ASPE Cross Connection Control
ASPE Cross Connection Control
Control
CEU 326
December 2023
Note: In determining your answers to the CE questions, use only the material presented in the corresponding continuing education article. Using information from other
materials may result in a wrong answer.
Cross-Connection Control
Reprint from PEDH Volume 4 – Chapter 9
All rights reserved.
Protecting potable water is an important aspect of plumbing engineering, and cross-connection control is the primary means used in the
plumbing profession to accomplish this. The importance of cross-connection control, or backflow protection, was brought to light in the
early part of the 20th century when major outbreaks of waterborne diseases such as dysentery occurred. By not ensuring that every opening,
outlet, and connection to the potable water supply is protected, backflow from nonpotable sources can contaminate the potable water supply.
For this reason, the plumbing engineer must evaluate every opening, outlet, and connection to a nonpotable source for proper protection
against backflow. Whatever the source of potable water, protection against cross-connections is imperative.
TYPES OF BACKFLOW
Backflow occurs through either siphonage or backpressure. Siphonage, also called backsiphonage, is the reversal of water flow when the
pressure on the inlet side of the water supply is lower than that on the outlet side. Siphonage can occur due to a water main break, a fire
pumper connected to the water main, or poor design in the water distribution system, among other reasons.
The other backflow occurrence is backpressure. Backpressure occurs when a higher pressure is applied on the outlet or connection side
of the water distribution side than on the inlet. Examples of backpressure occurrences include an elevated column of water, such as in a
multistory building, a pumped connection that pressurizes the water supply, or a pressurized nonpotable system.
Examples of potential cross-connections include plumbing fixtures, faucets, fixture fittings, hose bibbs, appliance connections, hydronic
water supply connections, fire sprinkler and standpipe water supply connections, water supply connections to industrial processes, laundries,
medical equipment, food service equipment, carbonated beverage dispensers, filters for beverage dispensers, HVAC equipment, swimming
pool water makeup, water treatment equipment, trap primers, irrigation taps, dispensers that dilute their product with water, pressure-relief
valve discharge piping, and drain-flushing water supplies.
The potential for backflow can occur at any opening, outlet, or connection to the potable water supply. Opening and outlet are words often
used interchangeably to identify a point where potable water is discharged. Examples of openings and outlets include faucets, fixture fittings,
hose bibbs, fill valves, and relief valves.
Connections are piping systems that interconnect a potable water supply to a nonpotable water system. Not all piping connections are to
a hazardous source, but all of the sources can contaminate the potable water supply.
HYDROSTATIC FUNDAMENTALS
To derive the pressure relationship in a hydrostatic fluid, consider the volume of the fluid at a given depth. The pressure of a 1-foot (305-mm)
column of water can be calculated using Equation 9-1. The pressure at the base of a water column can be determined using Equation 9-2.
Equation 9-1
p1 = ρ/A
Equation 9-2
p = h × p1
where
p1 = Pressure (gauge) per unit of head, 0.433 pounds per square inch (psi) per ft (9.79 kPa/m) of wc
ρ = Density of water, 62.4 lb/ft3 (1,000 kg/m3 = 102 N/m3)
A = Area, 144 in.2/ft2 (m2/m)
p = Pressure at the base of a column of water
h = Static head, ft (m)
Figure 9-1 Maximum Figure 9-2 Siphon Action The maximum density of water is 62.434 pounds per cubic foot (1.000
Rise of Water from a Lifting Water from a Tank kg/L) at a temperature of 39.2°F (4.0°C). When the temperature of water is
Vacuum increased or decreased, the density decreases. At 212°F (100°C), the density
of water is 59.843 pounds per cubic foot (0.9586 kg/L). Assuming a density
Vacuum pump of 62.4 pounds per cubic foot (1.00 kg/L) and applying Equation 9-1, the
pressure at the base of a 1-foot column of water is 0.433 psi (62.4 divided by
20 ft
8.66 psi 144 square inches per square foot). For SI, water is 1,000 kg/m , except that
3
14.7 psi
(101.4 kPa) (6.1 m 1 kPa = 1,000 Pa and 1,000 Pa = 1,000 N/m . To convert kg to N, multiply
2
59.7 kPa) 1,000 kg by 9.79 m/s2 (gravity) to get 9,790 N/m3, so at 1 meter head, the
pressure is 9,790 N/m2 = 9.79 kPa.
