Correction Factors
Correction Factors
Table B.2 – Current ratings for single-core cables with XLPE insulation –
Rated voltage 3,6/6 kV to 18/30 kV * –
Copper conductor
Flat
Nominal Flat
Trefoil Flat spaced Trefoil ducts touching Trefoil Flat spaced
area of touching
ducts
conductor
De
≥ 0,5 × De ≥ 0,5 × De
≥ 0,5 × De
mm 2 A A A A A A A
16 109 113 103 104 125 128 150
25 140 144 132 133 163 167 196
35 166 172 157 159 198 203 238
* Current rating calculated for cables having a rated voltage of 6/10 kV.
--`,,```,,,,````-`-`,,`,,`,`,,`---
– 60 – 60502-2 © IEC:2014
Table B.3 – Current ratings for single-core cables with XLPE insulation –
Rated voltage 3,6/6 kV to 18/30 kV * –
Aluminium conductor
Flat
Nominal Flat
Trefoil Flat spaced Trefoil ducts touching Trefoil Flat spaced
area of touching
ducts
conductor
De
≥ 0,5 × De ≥ 0,5 × De
≥ 0,5 × De
mm 2 A A A A A A A
16 84 88 80 81 97 99 116
25 108 112 102 103 127 130 153
35 129 134 122 123 154 157 185
--`,,```,,,,````-`-`,,`,,`,`,,`---
185 317 324 303 307 424 432 504
* Current rating calculated for cables having a rated voltage of 6/10 kV.
60502-2 © IEC:2014 – 61 –
Table B.4 – Current ratings for single-core cables with EPR insulation –
Rated voltage 3,6/6 kV to 18/30 kV * –
Copper conductor
Flat
Nominal Flat
Trefoil Flat spaced Trefoil ducts touching Trefoil Flat spaced
area of touching
ducts
conductor
De
≥ 0,5 × De ≥ 0,5 × De
≥ 0,5 × De
mm 2 A A A A A A A
16 106 109 99 100 116 119 138
25 136 140 128 129 153 156 181
35 162 167 153 154 186 190 221
* Current rating calculated for cables having a rated voltage of 6/10 kV.
--`,,```,,,,````-`-`,,`,,`,`,,`---
– 62 – 60502-2 © IEC:2014
Table B.5 – Current ratings for single-core cables with EPR insulation –
Rated voltage 3,6/6 kV to 18/30 kV * –
Aluminium conductor
Flat
Nominal Flat
Trefoil Flat spaced Trefoil ducts touching Trefoil Flat spaced
area of touching
ducts
conductor
De
≥ 0,5 × De ≥ 0,5 × De
≥ 0,5 × De
mm 2 A A A A A A A
16 82 84 77 78 90 92 107
25 105 109 99 100 119 121 141
35 126 130 118 120 144 147 171
Unarmoured Armoured
≥ 0,3 × De ≥ 0,3 × De
2
mm A A A A A A
16 101 87 109 101 88 110
25 129 112 142 129 112 143
35 153 133 170 154 134 172
50 181 158 204 181 158 205
* Current rating calculated for cables having a rated voltage of 6/10 kV.
--`,,```,,,,````-`-`,,`,,`,`,,`---
– 64 – 60502-2 © IEC:2014
Unarmoured Armoured
≥ 0,3 × De ≥ 0,3 × De
2
mm A A A A A A
16 78 67 84 78 68 85
25 100 87 110 100 87 111
35 119 103 132 119 104 133
50 140 122 158 140 123 159
* Current rating calculated for cables having a rated voltage of 6/10 kV.
60502-2 © IEC:2014 – 65 –
Unarmoured Armoured
≥ 0,3 × De ≥ 0,3 × De
2
mm A A A A A A
16 98 84 104 98 85 104
25 125 109 135 125 109 136
35 150 130 164 150 131 164
50 176 154 195 177 155 197
* Current rating calculated for cables having a rated voltage of 6/10 kV.
--`,,```,,,,````-`-`,,`,,`,`,,`---
– 66 – 60502-2 © IEC:2014
Unarmoured Armoured
≥ 0,3 × De ≥ 0,3 × De
2
mm A A A A A A
16 76 65 80 76 66 81
25 97 84 105 97 85 105
35 116 101 127 116 101 127
50 137 119 151 137 120 153
* Current rating calculated for cables having a rated voltage of 6/10 kV.
Single-core cables
≤185 mm 2 >185 mm 2
0,5 1,04 1,06 1,04
0,6 1,02 1,04 1,03
Single-core cables
Three-core
Depth of laying Nominal conductor size cable
m mm 2
≤185 mm 2 >185 mm 2
--`,,```,,,,````-`-`,,`,,`,`,,`---
60502-2 © IEC:2014 – 71 –
Table B.22 – Reduction factors for groups of more than one multi-core cable in air –
To be applied to the current-carrying capacity for one multi-core cable in free air
≥ 20 mm
3 1,00 0,86 0,79 0,76 0,71 0,66
Cables on
–
perforated trays Spaced 1 1,00 1,00 0,98 0,95 0,91
De
–
2 1,00 0,99 0,96 0,92 0,87
≥ 20 mm –
3 1,00 0,98 0,95 0,91 0,85
≥
225 mm
1 1,00 0,88 0,82 0,78 0,73 0,72
Touching
Cables on vertical
perforated trays
≥ –
225 mm 1 1,00 0,91 0,89 0,88 0,87
De –
2 1,00 0,91 0,88 0,87 0,85
Spaced
≥ 20 mm
3 1,00 0,85 0,79 0,76 0,73 0,70
Cables on ladder
supports, cleats, Spaced –
etc. 1 1,00 1,00 1,00 1,00 1,00
De
–
2 1,00 0,99 0,98 0,97 0,96
≥ 20 mm –
3 1,00 0,98 0,97 0,96 0,93
NOTE 1 Values given are averages for the cable types and range of conductor sizes considered. The spread of values is
generally less than 5 %.
NOTE 2 Factors apply to single layer groups of cables as shown above and do not apply when cables are installed in more
than one layer touching each other. Values for such installations may be significantly lower and must be determined by an
appropriate method.
NOTE 3 Values are given for vertical spacings between trays of 300 mm and at least 20 mm between trays and wall. For closer
spacing, the factors should be reduced.
NOTE 4 Values are given for horizontal spacing between trays of 225 mm with trays mounted back to back. For closer spacing,
the factors should be reduced.
--`,,```,,,,````-`-`,,`,,`,`,,`---
60502-2 © IEC:2014 – 73 –
Table B.23 – Reduction factors for groups of more than one circuit of single-core cables
(Note 2) – To be applied to the current-carrying capacity for one circuit of single-core
cables in free air
≥
Vertical 225 mm 1 1,00 0,91 0,89
perforated ≥ 2De Three cables
trays in trefoil
formation
(Note 4) 2 1,00 0,90 0,86
De
Spaced
1 1,00 1,00 1,00
Ladder ≥ 2De De
supports,
cleats, etc. 2 0,97 0,95 0,93
(Note 3) ≥ 20 mm
3 0,96 0,94 0,90
NOTE 1 Values given are averages for the cable types and range of conductor sizes considered. The spread
of values is generally less than 5 %.
NOTE 2 Factors are given for single layers of cables (or trefoil groups) as shown in the table and do not apply
when cables are installed in more than one layer touching each other. Values for such installations may be
--`,,```,,,,````-`-`,,`,,`,`,,`---