VEGA Level Sensor VEGAPULS 64 Radar Level Sensor Quick Setup Guide

This quick setup guide provides instructions for safely setting up the VEGAPULS 64 radar sensor for continuous level measurement of liquids. Key steps include mounting the sensor to the vessel according to the instructions, connecting the sensor to the power supply, and using the display module to complete the sensor setup and parameter adjustment. Safety information is also provided to ensure proper use of the sensor.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
136 views

VEGA Level Sensor VEGAPULS 64 Radar Level Sensor Quick Setup Guide

This quick setup guide provides instructions for safely setting up the VEGAPULS 64 radar sensor for continuous level measurement of liquids. Key steps include mounting the sensor to the vessel according to the instructions, connecting the sensor to the power supply, and using the display module to complete the sensor setup and parameter adjustment. Safety information is also provided to ensure proper use of the sensor.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 24

Quick setup guide

Radar sensor for continuous level


measurement of liquids

VEGAPULS 64
4 … 20 mA/HART - two-wire

Document ID: 51462


Contents

Contents
1 For your safety
1.1 Authorised personnel........................................................................................................ 3
1.2 Appropriate use................................................................................................................. 3
1.3 Warning about incorrect use.............................................................................................. 3
1.4 General safety instructions................................................................................................ 3
1.5 CE conformity.................................................................................................................... 4
1.6 NAMUR recommendations............................................................................................... 4
1.7 Radio license for Europe................................................................................................... 4
1.8 Environmental instructions................................................................................................ 4
2 Product description
2.1 Configuration..................................................................................................................... 6
3 Mounting
3.1 Mounting preparations, mounting strap............................................................................. 7
3.2 Mounting instructions........................................................................................................ 7
4 Connecting to power supply
4.1 Connecting........................................................................................................................ 9
4.2 Wiring plan, single chamber housing.............................................................................. 10
5 Set up with the display and adjustment module
5.1 Insert display and adjustment module............................................................................. 12
5.2 Parameter adjustment - Quick setup............................................................................... 13
5.3 Parameter adjustment - Extended adjustment................................................................ 15
6 Supplement
6.1 Technical data................................................................................................................. 21

Information:
This quick setup guide enables quick setup and commissioning of
your instrument.
You can find supplementary information in the corresponding, more
detailed Operating Instructions Manual as well as the Safety Manual
that comes with instruments with SIL qualification. These manuals are
available on the supplied DVD or in the download area of "www.vega.
51462-EN-160111

com".

Operating instructions VEGAPULS 64 - 4 … 20 mA/HART - two-


wire: Document-ID 51141
Editing status of the quick setup guide: 2015-12-04

2 VEGAPULS 64 • 4 … 20 mA/HART - two-wire


1 For your safety

1 For your safety


1.1 Authorised personnel
All operations described in this operating instructions manual must
be carried out only by trained specialist personnel authorised by the
plant operator.
During work on and with the device the required personal protective
equipment must always be worn.

1.2 Appropriate use


VEGAPULS 64 is a sensor for continuous level measurement.
You can find detailed information about the area of application in
chapter "Product description".
Operational reliability is ensured only if the instrument is properly
used according to the specifications in the operating instructions
manual as well as possible supplementary instructions.

1.3 Warning about incorrect use


Inappropriate or incorrect use of the instrument can give rise to
application-specific hazards, e.g. vessel overfill or damage to system
components through incorrect mounting or adjustment. Also the pro-
tective characteristics of the instrument can be influenced.

1.4 General safety instructions


This is a state-of-the-art instrument complying with all prevailing
regulations and guidelines. The instrument must only be operated in a
technically flawless and reliable condition. The operator is responsible
for the trouble-free operation of the instrument.
During the entire duration of use, the user is obliged to determine the
compliance of the necessary occupational safety measures with the
current valid rules and regulations and also take note of new regula-
tions.
The safety instructions in this operating instructions manual, the na-
tional installation standards as well as the valid safety regulations and
accident prevention rules must be observed by the user.
For safety and warranty reasons, any invasive work on the device
beyond that described in the operating instructions manual may be
carried out only by personnel authorised by the manufacturer. Arbi-
trary conversions or modifications are explicitly forbidden.
The safety approval markings and safety tips on the device must also
be observed.
Depending on the instrument version, the emitting frequencies are in
the C, K or W band range. The low emitting frequencies are far below
51462-EN-160111

the internationally approved limit values. When used correctly, the


device poses no danger to health.

