0% found this document useful (0 votes)
180 views

EDC-TP-002-Earthing For MV and LV Distribution Networks

This document provides guidelines for earthing medium voltage (MV) and low voltage (LV) distribution networks in Cambodia. It discusses the purposes and types of earthing, including earthing of network masses and neutral conductors. It also addresses earthing connections for MV overhead lines, underground cables, substations, and LV networks. The document provides guidance on proper earthing characterization, implementation, measurements, and technical management to ensure safety and reliability of the distribution system.

Uploaded by

Joe biloute
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
180 views

EDC-TP-002-Earthing For MV and LV Distribution Networks

This document provides guidelines for earthing medium voltage (MV) and low voltage (LV) distribution networks in Cambodia. It discusses the purposes and types of earthing, including earthing of network masses and neutral conductors. It also addresses earthing connections for MV overhead lines, underground cables, substations, and LV networks. The document provides guidance on proper earthing characterization, implementation, measurements, and technical management to ensure safety and reliability of the distribution system.

Uploaded by

Joe biloute
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 32

KINGDOM OF CAMBODIA

NATION RELIGION KING

ELECTRICITE DU CAMBODGE

TECHNICAL POLICY

E DC-TP-002
EARTH INGS for MV and LV distribution
networks
August 2019

Version 1.0

/
EDC-TP-002 - EARTH INGS for MV and LV Distribution Networks

ELECTRICITE DU CAMBODGE

Version Date Technical Policy Name Authorized by:


(name and signature)

Earthing for MV and LV Distribution


1.0 August, 2019
Networks
Dr. ER.A.I.NG ..

Page3/33 (l4
EDC-TP-002 - EARTH INGS for MV and LV distribution networks

Version Drafted/reviewed by Verified by Approved by Date


Drafti AD
Draft 2 AD/EDC Aug/2018
Final AD/EDC Dec/ 2018
Final 1 AD/EDC Aug/2019

Page4/33
EDC-TP-002 - EARTH INGS for MV and LV Distribution Networks

Content
1 PrinciplesofEarthings 8

1.1 Purpose of Earthings 8

1.1.1 Definitions 8

1.1.2 Role of an Earthing/Grounding 8

1.2 The Different Types of Earthing 9

1.2.1 Earthing of the Masses of Electrical Installations 9

1.2.2 Earthing of the Neutral Conductor 10

1.2.3 Earthing for Protections of MV Network Overvoltage 10

1.3 Taking into Account the Proximity between Earthing/Grounding 11

1.3.1 Elevation of Soil Potential Around a Ground 11

1.3.2 Electrical Coupling of Earthing 11

2 Earthings Connections of the MV and LV Structures: 12

2.1 MetalofEarthing 12

2.1.1 Copper Conductor 12

2.1.2 Mild Steel Galvanised Conductor 12

2.2 MV Overhead Lines and Underground Cables 13

2.2.1 MV OHL with Bare Conductors 13

2.2.2 Particular Point of Shield Wires 14

2.2.3 MV ABC Overhead Network 14

2.2.4 Underground MV Network 14

2.2.5 MV Overhead/Underground Interface 15

2.3 RMU Cabinets, One Pillar Substations and MV / LV Substations 15

2.3.1 MV RMU Cabinets and One Pillar Substations 15

2.3.2 MV / LV Built or Prefabricated Substations 16

2.3.3 MV / LV Substations in Buildings or with Adjoining Premises 17

2.3.4 Pole Mounted MV / LV Substation 17

2.4 LV Network 18

2.4.1 General 18

2.4.2 LV Overhead Networks 18

2.4.3 LV Underground Networks 19

2.5 Interconnection and Separation Conditions Between the Earthing of the MV/LV Masses and
The LV Neutral Earthing of MV / LV Substations

2.5.1 General / .........


I
2.5.2 Transformation Substation Located in Urban Area

Page 5/33 M rio


EDC-TP-002 - EARTHINGS for MV and LV distribution networks

2.5.3 MV I LV Substation Located in Pen-urban Area 19

2.5.4 Transformation Substation Located in Pen-urban or Rural Area 20

2.6 Specific Locations 20

2.6.1 MV/LVJointPoIe 20

2.6.2 Common Support: LV I Telecommunications Network or Video Communication 20

2.7 Proximity Between MV And LV Network Earthing and Other Facilities of Electrical Energy 20

2.7.1 MV and LV Distribution Networks and HV Transmission Structures 20

2.7.2 MV and LV Networks and Public Lighting Installations 21

2.7.3 Earthing of The LV Network Neutral and LV Installations 21

3 Practical Realization of Earthing/Grounding 21

3.1 Characterization of a Grounding 21

3.1.1 Current Origin 22

3.1.2 Impact on the Number of Earthing Wires 23

3.1.3 Type of Soil 23

3.1.4 Maintenance of the Characteristics of the Earthing 24

3.2 Methodology of Realization of a Grounding 24

3.3 Choice of Techniques and Equipment 25

4 Resistance, Resistivity and Coupling Measurements - Control Policy 25

4.1 Conditions for Intervention on Earthings 25

4.1.1 Reminder of the Risks to be Controlled. 25

4.1.2 Individual Protections 26

4.1.3 Authorizations 26

4.1.4 Operating Process 26

4.2 Method of Measuring the Soil Resistivity 26

4.2.1 Wenner Method 26

4.2.2 Resistivity of Soils 27

4.3 Control and Measurement of the Earth 28

4.3.1 In Urban Areas (see § 2.5.2) 28

4.3.2 Other Areas 29

4.3.3 Measuring the resistance of a grounding 29

4.3.4 Measurement of the Coupling Coefficient 30

4.3.5 Chronology of a Coupling Measure 31

5 TthicajManagementoftheEarthing 31

31

Version Page 6 I 33 'k.


EDC-TP-002 - EARTH INGS for MV and LV Distribution Networks

Page7/33 (L
EDC-TP-002 - EARTHINGS for MV and LV distribution networks

EARTH INGS for MV and LV Distribution


Networks

1 Principles of Earthings

1.1 Purpose of Earthings

1.1.1 Definitions

The earthing of an electrical network consists in connecting its masses, or its neutral conductors, to a
grounding point by means of one or more protective conductors.

A grounding consists of a set of buried conductors, in direct contact with the ground and electrically
connected to each other.

For a small structure (pole) or structure (MV/LV substation etc..), the term 'earthing" is used, and for
major structures (such as HV / MV substations) the term earthing grid" is used.

This document deals with some parts of the earthing of the MV network neutral conductor that is
explained and developed in EDC-TP-001 technical policy.

1.1.2 Role of an Earthing/Grounding

The role of earthing on electrical work is to allow the flow of various fault currents inside the ground,
as lightning currents, fault currents at 50 Hz. or electrostatic charge flow currents.

