VEGAPULS 64
4 … 20 mA/HART - two-wire
Contents
1 For your safety
1.1 Authorised personnel........................................................................................................ 3
1.2 Appropriate use................................................................................................................. 3
1.3 Warning about incorrect use.............................................................................................. 3
1.4 General safety instructions................................................................................................ 3
1.5 CE conformity.................................................................................................................... 4
1.6 NAMUR recommendations............................................................................................... 4
1.7 Radio license for Europe................................................................................................... 4
1.8 Environmental instructions................................................................................................ 4
2 Product description
2.1 Configuration..................................................................................................................... 6
3 Mounting
3.1 Mounting preparations, mounting strap............................................................................. 7
3.2 Mounting instructions........................................................................................................ 7
4 Connecting to power supply
4.1 Connecting........................................................................................................................ 9
4.2 Wiring plan, single chamber housing.............................................................................. 10
5 Set up with the display and adjustment module
5.1 Insert display and adjustment module............................................................................. 12
5.2 Parameter adjustment - Quick setup............................................................................... 13
5.3 Parameter adjustment - Extended adjustment................................................................ 15
6 Supplement
6.1 Technical data................................................................................................................. 21
Information:
This quick setup guide enables quick setup and commissioning of
your instrument.
You can find supplementary information in the corresponding, more
detailed Operating Instructions Manual as well as the Safety Manual
that comes with instruments with SIL qualification. These manuals are
available on the supplied DVD or in the download area of "www.vega.
51462-EN-160111
com".
1.5 CE conformity
The device fulfills the legal requirements of the applicable EC guide-
lines. By affixing the CE marking, we confirm successful testing of the
product.
You can find the CE Certificate of Conformity in the download section
of our homepage.
2 Product description
2.1 Configuration
Type label The type label contains the most important data for identification and
use of the instrument:
1
2
3
12
4
5 11
6
10
7
9
8
Fig. 1: Layout of the type label (example)
1 Instrument type
2 Product code
3 License label
4 Power supply and signal output, electronics
5 Protection rating
6 Measuring range
7 Process and ambient temperature, process pressure
8 Material, wetted parts
9 Serial number of the instrument
10 Data-Matrix-Code for smartphone app
11 Symbol of the device protection class
12 Reminder to observe the instrument documentation
Serial number - Instru- The type label contains the serial number of the instrument. With it
ment search you can find the following instrument data on our homepage:
• Product code (HTML)
• Delivery date (HTML)
• Order-specific instrument features (HTML)
• Operating instructions and quick setup guide at the time of ship-
ment (PDF)
• Order-specific sensor data for an electronics exchange (XML)
• Test certificate (PDF) - optional
Go to www.vega.com "VEGA Tools" and "Instrument search". Enter
the serial number.
Alternatively, you can access the data via your smartphone:
• Download the smartphone app "VEGA Tools" from the "Apple App
Store" or the "Google Play Store"
•
51462-EN-160111
Scan the Data Matrix code on the type label of the instrument or
• Enter the serial number manually in the app
3 Mounting
3.1 Mounting preparations, mounting strap
The mounting strap is supplied unassembled (optionally) and must be
screwed to the sensor before setup with three hexagon socket screws
M5 x 10 and spring washers. Max. torque, see chapter "Technical
data". Required tools: Allen wrench size 4.
There are two different variants of screwing the strap to the sensor,
see following illustration:
1 2
Fig. 2: Mounting strap for screwing to the sensor
1 For angle of inclination in steps
2 For angle of inclination, infinitely variable
1
51462-EN-160111
Information:
When the housing is rotated, the direction of polarization changes
and hence the influence of the false echo on the measured value.
Please keep this in mind when mounting or making changes later.
Installation position When mounting the sensor, keep a distance of at least 200 mm
(7.874 in) from the vessel wall. If the sensor is installed in the center
of dished or round vessel tops, multiple echoes can arise. However,
these can be suppressed by an appropriate adjustment (see chapter
"Setup").
If you cannot maintain this distance, you should carry out a false
signal storage during setup. This applies particularly if buildup on the
vessel wall is expected. In such cases, we recommend repeating the
false signal storage at a later date with existing buildup.
> 200 mm
(7.87")
51462-EN-160111
6. Insert the wire ends into the terminals according to the wiring plan
Information:
Solid cores as well as flexible cores with wire end sleeves are insert-
ed directly into the terminal openings. In case of flexible cores without
end sleeves, press the terminal from above with a small screwdriver,
the terminal opening is then free. When the screwdriver is released,
the terminal closes again.
You can find further information on the max. wire cross-section under
"Technical data - Electromechanical data"
7. Check the hold of the wires in the terminals by lightly pulling on
them
8. Connect the screen to the internal ground terminal, connect the
external ground terminal to potential equalisation
9. Tighten the compression nut of the cable entry gland. The seal
ring must completely encircle the cable
10. Reinsert the display and adjustment module, if one was installed
11. Screw the housing lid back on
The electrical connection is finished.
4...20mA
3
(+)1 2(-) 5 6 7 8
4
1
Fig. 9: Installing the display and adjustment module in the electronics compart-
ment of the single chamber housing
51462-EN-160111
1 2
Fig. 10: Installing the display and adjustment module in the double chamber
housing
1 In the electronics compartment
2 In the terminal compartment
Note:
If you intend to retrofit the instrument with a display and adjustment
module for continuous measured value indication, a higher lid with an
inspection glass is required.
Quick setup process Select the individual menu items with the [->] key. Carry out the steps
in the below sequence.