If a column of water is 10 feet (3.048 m) in height, the pressure at the
base of the column is 4.33 psi (69.4 kPa). The pressure is identified as gauge
pressure, assuming atmospheric pressure to be 0 psi (0 kPa). At sea level,
atmospheric pressure is 14.7 psi (101.4 kPa).
A perfect vacuum would be 0 psi (0 kPa) absolute, or -14.7 psi (-101.3
kPa) gauge. Any vacuum or negative pressure would result in a column of
water rising in the piping. With a perfect vacuum, a column of water would
33.9 ft rise against atmospheric pressure (-14.7 psi [-101.3 kPa]), which equates to
(10.35 m) 33.9 feet (10.35 m). Hence, for a perfect vacuum, water can only rise 33.9 feet
(10.35 m) in a pipe (see Figure 9-1).
14.7 psi
(101.4 kPa) Water will rise in a pipe up to 33.9 feet (10.35 m) and return to the source
under a vacuum or siphon action (see Figure 9-2). When the upstream pressure
is lower than the outlet or connection pressure, flow will be reversed in the
piping system. The reversal of water flow can contaminate the potable water supply by introducing nonpotable
water or contaminants into the system.
Backflow protection is based on preventing the reversal of flow that may occur when the upstream pressure
drops lower than the outlet or connection pressure. A means must be provided to prevent the reversal of flow
under all possible conditions.
Classification of Hazards
The potential hazards from a cross-connection are identified as low hazard and high hazard. A high hazard is any contamination that can
cause sickness, disease, long-term health effects, or death. Examples are sewage, chemicals, body fluids, lubricants, and fertilizers. A low hazard
impacts the aesthetics of the potable water, but the pollutant will not immediately cause sickness, disease, or death. Examples are juices, coffee,
tea, and humidifier water. Some of the identified pollutants are drinks that are consumed by humans. However, if the drink enters the potable
water system, the water does not remain potable.
Air Gap
An air gap is a space between the outlet of the potable water supply and the flood level rim of the fixture or device being supplied with water.
The flood level rim is defined as the point where water overflows the fixture or device.
An air gap is considered the highest level of protection against backflow. An air gap provides a physical separation between the opening or
outlet and the water in the fixture, vessel, or pipe. An air gap is the most common method of backflow protection. The water supply to most
sink faucets, lavatory faucets, shower valves, bathtub fillers, and drinking fountains is protected against backflow by an air gap.
Since the physical separation is by means of air, an air gap is considered to protect against siphonage only. No backpressure can occur
with an air gap since any physical connection that creates backpressure would defeat the air gap.
Table 9-3 identifies the minimum air gap spacing requirements between the opening or outlet and the flood level rim. The table identifies
the minimum spacing based on whether or not the air gap is affected by a side wall. The side wall will affect the air gap when it is located
within three times the effective opening diameter. For example, if the opening was ½ inch (13 mm) in diameter, the side wall would have to
be located a minimum of 1½ inches (38 mm) from the opening. Where two walls intersect, the distance increases to four times the opening
to not be affected by the side wall.
Backflow Preventer with an Intermediate Atmospheric Vent Figure 9-6 Backflow Preventer with an
Intermediate Atmospheric Vent, ASSE 1012
A backflow preventer with an intermediate atmospheric vent (see Figure 9-6) has two
independently acting check valves and a vent that opens to atmosphere. When the first
check valve opens, it closes off the opening to the vent. When the first check valve moves
to the closed position, the intermediate atmospheric vent opens to vent any nonpotable
water that flows past the second check valve. The intermediate atmospheric vent must Inlet Outlet
discharge through an air gap.
These types of backflow preventers are only available in ¼ inch through ¾ inch (DN 8
through 20). The common installation of this backflow preventer is on the fill line to a boiler
Vent
that does not have conditioning chemicals. This device provides backflow protection similar
to an RP but in a compact, less-expensive design that is not testable or repairable in line.
