Torsion Problem 1

This document provides calculations to determine seismic shears in storeys of a 4-storey reinforced concrete building located in seismic zone IV. It includes data on member sizes, building dimensions, material properties, and seismic weights. Calculations are shown for fundamental period, design base shear, seismic forces and shears at each floor considering effects of mass and stiffness eccentricities. Torsional moments and shears are determined for each column line in the X and Y directions. Tables are provided summarizing seismic shear forces and torsional shears at each floor.

Uploaded by

sachin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
36 views

Torsion Problem 1

This document provides calculations to determine seismic shears in storeys of a 4-storey reinforced concrete building located in seismic zone IV. It includes data on member sizes, building dimensions, material properties, and seismic weights. Calculations are shown for fundamental period, design base shear, seismic forces and shears at each floor considering effects of mass and stiffness eccentricities. Torsional moments and shears are determined for each column line in the X and Y directions. Tables are provided summarizing seismic shear forces and torsional shears at each floor.

Uploaded by

sachin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Example 2 :

A four storeyed RC OMR frame building has plan as shown in Fig. 3 is situated in seismic zone
IV. Workout the seismic shears in storeys as per is 1893(Part I) 2002. The other data-

Beam size - 0.25mx 0.50m and 0.25 x 0.40m

Column size - 0.40m x 0.60m

Height of each storey - 3m

Thickness of wall - 0.25m

Thickness of slab - 0.15m

Modulus of elasticity of concrete - 22x106kN/m2

Unit weight of concrete - 24 kN/m2

Unit weight of masonary - 20 kN/m2

Live load - 3 kN/m2

CR 4
4@5m=20m

ey CM

ex 3

1
A B C D E F G

6@6m=36m
Fig. 3 BUILDING PLAN
Solution:
Calculations of seismic weights

(i) Total weight of columns in a storey


= 27x 3 x 0.4 x 0.6 x 24
= 466.6 kN
(ii) Total weight of beams in a storey
= [(22 x 6 x 0.25 x 0.50) + (20 x 5 x 0.25 x 0.40)] x 24

1
= 636.0 kN
(iii) Total weight of slab in a storey
= (12 x 20 + 24 x 10) x 0.15 x 24
= 1728 kN
(iv) Total weight of walls in a storey
= (12 + 10 +24 + 10 +36 +20) x 0.25 x 3 x 20
= 1680 kN
(v) Live load on each floor
= (12 x 20 + 24 x 10) x 3 x 0.25
= 360 kN
(vi) Lumped weight at floor 1, 2 and 3
= 466.6 + 636.0 + 1728 + 1680 + 360
= 4870.56 kN
(vii) Lumped weight at roof floor
= 466.6 + 636.0 + 1728 + 1680
= 4510.56 kN
(viii) Total weight of building
= 3X4870.56 + 4510.56
= 19122.24 kN

Fundamental natural period of vibration of moment resisting frame with brick infill

0.09 ℎ
𝑇=
√𝑑
0.09 × 12
𝑇=
√36

𝑇 = 0.18 𝑠𝑒𝑐

Design seismic base shear

𝑉𝐵 = 𝐴ℎ × 𝑊

𝑧 𝑆𝑎 𝐼
𝑉𝐵 = × × ×𝑊
2 𝑔 𝑅

0.24 2.5
𝑉𝐵 = ×
2 3 × 19112.8

19.3 𝑘𝑁 kN
𝑉𝐵 = 1912.22

Table 1 – Nodal forces and seismic shear forces at various levels:

