This document provides an installation, operation, and maintenance manual for WEG electric motors. It contains information on motor types, applicable standards, storage guidelines, and bearing maintenance. The manual instructs users to store motors in dry, clean environments and rotate shafts monthly if stored for over 6 months. It also provides lubrication amounts for bearings and guidelines on relubrication or replacement if stored for over 2 years. Contact WEG for any questions about using the manual.

Uploaded by

ridipisa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
220 views6 pages

WEG Motors-Storage

This document provides an installation, operation, and maintenance manual for WEG electric motors. It contains information on motor types, applicable standards, storage guidelines, and bearing maintenance. The manual instructs users to store motors in dry, clean environments and rotate shafts monthly if stored for over 6 months. It also provides lubrication amounts for bearings and guidelines on relubrication or replacement if stored for over 2 years. Contact WEG for any questions about using the manual.

Uploaded by

ridipisa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

www.weg.

net

INSTALLATION, OPERATION AND MAINTENANCE


MANUAL OF ELECTRIC MOTORS
This manual provides information about WEG induction motors fitted with squirrel cage,
permanent magnet or hybrid rotors, low, medium and high voltage, in frame sizes IEC 56
to 630 and NEMA 42 to 9606/10.
The motor lines indicated below have additional information that can be checked in their
respective manuals:
g Smoke Extraction Motors;

g Electromagnetic Brake Motors;

g Hazardous Area Motors.

These motors meet the following standards, if applicable:


g NBR 17094-1: Máquinas Elétricas Girantes - Motores de Indução - Parte 1: trifásicos.

g NBR 17094-2: Máquinas Elétricas Girantes - Motores de Indução - Parte 2: monofásicos.

g IEC 60034-1: Rotating Electrical Machines - Part 1: Rating and Performance.

g NEMA MG 1: Motors and Generators.

g CSA C 22.2 N°100: Motors and Generators.

g UL 1004-1: Rotating Electrical Machines - General Requirements.

If you have any questions regarding this manual please contact your local WEG branch,
contact details can be found at www.weg.net.

58 Manual of Electric Motors


www.weg.net

5. Storage
If the motor is not installed immediately, it must be stored in a dry and clean environment, with relative humidity
not exceeding 60%, with an ambient temperature between 5 ºC and 40 ºC, without sudden temperature
changes, free of dust, vibrations, gases or corrosive agents. The motor must be stored in horizontal position,
unless specifically designed for vertical operation, without placing objects on it. Do not remove the protection
grease from shaft end to prevent rust.

If the motor are fitted with space heaters, they must always be turned on during the storage period or when the
installed motor is out of operation. Space heaters will prevent water condensation inside the motor and keep
the winding insulation resistance within acceptable levels. Store the motor in such position that the condensed
water can be easily drained. If fitted, remove pulleys or couplings from the shaft end (more information are given
on item 6).

The space heaters should never be energized when the motor is in operation.

5.1. Exposed machined Surfaces


All exposed machined surfaces (like shaft end and flange) are factory-protected with temporary rust inhibitor. A
protective film must be reapplied periodically (at least every six months), or when it has been removed and/or
damaged.
5.2. Storage
The stacking height of the motor packaging during the storage period should not exceed 5 m, always
considering the criteria indicated in Table 5.1:
Table 5.1 - Max. recommended stacking height

ENGLISH
Packaging type Frame sizes Maximum stacking quantity
IEC 63 to 132 Indicated on the top side of
Cardboard box
NEMA 143 to 215 the cardboard box
IEC 63 to 315
06
NEMA 48 to 504/5
IEC 355
Wood crate 03
NEMA 586/7 and 588/9
HGF IEC 315 to 630
Indicated on the packaging
HGF NEMA 5000 to 9600

Notes:
1) Never stack larger packaging onto smaller packaging;
2) Align the packaging correctly (see Figure 5.1 and Figure 5.2);

