GENERAL TECHNICAL SPECIFICATIONS
1. DESIGN:
Oil Immersed, Core Type Double Wound Transformer with Class “A” Insulation,
designed for continuous duty at rated capacity with particular reference to tropical
conditions confirming to IS 1180 /IS 2026 / IEC 60076.
2. STANDARDS:
IS 1180 / IEC 60076 : Distribution Transformers.
IS 2026 / IEC 60076 : Power Transformers.
IS 3639 / IEC : Fittings & Accessories for Power Transformer
IS 335 / IEC 60296 : Transformer Oil.
IS 1271/ IEC 60085 : Insulating Material.
IS 3347 / IEC 60137 : Bushings.
3. CONSTRUCTIONS:
a) CORE: The core shall be C.R.G.O. Steel Material having Low Losses and good grain
properties, bolted together to the frame firmly to prevent vibration and noise. Special
Step lap core assembly method is used to further lower the losses.
b) WINDING: Winding shall be made out of 100 % Electrolytic Grade
Copper/Aluminum Wires / Strips. Generally, H.V. Winding shall be crossover or
disc type and the L.V. Winding shall be Cylindrical Type / Disc Type or Helical Type
depending up on the Voltage and currents.
c) TANK: Transformer Tank shall be of Robust Construction and shall be fabricated
with M.S.Plates. Proper reinforcement shall be provided to ensure no bulging occur
during service. The Tank shall be pressure and Vacuum Tested. All joints of tank &
fittings shall be leak proof.
d) FITTINGS & ACCESSORIES: All the fittings and accessories shall be of good
quality and conforming to relevant IS Specifications.
e) OIL: The Transformer shall be supplied with first filling of oil as per IS 335 (Apar or
Savita make).
f) PAINTING: Tank inside shall be painted by heat and oil resistant paint. The exterior
of the Transformer shall be painted with one coat of Epoxy Primer and top coat of
Epoxy / PU paint.
GUARANTEED TECHNICAL PARTICULARS
S.No PATICULARS Details
1 Manufacturer’s Name and Address ABC TRANSFORMERS PVT LTD
2 Reference Standard IS:1180, EEL-1
3 Continuous max. Rating 1600 KVA
4 Type Hermatically Sealed
5 Application/Installation Indoor Application in CSS
6 Winding Material: HV/LV Copper
7 Rated Voltage : HV/LV 11000 V / 433 V
8 Rated Current : HV/LV 83.98 / 2133.45 A
9 No of Phases & rated frequency 3 Phase & 50 Hz
10 Vector group reference Dyn-11
11 Connection HV- Delta, LV- Star
12 +5% to -15% / in step of 1.25%(16
Tapping Range & no. of steps
Step 17 position)
13 Type of Tapping Switch OLTC
14 Type of cooling ONAN
15 Maximum Temperature rise of top oil / winding 40˚C / 45˚C
16 Max. flux density at rated voltage and rated frequency 1.69 Tesla (Max)
17 Total Losses @ 50 % Load ( @ 75 °C) 4200 W
18 Total Losses @ 100 % Load ( @ 75 °C) 11800 W
Efficiency at 75˚C :- At U.P.F. At 0.8 P.F.
19 i) At 100% of full load 99.26 % 99.07 %
ii) At 75% of full load 99.38 % 99.23 %
iii) At 50% of full load 99.48 % 99.35 %
% regulation at full load & at 75˚C:
20
a) At unity power factor 0.681 %
b) At 0.8 power factor 4.250 %
21 Percentage Impedance at full load and at 75˚C 6.25 % (Tol. as per IS)
22 Insulation level of transformer : HV/LV 28 KV, 75 KVp / 3 KV
23 Class of Insulation A Class
24 Weight of Core & winding assembly 2350 Kg
25 Weight of tank & fittings 1535 Kg
26 Weight / volume of oil 1080 Kg / 1365 Ltrs.
27 Total weight of complete transformer 4965 Kg
Accessories
28 1. Name, Rating & Diagram Plate 1 No.
