E2 General Notes and Specification

1) The document provides specifications for a grid-tied solar PV installation with net metering in Koronadal City, Philippines. 2) Key requirements include following the Philippine Electrical Code, using copper THHN wire rated for 600V AC circuits, and ensuring cable insulation resistance is at least 1 mega-ohm. 3) The solar panel installation must include bypass diodes and junction boxes, operate at 85C or less, and use MC4 connectors on panels rated for 450W, 41.5V, and 10.85A.

Uploaded by

rafael velarde
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (1 vote)
980 views

E2 General Notes and Specification

1) The document provides specifications for a grid-tied solar PV installation with net metering in Koronadal City, Philippines. 2) Key requirements include following the Philippine Electrical Code, using copper THHN wire rated for 600V AC circuits, and ensuring cable insulation resistance is at least 1 mega-ohm. 3) The solar panel installation must include bypass diodes and junction boxes, operate at 85C or less, and use MC4 connectors on panels rated for 450W, 41.5V, and 10.85A.

Uploaded by

rafael velarde
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

8 7 6 5 4 3 2 1

GENERAL NOTES AND SPECIFICATIONS


GENERAL NOTES
F Grid Tied Solar PV Installation w/ Net Metering
Grid Tied Solar PV Installation w/ Net Metering F
Equipments, fixtures, materials and installation of the Solar PV System Installation shall conform to Koronadal City Engineering Office
Ordinances and its building code and regulation, Philippine Electrical Code and other applicable National or Provincial codes, Wires and cable for general use for AC circuits from Inverter to AC loads shall be stranded copper conductor with type THHN
insulation rated at 90 Degrees Celsius, 600 Volts. All cable and wires must be installed in raceways.
ordinances and regulation.
All cables and wires must be tested to pass the insulation resistance test (1,000). The insualtion resistance between conductors
The Solar PV Sytem under the Net Metering System for Renewable Energy (RE) was approved on May 27, 013 in Pasig City and from each conductor to ground shall no less than 1 Mega-ohms minimum or more.
by the Energy Regulatory Commission (ERC). A Resolution adopting the rules enabling the Net-Meter Program for Renewable
Energy, Resolution No. 09 series of 2013. Splices or joints are not allowed to be made inside raceways or conduits or ducts. A special junction box for splices and joints
must be fabricated or installed for periodic inspection and maintenance.
Section 8 Compliance Standard:
Grounding conductors for general use shall be stranded, copper conductor, sized in accordance with the Philippine Electrical
The RE System to be installed within the Qualified End-User's (QE) premises must be compliant with the standards set by the
Code (PEC) unless shown otherwise on the drawings, insulated with green THHN insulation rated 90 Degrees Celsius, 600 Volts. The
Philippine Electrical Code, the Philippine Distribution Code (PDC), the Distribution Service Open Access Rules (DSOAR) and the
ground resistance shall not exceed 5 ohms.
Net Metering Interconnection Standards.
The Solar Module Frame must be made of anodized aluminum alloy, with front tempered glass of not less than 3.2mm thick.
Section 9 Interconnection Set-Up: Each module must have six (6) serviceable by-pass diode (3x2 in parallel) with compatible connectors; preferably MC4.
The RE System shall be embedded in the QE's premises and shall install two (2) uni-directional meters, one for the import and one
E for the export, or a single bi-directional meter, whichever is more economical on a case to case basis. The Distribution Utility (DU) The operating temperature must be at 85 Degree Celsius Max and the maximum voltage should be not more than 1,000 Volts at STC. E
may, at any time, also install a third meter in proximity to the RE System to measure the total RE generated. The maximum series fuse rating of all the module shall not exceed 15 Amperes DC. Junction Box must be IP65. PV module cables
will use 2 x 4.0mm2, PV 1-F Tinned Coppper, XLPE, with a rating of 1,000VDC.
Section 10 du Inspection:
The QE shall allow the DU to enter the QE's premises to inspect, test, maintain and operate the protective devices and read or test Protection devices should be installed such as DC & AC Circuit Breakers and SUrge Protection Devices. Protection devices should
of any hazard to the grid or due to maintenance work on the grid. Labels, markings and warning signs, will be installed near the be built-in in the inverter such as Ground Fault Monitoring / Grid Monitoring, DC Reverse Polarity Protection, AC Short Circuit Current.
Connection Point to alert DU Personnel of an RE facility. The AC Box will also provided with disconnecting device for visual
indication of the contact's position and the handle will be lockable with oprn position with a padlock. It shall be readily accesible
at all times by the DU Personnel.
GENERAL NOTES
SCALE : NTS
GENERAL NOTES AND SPECIFICATION
SCALE : NTS