Figure 5.1 - Correct stacking


X
Figure 5.2 - Incorrect stacking

Manual of Electric Motors 73


www.weg.net

3) The feet of the crates above should always be supported by suitable wood battens (Figure 5.3) and never stand on the steel tape or
without support (Figure 5.4);

Figure 5.3 - Correct stacking


X XFigure 5.4 - Incorrect stacking

4) When stacking smaller crates onto longer crates, always ensure that suitable wooden supports are provided to withstand the weight
(see Figure 5.5). This condition usually occurs with motor packaging above IEC 225S/M (NEMA 364/5T) frame sizes.
ENGLISH

Figure 5.5 - Use of additional battens for stacking

5.3 Bearings
5.3.1 Grease lubricated bearings
We recommend rotating the motor shaft at least once a month (by hand, at least five revolutions, stopping the
shaft at a different position from the original one). If the motor is fitted with shaft locking device, remove it before
rotating the shaft and install it again before performing any handling procedure. Vertical motors may be stored
in the vertical or in horizontal position. If motors with open bearings are stored longer than six months, the
bearings must be relubricated according to item 8.2 before commissioning of the motor.
If the motor is stored for longer than 2 years, the bearings must be replaced or removed, washed, inspected
and relubricated according to item 8.2.

5.3.2 Oil lubricated bearings


The motor must be stored in its original operating position and with oil in the bearings. Correct oil level must be
ensured. It should be in the center of the sight glass.
During the storage period, remove the shaft locking device and rotate the shaft by hand every month, at least
five revolutions, thus achieving an even oil distribution inside the bearing and maintaining the bearing in good
operating conditions. Reinstall the shaft locking device every time the motor has to be moved.
If the motor is stored for a period of over six months, the bearings must be relubricated according to Item 8.2
before starting the operation. If the motor is stored for a period of over two years, the bearings must be
replaced or removed, washed according to manufacturer instructions, checked and relubricated according to
Item 8.2. The oil of vertical mounted motors that are transported in horizontal position is removed to prevent oils
leaks during the transport. These motors must be stored in vertical position after receiving and the bearing
must be lubricated.

74 Manual of Electric Motors


www.weg.net

5.3.3 Oil Mist lubricated bearings


The motor must be stored in horizontal position. Lubricate the bearings with ISO VG 68 mineral oil in the
amount indicated in the Table 5.2 (this is also valid for bearings with equivalent dimensions). After filling with oil,
rotate the shaft by hand, at least five revolutions)
During the storage period, remove the shaft locking device (if any) and rotate the shaft by hand every week, at
least five revolutions, stopping it at a different position from the original one. Reinstall the shaft locking device
every time the motor has to be moved. If the motor is stored for a period of over two years, the bearings must
be replaced or removed, washed according to manufacturer instructions, checked and relubricated according
to item 8.2.
Table 5.2 - Amount of oil per bearing
Bearing size Amount of oil (ml) Bearing size Amount of oil (ml)
6201 15 6309 65
6202 15 6311 90
6203 15 6312 105
6204 25 6314 150
6205 25 6315 200
6206 35 6316 250
6207 35 6317 300
6208 40 6319 350
6209 40 6320 400
6211 45 6322 550
6212 50 6324 600
6307 45 6326 650
6308 55 6328 700

ENGLISH
The oil must always be removed when the motor has to be handled. If the oil mist system is not operating after
installation, fill the bearings with oil to prevent bearing rusting. During the storage period, rotate the shaft by
hand, at least five revolutions, stopping it at a different position from the original one. Before starting the motor,
all bearing protection oil must be drained from the bearing and the oil mist system must be switched ON.

5.3.4 Sleeve bearing


The motor must be stored in its original operating position and with oil in the bearings. Correct oil level must be
ensured. It should be in the middle of the sight glass. During the storage period, remove the shaft locking
device and rotate the shaft by hand every month, at least five revolutions, and at 30 rpm, thus achieving an
even oil distribution inside the bearing and maintaining the bearing in good operating conditions. Reinstall the
shaft locking device every time the motor has to be moved.
If the motor is stored for a period of over six months, the bearings must be relubricated according to the Item
8.2 before starting the operation.
If the motor is stored for a period longer than the oil change interval, or if it is not possible to rotate the motor
shaft by hand, the oil must be drained and a corrosion protection and dehumidifiers must be applied.
5.4. INSULATION RESISTANCE
We recommend measuring the winding insulation resistance at regular intervals to follow-up and evaluate its
electrical operating conditions. If any reduction in the insulation resistance values are recorded, the storage
conditions should be evaluated and corrected, where necessary.

