Distance Protection
Distance Protection
SUBSTATION ELECTRICAL
PROTECTION & SWITCHGEAR
PRESENTED BY
2
Agenda
• Persistent faults
– can be caused by a broken conductor fallen down
– can be a tree falling on a line
– must be located and repaired before normal service
Warrington´s formula
L= length of arc in meters
I= the actual fault current in A Tower Footing resistance
Zk B
A
Ik
Z<
Distance protection= Under Impedance + Directional
NILE POWER COMPANY
General Line Protection
12
The principle of distance protection
• Power lines have impedances of size 0,3- 0,4 ohm/ km and normal
angles of 80 - 85 degrees in a 50Hz systems.
A B
ZL=R+jX
Z< Z<
IN RN XN
Zs RL XL
IL1
UL1-L2 IL2
2- Operating Characteristic
Fast Operation
Directional Discrimination
RF Quadrilateral characteristic
X R
F
Z3 Z3
t3
t2 Z2 Z2
t1 Z1 Z1
l
A B C
f1 f2 f3
~ ZOM ~
ZL
~ ~
• In double circuit lines and parallel lines the zero sequence coupling
will result in measuring errors, specially at ground faults.
PSB IN
PSB out
R
t
t = 40 ms
5- Communication scheme
Z< Z<
NILE POWER COMPANY
General Line Protection 31
Communication equipment
A B
Z< Z<
Communication equipment
NILE POWER COMPANY
General Line Protection 32
Z< Z<
Communication equipment
Z< Z<
7- Switch on to fault
CR CS (echo)
Z< Z<
t3 CS CR
t2
t1
CS = ZM2 TRIP = ZM1 + ZM2(CR + t2)
l
CS (echo)=CR x low voltage x no start forward or reverse
CS (Echo & Trip)=CR x low voltage x no start forward or reverse
NILE POWER COMPANY
General Line Protection 42
• Time required for the de-ionising of the fault path depends on:- arcing
time, fault duration, wind conditions, circuit voltage, capacitive
coupling to adjacent conductors, etc.
• Single phase dead time of 1.0 sec is recommended for both 400kV
and 220kV system.
• If reclosing shot has been carried out and the line is energized and a
new fault occurs before the reclaim time has elapsed, the auto-reclosing
equipment is blocked and a signal for definite tripping of the breaker is
obtained.
• The reclaim time must not be set to such a low value that the intended
operating cycle of the breaker is exceeded, when two faults incidents
occur close together.