Figure 9-7
Dual Check Valve Dual Check Valve, ASSE 1032
A dual check valve (see Figure 9-7) has two independently acting check valves without an Inlet Outlet
atmospheric vent opening, shutoff valves on either end, or test cocks. The many styles of dual
check valves depend on the application of use. Larger dual check valves are available in sizes
up to 2 inches (DN-50) in diameter. These types of valves are commonly used on the inlet
supply to a building or on the water supply to a residential sprinkler system. Smaller-diameter
dual check valves are used for backflow protection on the water supply to equipment such as
juice dispensers, coffee makers, and humidifiers. The small sizes are also used on laboratory
faucets and shampoo sinks. This device provides backflow protection similar to
Figure 9-8
a double check (DC) but in a compact, less-expensive design that is not testable Backflow Preventer for Carbonated Beverage
or repairable in line. Dual checks are usually referred to as a “DuC” and should Machines, ASSE 1022
not be confused with a double check.
Inlet Outlet
Not all plumbing codes recognize the use of dual check valves. When dual
check valves are permitted by the plumbing codes, they are typically restricted
to a narrow application of use for backflow protection.
Vacuum Breakers
Vacuum breakers are designed to break a siphon by allowing the introduction
of air into the piping system. Vacuum breakers are only designed to prevent
siphonage; however, certain vacuum breaker are tested for low-head backpressure,
which typically means a column of water elevated to 10 feet (3.3 m) or less. For
Atmospheric vent
some applications, a lower head height is anticipated. Vacuum breakers must be
installed above the flood level rim of the fixture, vat, vessel, or tank that they are
protecting against backflow.
Atm nt
ve
a pressure vacuum breaker must be tested. An annual test also is required.
.
Pressure vacuum breakers were originally designed to be installed outdoors (see Figure 9-11), but Outlet
they can be installed indoors provided measures are taken to prevent damage when the valve discharges
water. Pressure vacuum breakers are often referred to as spitting when water first flows through the valve.
The spitting is the discharge of water out of the top bonnet, which occurs until the disk seals off the air
Inlet
opening. The amount of water that discharges is less than a gallon; however, some form of drainage, such
as a floor drain, should be located near the pressure vacuum breaker. Most pressure vacuum breakers are
required to be installed a minimum of 12 inches (305 mm) above the Figure 9-11 Pressure Vacuum Breaker on the Water Supply
flood level rim or highest downstream outlet. to a Lawn Sprinkler System, ASSE 1020
breaker; however, they are all tested for low-head backpressure, which can be
ve
.
part of the pressurized tank design. The backflow protection for tank-type
ve
.
INSTALLATION
All backflow preventers must be accessible for inspection, service, repair, maintenance, or replacement
via a panel, door, or access opening. Testable backflow preventers must be installed so their test cocks
are accessible for installing the test gauges. For this reason, some manufacturers may advise to limit the Vent to
atmosphere
installation height of the bottom of the device to 30 inches (762 mm) off the finished grade.
The standard orientation for reduced pressure principle backflow preventers and double check valve
assemblies is horizontal. A reduced pressure principle backflow preventer and double check valve assembly
can only be installed in the vertical orientation when the device is tested and listed for vertical orientation.
For reduced pressure principle backflow preventers and double check valve assemblies that are 3 Cold water in
inches (DN-80) or smaller in diameter, the minimum spacing between the side of the device with the
test cocks and the side wall of the building is recommended to be 24 inches (610 mm). The Table 9-4 Reduced Pressure Principle
remaining sides of the device should have a spacing of 12 inches (305 mm) minimum. For Backflow Preventer Discharge Rates
4-inch (DN-100) and larger reduced pressure principle backflow preventers and double check Relief Valve
valve assemblies, the minimum spacing on the side with the test cocks should be 48 inches Backflow Discharge Rate at
Preventer Size, in.
(1,220 mm). The remaining sides should have a minimum spacing of 24 inches (610 mm). 80 psi (552 kPa),
(DN)
Reduced pressure principle backflow preventers must be installed with an air gap for the gpm (L/m)
relief valve discharge port. The location of a reduced pressure principle backflow preventer 1½ (40) 80 (303)
must prevent the relief valve discharge port from becoming submerged. Many plumbing 2 (50) 150 (568)
codes prohibit a reduced pressure principle backflow preventer from being installed in a pit
3 (80) 240 (908)
or underground, which can be interpreted as prohibiting the device from being installed in a
basement that could be flooded. Other plumbing codes allow pit or underground installations if 4 (100) 620 (2,350)
adequate drainage is provided to prevent the relief valve discharge port from being submerged. 6 (150) 620 (2,350)
Double check valve assemblies do not have the same concern about being submerged. Most 8 (200) 620 (2,350)
plumbing codes allow double check valve assemblies to be installed in pits or underground.