During the flow of such currents through a grounding point or an earthing, potential differences may
occur between certain points, such as between two distinct metallic masses, or between the earth
electrode and the surrounding ground, or between two points of the ground.

The design of earthing and earthing grid must be such as to ensure:

• The safety of people,

• The protection of power installations,

• The protection of sensitive equipment,

• The fixing of a reference potential.

1.1.2.1 The safety of people


When high currents flow into the ground, safety must be ensured:

• inside the electrical installation, limiting to non-hazardous values the potential difference
between simultaneously accessible masses;

j I i'tHpediate surroundings by limiting the step voltage and the contact (or touch) voltage
to aItis hat are not dangerous for people

Page 8 / 33
EDC-TP-002 - EARTH INGS for MV and LV Distribution Networks

This limitation is achieved through knowledge and control of the distribution of potential at the soil
surface. In the case of an extended electrical installation, the ideal situation is that one that can seek
to approach is the equipotentiality of all the masses.

1.1.2.2 Protection of power installations and equipment operating at low levels of


equipotentiality

The earth network of an electrical structure must limit the effects of potential increases caused by:

• faults at 50 Hz;

• switch operations in generation stations, substations or distribution network;

• Overvoltage of atmospheric origin (surges).

This limitation is the more effective when this earthing facilitates the flow of the current in the ground,
that is to say it has a low earth impedance as well for slow phenomena (50 Hz faults) only and for fast
(high frequency) phenomena, such as those caused by lightning.

In addition to power structures, equipment or stations operating at much lower voltage levels are often
found in substations or power plants: electronic or electromechanical relaying equipment,
telecommunications installations, etc.

This equipment is also exposed to the overvoltage effects experienced by the power structures, with
which they can be linked by resistive (or galvanic), inductive, capacitive or more generally
electromagnetic coupling.

Different equipment placed in the same structure must, when electrically connected, remain attached
to the same potential, including during the disturbances mentioned above. This shows the importance
of the earth resistance and the equipotentiality quality of the earthing grid, especially for low-level
equipment.

1.2 The Different Types of Earthing

In electrical power distribution systems, earthing is usually referred to the part to which it is connected.
Thus, the following earths are identified:

• Earthing of the masses of electrical installations,

• earthing of the neutral conductor,

• earthing for overvoltage protections of the network.

These earthing are the subject of prescriptions described in several articles of the General
Requirements of Electric Power Technical Standard of the Kingdom of Cambodia of July 2004 including
all amendments.

Nevertheless, some important information not clearly mentioned in the PROKAS needs to be explained
as follow:

1.2.1 Earthing of the Masses of Electrical Installations

"The resistance of the earth electrode shall have an appropriate value


corresponding earth connection is intended. (Class of earthing) .) \

1*!'

Page 9/33 / 'EDUinLO


EDC-TP-002 - EARTH INGS for MV and LV distribution networks

Protect people against the risks that will result for them from simultaneous contact with masses and
conductive elements."

The main purpose of these provisions is the protection of persons intervening or approaching the
vicinity of the installations.

These persons must be protected against the risks which would result for them from simultaneous
contacts between two points brought to different potentials (masses and metal parts in connection
with them, floors and walls, etc.).

It is therefore necessary to fix the potential of the earth all the metal parts of an installation. It is for
this purpose that we seek to connect all conductive elements or conductive parts simultaneously
accessible.

A low value of the earth resistance of the masses also makes it possible to limit the rise in local
potential.

1.2.2 Earthing of the Neutral Conductor


"For LV distribution networks the three-phase distribution must include a neutral conductor connected
to a neutral point and grounded. The single-phase distribution must have a neutral point placed directly
to the ground."

This arrangement makes it possible to set the potential of the LV network.

"For MV networks, earthing, via a low value impedance of the neutral point of power transformers of
MV networks..."

In the case of a single-phase MV fault, the impedance inserted in the neutral earthing limits the earth
fault current value to control:

• the rise in local potential;

• induction phenomena on telecommunications installations;

• the electrodynamic and thermal forces on the equipment.

1.2.3 Earthing for Protections of MV Network Overvoltage


The characteristics (shape, extent, etc.) of the earthing surge arresters shall be provided to discharge
the surge voltages of atmospheric origin as they are connected to the surge arrester, as well as the
overvoltage to 50 Hz.

The grounding of spark gaps and surge arresters ensures the protection of the equipment by controlling
the rise in potential that may lead to internal ignitions in the transformer or LV equipment of the MV I
LV substation during the flow of atmospheric overvoltage.

The shape of the grounding must therefore be adapted to the flow of high frequency currents.

This point must be integrated in the choice of the forms of the selected grounding. The recommended
technical solution is the multidirectional surface grounding.

These earth connections must also flow industrial currents in the same conditions as the earthing of
mases.
/

Page 10 I 33 l((
EDC-TP-002 - EARTH INGS for MV and LV Distribution Networks

1.3 Taking into Account the Proximity between Earthing/Grounding

During the potential rise of a grounding, another nearby grounding is likely to rise to potential as well.

1.3.1 Elevation of Soil Potential Around a Ground

The flow of a current I in an earthing causes a rise in potential of the surrounding ground U, which is
function of the resistivity p of the ground and the distance d with respect to the ground.

The value of this potential can be determined by the following approximate formula

u=
2iid
Rod Equivaient hemisphere

C.

Equiva'ent hemisphere

Rod

0
Linear coordinates

Voltage distribution around a rod and its equivalent hemisphere

1.3.2 Electrical Coupling of Earthing

With two neighbours earthing M and N, with respectively resistance RM and RN; the influence of the
flow a current through the earthing M on the earthing N can be represented by the following figure
where RC is the common part of two earth, called coupling resistance.

Pagell/33 4L
EDC-TP-002 - EARTH INGS for MV and LV distribution networks

Masses earthing Neutral earthing

U<

Numerical example - Measured values RM = 28 0, RN = 38 0 and NMR = 60 0

- The calculation (developed in 4.3.4.1) indicates an RC coupling resistance of 3 0 and a coupling


coefficient between earth of the masses and earth of the neutral of about 10%;

- In relation to a distant earthing, the point N will therefore undergo a potential rise of about 10% of
that in the point M.

2 Earthings Connections of the MV and LV Structures:

The grounding rules for MV and LV electrical installations are described below; they are detailed in the
data sheets attached to this document.

2.1 Metal of Earthing

Considering copper stealing in many areas, the conductors used for earthing are different according
the earthing location.

