Column and Footing Details

This document provides reinforcement details for three types of column footings - C1 for stub columns, C2 for portico columns, and C3 for main columns. It includes dimensions, reinforcement quantities and spacing, concrete mix specifications, and general notes on construction practices and responsibilities. Reinforcement includes mild steel and tor steel ranging from #8 to #20 bars. Concrete mix is M25 for RCC and M35 for roof elements. Adherence to construction codes and addressing discrepancies with the consultant are noted.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views

Column and Footing Details

This document provides reinforcement details for three types of column footings - C1 for stub columns, C2 for portico columns, and C3 for main columns. It includes dimensions, reinforcement quantities and spacing, concrete mix specifications, and general notes on construction practices and responsibilities. Reinforcement includes mild steel and tor steel ranging from #8 to #20 bars. Concrete mix is M25 for RCC and M35 for roof elements. Adherence to construction codes and addressing discrepancies with the consultant are noted.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

6Nos-20# +

8Nos-16# 6Nos-16#
4Nos-16#

1'-6"
+2Nos-12#

1'-3"
8# @4"/6"c/c 8# @4"/6"c/c 8# @4"/6"c/c

1'
(refer typ. column section) (refer typ. column section)
9" 9" 1'

Lateral Tie Section 1-1 Lateral Tie Section 2-2 Lateral Tie Section 3-3

NGL NGL
NGL
1 1 2 2
3 3
upto 6' (or) to hard strata

upto 6' (or) to hard strata

upto 6' (or) to hard strata


4Nos-16# 8Nos-16#
+2Nos-12# 6Nos-20# +
6Nos-16#
8# @4"c/c 8# @4"c/c
8# @4"c/c
eq eq
eq eq eq eq

2'
1'-6"
1-3"

1'-6" 1'-6"
10# @6"c/c (typ) (typ) 10# @4"c/c 12# @4"c/c
Bothways Bothways Bothways
6"

6"

6"
P.C.C 1:5:10 mix P.C.C 1:5:10 mix P.C.C 1:5:10
mix
3'6"x3'6" 4'6"x4'6" 6'6"x6'6"

R.C.C. COLUMN AND FOOTING-C1 R.C.C. COLUMN AND FOOTING-C2 R.C.C. COLUMN AND FOOTING-C3
FOR STUB COLUMNS FOR PORTICO COLUMNS FOR MAIN COLUMNS
GENERAL NOTES
1) All dimensions are in foot and inches.
2) Use concrete mix: M25 for RCC (1:1:2)
Use concrete mix: M35 for Roof beam 5) Clear cover to the reinforcement for 8) Crank at L/4of clear span 13) Client / Builder ensures that strict 15) Study both Architectural drawings and
and slab Footing:50mm, Column:40mm, 9) Extra rod at top to a length of 0.3L adherence to the GOOD CONSTRUCTION Structural drawings before start the work
3) Minimum cement content shall not be Beam:30mm, Slab:15mm of clear span from support PRACTICE is followed at site as per if any discrepancies are to be brought to
less than 390 Kg/Cu.m of concrete. 6) Provide lap length 50D for Beam 10) ST - indicates Straight rod. the relevant IS code. the notice of the consultant before the
4) The reinforcement shall be High Strength 7) No admixtures shall be added without 11) CKD- indicates Cranked rod . 14) Structural Engineer's responsibility commencement of work.
Deformed bars of Grade Fe 500(#) permission of consultant. 12) # - Indicates TOR Steel is limited to designing and issual of
confirming to IS 1786-1985. structural drawing only

Notes: PROJECT: PROMOTER: STRUCTURAL CONSULTANT:


1) This drawing should be read along with
Architectural drawing.
P.VETRIVENTHAN,M.E.,(Struct)
2) Foundation Designed For G+1 floors.
PROPOSED COMMERCIAL BUILDING Thanvik Associates
3) SBC of soil taken as 240 kN/m²
VSK Building, Thondamuthur Rd,
DRAWING TITLE: Vadavalli,Coimbatore - 641041.
DATE: 11/07/23 DRAWN BY : P.V
Mobile : 9486050288
Scale: NTS CHECKED BY : P.V Email : [email protected]
R.C.C COLUMN AND FOOTING DETAILS
FILE NAME REV NO & DATE : 0