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 3


1 For your safety

1.5 CE conformity
The device fulfills the legal requirements of the applicable EC guide-
lines. By affixing the CE marking, we confirm successful testing of the
product.
You can find the CE Certificate of Conformity in the download section
of our homepage.

1.6 NAMUR recommendations


NAMUR is the automation technology user association in the process
industry in Germany. The published NAMUR recommendations are
accepted as the standard in field instrumentation.
The device fulfills the requirements of the following NAMUR recom-
mendations:
• NE 21 – Electromagnetic compatibility of equipment
• NE 43 – Signal level for malfunction information from measuring
transducers
• NE 53 – Compatibility of field devices and display/adjustment
components
• NE 107 – Self-monitoring and diagnosis of field devices
For further information see www.namur.de.

1.7 Radio license for Europe


The instrument is approved according to EN 302372-1/2 V1.2.1
(2011-02) for use in closed vessels.
For operation inside of closed vessels, the following conditions must
be fulfilled:
• The instrument must be permanently mounted on a closed vessel
made of metal, reinforced concrete, or comparable attenuating
materials.
• Flanges, process fittings and mounting accessories must ensure
the microwave impermeability of the vessel and not let the radar
signal escape to the outside
• If necessary, existing viewing windows in the vessel must be
coated with a microwave impermeable material (e.g. electrically
conductive coating)
• Manholes and flanges on the vessel must be closed and sealed to
avoid penetration of the radar signal
• The instrument should be preferably mounted on top of the vessel
with antenna orientation downward
• The instrument must only be installed and maintained by appropri-
ately qualified staff

1.8 Environmental instructions


51462-EN-160111

Protection of the environment is one of our most important duties.


That is why we have introduced an environment management system
with the goal of continuously improving company environmental pro-
tection. The environment management system is certified according
to DIN EN ISO 14001.

4 VEGAPULS 64 • 4 … 20 mA/HART - two-wire


1 For your safety

Please help us fulfill this obligation by observing the environmental


instructions in this manual:
• Chapter "Packaging, transport and storage"
• Chapter "Disposal"
51462-EN-160111

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 5


2 Product description

2 Product description
2.1 Configuration
Type label The type label contains the most important data for identification and
use of the instrument:

1
2
3
12
4
5 11
6
10
7
9
8
Fig. 1: Layout of the type label (example)
1 Instrument type
2 Product code
3 License label
4 Power supply and signal output, electronics
5 Protection rating
6 Measuring range
7 Process and ambient temperature, process pressure
8 Material, wetted parts
9 Serial number of the instrument
10 Data-Matrix-Code for smartphone app
11 Symbol of the device protection class
12 Reminder to observe the instrument documentation

Serial number - Instru- The type label contains the serial number of the instrument. With it
ment search you can find the following instrument data on our homepage:
• Product code (HTML)
• Delivery date (HTML)
• Order-specific instrument features (HTML)
• Operating instructions and quick setup guide at the time of ship-
ment (PDF)
• Order-specific sensor data for an electronics exchange (XML)
• Test certificate (PDF) - optional
Go to www.vega.com "VEGA Tools" and "Instrument search". Enter
the serial number.
Alternatively, you can access the data via your smartphone:
• Download the smartphone app "VEGA Tools" from the "Apple App
Store" or the "Google Play Store"

51462-EN-160111

Scan the Data Matrix code on the type label of the instrument or
• Enter the serial number manually in the app