2.1.1 Copper Conductor

35 mm2 copper conductor is used for all "indoor" earthings as built substations, OPS, RMU cabinets,
prefabricated substations, etc.... and for MV and LV underground networks. The whole earthing circuit
is made of copper (outside and inside the soil)

2.1.2 Mild Steel Galvanised Conductor

,.5rrrrtel hot dip galvanized conductor is used for all earthing installed all along a pole. This is
the ca~ ftrr pole mounted substations load break switches recloser surge arresters LV neutral
earthing etc The whole earthing circuit is made of mild steel hot dip galvanized conductor (outside
and inside the oil)

Version 1 Page 12 / 33
EDC-TP-002 - EARTH INGS for MV and LV Distribution Networks

2.2 MV Overhead Lines and Underground Cables

2.2.1 MV OHL with Bare Conductors

2.2.1.1 Poles without apparatus

Mass Cross arm


Pole Type Pole earthing Data sheet ref.
earthing earthing

Metallic pole YES YES (1) By design TDS N°4

Concrete pole NO NO NO No

(1) loop at the bottom of the excavation connected at the bottom of the support

Table 1: Regulatory Provisions for the grounding of MV OHL poles with bare conductors

2.2.1.2 Poles with surge arresters and cross arm only

Surge arresters Cross arm earthing Data sheet ref.

Origin of the earthing Tap connected to the TDS N°9


main earthing circuit from
the surge arresters

Table 2: Grounding of pole with surge arrester

2.2.1.3 Line poles with switch and recloser

The earthing of the masses of these poles are intended to ensure the protection of persons and
apparatus. The conditions are described in Table 2 below.

Air load break switch GIS load break switch GIS recloser

Surge arresters Origin of the earthing Origin of the earthing

Cross arms, frames, Tap connected to the Tap connected to the Tap connected to the
equipment support, main earthing circuit main earthing circuit main earthing circuit
operating rods and from the top cross arm from the surge from the surge
bevel, .... arresters arresters

Apparatus Tap connected Connected at the Connected at the


earthing origin using earthing origin using
35 copper insulated 35 copper insulated
conductor with two conductor with two
forged tin copper lugs forged tin copper lugs
between earthing between earthing
origin and apparatus. origin and apparatus.
(1) (1)

Control box Tap connected to the Tacnti . the


main earthing circuit - s:&ir it
from the surge 4he
arresters (*rjfe

Page 13 / 33 (
EDC-TP-002 - EARTH INGS for MV and LV distribution networks

Masses and One Tap connected to the Tap connected to the


secondary LV terminal main earthing circuit main earthing circuit
ofsupplytransformer from the surge from the surge
arresters arresters

Operating platform Tap connected to the Tap connected to the Tap connected to the
(reinforces concrete or main earthing circuit main earthing circuit main earthing circuit
additional) from the surge from the surge from the surge
arresters arresters arresters

DATA SHEET TDS N°5 TDS N°7 TDS N°8

(1) In case the surge arresters are installed on the apparatus frame, the origin of the earthing
circuit is the apparatus frame. There is no need of connection using copper insulated cable (see
TDS N°6).

Table 3: Grounding of MV switchgear on overhead networks

Note: The LBS or recloser supporting cross arm or bracket is not connected to the earthing circuit
because the equipment is bolted on and is already connected.

2.2.2 Particular Point of Shield Wires

Shield wire is sometime used in area densely hit by lightning. It is to be reminded that a shield wire
only protects OHL against direct stroke and not against indirect strokes. So, installing surge arresters is
mandatory for efficient OHL equipment protection.

It is also necessary to compare the cost of the complete shield wire earthing system (it is reminded
that the wire must be earthed on each pole with an earthing value ~ 1OQ) with the cost of surges
arresters sets (every 400m as example). Most of time the advantage efficiency/cost is at the
advantage of surge arresters sets

In all case, the decision to install shield wire shall be taken by EDC Head office in Phnom Penh.

2.2.3 MV ABC Overhead Network


The cable consists of an insulated steel messenger surrounded by twisted, isolated phase conductors,
and the following provisions are made:

• the steel messenger must be grounded at each end of the line;

• phase conductor metallic screens shall be grounded at each end of the line, and at every joint
(See TDS N°1O.1 and TDS N°1O.2)

2.2.4 Underground MV Network

To allow the flow of one part of the capacitive current between phase and ground in normal service
and secondly of short circuit currents in the event of a ground fault, the phase metallic screens are
connected to the ground at the cable ends.

The interconnection between the screens is performed at each junction (or T); there is no electrical
• • 0
cticn the earth of the interconnection, See TDS N 11.

B These ovisions concern twisted cables with a cross section of less than or equal to 240 mm2
Aiiyother realization (bigger section layering of unipolar conductors doubling of cables etc ) must

Version 1.0 Page 14/33 i,


EDC-TP-002 - EARTH INGS for MV and LV Distribution Networks

be the subject of a specific study taking into account in particular the permanent flowing of heavy
currents in core and screens.

2.2.5 MV Overhead/Underground Interface

The combined grounding circuit of the masses/surge arrester is made of bare 50 mm2 mild steel
galvanized conductors. It consists of an equipotential bonding conductor connecting the support
bracket of the surge arresters and cable termination screens to the earth electrode.

The main earthing circuit start at the surge arrester cross arm.

This grounding is done at the foot of the pole respecting a geometry adapted to lightning currents flows
and the resistivity of the ground.

The following elements are tap connected the earthing circuit:

• the grounding braids of the MV cable screens at the terminations;


• the cross arms of the MV conductors.
There is no need to install an equipotential loop around the pole.

(See TDS N°12)

2.3 RMU Cabinets, One Pillar Substations and MV / LV Substations

2.3.1 MV RMU Cabinets and One Pillar Substations

The equipment must be connected individually by a 35 mm2 copper conductor to an equipotential


bonding conductor forming the earthing collector circuit of the RMU cabinet or one pillar substation.

The latter, must terminate at a point easily accessible (near the door) on a main earth terminal, or earth
collector, provided with a 12 mm diameter copper terminal and 40 mm length in order to allow the
measurement of earth resistance and the installation of short-circuiting and grounding clamps.

No interrupting device (connector, switch, disconnector, etc.) is allowed in this equipotential bonding
conductor.

Using the metallic envelop or body of OPS and RMU cabinet as equipotential bonding conductor is
STRICTLY FORBIDEN. Metallic envelop or body MUST BE CONNECTED to the 35 mm2 copper
conductor equipotential bonding conductor.

The elements to be connected to this equipotential bonding conductor are described in the TDS N°14.

The following main elements can be mentioned: the cabinet envelope if it is metallic, the MV panel
envelope from the terminal provided for this purpose, the transformer is any, the metal screens and
the terminations or separable connectors of the MV cables, the metal reinforcement of the concrete
of the basement, the slab and the operating sidewalk (if it exists), the doors,....

