Fire Alarm LOA NGP
Fire Alarm LOA NGP
do
CENTRAL RLY
NAGPUR-CR-
DIVISION-S AND T
SR.DSTE/CO OFFICE,
2ND FLOOR, DRM
BUILDING
NAGPUR, 440001
Maharashtra, India
https://ireps.gov.in/epsn/works/tds/publishLOAWorksLetter.do 1/6
1/10/24, 1:19 PM ireps.gov.in/epsn/works/tds/publishLOAWorksLetter.do
Commerce and Industry, DIPP shall be informed to this effect. The failed
Contractor shall be debarred from participating in re-tender for that work.
The entire work shall be completed within 9 month from the date of
issue of Letter of Acceptance.
Condition 2: The work will be carried out under supervision of Sr. Section
Engineer (Sig) Nagpur under ADSTE North
Condition 3: You will deal all the matters with Sr. Section Engineer (Sig)
Nagpur relating to work completion, recording measurements and
preparation of bill etc. for their respective section under ADSTE North
Condition 5: Please submit the detailed execution plan of the work within
07 days after the date of receipt of letter of acceptance and shall commence
the work within 15 days of receipt of acceptance letter so as to complete
the total work within the agreed completion period.
https://ireps.gov.in/epsn/works/tds/publishLOAWorksLetter.do 2/6
1/10/24, 1:19 PM ireps.gov.in/epsn/works/tds/publishLOAWorksLetter.do
complying to
RDSO/SPN/217/2019
Ver 3 or latest moduar,
1 loop (minimum 125
detector/devices per
loop-expandable to 2
loops) with 320
Character with soft keys
for displaying alarm,
events and operating
functions, Day/Night
operation function,
Remote maintenance
service feature etc. The
panel should be multi-
protocol i.e. able to
support at least 2
different makes of
addressable detectors.
The panel should have
minimum two relay
outputs & 1 Monitored
Sounder Output. It
should have provision to
be connected to
repeater panels in
future. The panel shall
capable to operate on
230 volts AC power
supply, automatic
battery charger, 24
volts, sealed lead acid
maintenance free
batteries sufficient for
24 hours normal
working and then be
capable of operating the
system for 30 minutes
during emergency
condition. Panel should
be Vds Certified.(Insp
Agency-RDSO)
Supply, Installation,
Testing &
Commissioning of
Analogue Addressable
Multisensor Detector
2 complying to 2 140 Numbers 3396.99 At Par 475578.60
RDSO/SPN/217/2019
Ver 3 or latest As per
latest VDS
approved/Listed (Insp
Agency-RDSO).
Supply, Installation,
Testing &
Commissioning of
Manual call points,
complying to
3 3 15 Numbers 5226.59 At Par 78398.85
RDSO/SPN/217/2019
Ver 3 or latest As per
latest VDS
approved/Listed. (Insp
Agency-RDSO)
4 Supply, Installation, 4 300 Metre 1414.13 At Par 424239.00
Testing &
Commissioning of
Resettable, Analogue
Type Liner Heat Sensing
(LHS) Cable complying
to RDSO/SPN/217/2019
Ver 3 or latest As per
latest UL or FM of LPCB
https://ireps.gov.in/epsn/works/tds/publishLOAWorksLetter.do 3/6
1/10/24, 1:19 PM ireps.gov.in/epsn/works/tds/publishLOAWorksLetter.do
approved/Listed. (Insp
Agency-RDSO)
Suply, Installation,
Testing &
Commissioning of LHS
Interfaxe Module with
all accessories for single
stretch, complying to
5 5 15 Numbers 134184.14 At Par 2012762.10
RDSO/SPN/217/2019
Ver 3 or latest As per