5.4.1. Insulation resistance measurement


We recommend measuring the winding insulation resistance at regular intervals to follow-up and evaluate its
electrical operating conditions. If any reduction in the insulation resistance values are recorded, the storage
conditions should be evaluated and corrected, where necessary.

The insulation resistance must be measured in a safe environment.

Manual of Electric Motors 75


www.weg.net

The insulation resistance must be measured with a megohmmeter. The machine must be in cold state and
disconnected from the power supply.

To prevent the risk of an electrical shock, ground the terminals before and after each measurement.
Ground the capacitor (if any) to ensure that it is fully discharged before the measurement is taken.

It is recommended to insulate and test each phase separately. This procedure allows the comparison of the
insulation resistance between each phase. During the test of one phase, the other phases must be grounded.
The test of all phases simultaneously evaluates the insulation resistance to ground only but does not evaluate
the insulation resistance between the phases.
The power supply cables, switches, capacitors and other external devices connected to the motor may
considerably influence the insulation resistance measurement. Thus all external devices must be disconnected
and grounded during the insulation resistance measurement.
Measure the insulation resistance one minute after the voltage has been applied to the winding. The applied
voltage should be as shown in Table 5.3.
Table 5.3 - Voltage for the insulation resistance

Winding rated voltage (V) Testing voltage for measuring the insulation resistance (V)
< 1000 500
1000 - 2500 500 - 1000
2501 - 5000 1000 - 2500
5001 - 12000 2500 - 5000
> 12000 5000 - 10000

The reading of the insulation resistance must be corrected to 40 °C as shown in the Table 5.4.

Table 5.4 - Correction factor for the insulation resistance corrected to 40 °C


ENGLISH

Measuring temperature Correction factor of the Measuring temperature of Correction factor of the
of the insulation insulation resistance the insulation resistance insulation resistance
resistance (°C) corrected to 40 °C (°C) corrected to 40 °C
10 0.125 30 0.500
11 0.134 31 0.536
12 0.144 32 0.574
13 0.154 33 0.616
14 0.165 34 0.660
15 0.177 35 0.707
16 0.189 36 0.758
17 0.203 37 0.812
18 0.218 38 0.871
19 0.233 39 0.933
20 0.250 40 1.000
21 0.268 41 1.072
22 0.287 42 1.149
23 0.308 43 1.231
24 0.330 44 1.320
25 0.354 45 1.414
26 0.379 46 1.516
27 0.406 47 1.625
28 0.435 48 1.741
29 0.467 49 1.866
30 0.500 50 2.000

76 Manual of Electric Motors


www.weg.net

The motor insulation condition must be evaluated by comparing the measured value with the values
indicated in Table 5.5 (corrected to 40 °C):
Table 5.5 - Evaluation of the insulation system
Limit value for rated voltage Limit value for rated voltage
Situation
up to 1.1 kV (MΩ) above 1.1 kV (MΩ)
Dangerous. The motor can not
Up to 5 Up to 100
be operated in this condition
5 to 100 100 to 500 Regular
100 to 500 Higher than 500 Good
Higher than 500 Higher than 1000 Excellent

The values indicated in the table should be considered only as reference values. It is advisable to log all
measured values to provide a quick and easy overview on the machine insulation resistance.
If the insulation resistance is low, moisture may be present in the stator windings. In this case the motor
should be removed and transported to a WEG authorized Service Center for proper evaluation and repair
(This service is not covered by the warranty). To improve the insulation resistance through the drying
process, see section 8.4.

ENGLISH

Manual of Electric Motors 77