Power System Protection - Overcurrent Protection
Power System Protection - Overcurrent Protection
99
Power system Protection
Overcurrent relays
Overcurrent relaying is the simplest and cheapest type of protection used
for protection of lines, transformers, generators and motor.
Fig.1
011
Power system Protection Part – 5
010
Power system Protection Part – 5
Time
Adjustable
tset
Current
In Iset = xIn
011
Power system Protection Part – 5
These relays also have two settings: the pick-up current and the curve
level. In early electromechanical relays the curve is set by means of a
dial. Thus, the setting is called the “time dial setting - TDS”.
Time
t1 Adjustable
tins
10In Current
In 2 In
011
Power system Protection Part – 5
IEEE does not specify coefficients in the standard curve equation. Thus,
each manufacturer’s curve is similar. But different IEC curves are
standardized
011
Power system Protection Part – 5
011
Power system Protection Part – 5
011
Power system Protection Part – 5
Instantaneous
tins
In nIn I
011
Power system Protection Part – 5
Definite - Time
Instantaneous
tins
In nIn I
The most commonly used type of relay is the inverse definite with
minimum time lag relay (IDMT) in which inverse characteristic plus
definite time characteristic are used.
In this relay, the operating time is approximately inversely proportional to
the fault current near pickup value and become substantially constant
slightly above the pick up value of the relay. This characteristic is shown
in the following figure.
011
Power system Protection Part – 5
Definite - Time
tins
In nIn I
019
Power system Protection Part – 5
001
Power system Protection Part – 5
000
Power system Protection Part – 5
001
Power system Protection Part – 5
001
Power system Protection Part – 5
Figure- 1A
(c ) OR the above figure can be given as:
Figure – 1B
001
Power system Protection Part – 5
Curve Equations
1. The typical time curves for CO-8 American overcurrent
relay(normal inverse) characteristics can be approximated
by the following equation.
0.14 TMS
trelay 0.02
IF
1
CTR PS
001
Power system Protection Part – 5
Timing 246
dial
Lagging
coil
Current
Taps Braking
or
Plug
Settings 1 2
Induction
(PS)
disk
001
Power system Protection Part – 5
Example: Calculate the plug setting and time multiplier setting for an IDMTL relay
on the following network so that it will trip in 2.4 s (see Figure 1).The relay
characteristic is shown in Figure2.The C.T. setting is 100/5 A and the fault current is
1000 A.
Figure 1
001
Power system Protection Part – 5
Answer:
Fault current = 1000 A
CT ratio = 100/5 A
Hence expected current into relay under fault conditions,
Ir = (1000 x 5/100) = 50 A
Choose plug setting of 5 A (100%). Therefore, current into relay as a multiple of plug
setting during fault: 50 / 5 = 10
We require the relay to operate after 2.4 s as soon as this much current starts
flowing in the circuit. Referring to characteristic curves given in Figure 2
above, read time multiplier setting where 10 times plug setting current and 2.4
s cross, which is about 0.8. Accordingly, relay settings = current plug tap 5 A
(100%) and time multiplier 0.8.
Alternatively, if the current plug setting is chosen as 125% (6.25 A), the fault
current through the relay will be 50/6.25 = 8 A. The graph shows that eight
times plug setting to operate in 2.4 s, the time multiplier should be about 0.7.
This technique is fine if the required setting falls exactly on the TM curve.
However, if the desired setting falls between the curves, it is not easy to
estimate the intermediate setting accurately as the scales of the graph are
log/log. The following procedure is therefore recommended (see Figure 3).
Go to the multiple of plug setting current and read the second value
corresponding to the 1.0 time multiplier curve. Then divide the desired time
setting by this figure. This will give the exact time multiplier setting:
Second value at 10 times = 3
( at 8 times it is about 3.3s)
Desired setting = 2.4s.
Figure 3
(Figure – 1B previously)
001
Power system Protection Part – 5
Examples :
Example1: Determine the PSM (plug setting multiplier) of a 5A, 2.2 sec over
current relay having a plug setting Ps=200%. The supply CT is rated 400:5A
and the fault current is 12000A.
Solution:
I p 12000 A
5
I s 12000 150 A
400
On PS of 200%:
200
The relay current 5 10 A
100
150
Hence PSM 15
10
Fig. EX2-1
009
Power system Protection Part – 5
2) From the curve of TMS=1(Fig. EX.2-2) , the operating time top for PSM=8
0.6
is 3.3sec (TMS=1) and for TMS=0.6 is 1.92sec ( 3.3 .)
1.0
This comes from:
TMS top
1 3.3
0.6 ?
0.6
?= 3.3 .=1.92 sec
1.0
Fig. EX.2-2
Fig. EX.2-3
For PSM = 8 , top = 3.3 sec. for TMS =1. Now convert top to TMS =0.6 as above:
TMS top
1 3.3
0.6 ?
0.6
?= 3.3 .=1.92 sec
1.0
011
Power system Protection Part – 5
Example3: If the rated current (pick up current) of a relay is 3A, and the time dial
setting is 1. (a) How long does it take the relay to trip if the supply C.T is rated at
400:5 A, and the fault current is 480A? The type of the OC relay is CO-8.
(b) Solve using the standard curve equation and compare the results.
Solution:
(a) I p 480 A
5
I s 480 6A
400
Tap value of current=3A
Multiple of tap value current
I 6
s 2
I tap 3
From the CO-8 characteristic curves (see Figure
below) :
Operating time=2.1 sec.
5.95
t relay TD 2 0.18
M 1
TD 1 TDS
Is I 6
M s 2
I pickup I tap 3
5.95
t relay 1 2 0.18
(2) 1
2.16 sec (Same result)
010
Power system Protection Part – 5
Example4: For the relay R1 in the system shown determine the current tap setting
CTS. If the maximum three-phase fault current is 2400A and the TDS=2.0 find the
operating time if the relay type is CO-8 (inverse type).
Solution:
S 4.5 10 6
I L1 196.82 A
3V 3 13.2 10 3
5
The relay current I R 196.82 3.28 A
300
Since the current tap setting (CTS) of CO-8 relay available are 4,5,6,7,8,10 and 12
5
Relay current during fault 2400 40 A
300
40
As multiple of selected CTS 10
4
011