679 Volume Flow Transmitter
679 Volume Flow Transmitter
Pressure and flow Huba Control Type 679 | Technical data subject to change | Edition 09/2020 1/5
Technical overview
Measuring range
Flow and velocity for following pressure ranges -1 ... 1 mbar / 0 ... 0.3 – 50 mbar
Operating conditions
Medium Air and neutral gases
Medium / ambient 0 ... +70 ºC
Temperature Storage -10 ... +70 ºC
No condensation
< 3 mbar P1 = 50 mbar P2 = 4 mbar
Application at over pressure range
> 3 mbar P1 = 100 mbar P2 = 4 mbar
Tolerable overload on one side < 3 mbar P1 = -4 mbar P2 = -50 mbar
Application at under pressure range
> 3 mbar P1 = -4 mbar P2 = -100 mbar
ambient temperature 2 x overload
Rupture pressure
70 ºC 1.5 x overload
Electrical overview
Output 1) Power supply 1) Load Current consumption 2)
2 wire 4 ... 20 mA 8.0 ... 33 VDC < supply 0.02
voltage - 8 V
A [Ohm] < 20 mA
0 ... 10 V 13.5 ... 33 VDC / 24 VAC ±15% > 10 kOhm < 10 mA
0 ... 20 mA 13.5 ... 33 VDC / 24 VAC ±15% < 500 Ohm < 30 mA
3 wire 4 ... 20 mA 13.5 ... 33 VDC / 24 VAC ±15% < 500 Ohm < 30 mA
0 ... 5 V 3) 6.5 ... 33 VDC / 24 VAC ±15% > 10 kOhm < 10 mA
Filter Response time switchable by off / 0.2s / 1s / 5s / 20s
Polarity reversal protection Short circuit proof and protected against polarity reversal. Each connection is protected against crossover up to max. supply voltage.
Dynamic response
Response time < 20 ms
Load cycle < 10 Hz
Protection standard
Without cover IP 00
IP 54
With cover
IP 65
Display
Double spaced per 8 digit alphanumeric
LCD Display
At additional backlight LCD-Display 30 mA current consumption
Ranges of adjustment
The zero piont is adjustable by reset button.
The Full scale is adjustable by DIP-Switch and additional by the turbopoti.
Display adjustable between flow and velocity.
Pressure Flow: Velocity:
Available units:
mbar, Pa, mmWS, kPa, hPa, inH2O m3/s, m3/h, cfm, L/s m/s, fpm
Electrical connection
Screw terminals for wire and stranded conductors up to 1.5 mm2
Cable gland with built-in strain relief PG11
Pressure connection
Connection pipe Ø 6.2 mm
Mounting instructions
Installation arrangement Recommendation: Vertical, with pressure connections downwards
Mounting Mounting bracket (integrated in case)
Tests / Admissions
UL
Electromagnetic compatibility CE-conformity acc. EN 61326-2-3
Weight
~ 100 g
Packaging
Single packaging in cardboard
Multiple packaging 20 / 40 / 120
Accuracy
Parameters Unit ±0.5 mbar 0 ... 1 mbar 0 ... 3 mbar 0 ... 5 mbar 0 ... 10 - 50 mbar
Tolerance zero point max. % FS ±1.0 ±1.0 ±0.7 ±0.7 ±0.7
Tolerance full scale max. % FS ±1.0 ±1.0 ±0.7 ±0.7 ±0.7
Resolution % FS 0.2 0.2 0.1 0.1 0.1
Total of linearity, hysteresis and repeatability max. % FS ±1.0 ±1.0 ±1.0 ±1.0 ±0.6
Long therm stability acc. DIN EN 60770 % FS ±1.0 ±1.0 ±1.0 ±1.0 ±1.0
TC-Zero point 4) typ. % FS/10K ±0.2 ±0.2 ±0.2 ±0.1 ±0.1
TC-Zero point 4) max. % FS/10K ±1.0 ±1.0 ±0.5 ±0.4 ±0.4
TC sensitivity 4) typ. % FS/10K ±0.3 ±0.3 ±0.2 ±0.1 ±0.1
TC sensitivity 4) max. % FS/10K ±0.6 ±0.6 ±0.5 ±0.5 ±0.2
- no additional root-extracted errors Test conditions: 25 ºC, 45% rF, Power supply 24 VDC
- For changing diaphragm position, compensable with zero point reset TC z.p. / TC z.p. 0 … 70 ºC
1)
Adjustable by DIP-Switch 2)
At nominal pressure 3)
Additional adjustable by software 4)
TC = Temperature coefficient
2/5 Pressure and flow Huba Control Type 679 | Technical data subject to change | Edition 09/2020
1 2 3 4 5 6 7 8 9 10
Zero @ 50%
Zero @ 10%
0%
0% Pressure 100% -10% 1) Pressure 90% -100%1) 0% 100%
Pressure
1)
under pressure max. acc. order code selection table = -50 Pa/ 100 Pa 2)
Accessories supplied loose
Pressure and flow Huba Control Type 679 | Technical data subject to change | Edition 09/2020 3/5
Dimensions in mm / Electrical connections
92 4
6 11.6
51
35.2
28
97
EN 60 715-TH 35-7.5
4/5 Pressure and flow Huba Control Type 679 | Technical data subject to change | Edition 09/2020
Huba Control AG
Headquarters Schweiz
Industriestrasse 17
CH-5436 Würenlos
Telefon +41 56 436 82 00
Fax +41 56 436 82 82
[email protected]