6 VEGAPULS 64 • 4 … 20 mA/HART - two-wire


3 Mounting

3 Mounting
3.1 Mounting preparations, mounting strap
The mounting strap is supplied unassembled (optionally) and must be
screwed to the sensor before setup with three hexagon socket screws
M5 x 10 and spring washers. Max. torque, see chapter "Technical
data". Required tools: Allen wrench size 4.
There are two different variants of screwing the strap to the sensor,
see following illustration:

1 2
Fig. 2: Mounting strap for screwing to the sensor
1 For angle of inclination in steps
2 For angle of inclination, infinitely variable

Depending on the selected variant, the sensor can be rotated in the


strap:
• Single chamber housing
–– Angle of inclination in three steps 0°, 90° and 180°
–– Angle of inclination 180°, infinitely variable

• Double chamber housing


–– Angle of inclination 90°, infinitely variable
–– Angle of inclination in two steps 0° and 90°

3.2 Mounting instructions


Polarisation Radar sensors for level measurement emit electromagnetic waves.
The polarization is the direction of the electrical component of these
waves.
The polarization direction is marked by a nose on the housing, see
following drawing:

1
51462-EN-160111

Fig. 3: Position of the polarisation


1 Nose for marking the direction of polarisation

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 7


3 Mounting

Information:
When the housing is rotated, the direction of polarization changes
and hence the influence of the false echo on the measured value.
Please keep this in mind when mounting or making changes later.

Installation position When mounting the sensor, keep a distance of at least 200 mm
(7.874 in) from the vessel wall. If the sensor is installed in the center
of dished or round vessel tops, multiple echoes can arise. However,
these can be suppressed by an appropriate adjustment (see chapter
"Setup").
If you cannot maintain this distance, you should carry out a false
signal storage during setup. This applies particularly if buildup on the
vessel wall is expected. In such cases, we recommend repeating the
false signal storage at a later date with existing buildup.

> 200 mm
(7.87")

Fig. 4: Mounting of the radar sensor on round vessel tops

In vessels with conical bottom it can be advantageous to mount the


sensor in the center of the vessel, as measurement is then possible
down to the lowest point of the vessel bottom.

51462-EN-160111

Fig. 5: Mounting of the radar sensor on vessels with conical bottom

8 VEGAPULS 64 • 4 … 20 mA/HART - two-wire


4 Connecting to power supply

4 Connecting to power supply


4.1 Connecting
Connection technology The voltage supply and signal output are connected via the spring-
loaded terminals in the housing.
Connection to the display and adjustment module or to the interface
adapter is carried out via contact pins in the housing.
Information:
The terminal block is pluggable and can be removed from the
electronics. To do this, lift the terminal block with a small screwdriver
and pull it out. When reinserting the terminal block, you should hear it
snap in.

Connection procedure Proceed as follows:


1. Unscrew the housing lid
2. If a display and adjustment module is installed, remove it by turn-
ing it slightly to the left.
3. Loosen compression nut of the cable gland and remove blind
plug
4. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.
1 cm (0.4 in) of insulation from the ends of the individual wires
5. Insert the cable into the sensor through the cable entry

Fig. 6: Connection steps 5 and 6 - Single chamber housing


51462-EN-160111

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 9


4 Connecting to power supply

Fig. 7: Connection steps 5 and 6 - Double chamber housing

6. Insert the wire ends into the terminals according to the wiring plan
Information:
Solid cores as well as flexible cores with wire end sleeves are insert-
ed directly into the terminal openings. In case of flexible cores without
end sleeves, press the terminal from above with a small screwdriver,
the terminal opening is then free. When the screwdriver is released,
the terminal closes again.
You can find further information on the max. wire cross-section under
"Technical data - Electromechanical data"
7. Check the hold of the wires in the terminals by lightly pulling on
them
8. Connect the screen to the internal ground terminal, connect the
external ground terminal to potential equalisation
9. Tighten the compression nut of the cable entry gland. The seal
ring must completely encircle the cable
10. Reinsert the display and adjustment module, if one was installed
11. Screw the housing lid back on
The electrical connection is finished.