The grounding of the cabinet is carried out at the bottom of the excavation during the execution of the
foundations or if no foundations this grounding is done under the cabinet (40 cm
copper conductors, forming a grid and a closed loop on itself, is arranged o/
cabinet. This conductor emerges inside the cabinet at a height of 0.3 m abov t
and it is connected to the main earth terminal board (see TDS N°16).
(

Page 15 / 33
EDC-TP-002 - EARTH INGS for MV and LV distribution networks

In order to control touch voltages, an equipotential belt is also connected to the main earth terminal
board. This belt (loop) consists of a bare 35 mm2 copper conductors, looped on itself in the immediate
vicinity of its connection to the main earth terminal board. It is buried at a minimum distance of 1 m
around the cabinet between 0.5 m and 1 m (in case of impossibility at a depth of about 0.3 m
minimum).

Earthing circuit is described in the TDS N°15.

Note: Earthing Conductors inside the ground must be as close as possible to direct contact with the
original soil

OPS LV Neutral

A 35 mm2 cross section insulated copper conductor connection is made between the LV distribution
board (from the neutral busbar downstream of the switch or a specific terminal of the switchboard)
and the main earthing terminal board (see TDS N°16) of the OPS.

The conditions for connecting or not connecting the LV neutral to the earth ground circuit are
described in paragraph 2. 4 of this chapter.

2.3.2 MV / LV Built or Prefabricated Substations

2.3.2.1 Masses of equipment

The device masses must be connected individually by a 35 mm2 copper conductor to an equipotential
bonding conductor forming the earthing collecting circuit of the substation.

The earth circuit, consisting of a 35 mm2 cross section copper conductor, shall terminate at an easily
accessible point on a main earth terminal board or earth collector with a copper terminal of 12 mm.
mm in diameter and 40 mm in length to allow measurement of earth resistance and installation of
clamping devices for short-circuiting and earthing.

No interrupting device (connector, switch, disconnector, etc.) is allowed in this equipotential bonding
conductor.

Using the metallic envelop of the prefabricated substation as equipotential bonding conductor is
STRICTLY FORBIDEN. Metallic envelop or body MUST BE CONNECTED to the 35 mm2 copper
conductor equipotential bonding conductor.

The elements to be connected to this equipotential bonding conductor are described in the
corresponding data sheets.

The following main elements can be mentioned:

• Steel reinforcement of the concrete by a connection connecting one of the bars of the
reinforcement to the main equipotential bonding conductor
• the MV cable screens via the protective conductor of the MV switchboard;
• the MV RMU via a terminal provided for this purpose;
• the sarn.t of LV switchboards;
atab!etiys
.thé transforrne tank;
earth terminals of measurement transformers, capacitors, etc.

Version 1.0' Page 16 / 33


EDC-TP-002 - EARTH INGS for MV and LV Distribution Networks

• protective metal screens and panels;


• the cell fences, the control panel of the devices and the various fittings in the open type
substations
• the doors;
• the masses of control equipment
• envelop of metallic prefabricated substation
• any other metal masses.
The grounding of the substation is carried out at the bottom of the excavation during the execution of
the foundations or if no foundations this grounding is done under the substation basement.

A bare 35 mm2 copper conductor, forming a grid and a closed loop on itself, is arranged on the surface
of the substation. This conductor emerges inside the cabinet at a height of 0.3 m above the floor and
it is connected to the main earthing terminal board (see TDS N°16).

In order to control touch voltages, an equipotential belt is also connected to the main earth terminal
board. This belt consists of a bare 35 mm2 copper conductors, looped on itself in the immediate vicinity
of its connection to the main earth terminal board. It is buried at a minimum distance of 1 m around
the cabinet between 0.5 m and 0.8 m depth (in case of impossibility at a depth of about 0.3 m
minimum).

Earthing circuit is described in TDS N°15.

2.3.2.2 LV neutral

A 35 mm2 cross section insulated copper conductor connection is made between the LV distribution
board (from the neutral busbar downstream of the switch or a specific terminal of the switchboard)
and the main earthing terminal board of the substation (see TDS N°16).

The conditions for connecting or not connecting the LV neutral to the earth ground circuit are
described in paragraph 2. 4 of this chapter.

2.3.3 MV / LV Substations in Buildings or with Adjoining Premises

When the substation is integrated into a building civil engineering structure, and in particular because
of the existence of an earthing network for this building, the equipotential belt is not necessary.

When the surface of the substation is predominant in relation to the built-up unit (adjoining room, etc.)
or if this set does not have an earthing network, an equipotential belt is to installed around the building
(substation and premise).

2.3.4 Pole Mounted MV / LV Substation

The origin of the earthing circuit of the masses and surge arresters (combined both) is the support
bracket (or cross arm) of the surge arresters.

A bare 50 mm2 mild steel galvanized conductor starts from this fitting until the grounding inside the
ground at the bottom of the support.

The transformer tank is to be connected to the origin of this circuit by an insulated c.


of 35mm2 of cross section using two tin copper forged lugs. ,

I*/

Page 17/33 : \
EDC-TP-002 - EARTH INGS for MV and LV distribution networks

The other masses to be connected individually to this earth circuit, in derivation by a conductor of the
same section, are the following:

• the cross arm of the line conductors

• The FCO cross arm

• the fixing system for the LVDB

• the metal frame of the operating platform (if any), etc.

The transformer supporting cross arm or bracket is not connected to the earthing circuit.

This section is described in TDS N°17.

Note: The installation of an equipotential loop for the pole mounted MV/LV substation is not required.

2.4 LV Network

2.4.1 General
In order for the equipment to have no mass, it must be double insulated or reinforced by construction
or installation.

This provision is part of the design of LV networks at ELECTRICITY du CAM BODGE and most of utilities.
Thus, a level of isolation, by design or implementation, of at least 6 kV of equipment used on the
networks was chosen. Under these conditions, earthing only concerns the neutral conductor.

The Cambodia PROKAS set the neutral earthing value to a maximum of 10 Q or 5 0 without mentioning
if this value is the global value for the whole LV neutral or if this is a maximal individual value.

Nevertheless, considering the network development in Cambodia and the troubles encountered on
the network in case of MV fault that could flow through the LV neutral, it is then propose to set up
to 10 0 the maximum resistance value of an individual grounding neutral and to a maximum of 5 0
for the LV neutral global value.

This value must therefore be respected in all circumstances. However, in areas where there are few
individual neutral groundings, it is recommended to have a maximum individual value of 10 0, the goal
being that all interconnected neutral grounding points is in accordance with the value requested for
the overall resistance of the neutral.

2.4.2 LV Overhead Networks


An aerial LV structure concerns the aerial LV network in bare conductors and the aerial LV network
made with LV aerial bundled conductors.

In all cases, the neutral conductor must be grounded in more than one point.