2. Medium
In this menu item you select the medium. The selection comprises
liquids with different properties.
3. Application
In this menu item you determine the application.
4. Vessel form
In this menu item you specify the for of the vessel bottom and top.
6. Max. adjustment
In this menu item you carry out the max. adjustment.
Enter the measuring distance for 100 % filling.
7. Min. adjustment
In this menu item you carry out the min. adjustment.
Enter the measuring distance for 0 % filling.
8. Termination
"Quick setup terminated successfully" is displayed briefly.
Information:
51462-EN-160111
The echo curve of setup was stored automatically during the quick
setup.
The quick setup is finished.
The return to the measured value indication is carried out through the
[->] or [ESC] keys or automatically after 3 s
Extended adjustment The menu "Extended adjustment" is available for further settings. Im-
portant functions are described in the following chapter. You can find a
complete description of all functions of the "Extended adjustment" in
the operating instructions manual of VEGAPULS 64.
Setup - Adjustment Since the radar sensor is a distance measuring instrument, the
distance from the sensor to the product surface is measured. To
indicate the actual level, an allocation of the measured distance to the
percentage height must be carried out.
To perform the adjustment, enter the distance with full and empty ves-
sel, see the following example:
51462-EN-160111
100% 2
(19.68")
0,5 m
(196.9")
5m
0% 1
If these values are not known, an adjustment with the distances of e.g.
10 % and 90 % is possible. Starting point for these distance specifica-
tions is always the sealing surface of the thread or flange. You can find
specifications on the reference plane in chapter "Technical data". The
actual level is calculated on the basis of these settings.
The actual product level during this adjustment is not important,
because the min./max. adjustment is always carried out without
changing the product level. These settings can be made ahead of
time without the instrument having to be installed.
Diagnostics - Echo curve The function "Setup" allows the echo curve to be saved at the time of
memory setup.
Information:
This is generally recommended, however, for use of the Asset
Management functions it is absolutely necessary. Saving should be
carried out with a very low level.
The function "Echo curve memory" allows up to ten individual echo
curves to be stored, for example to detect the measurement behav-
iour of the sensor in different operating conditions.
With the adjustment software PACTware and the PC, the stored echo
curves can be displayed with high resolution and used to recognize
signal changes over time. In addition, the echo curve saved during
setup can also be displayed in the echo curve window and compared
51462-EN-160111
Menu - Display
Menu item Default setting
Menu language Order-specific
Displayed value 1 Filling height in %
Displayed value 2 Electronics temperature in °C
Backlight Switched on
Menu - Diagnosis
Menu item Parameter Default setting
51462-EN-160111
Sensor status -
Peak value Distance -
Meas. certainty -
Menu - Info
Menu item Parameter
Device name VEGAPULS 6.
Instrument version Hardware and software version
Factory calibration Date
51462-EN-160111
date
Sensor characteristics Order-specific characteristics
Additional adjustments - The following circumstances cause interfering reflections and can
False signal suppression influence the measurement:
• High sockets
• Vessel installations such as struts
• Agitators
• Buildup or welded joints on vessel walls
Note:
A false signal suppression detects, marks and saves these false
signals so that they are no longer taken into account in the level
measurement.
This should be done with a low level so that all potential interfering
reflections can be detected.
Proceed as follows:
1. Select with [->] the menu item "False signal suppression" and
confirm with [OK].
4. Confirm again with [OK] and enter the actual distance from the
sensor to the product surface.
5. All interfering signals in this section are detected by the sensor
and stored after confirming with [OK].
Note:
Check the distance to the product surface, because if an incorrect
(too large) value is entered, the existing level will be saved as a false
signal. The level would then no longer be detectable in this area.
If a false signal suppression has already been saved in the sensor,
the following menu window appears when selecting "False signal
suppression":
51462-EN-160111
51462-EN-160111
6 Supplement
6.1 Technical data
Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 bar
Options of the cable entry
ƲƲ Cable entry M20 x 1.5, ½ NPT
ƲƲ Cable gland M20 x 1,5; ½ NPT (cable ø see below table)
ƲƲ Blind plug M20 x 1.5; ½ NPT
ƲƲ Closing cap ½ NPT
Voltage supply
Operating voltage UB
ƲƲ Non-Ex instrument 12 … 35 V DC
ƲƲ Ex-d instrument 12 … 35 V DC
ƲƲ Ex ia instrument 12 … 30 V DC
ƲƲ Ex-d-ia instrument 17 … 35 V DC
Operating voltage UB - illuminated display and adjustment module
ƲƲ Non-Ex instrument 18 … 35 V DC
ƲƲ Ex-d instrument 18 … 35 V DC
ƲƲ Ex ia instrument 18 … 30 V DC
ƲƲ Ex-d-ia instrument Due to the barrier, no lighting possible
Reverse voltage protection Integrated
Permissible residual ripple - Non-Ex, Ex-ia instrument
ƲƲ for 12 V< UB < 18 V ≤ 0.7 Veff (16 … 400 Hz)
ƲƲ for 18 V< UB < 35 V ≤ 1.0 Veff (16 … 400 Hz)
Permissible residual ripple - Ex-d-ia instrument
ƲƲ for 18 V< UB < 35 V ≤ 1 Veff (16 … 400 Hz)
51462-EN-160111
Load resistor
ƲƲ Calculation (UB - Umin)/0.022 A
ƲƲ Example - Non-Ex instrument with (24 V - 12 V)/0.022 A = 545 Ω
UB= 24 V DC
51462-EN-160111
51462-EN-160111