4.2 Wiring plan, single chamber housing


The following illustration applies to the non-Ex as well as to the Ex-ia
version.
51462-EN-160111

10 VEGAPULS 64 • 4 … 20 mA/HART - two-wire


4 Connecting to power supply

Electronics and terminal 2


compartment

4...20mA
3

(+)1 2(-) 5 6 7 8
4
1

Fig. 8: Electronics and terminal compartment, single chamber housing


1 Voltage supply, signal output
2 For display and adjustment module or interface adapter
3 For external display and adjustment unit
4 Ground terminal for connection of the cable screen
51462-EN-160111

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 11


5 Set up with the display and adjustment module

5 Set up with the display and adjustment


module
5.1 Insert display and adjustment module
The display and adjustment module can be inserted into the sensor
and removed again at any time. You can choose any one of four differ-
ent positions - each displaced by 90°. It is not necessary to interrupt
the power supply.
Proceed as follows:
1. Unscrew the housing lid
2. Place the display and adjustment module on the electronics in the
desired position and turn it to the right until it snaps in.
3. Screw housing lid with inspection window tightly back on
Disassembly is carried out in reverse order.
The display and adjustment module is powered by the sensor, an ad-
ditional connection is not necessary.

Fig. 9: Installing the display and adjustment module in the electronics compart-
ment of the single chamber housing
51462-EN-160111

12 VEGAPULS 64 • 4 … 20 mA/HART - two-wire


5 Set up with the display and adjustment module

1 2
Fig. 10: Installing the display and adjustment module in the double chamber
housing
1 In the electronics compartment
2 In the terminal compartment

Note:
If you intend to retrofit the instrument with a display and adjustment
module for continuous measured value indication, a higher lid with an
inspection glass is required.

5.2 Parameter adjustment - Quick setup


To quickly and easily adapt the sensor to the application, select
the menu item "Quick setup" in the start graphic on the display and
adjustment module.

Quick setup process Select the individual menu items with the [->] key. Carry out the steps
in the below sequence.

1. Measurement loop name


In the first menu item you assign a suitable measurement loop name.
Permitted are names with max. 19 characters.
51462-EN-160111

2. Medium
In this menu item you select the medium. The selection comprises
liquids with different properties.

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 13


5 Set up with the display and adjustment module

3. Application
In this menu item you determine the application.

4. Vessel form
In this menu item you specify the for of the vessel bottom and top.

5. Vessel height/Measuring range


In this menu item you enter the height of the vessel and hence the
active measuring range.

6. Max. adjustment
In this menu item you carry out the max. adjustment.
Enter the measuring distance for 100 % filling.

7. Min. adjustment
In this menu item you carry out the min. adjustment.
Enter the measuring distance for 0 % filling.

8. Termination
"Quick setup terminated successfully" is displayed briefly.
Information:
51462-EN-160111

The echo curve of setup was stored automatically during the quick
setup.
The quick setup is finished.

14 VEGAPULS 64 • 4 … 20 mA/HART - two-wire


5 Set up with the display and adjustment module

The return to the measured value indication is carried out through the
[->] or [ESC] keys or automatically after 3 s

Extended adjustment The menu "Extended adjustment" is available for further settings. Im-
portant functions are described in the following chapter. You can find a
complete description of all functions of the "Extended adjustment" in
the operating instructions manual of VEGAPULS 64.

5.3 Parameter adjustment - Extended adjustment


Main menu The main menu is divided into five sections with the following func-
tions:

Setup: Settings, e.g., for measurement loop name, units, application,


adjustment, signal output
Display: Settings, e.g., for language, measured value display, lighting
Diagnosis: Information, for example, on device status, peak value,
simulation, echo curve
Additional adjustments: Date/Time, reset, copy function, scaling,
current output, false signal suppression, linearization, HART mode,
special parameters
Info: Instrument name, hardware and software version, calibration
date, instrument features
In the main menu item "Setup", the individual submenu items
should be selected one after the other and provided with the correct
parameters to ensure optimum adjustment of the measurement. The
procedure is described in the following.