D Inverter Specification
D
PV MODULES Maker HUAWEI
WATTAGE PER MODULE VOLTAGE PER MODULE CURRENT PER MODULE WIRE SIZE PER STRING DC CB PER STRING
NO. OF PV MODULES (WATTS) (Vmp) (Imp) (DC Side) (Amps) CONDUIT SIZE Model SUN2000-20KTL-M2

450 41.5 10.85 2 X 4.0MM2 PER STRING BUILT-IN DC PROTECTION 4" X 6" HDG CABLE
Max. Efficiency
ON INVERTER TRAY / TRUNK
98.8% @480V
RATING: 1,000VDC
36 TOTAL WATTS DC VOLTAGE IN SERIES BRAND: LEADER 50MM DIA EMT PIPE
CURRENT PER MPPT
PV MODULE PV MODULE European Efficiency 98.6% @480V
16,200 166 22
PV Maximum Input Voltage 1080VDC
Solar Panel Specification
MPPT Voltage Range 160V to 950VDC
INVERTER Maker LONGi
C NO. OF INVERTER
WATTAGE PER INVERTER
OUTPUT VOLTAGE, VAC
WIRE SIZE
CIRCUIT BREAKERS SIZE OF WIRE CONDUIT SIZE
Max. Input Current per MPPT 22A C
(WATTS) (Inverter Side) Model LR4-72HPH-450M
3 X 14MM2 THHN WIRE 50AT, 100AF, 12KAIC 3 X 38MM2 THHN WIRE Rated Input Voltage 600 V @ 400V
20,000 400
+ 1 - 5.5MM2 WIRE 3-P, 600V, MCCB + 1 - 14MM2 WIRE Peak Power Watts (Pmax) Wp 450W
40MM DIA IMC
1 SEC. TRANSFORMER WIRE SIZE MAIN CIRCUIT
INVERTER MODEL CIRCUIT BREAKERS 40MM DIA PVC Rated Output Voltage
OUTPUT VOLTAGE, VAC (Sec. Side of Transformer) BREAKER 400 Vac, 3W + PE Maximum Power Voltage (Vmp) 41.5V
SUN2000-20KTL-M3 230 3 X 38MM2 THHN WIRE 100AT, 100AF, 12KAIC 100AT, 100AF, 12KAIC
+ 1 - 14MM2 WIRE 3-P, 600V, MCCB 3-P, 600V, MCCB Max AC output current 33.5A @400V Maximum Power Current (Imp) 10.85A

Nominal Grid Frequency 50Hz/60Hz Open Circuit Voltage (Voc) 49.3V


MATERIALS, DEVICES AND EQUIPMENT TO USE Rated AC Active Power 20,000W Short Circuit Current (Isc) 11.6A
SCALE : NTS
Operating Temp Range -25 C to +60 C Power Production Tolerance 3%

B B

SOLAR PANEL AND INVERTER SPECS


SCALE : NTS

PROJECT PROPONENT: PROJECT CONSULTANT: PROJECT TITLE: GENERAL NOTES: NAME DATE REVISION SHEET CONTENT: SHEET NO.:
A FIL-ASIA ENERGY & REPRODUCTION OF THE DRAWING IN DRAWN RV 01/20/24
>> GENERAL NOTES AND SPECS
A
EURO HYDRO POWER
(ASIA) HOLDINGS, INC.
TECHNICAL SERVICES,
PROPOSE 16.2KWp SOLAR
GRID TIED SYSTEM
ANY FORM IN PART OR IN WHOLE IS
PROHIBITED WITHOUT PRIOR
CHK'D
APPV'D
DESCRIPTION >> GENERAL NOTES
>> MATERIALS, DEVICES AND
2
INC. CONSENT FROM EURO HYDRO POWER EQUIPMENT TO USE
267 JUNA SUBDIVISION, QUIMPO BOULEVARD, BRGY. BUCANA, DAVAO CITY 267 JUNA SUBDIVISION, QUIMPO BOULEVARD, BRGY. BUCANA, DAVAO CITY BRGY. CARPENTER HILLS, KORONADAL CITY
(ASIA) HOLDINGS, INC. DATE OF REV.
>> SOLAR PANEL AND INVERTER
SPECIFICATION
6