At a minimum, neutral grounding must be done by start under the following conditions:

• in addition to a point if the length of the network exceeds 100 meters,


• with a minimum average number of neutral earths of one for every 200 meters of network.
lnprácte,theV neutral is grounded in the following places

th' first wpport after the MV I LV substation;


• :tthe4tjOrk ends;

VersiOn 1. Page 18 / 33
EDC-TP-002 - EARTH INGS for MV and LV Distribution Networks

• at each network branch;


• close to important nodes of customer connections.
See TDS N°18 and TDS N°19.

2.4.3 LV Underground Networks

Grounding of the neutral on an underground LV network is located at the following points:

• to each junction or branch accessoryon the network,


• Cabinet: connection, cut-off, sectioning cabinet, protection cut-off box.
The earth electrode consists of an earthing net made of copper with a total cross section of about 35
mm2 placed in the bottom of the trench directly in contact with the natural ground; this net is
electrically connected to the neutral conductor of the network incoming cable.

These provisions are such that for each section of LV cable between two connection accessories
includes at least one neutral earthing so that the grounding of the neutral is maintained regardless of
the operating scheme; thus, when disconnect a cable section, the short-circuiting of the conductors at
the same time ensures the grounding through the neutral.

SeeTDSN°2OandTDSN°21.

2.5 Interconnection and Separation Conditions Between the Earthing of the MV/LV
Masses and The LV Neutral Earthing of MV / LV Substations

2.5.1 General

The design of the networks must be such that the earth flowing of a MV fault current does not generate
a rise in potential of the LV conductors beyond 1500 volts compared to a distant earth.

According the network structure, the following rules, applied to three categories of MV / LV
substations:

2.5.2 Transformation Substation Located in Urban Area

An area is called urban if, the MV feeder being entirely underground, there is continuity of the
protective conductors and equipotential links (screens and / or armour of the MV cables) from the
HV/MV station to the considered MV/LV substation. An equipotential network is thus constituted. In
addition, this underground network is not subject to atmospheric currents.

In this zone, the overall value of earthing of the masses is considered to be less than 1 ohm: a
connection is made between the neutral of the LV switchboard, downstream of the main switch, and
the grounding circuit of the substation masses.

See TDS N°22.

2.5.3 MV / LV Substation Located in Pen-urban Area

In a so-called pen-urban zone, the continuity of the cable screens from the HV/MV station to the MV!
LV substation is not assured, but there is electrical continuity in more or less extejs.e..reas
(underground networks, sub-urban zones, craft or industrial, ...). In addition, the el%fiTJ
between earth connections is sometimes difficult to reach. / ' v'
Also, if all of the following conditions are true:
"' g A
t:'

I *
;...
EL..
.\

(2
Page19/33 fkC
-.
EDC-TP-002 - EARTH INGS for MV and LV distribution networks

• Earthing of neutral MV of type 800 amps (phase/ground fault current) at least,

• Earthing value of considered the MV / LV substation is ~ 10 C),


• Overall earthing value of the LV neutral of the considered MV / LV substation is ~ 5 C),

• Global grounding value of the interconnected masses plus LV neutral (MV cable network, MV
/ LV, LV neutral) of the zone is ~ 1 C).
The LV neutral and the substation masses can be interconnected in a manner identical to that one
specified in 2.5.2.

If this is not the case, the electrical grounding of the neutral LV and earth ground of the MV masses is
carried out under the conditions described below in 2.5.4. and are electrically separated.

See TDS N°22.

2.5.4 Transformation Substation Located in Pen-urban or Rural Area

If the provisions mentioned above are not observed, the mass earthing of the MV / LV substation is
electrically separated from the LV neutral earthing.

The grounding of the LV neutral is then carried out with clear separation from mass earthing and at a
distance such that, depending on the resistivity of the ground and its environment, the coupling
coefficient between the grounding of the MV masses and the first earthing of the LV neutral is less
than 15%.

The measurement conditions and the calculation of the coupling coefficient are detailed in § 4. 3. 4

So, in case of LV ABC network, the first LV neutral earthing is located at the first pole after the
substation. This is the case for all LV feeders.

In case of LV underground network, the first LV neutral earthing is located at the first connecting
accessory inside a cabinet.

2.6 Specific Locations

2.6.1 MV / LV Joint Pole

A mixed line pole with an MV network and a LV network must not have a neutral LV earthing.

2.6.2 Common Support: LV / Telecommunications Network or Video Communication

In order to limit the potential rise associated with the coupling between earth connections, an
individual grounding of the LV neutral must not be carried out on a support comprising a
telecommunication or video network grounding.

2.7 Proximity Between MV And LV Network Earthing and Other Facilities of Electrical
Energy

2.7.1 MV and LV Distribution Networks and HV Transmission Structures

The gej faizteristics of realization of the earthing of HV towers are the following ones:

• The eat1 ff tte HV pylons (115 kV, 220 kV and 500 kV) is made by three loops on each of
/;the four feif-v1th an overall resistance of the grounding less than 10 0.

Version Page 20/ 33 4


EDC-TP-002 - EARTH INGS for MV and LV Distribution Networks

These characteristics make the radius of the equivalent hemisphere of the widest loop is of the order
of 5 meters for the towers.

Now, in general, we consider that two earthing networks are electrically distinct if their distance is
greater than ten times the radius of the equivalent hemisphere of the largest.

Also, to guard against an excessive potential rise by coupling on MV and LV neutral earthing of
distribution facilities a minimum distance of 50 meters from an HV steel tower must be respected.

Note: These values may be lower if the HV line has a shield wire.

2.7.2 MV and LV Networks and Public Lighting Installations

Public lighting installations are installed in accordance with the Cambodia recommendations. In
particular the candelabra drums are either grounded individually or interconnected by a ground
conductor providing equipotential bonding.

In the event of a ground fault on a nearby power distribution system, the potential for ground-level
candelabra drums must be controlled, resulting in recommendations to the extent practicable. The
following separation rules between distribution networks and public lighting networks.

2.7.2.1 Ground connections of MV masses and public lighting installations

In urban or pen-urban areas, and when the LV neutral and the MV masses are interconnected, there
are no separation conditions to be respected, nor a particular search for equipotentiality between the
networks.

In other areas, the arrangements to be made are those ensuring the separation between a MV masses
grounding and a LV neutral earthing (see chapter 1.3.2).

2.7.2.2 LV neutral grounding and public lighting installations


In urban or pen-urban areas, and when the LV neutral and the MV masses are interconnected, there
are no separation conditions to be respected, nor a particular search for equipotentiality between the
networks.

In the other zones, a minimum distance of 2 meters between an earthing of the LV neutral and a public
lighting installation connected to the ground (candelabra, equipotential bonding, ??) is to be taken into
account as far as possible.