Setup - Adjustment Since the radar sensor is a distance measuring instrument, the
distance from the sensor to the product surface is measured. To
indicate the actual level, an allocation of the measured distance to the
percentage height must be carried out.
To perform the adjustment, enter the distance with full and empty ves-
sel, see the following example:
51462-EN-160111

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 15


5 Set up with the display and adjustment module

100% 2

(19.68")
0,5 m

(196.9")
5m
0% 1

Fig. 11: Parameter adjustment example min./max. adjustment


1 Min. level = max. measuring distance
2 Max. level = min. measuring distance
3 Reference plane

If these values are not known, an adjustment with the distances of e.g.
10 % and 90 % is possible. Starting point for these distance specifica-
tions is always the sealing surface of the thread or flange. You can find
specifications on the reference plane in chapter "Technical data". The
actual level is calculated on the basis of these settings.
The actual product level during this adjustment is not important,
because the min./max. adjustment is always carried out without
changing the product level. These settings can be made ahead of
time without the instrument having to be installed.

Diagnostics - Echo curve The function "Setup" allows the echo curve to be saved at the time of
memory setup.
Information:
This is generally recommended, however, for use of the Asset
Management functions it is absolutely necessary. Saving should be
carried out with a very low level.
The function "Echo curve memory" allows up to ten individual echo
curves to be stored, for example to detect the measurement behav-
iour of the sensor in different operating conditions.
With the adjustment software PACTware and the PC, the stored echo
curves can be displayed with high resolution and used to recognize
signal changes over time. In addition, the echo curve saved during
setup can also be displayed in the echo curve window and compared
51462-EN-160111

with the current echo curve.

16 VEGAPULS 64 • 4 … 20 mA/HART - two-wire


5 Set up with the display and adjustment module

Menu and parameter Menu - Setup


overview
Menu item Parameter Default setting
Measurement Sensor
loop name
Units Distance in m
Temperature in °C
Application Medium Water based
Application Storage tank
Vessel top/Vessel Dished form/Dished form
bottom
Vessel height/ 30 m
Measuring range
Adjustment Max. adjustment 0,000 m(d)
100.00 %
Min. adjustment 30 m
0.00 %
Damping Integration time 0.0 s
Current output Current output - Output characteristics
Mode 4 … 20 mA
Reaction when malfunctions occur
≤ 3.6 mA
Current output - 3.8 mA
Min./Max. 20.5 mA
Lock adjustment Released

Menu - Display
Menu item Default setting
Menu language Order-specific
Displayed value 1 Filling height in %
Displayed value 2 Electronics temperature in °C
Backlight Switched on

Menu - Diagnosis
Menu item Parameter Default setting
51462-EN-160111

Sensor status -
Peak value Distance -
Meas. certainty -

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 17


5 Set up with the display and adjustment module

Menu item Parameter Default setting


Peak values, ad- Temperature -
ditional
Curve indication Echo curve -
False signal sup- -
pression
Simulation Percent
Echo curve Percent
memory

Menu - Additional adjustments


Menu item Parameter Default setting
Date/Time Actual date/Actual time
Reset -
Copy in- -
strument
settings
Scaling Scaling size Volume in l
Scaling format 0 % corresponds to 0 l
100 % corresponds to 0 l
Current out- Current output - Meas. vari- Lin. percent - Level
put 1 able
Current output - Adjustment 0 … 100 % correspond to
4 … 20 mA
Current out- Current output - Meas. vari- Lin. percent - Level
put 2 able
Current output - Adjustment 0 … 100 % correspond to
4 … 20 mA
False signal -
suppression
Linearization Linear
HART mode Address 0
Special pa- -
rameters

Menu - Info
Menu item Parameter
Device name VEGAPULS 6.
Instrument version Hardware and software version
Factory calibration Date
51462-EN-160111

date
Sensor characteristics Order-specific characteristics

18 VEGAPULS 64 • 4 … 20 mA/HART - two-wire


5 Set up with the display and adjustment module

Additional adjustments - The following circumstances cause interfering reflections and can
False signal suppression influence the measurement:
• High sockets
• Vessel installations such as struts
• Agitators
• Buildup or welded joints on vessel walls

Note:
A false signal suppression detects, marks and saves these false
signals so that they are no longer taken into account in the level
measurement.
This should be done with a low level so that all potential interfering
reflections can be detected.
Proceed as follows:
1. Select with [->] the menu item "False signal suppression" and
confirm with [OK].

