Fire Alarm Checklist
Fire Alarm Checklist
PL A N C H EC K L IST
( F o r P la n D e sig n R e vie w )
Revised – 07/31/12
Occupancy Type:_______________
(as defined in NFPA 101, the Florida 2009 edition, Chapter 3 – Definitions)
Occupancy Chapter:_______________
(as referenced in NFPA 101, the Florida 2009 edition, Chapter 3 – Definitions)
Occupancy Load:_______________
(show occupant load calculation breakdown using NFPA 101, the Florida 2009
edition, Table 7.3.1.2 – Occupant Load Factors)
YES NO 29. If answer to #27 is yes, has compliance with NFPA 72 (2007 edition) 4.7,
6.8.4.11 and 6.8.6 been demonstrated?
YES NO 30. Is “Emergency Forces Notification” provided in accordance with NFPA 101 –
the Florida 2009 edition and the 2010 FBC section 907.6.5?
YES NO 31. Are all Notification Appliance Circuits (NACs), Initiating Device Circuits (IDCs) &
Signaling Line Circuits (SLCs)… including appropriate EOLs, clearly delineated
and congruent on the both the riser diagram and floor plans?
YES NO 32. Is the class AND style designation shown on the drawings for all initiating,
notification, and signaling line circuits? {NFPA 72 (2007 ed.) 6.4.2.1.1 and
6.4.2.2}
YES NO 33. Is each device, appliance, circuit and component indicated and enumerated on
the floor plan?
YES NO 34. Has a Riser Diagram been provided delineating each floor, circuit and zone and
ALL devices, appliances and/or components?
YES NO N/A 35. In a non-addressable system, is the number of zones shown in the
submittal/drawings and has a Zone Legend been provided?
YES NO 36. Are ALL device and component model #s and quantities of each, specified on
the plan or bill of materials?
YES NO 37. Are ALL components “compatible” and “listed” for the specific fire alarm
applications for which they are used and are all detection devices that receive
power from the IDC or SLC of a control unit listed for use with that control unit as
required by NFPA 72 (2007 ed.) 4.4.2? Provide verification of compatibility
between components and the respective panel.
YES NO 38. Has a detailed Sequence of Operation been provided with the submittal
package (via Input/Output Matrix or Narrative) and does it detail ALL alarm,
supervisory and trouble conditions, as well as ALL emergency functions?
YES NO 39. Are fire alarm system components “listed” for the ambient conditions (i.e.,
voltage, temperature and humidity) expected at the proposed location of the
installed components? {NFPA 72 (2007 ed.) 4.4.4.1, 4.4.4.2.4}
YES NO 40. Are ALL wire sizes, types, quantities, as well as conduit sizes and types, listed
on the riser diagram and floor plan?
YES NO 41. Is all wiring that is located in wet or damp locations, listed for this use (Wet &
Direct Burial) and are specification sheets included? {NFPA 70 (2008 ed.)
110.11, 300.5, 310.7, 310.8}
NOTE: this means that trouble signals from a suppression system control unit
must report to the master FACP as a SUPERVISORY CONDITION , indicating
the interconnected control unit is off-normal. Also, the interconnection between
the suppression system control unit and the master FACP is monitored for
integrity and if that circuit experiences a fault condition, a TROUBLE
CONDITION for that circuit (zone or point) is indicated at the master fire alarm
control unit {NFPA 72 (2007 ed.) 6.8.5.7.2}
YES NO N/A 94. Is the electric Fire Pump monitored for run, phase reversal & power failure?
{NFPA 72 (2007 ed.) 6.8.5.9}
YES NO N/A 95. Is the engine-driven Fire Pump monitored for run, failure to start, controller
off “automatic,” and trouble (e.g., low oil, high temperature, overspeed)?
{NFPA 72 (2007 ed.) 6.8.5.9}
YES NO N/A 96. Is the Generator monitored according to NFPA 110? (note class or type)
{NFPA 72 (2007 ed.) 4.4.1.9.1 through 4.4.1.9.7}
YES NO N/A 97. Are the Elevator Recall detectors connected to the fire alarm system as
required by NFPA 72 (2007 ed.) 6.16.3.1?
YES NO N/A 99. Do the smoke detectors used for elevator recall and the heat detectors used
to shutdown elevator power initiate an alarm condition and actuate the fire
alarm system notification appliances? (Collier County Fire Prevention and
Protection Code Policy and Procedure Manual Articles FAL02-04)
YES NO N/A 100. Is the control circuit used to shut down elevator power monitored for
presence of operating voltage? Loss of this voltage shall indicate a
supervisory signal at the control unit and remote annunciators. {NFPA 72
(2007 ed.) 6.16.4.4}
YES NO N/A 101. Does each audio/visual appliance have its candela rating listed on the floor
plan, adjacent to each appliance?
YES NO N/A 102. Is each visual appliance adequate for the area covered and located per NFPA
72 (2007 ed.) 7.5 requirements? (see also the Appendix section)
YES NO N/A 103. Has the fire alarm system been designed to comply with the ADA and the
Florida Accessibility Code? (NFPA 101 – the Florida 2009 edition, section
9.6.3.5; 2010 FBC section 907.9, 2010 FBC (Accessibility) 702.)
YES NO N/A 104. Are visual signal appliances provided in each of the following areas: restrooms
and any other general usage areas, meeting rooms, conference rooms,
hallways, lobbies and any other area for common use? NOTE: Common use
areas also include classrooms, cafeterias, filing and photocopy rooms, employee
break rooms, dressing rooms, examination rooms, treatment rooms, and similar
spaces that are not used solely s employee work areas. (2010 FBC 907.9 and
2010 FBC (Accessibility) 702., U.S. Architectural and Transportation Barriers
Compliance Board – Bulletin #2)
YES NO N/A 105. Where required to be “ACCESSIBLE” to those with physical disabilities, are
rooms and bathrooms within a dwelling unit provided with appropriate
notification appliance coverage? (i.e. weatherproof strobes in bathrooms,
proper candela ratings, and proper mounting locations for devices/appliances
in the sleeping areas) {NFPA 101 – the Florida 2009 edition, section 9.6.3.5; the
2010 FBC section 907.9; NFPA 72 (2007 ed.) section 7.5.4.6}
YES NO N/A 106. In “ACCESSIBLE” rooms, have provisions been made to actuate the visual
alarm notification appliance(s) by BOTH the in-room smoke alarm and by the
building fire alarm system? {NFPA 101 – the Florida 2009 edition, section
9.6.3.5; the 2010 FBC section 907.9.; NFPA 72 (2007 ed.) section 7.5.4.6}
YES NO N/A 107. Will audible public mode notification appliances produce a sound level at
least 15dB above the average ambient sound level or 5dB above the maximum
sound level lasting at least 60 seconds, whichever is greater, measured 5’ above
the floor in the occupiable area, using the A-weighted scale (dBA)? {NFPA 72
(2007 ed.) 7.4.2.1}
YES NO N/A 108. Do audible appliances provide a distinctive three-pulse temporal pattern fire
alarm evacuation signal? (NOTE: such a signal is not required, with the approval
of the AHJ, if the planned action during a fire emergency is not evacuation, but
rather is the relocation of occupants or their protection in place) {NFPA 72 (2007
ed.) 6.8.6.5}
I hereby attest that, to the best of my knowledge, the aforementioned checklist information and the
battery calculation(s) are accurate and adequate for the fire alarm system being submitted.
E-mail address