2.7.3 Earthing of The LV Network Neutral and LV Installations

In urban and pen-urban areas, when the LV neutral and the MV masses are generally interconnected
(see § 2.5), there are no separation conditions to be respected, nor any particular search for
equipotentiality.

In the other zones, a 10-meter protective distance between an earthing of the LV neutral and the earth
ground of the customer must be respected as far as possible.

3 Practical Realization of Earthing/G rounding

3.1 Characterization of a Grounding


ji
From an electrical point of view, a buried conductor in the ground can be pa
circuit comprising resistors, inductors and capacities. ( -o

Page2l/33 (k
EDC-TP-002 - EARTH INGS for MV and LV distribution networks

Electrical representation of a buried conductor

Depending on the nature of the currents to flow (HF currents due to lightning or 50 Hz currents due
to electrical faults) and the type of soil, some of these circuits become predominant.

3.1.1 Current Origin

It has been demonstrated that the geometry of the earth electrode has an influence on its effectiveness
in draining currents generated by lightning (surge); this allowed to state the following
recommendations illustrated in the figure here after.

Impact of the conductor length

100-

00-

Zeff 7,c irn


60- 10
5 iii
0 rn
100 rn
1000 m
2U -

0 I I

kFIz100
o,00i ooi oi I ic jJfflJ 100000

Frequency response of a buried horizontal conductor of variable length in a medium soil resistivity
(100 ftm)

For a given frequency, there is a length beyond which the efficiency of a linear grounding conductor no
longer increases.

Page 22 I 33 /14
EDC-TP-002 - EARTH INGS for MV and LV Distribution Networks

3.1.2 Impact on the Number of Earthing Wires

1441
fl

I 20

1110 Om
80 25m

60 1
• 4fl
— — — I2m

.0

0
10 11W 1000 kUz 10000
/. .

Frequency response of a grounding stranded (1 x 50 m, 2 x 25 m, 3 x 16 m and 4 x 12 m) in a high


resistivity of soil (1000 ftm)

For a low frequency (50 Hz) earthing resistance and the same total length of buried conductor in the
ground, a high frequency earthing made with several conductors with a central point of current
injection is more effective than a grounding made with a single conductor.

So, an earthing intended for flowing high frequencies current (about 1 MHz) is to be designed by taking
into account these two parameters.

An earthing that only drain current at 50 Hz must consider only a low frequency impedance matched
to its use.

On facilities connected to overhead lines such as earthing connections will flow these two types of
current, the earthing design must take all this into account.

As summary, earthing rods are efficient to flow 50Hz currents only and an earthing comprising three
120° earthing conductors of 10 m length is efficient to flow atmospheric and 50 Hz currents.

3.1.3 TypeofSoil

The impedance of a grounding and the distribution of the potential in the ground depend on the
electrical characteristics of the ground that is to say on its resistivity. This is why the design of the earth
network of an electrical installation must begin with a study of the nature of the soil in which it will be
realized.

The resistance of an earthing network is proportional to the resistivity of the soil and subsoil in which
it is buried. However, the resistivity of the natural grounds presents the following peculiarities:
• it is extremely variable from one place to another depending on the nature of the soil and the
moisture content. Extreme values encountered in practice can vary from a few ohm-meters for
greasy and wet ground to a few thousand ohm-meters for very healthy and veryjgranites
(see § 5.2.3);
• at a given location, the soil is often heterogeneous, both horizontally an
• the resistivity of the surface layers of a site presents seasonal variati
frost and drought (which increase it) or humidity (which decreases itt. 1ii
to a depth of several meters in extreme and prolonged climatic conditiari

eS' /'
Page 23 / 33 iY i&i4$
L --' V
EDC-TP -002 - EARTH INGS for MV and LV distribution networks

3.1.4 Maintenance of the Characteristics of the Earthing

A grounding must be strong enough and designed to withstand mechanical, thermal, chemical and
electrochemical degradation.

Earthing and equipotential bonding conductors must be protected against mechanical and chemical
damage; their connections to the ground, in the ground, the neutral point or the neutral conductor
and to each other must be made in such a way as to avoid untightening or loosening.

3.2 Methodology of Realization of a Grounding

The realization of a grounding must be the subject of a preliminary study integrating the nature of the
currents to be discharged, the ohmic value of grounding to obtain, the resistivity of the ground, its
location and its proximity to the neighbouring networks, its form and the components to be used (the
results of this study must be part of the implementation design file).

The diagram below summarizes this implementation approach

Analysis and classification of the area

Urban area Pen-urban area Pen-urban or rural area

Implementation of masses Mesure of soil resistivity Mesure of soil resistivity

Verification of MV cables Implementation of earthing Implementation of earthing


screen continuity and Mesure and mesure

Checking of cumulative Verification of thecoupling


interconnection conditions coefficient between HV
Paragraph 2.5.3 masses earthing and LV
neutral earthing (<15%)

Yes No

Verification of MV cables Verification of thecoupling


screen continuity coefficient between HV
masses earthing and LV
neutral earthing (<15%)

Interconnection of masses
and LV neutral earthing

,
J'riocficthecks every 5 years Condition of interconnection ohmic value improvement if necessary

\ Figure 6: Diagram of step of realization of a grounding

It4, /
Version Page24/33
EDC-TP-002 - EARTH INGS for MV and LV Distribution Networks

3.3 Choice of Techniques and Equipment

Once the shape of the grounding has been determined (see Technical data sheet N°3), we use:

1. For soil of low resistivity:


• Earthing rods. In order to overcome the seasonal variations of humidity the length of rods
shall be of at least 3 meters (3 meters rods or self-expandable rods). The connection of
the earthing cable to the rod is imperative to be done by an approved or authorized
equipment or technique in particular, the use of the car battery terminal is forbidden. It
is reminded that this kind of earthing done with rods is efficient only for 50Hz currents
so rods cannot be used for surge arrester earthing.
• Grounding made by earthing net or/and folded bare conductor at the bottom of a 80 cm
deep trench.

2. In areas of medium and high resistivity soil:


• Grids of earthing nets; these increase the surface of contact between earthing circuit and soil
and allow to lower substantially the ohmic values; arranged in a star form with at least 3
earthing nets, they also provide a satisfactory answer in high frequency current flow, by their
capacitive coupling.
• Conductive modules, with "chemical' coating, arranged in line or in star; these modules give
good results for both types of current to flow (50 Hz and lightning); for a good ohmic value
search, it is also possible to use them in deep drilling, associated with bentonite.

Depending on the nature of the soil and the use of the earthing, the realization of a "deep" grounding
by drilling, can allow the lowering of the ohmic value at low frequency (and only this one); before any
commitment of realization, it is essential to know the resistivity of the various layers of ground
(measurements, geological maps, ...). These deep earthings are effective only for currents at 50 Hz.