2. Confirm again with [OK].

3. Confirm again with [OK].

4. Confirm again with [OK] and enter the actual distance from the
sensor to the product surface.
5. All interfering signals in this section are detected by the sensor
and stored after confirming with [OK].
Note:
Check the distance to the product surface, because if an incorrect
(too large) value is entered, the existing level will be saved as a false
signal. The level would then no longer be detectable in this area.
If a false signal suppression has already been saved in the sensor,
the following menu window appears when selecting "False signal
suppression":
51462-EN-160111

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 19


5 Set up with the display and adjustment module

Delete: An already created false signal suppression will be com-


pletely deleted. This is useful if the saved false signal suppression no
longer matches the metrological conditions in the vessel.
Extend: is used to extend an already created false signal suppres-
sion. This is useful if a false signal suppression was carried out with
too high a level and not all false signals could be detected. When
selecting "Extend", the distance to the product surface of the created
false signal suppression is displayed. This value can now be changed
and the false signal suppression can be extended to this range.

51462-EN-160111

20 VEGAPULS 64 • 4 … 20 mA/HART - two-wire


6 Supplement

6 Supplement
6.1 Technical data
Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 bar
Options of the cable entry
ƲƲ Cable entry M20 x 1.5, ½ NPT
ƲƲ Cable gland M20 x 1,5; ½ NPT (cable ø see below table)
ƲƲ Blind plug M20 x 1.5; ½ NPT
ƲƲ Closing cap ½ NPT

Material ca- Material seal Cable diameter


ble gland insert
4.5 … 8.5 mm 5 … 9 mm 6 … 12 mm 7 … 12 mm 10 … 14 mm
PA NBR – ● ● – ●
Brass, nickel- NBR
● ● ● – –
plated
Stainless NBR
– ● ● – ●
steel

Wire cross-section (spring-loaded terminals)


ƲƲ Massive wire, stranded wire 0.2 … 2.5 mm² (AWG 24 … 14)
ƲƲ Stranded wire with end sleeve 0.2 … 1.5 mm² (AWG 24 … 16)

Voltage supply
Operating voltage UB
ƲƲ Non-Ex instrument 12 … 35 V DC
ƲƲ Ex-d instrument 12 … 35 V DC
ƲƲ Ex ia instrument 12 … 30 V DC
ƲƲ Ex-d-ia instrument 17 … 35 V DC
Operating voltage UB - illuminated display and adjustment module
ƲƲ Non-Ex instrument 18 … 35 V DC
ƲƲ Ex-d instrument 18 … 35 V DC
ƲƲ Ex ia instrument 18 … 30 V DC
ƲƲ Ex-d-ia instrument Due to the barrier, no lighting possible
Reverse voltage protection Integrated
Permissible residual ripple - Non-Ex, Ex-ia instrument
ƲƲ for 12 V< UB < 18 V ≤ 0.7 Veff (16 … 400 Hz)
ƲƲ for 18 V< UB < 35 V ≤ 1.0 Veff (16 … 400 Hz)
Permissible residual ripple - Ex-d-ia instrument
ƲƲ for 18 V< UB < 35 V ≤ 1 Veff (16 … 400 Hz)
51462-EN-160111

Load resistor
ƲƲ Calculation (UB - Umin)/0.022 A
ƲƲ Example - Non-Ex instrument with (24 V - 12 V)/0.022 A = 545 Ω
UB= 24 V DC

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 21


Notes

51462-EN-160111

22 VEGAPULS 64 • 4 … 20 mA/HART - two-wire


Notes
51462-EN-160111

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 23


Printing date:

51462-EN-160111

All statements concerning scope of delivery, application, practical use and operat-
ing conditions of the sensors and processing systems correspond to the information
available at the time of printing.
Subject to change without prior notice

© VEGA Grieshaber KG, Schiltach/Germany 2016