2. 12 KV, 250 A porcelain bushing 3 Nos.
3. 1.1 KV, 2500 A Epoxy bushing 4 Nos.
4. Thermometer Pocket 2 Nos.
5. On load Tap Changer with in built AVR 1 No.
6. Plain oil level gauge 1 No.
7. Lifting lugs 1 set
8. Earthing terminals 2 Nos.
9. Drain cum Filter valve Both Side 1 No.
10. Air release plug 1 No.
11. Base Channel 2 Nos.
12. Radiator Corrugated Type
13. WTI & OTI 1 No.
14. PRV 1 No.
Note: 1-All electrical performances are subject to tolerance as per IS-1180, IS-2026, IEC-76
2-Weights & dimensions are subject to tolerance of ±10%.
1 2 3 4 5 6 7 8
TANK
A OLTC SIDE A
B B
ROLLER C/C=900 FND C/C=550
150
VIEW FROM HV SIDE
C C
LV SIDE SIDE VIEW
2500
1490
D D
PLINTH
E E
FDN=550
1500
620
NOTE :
1)TOLERANCE ON DIMENSIONS ARE +10%
F F
2)UNDER BASE CHANNEL :150X75 x1390 lg 2nos
FDN=700
G G
ROLLER C/C=900 A - 41, SECTOR -58, NOIDA (U.P.)
6" Plan Rollers
4 Nos. FOUNDATION REV. DATE DESCRIPTION CHKD. APPD. CUSTOMER : PRODUCT :
HV SIDE DRN. DALBIR
DRAWING NO. : TITLE :
H CHKD. H
ABC/1600/FD/02
Foundation Detail Drawing
BOTTOM VIEW APPD.
REV. PROJECTION SCALE PROJECT NO. OF SHEET- 01
NAME DATE SIGN 03 -- SHEET NO. - 01
1 2 3 4 5 6 7 8
1
1
ABC TRANSFORMERS PVT. LTD.
A-41, SECTOR -58, NOIDA,( U.P.) Phone : 120-2582203 , 120-4325219
E-Mail :
[email protected] Web. : abctransformers.in
3 PHASE COPPER WOUND TRANSFORMER
STANDARD IS :1180 (PART 1) ENERGY EFFICIENCY LEVEL 1
2
2
MAX. TOTAL LOSSES
KVA 1600 AT 50% RATED LOAD
W
MAX. TOTAL LOSSES
HV 11000 W
VOLTS AT AT 100% RATED LOAD
NO LOAD LV 433 ONAN
TYPE OF COOLING
HV 75/28
BIL OIL 40
LV /3KV TEMP. RISE
WDG 45
HV 84
3
3
AMPERES MASS OF OIL Kg 1080
LV 2133.39 TOTAL MASS
Kg 4980
VECTOR GROUP Dyn11 1365
VOL. OF OIL Ltr
IMPENDANCE VOLT % 6.25 MONTH & YEAR OF MFG. /2022
TAPPING ON LOAD SERIAL No.
FOR HV VARIATION
4
4
IN 1.25% STEPS FROM +5 % TO - 15 %
CUSTOMER
SWITCH
POSITION CONNECTIONS HV LV
WTI CT 1 20 - 3 11550
5
5
2 20 - 4 11412.5
2N 2U 2V 2W
1U 1V 1W 3 20 - 5 11275
4 20 - 6 11137.5
DRN.
APPD.
CHKD.
3 3 3 5 20 - 7 11000
4 4 4
REV. DATE
5 5 5 6 20 - 8 10862.5
6 6 6
7 7 7 10725
DALBIR
7 20 - 9
NAME
8 8 8
9 9 9 8 20 - 10 10587.5
10 10 10
11 11 11 9 20 - 11 10450
12 12 12 433
13 13 13 10 20 - 12 10312.5
DATE
22.6.22
14 14 14
DESCRIPTION
15 15 15 20 - 13 10175
11
6
6
16 16 16
17 17 17 10037.5
18 18 18 12 20 - 14
19 19 19
CHKD.