latest UL or FM of VDS
of LPCB
approved/Listed.(Insp
Agency-RDSO)
Supply, Installation,
Testing &
Commissioning of
Analogue Addressable
loop powered Monitor
6 6 30 Numbers 8745.91 At Par 262377.30
Module with inbuilt
isolator complying to
RDSO/SPN/217/2019
Ver 3 or latest. (Insp
Agency-RDSO)
Supply, Installation,
Testing &
Commissioning of
Analogue Addressable
7 loop powered Control 7 30 Numbers 8745.91 At Par 262377.30
Module complying to
RDSO/SPN/217/2019
Ver 3 or latest. (Insp
Agency-RDSO)
Supply, Testing &
Commissioning of
Hooter cum strobe
8 complying to 8 15 Numbers 7748.34 At Par 116225.10
RDSO/SPN/217/2019
Ver 3 or latest. (Insp
Agency-RDSO)
Supply, Testing &
Commissioning of 2C
1.5 sq mm twisted
shielded armoured
copper cable (Per Meter)
9 9 900 Metre 113.39 At Par 102051.00
with accessories
complying to the
RDSO/SPN/217/2019
Ver 3 or latest. (Insp
Agency-Consignee)
Suply, Testing &
Commissioning of
Isolator Device to
isolate the circuit in case
10 of short circuit, 10 15 Numbers 3721.39 At Par 55820.85
complying to the
RDSO/SPN/217/2019
Ver 3 or latest. (Insp
Agency-RDSO)
Schedule Totals 0.00
Supply of Master
Telephone of Electronic
LC gate Communcation
system as per RDSO
specification No.
1 RDSO/SPN/TC-51/2021 1 5 Numbers 50445.00 At Par 252225.00
(Rev 2013 1.0 or latest)
with voice logging
facility with latest
amendment .(Insp
Agency-RDSO)
Supply of Slave
Telephone for Electronic
LC Gate communication
system with Voice
2 logging facility as per 2 20 Numbers 4779.00 At Par 95580.00
RDSO Specification No.
RDSO/SPN/TC/51/2011
Rev. 3.0 or later. (Insp
Agency-RDSO)
Limit Switch new top
roller with 2 NO + 2NC
contacts for HEIDZ
Make Electrically
Operated Lifting Barrier
as per IRS-S41/70 and
3 3 200 Numbers 463.74 At Par 92748.00
as per RDSO
specification No.
RDSO/SPN/208/2012
ver 2.0 Make :
JAIBALAJI (Insp Agency-
Consignee)
4 3 Pole power contactors 4 60 Numbers 592.36 At Par 35541.60
with coil voltage suitable
for 110V AC coil with
minimum 9A current
rating, inbuilt 1NO+1NC
auxiliary contacts
suitable for use in
Indian Railway
Electrically operated
gates. Make: Schneider,
L&T, Siemens, Havells or
https://ireps.gov.in/epsn/works/tds/publishLOAWorksLetter.do 5/6
1/10/24, 1:19 PM ireps.gov.in/epsn/works/tds/publishLOAWorksLetter.do
similar make (Insp
Agency-Consignee)
Rotary Switch 10Amp
rating 4 NO + 4 NC
contacts, 4 pole for
Indian railway Signalling
5 5 200 Numbers 306.80 At Par 61360.00
operation. Make:
Kaycee, L&T,
Schneider,Havells (Insp
Agency-Consignee)
Boom stand and
solenoid lock assembly
suitable for 110V AC
Heidz make electric
lifting barrier as per
6 6 10 Numbers 26290.40 At Par 262904.00
RDSO Specification
RDSO/SPN/208/2012
Ver 2 or latest
amendment. (Insp
Agency-Consignee)
New magnet switch for
boom lock, magnet
proximity switch in
robust AL Die cast body
with dual contacts and 2
magnets for actuation
7 7 80 Numbers 1298.00 At Par 103840.00
for Heditz make
electrical lifting barrier
at various interlocked
level crossing gates.
(Insp Agency-
Consignee)
Schedule Totals 0.00
Total Value 6160775.80 4.00 %Below 5914344.77
Rebate on Total Value
0.00
(%)
Net Bid Value 5914344.77
Item Breakup
No break up item added