It is to be noticed that for some specific cases, the ohmic values can be drastically lowered by using
specifically minerals salts and component added in the bottom of the trenches in case of folded
earthing wire or earthing nets. The right value is obtained after several weeks but in case of very wet
soil the ohmic value will decrease after several months or year because water wash the components.
This is why this kind of earthing must be verified each 2 years

Note: use of conductive modules with chemical product or mineral salts for solving some specific
cases, EDC head office must be informed and only EDC head office will take the decision for using
such products.

4 Resistance, Resistivity and Coupling Measurements - Control Policy

4.1 Conditions for Intervention on Earthings

4.1.1 Reminder of the Risks to be Controlled.

A ground fault current flowing causes its rise in potential; at this moment, a person touching this
earthing or being close to, may be subject, depending on the circumstances, to a potential difference
called touch voltage or step voltage respectively.

Touching a metallic piece not connected to a ground and accidentally carri


electrical hazard. This is why it is forbidden, except special precautions, to oiie
structure in service. I

Page 25/33 /t ii
EDC-TP-002 - EARTH INGS for MV and LV distribution networks

In addition, the earth connections of certain installations may be influenced by the presence in the
vicinity of other installations, for example railway networks, cathodic protections, etc.

4.1.2 Individual Protections

In the case of a structure in service, the operator must wear LV protection equipment equivalent to
that of the LV hot line work (helmet, facial screen, insulating gloves, specific wear, safety shoes, etc....)
and use the LV insulating mat.

4.1.3 Authorizations
The operator responsible for taking measurements on the earthing circuits or on the neutral conductor
must be authorized to work on networks in the voltage range (MV and I or LV) and for the type of
structure concerned.

4.1.4 Operating Process

It is forbidden to intervene during thunderstorms on the earthing circuit of a structure in service.

In case the work requires the opening of the earthing circuit of a structure in service, the continuity
of the grounding of each circuit element to be separated must be ensured: either by placing a shunt
maintained throughout the intervention, either by connecting the part to be separated from the
earth ground to an existing or created auxiliary earth ground.

4.2 Method of Measuring the Soil Resistivity

4.2.1 Wenner Method


The method for measuring the apparent soil resistivity to be used is the method of Wenner, in which
the four electrodes are arranged in line and equidistant.
The measuring device is a four-terminal earthing measurement apparatus approved or authorized for
use. The two end electrodes are those of injection of the measurement current I; the two central
electrodes are those for measuring the potential AV.
The point "0" of the resistivity measurement is in the middle of a symmetrical system, between the
potential electrodes.
The distance 'a' between two adjacent electrodes is called "measurement base"; the distance between
the end electrodes on the "transmission line" is "3 a".

-
Figure 7: Measurement of soil resistivity

Page 26 / 33
EDC-TP-002 - EARTH INGS for MV and LV Distribution Networks

Equipment: 4 wires earthing measurement apparatus

0: position of the future grounding

Note: All measuring rods must be installed in straight line

General formula giving the value of the apparent resistivity:

p = 2R .a .R

p = resistivity in ohm. meter (Q.m)

a = distance in meters (m)

R = value in ohm read on the earthing measurement apparatus (0)

Example: for a depth of investigation of three meters, a is 4 m and two measurements in two
directions if possible perpendicular are to realize

In this case, p = 25 R

Knowing that the value obtained from p is an average value for a depth approximately equal to 0.75 x
"a", it is possible by varying the distance "a" to deduce the profile of the resistivity variations at depth.

For example, the values of "a" recommended to verify the validity of the possible use of rods of 3
meters and 6 meters are 4 meters and 8 meters.

In practice, two measurements will be made with a = 4 meters in two perpendicular directions.

These indications make it possible to predetermine a satisfactory solution for the realization of a
grounding and thus avoid successive improvements.

4.2.2 Resistivity of Soils

The typical resistivities according to the nature of the soil are given in the table below.

Soil type Resistivity (ftm)

-Wetland and rich in plant debris

Swampyland 5to30

Limon 20to 100

Humus lOto 150

Peat 5 to 100

-Clays and marl-limestone

Plastic clay 50

Compact mans and clays 100 to 200

Jurassic marls 30 to 40

-Sand and gravel /v

Claysand 50tcf

If Q /
7)
Page 27/33 0
EDC-TP-002 - EARTH INGS for MV and LV distribution networks

Soil type Resistivity (ftm)

Silty sand 200 to 3000

Bare stone floor 1500 to 3000

Stony soil covered with turf 300 to 500

-Limestone and shale

Limestone 100 to 300

Compact limestones 1000 to 5000

Cracked limestones 500 to 1000

Schists 50 to 300

Micaschiste 800

-Igneous rocks

Granite and sandstone more or less altered 1500 to 10 000

Granites and veryweathered sandstone lOOto 600

Compact Granites 10,000 to 15,000

Table 4: Typical resistivity of soils

It is recalled that seasonal variations affect the resistivity of the layers of the soil.

4.3 Control and Measurement of the Earth

'Verification of earthing and protective conductors:'

4.3.1 In Urban Areas (see § 2.5.2)

In urban areas it is not possible to perform a correct earthing measurement, given the strong coupling
existing between the auxiliary rods and the earth to be measured. However, it is important to check
that the earth circuits are well connected in each MV I LV substation with the grid of the MV cables.

The measurement of the resistance of the earthing in urban area is not significant and reliable because:

• the difficulty of finding a clear ground for the implantation of the auxiliary measuring
electrodes;
• the practical realization of the MV masses of a station in the cabin which does not generally
allow to isolate electrically the grounding of the MV masses of the other conductors of masses
of the work.

Under these conditions, the arrangement adopted is to control the good continuity of the screens (or
Armor) of the MV cables; it allows the paralleling of all the earth connections of the various MV / LV
nettwe&fed by the same underground feeder.
a

' AJso with iperiodicity of 5 years a visual check is made to verify that the different equipment is
connected to the station s earthing circuit This visual control mainly concerns the screens (or Armor)
of the MV cablEs, as well as the connection of the LV neutral to the grounding circuit

Version 1. Page 28 / 33
EDC-TP-002 - EARTH INGS for MV and LV Distribution Networks

4.3.2 Other Areas

Two cases considered:

4.3.2.1 MV Masses and LV Neutral Earthings Interconnected

• Masses earthing of a new substation must be measured before connection of the MV cables;
• the value of the overall grounding of the zone must be checked every 5 years, as well as the
continuity of the screens and the connection of the neutral (according to the same provisions
as those described in § 5.3.1)

4.3.2.2 Separate MV masses and LV neutral earthings

Are to be measured:

• Mass earthing of the MV / LV substation


• the overall grounding value of the LV neutral (all LV neutral earthing connected to LV
network)
• the coupling between the first earthing of the LV neutral and the earthing of the masses of
the MV ILV substation

The conditions of measurement and control are specified in Technical data sheets N°24.a and 24.b.
below.