13 20 - 15 9900
SIGN
20 20 20 14 20 - 16 9762.5
APPD.
15 20 - 17 9625
16 20 - 18 9487.5
17 20 - 19 9350
1U
CUSTOMER :
DRAWING NO. :
REV. PROJECTION
2U
ABC/1600/NP /03
7
7
--
SCALE
2V
2W
1W 1V
PROJECT
TITLE :
PRODUCT :
VECTOR GROUP Dyn11
8
8
A - 41, SECTOR 58, NOIDA (U.P.)
SHEET NO.
HARMETICALLY SEALED T/F
RATING & DIAGRAM PLATE
1600KVA,11/0.433KV Cu WOUND EEL-1
NO. OF SHEET- 01
- 01
F
E
B
A
H
D
C
G
1 2 3 4 5 6 7 8
M12
A 7 A
10 NOTE:-
108
1. STANDARD APPLICABLE : IS:3347
B B
3 2. RATED VOLTAGE : 12KV
3 RATED CURRENT : 250AMPS
5 4. BIL & WET/DRY POWE FREQUENCY WITH STAND VOLTAGE : 28KV
35
5 CREEPAGE DISTANCE : 25mm/KV
C 6. ALL DIMENSIONS ARE IN mm. C
6
MAKE : GEN, CJI OR EQUI
QTY : 3NOS
2
D D
371
11 HEXAGONAL NUT 04
E 1 10 HEXAGONAL NUT ( FOR STEM ) 03 E
09 SEALING WASHER. 01
08 GASKET 01
11 07 VENT PLUG. 01
06 SEPARATOR 01
4
F
05 SEALING WASHER FOR STEM 01 F
04 MS WASHER 04
9
03 CAP 01
02 STEM 01
01 PORCELAIN INSULATOR 12/ 250Amps . 01
TOP COVER # . DESCRIPTION QTY.
G G
A - 41, SECTOR 58, NOIDA (U.P.)
CHKD. APPD.
CLIENT PRODUCT :
REV. DATE DESCRIPTION
DRN. DALBIR 22.6.22
DRAWING NO. : TITLE :
H CHKD. HV BUSHING ASSEMBLY H
ABC/1600/HVB/05
123 PCD
APPD.
12 KV / 250 AMP
REV. PROJECTION SCALE PROJECT NO. OF SHEET- 01
NAME DATE SIGN 01
0 -- SHEET NO. - 01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
110
80
75
45
B B
10- HOLES
C C
130
63.5
35
35
100
D D
45 15
25 50 50
85
E E
25
315
F
FRONT VIEW F
SIDE VIEW
ELECTRICAL SPECIFICATION 2099-1986
1) RATED VOLTAGE 1.1KV
G 2) DRY POWER FREQUENCY WITHSTAND VOLTAGE TEST (1MINUTE) 5KV G
3) MAXIMUM CURRENT CAPACITY: 2500 AMPS
ABC TRANSFORMERS PVT. LTD.
A -41, SECTOR -58 NOIDA,( U.P.)
REV. DATE DESCRIPTION CHKD. APPD. CUSTOMER : PRODUCT :
CSS 1600KVA,11/0.433KV Cu WOUND EEL-1
DRN. DALBIR 25.11.21
DRG NO. : TITLE :
H CHKD. H
ABC/1600/EB/01 1.1KV/2500A, EPOXY BUSHING
APPD.
REV. PROJECTION SCALE ADDL. INFORMATION NO. OF SHEET-01
NAME DATE 01 -- SHEET NO.- 01
SIGN
1 2 3 4 5 6 7 8