However, some plumbing codes do not allow these devices to be installed in a pit if the test
cocks could be submerged, which could result in contamination of the potable water supply. Table 9-5 Flow Rate Through a PVC Drain
When installed outside, reduced pressure principle backflow preventers and double check Pitched ¼ in./ft (~2%) Flowing Half Full
valve assemblies must be protected from freezing in colder climates. Insulated enclosures Drain Size, Flow Rate, gpm
and heated, insulated enclosures specifically designed for backflow preventers are available to in. (DN) (Lpm)
protect the device from freezing. These outside enclosures also allow the water to discharge 1½ (40) 8.3 (31.4)
to the surrounding ground when a reduced pressure principle backflow preventer is installed. 2 (50) 15.7 (59.4)
This avoids the need for a drain to be installed.
3 (80) 39.6 (150)
One of the most overlooked installation design requirements is the size of the floor drain
in the immediate area of a reduced pressure principle backflow preventer. Table 9-4 lists the 4 (100) 81.7 (309)
discharge flow rates from the relief valve for one manufacturer’s reduced pressure principle 6 (150) 243.6 (922)
backflow preventer with a water supply pressure of 80 psi (552 kPa). Table 9-5 lists the flow 8 (200) 505.2 (1,912)
rates through a PVC drain pitched ¼ inch per foot (~2 percent) flowing half full. The drain 10 (250) 927 (3,510)
for a reduced pressure principle backflow preventer should have a flow rate equal to or greater
than the discharge rate from the backflow preventer.
All vacuum breakers must be installed in the orientation for which the device is listed (for example, vertical to horizontal orientation).
The critical level, typically marked “CL” on the vacuum breaker, must be installed above the flood level rim. Atmospheric vacuum breakers
typically require a minimum of 6 inches (152 mm) between the critical level and flood level rim. However, some special atmospheric vacuum
breakers, often called deck-mounted vacuum breakers, can be installed 1 inch (25 mm) above the flood level rim. Pressure vacuum breaker are
typically required to be installed a minimum of 12 inches (305 mm) above the flood level rim. A lower height may be acceptable if the device
has been so tested and listed. The minimum height is specified by the manufacturer and is part of the vacuum breaker’s listing.
Expiration date: Continuing education credit will be given for this examination through December 31, 2024.
Thank you to Tony Furst, MSEd, CPD, Leed AP, for authoring this month’s quiz.
1. A column of water 20’ tall exerts a pressure on its base of what? 7. The intermediate zone of an RP device is equipped with _______.
a. .866 psi a. A drain valve
b. .433 psi b. A test cock
c. 43.3 psi c. Two check valves
d. 8.66 psi d. A relief valve
2. Backflow protection is based on what? 8. Heat exchangers for domestic water use minimize cross contamination
a. Preventing the reversal of of flow potential through the use of _______.
b. Adding pressure drop to a system a. Double wall construction
c. Creating a test point in a system b. Double check valve assembly on the potable water side
d. Ensuring flow reversal c. Automatic isolation valves on the heat source
d. Electronic leak detection systems
3. Reverse flow can be caused by numerous situations. What are three
possble causes? 9. A 3” RP style backflow preventer has a relief valve discharge rate of
a. Over-pressure in the city water main, incorrect pipe size, excessive ______.
water demand a. 375 GPM
b. Fire department usage, pressure increase due to temperature increase, b. 90 GPM
broken city water main c. 240 GPM
c. Nonpotable system operating at a higher pressure than the potable d. 150 GPM
system, operator error, broken city main
d. Additional fixture load, higher demand on a lower flow, pumps 10. The minimum required level of backflow prevention for seperating
operated in reverse the potable water system from a heating hot water system containing
propylene glycol is?
4. An air gap is considered ______ against backflow. a. Reduced Pressure Zone or RP
a. The lowest level of protection b. Double Check Valve Assembly or DCDA
b. Not a usable level of protection c. Dual Check Valve
c. The highest level of protection d. Vacuum Breaker
d. The minimum level of protection
11. Testable backflow prevention devices must be tested and certified
5. A barometric loop is similar to _______. _________.
a. An atmospheic vacuum breaker a. At initial installation and every year thereafter
b. A double check valve backflow preventer b. At original installation and every five years thereafter
c. A reduced pressure zone backflow preventer c. By the manufacturer and every ten years thereafter
d. An air gap d. At time of original installation and never again