 2021;
pp. 1–6. [CrossRef]