4.3.3 Measuring the resistance of a grounding

The method to be used is that known as the potential drop, applied with an authorized four-terminal
earthing measurement apparatus with an on-line arrangement of the auxiliary electrodes.

Earthings to be
measured

Figure 8: Measuring the resistance of a grounding

Note: in the case of the measurement of the overall earthing of the LV neutra/'1f
measurement terminal in the substation (earth plate, specific terminal of a I/I/
or the direct connection to a bar of a LV feeder. The voltage between the msrtA

Page 29/33 jJ
EDC-TP-002 - EARTH INGS for MV and LV distribution networks

LV substation and the LV neutral must be measured before connection to point X and shall not exceed
20 volts to allow the measurements to be carried out; If more, it should be eliminated beforehand.

The device injects a current I, measure V, calculates V / I and thus gives directly: R = V / I

X, Y, Z must be aligned and spaced according to the diagram above (distance XY = 60% of distance XZ).

Wherever possible, Y and Z should not be located on an area where the presence of other existing
earth or buried metal conduit would distort the measurement.

N.B.: experience feedback has shown that the use of a shunt between terminals X and Xv of the
measurement apparatus is likely to generate measurement errors, especially for low values; in this
situation, when calculating the coupling coefficient, inconsistencies may appear (negative coupling, ...).

4.3.4 Measurement of the Coupling Coefficient

4.3.4.1 Coupling between the MV masses earthing and LV neutral earthing

In order determine the coupling coefficient the following measurement are carried out:

• Resistance measurement of the RM value of the masses earthing,

• Resistance measurement of the RN neutral earthing the LV,

• RMN measurement of the resistance between the neutral earthing and the masses earthing.

, RM+RNi—RMN
Then coupling the resistance is calculated using the following formula: c = 2

The coupling coefficient C is then equal to Rc / RM rate. It must remain below 15%.

We must therefore ensure that: RC < 0.15 x RM

LV neutral
Masses earthing
earthhig 14 =
MU

14 R-R
M u MN
Rc
2

Far Earthings

Figure 9: Measurement of the coupling resistance

Page 30/33
EDC-TP-002 - EARTH INGS for MV and LV Distribution Networks

4.3.4.2 Coupling between a MV masses earthing and a telecommunication line grounding

The measurement of the coupling coefficient between an MV masses earthing and a


telecommunication line earthing is similar, with a coupling coefficient however limited to 5%

(R< 0.05 x RM)

4.3.5 Chronology of a Coupling Measure

Measurement of MV Measurement of LV Measurement of coupling between MV masses


masses earthing neutral earthing earthing and LV neutral earthing

Precaution to take Determination of coupling coefficient

* X, Y, Z rods must be aligned and spaced 1 - Measure the resistance RM of the masses
according to the diagram above. The distance XY earthing
= 60% of the distance XZ.
2 - Measure the resistance RN of the first
* Move away from all earthing, metal pipes or grounding of LV neutral
cables.
3 - Measure the NMR resistance between the
* In any case, it is prudent to carry out at least two earthings. (see diagram above)
two measurements by moving the auxiliary rods
4 - Calculate the coupling resistance Rc:
to ensure that the value obtained is independent
of the position of the rods.
Rc = (RM + RN — RMN)/2
* The location of the measurement apparatus
and the position of the auxiliary electrodes can 5 - The coupling coefficient is equal to:
be judiciously chosen from the beginning of the c = R / RM
measurement (Masses — Neutral — Coupling)
Check that c < 0.15

Figure 10: Chronology of a coupling measurement

5 Technical Management of the Earthing

Earthing must be periodically checked and the results of the checking and measurements must be
recorded in a computerized file.

6 Terminology

Main earthing board Board with terminal or bar provided for connection to the main
Terminal or Main earthing conductor ground protection, and possibly the LV neutral conductor
Bar

Protective conductor Conductor intended to electrically connect all or some of the


following elements: ground, conductive elements, earth main
terminal, grounding point, power point connected to earth or to the
artificial neutral point. A protective conductor).açrrs4o
several circuits.
ttt\

Page 31 / 33
EDC-TP-002 - EARTH INGS for MV and LV distribution networks

Main protective conductor Protective conductor to which earth protection conductors, earth
conductors and possibly equipotential bonding conductors are
connected.

Equipotential bonding Protective conductor providing an equipotential bonding.


conductor

Ground conductor Protective conductor connecting the earthing board terminal or


ground bar to the grounding.

Elevation of earth potential Voltage between a grounding installation and the earth.

Impedance of the earthing Impedance at a given frequency of the earthing system, relative to the
reference earth.

equipotential bonding Primary Electrical connection bringing to the same potential, or to


neighbouring potentials, masses and conductive elements. A main
equipotential bonding makes it possible to ensure that, during an
external fault on the installation, no potential difference appears
between elements connected of the installation

Grounding or earthing Conductor or conductive body assembly in intimate contact with the
ground and providing an electrical connection with it.

Separated or independent Earthing/grounding sufficiently distant from one another so that the
earthing/grounding maximum current likely to be flown by one of them does not
significantly change the potential of others.

Overall resistance of Resistance between the main earthing board and the earth.
earthing

Earthing/grounding Resistive component of the grounding impedance


Resistance

Contact voltage (or touch Part of the elevation of ground potential created by a ground fault and
voltage) applied to a person, the current crossing the human body between a
hand and the feet (conventional horizontal distance of one meter).

Step voltage Part of the earth potential rise due to a ground fault and applied to a
person with a step length of one meter, the current flowing through
the human body from foot to foot.

Earthing The conductive mass of the earth whose potential at each point is
taken by convention, equal to zero.

Specific electrical resistance of the soil

Version L Page 32 / 33
EDC-TP-002 - EARTH INGS for MV and LV Distribution Networks

Analysis and classification of the area

Urban area Pen-urban area Pen-urban or rural area

Implementation of masses Mesure of soil resistivity Mesure of soil resistivity

Verification of MV cables Implementation of earthing Implementation of earthing


screen continuity and mesure and mesure

Checking of cumulative Verification of the coupling


interconnection conditions coefficient between HV
Paragraph 2.5.3 masses earthing and LV
neutral earthing (<15%)

Yes No

Verification of MV cables Verification of the coupling


screen continuity coefficient between HV
masses earthing and LV
neutral earthing (<15%)

Interconnection of masses
and LV neutral earthing

Periodic checks every 5 years: Condition of interconnection, ohmic value, improvement if necessary

Page 33/33

You might also like