2
Floor Qi =
Vi (Shear
Wi in kN hi in m Wihi2 Wi hi 2
𝑉𝐵 = force) in kN
∑ Wi hi 2

4 4510.56 12 6,49,520.64 983.23 983.23

3 4870.56 9 3,94,515.32 597.209 1580.43

2 4870.56 6 1,75,340.12 265.423 1845.86

1 4870.56 3 43,835.048 66.35 1912.221

∑ Wihi2 = 12,63,2211.2

Calculation of eccentricity ex and ey


Y

0.40 m X

0.60 m

1 1
Ix = bd3 = x 0.60x 0.403 = 0.0032 m4.
12 12

1 1
Iy = db3 = x 0.40x 0.603 = 0.0072 m4.
12 12

12EIx 12×22×106 x0.0032


Kx = = = 31289kN/m
l3 33

12EIy 12×22×106 x0.0072


Ky = = = 70400 kN/m
l3 33

Center of rigidity

Assuming origin at A-1, the co-ordinate of centre of rigidity


∑ Ky ∙ x
Xr =
∑ Ky

3
= (70400[5x0 + 5x6 +5x12+ 3x18 + 3x24 + 3x30+ 3x36])/27 x 70400
= 15.33 m
∑ Kx ∙ x
Yr =
∑ Kx
= (31289[7x0+7x5+7x10+3x15+3x20]/27x31289
=7.78 m

Centre of mass
∑ m .x ∑ m .y
Xm = ; Ym =
∑m ∑m

Xm= {(12x20x0.15x24x6)+(24x10x0.15x24x24)}/1728

Ym = {(12x20x0.15x24x10)+(24X10x0.15x24x5)}/1728

Xm = 15.0 m for first, second & third floors.

Ym = 7.50 m for first, second & third floors.

Xm = 15.00 m for roof floors.

Ym = 7.5 m for roof floors.

For the First, second and third floors,

ex = Xm ± X r = 15.00 ± 15.33 = -0.33 m

ey = Ym ± Y r = 7.50 ± 7.78 = -0.28 m

For roof floor,


Xm= {(12x20x0.15x24x6)+(24x10x0.15x24x24)}/1728
ex = 15.00 -15.33 =-0.33m

ey = 7.50 - 7.78 = -0.28 m

The design eccentricity, edi for first, second, third and roof floor,

edi = (1.5esi + 0.05bi) or (esi ± 0.05 ib


« whichever is more)

edix = 1.5 x (-0.33) +/- 0.05 x 20 = 0.505 m / -1.495m

ediy = 1.5 x (-0.28) +/- 0.05 x 36 = 1.38 m /-2.22 m


The rotational stiffness Ixy about center of rotation CR is given by

Ip = Σ (Kx Y2 + Ky X2)
ΣKxY2 = 31289 (7 x 7.782 + 7 x 2.782 + 7 x 2.222 + 7 x 7.222 + 3 x 12.222)
= 34939387.5

ΣKy X2 = 70400 (5x15.332 + 5x9.332 + 5x3.332 + 3x2.672 + 3x8.672 + 3x14.672


4
3x20.672)
= 270336021.1
Torsional moment Mt at various floors is as follows considering

seismic force in X direction only

Mt1 12Mt1=
. 1912.221 x 2.22=4245.13kNm

Mt2 = 1845.865 x 2.22 = 4097.82 kNm


Mt3 = 1580.439 x 2.22 = 3508.574 kNm

Mt4 = 983.23 x 2.22 = 2182.77 kNm

Table 2 – Torsional shear in various storey’s in ‘X’ direction in kN


Torsional shear at each column line is shown in table 2 by using

Vx=(Mt/Ip) . y . Kxx

Column line First Storey Second Storey Third Storey Forth Storey

1 23.69 22.87 19.58 12.18

2 8.46 8.17 6.99 4.35

3 6.76 6.52 5.58 3.47

4 9.42 9.09 7.78 4.84

5 15.95 15.39 13.18 8.20

Torsional moment Mt at various floors is as follows considering seismic force in Y direction


only
Mt1 = 1912.221 x 1.495 = 2858.77 kNm

Mt2 = 1845.865 x 1.495 = 2759.56 kNm

Mt3 = 1580.439 x 1.495= 2362.75 kNm

Mt4 = 983.23 x 1.495 = 1469.92 kNm

Torsional shears at each column line in Y direction according to expression,


𝑀𝑡
𝑉𝑦 = ( ) × 𝑥 × 𝐾𝑦𝑦
𝐼𝑝

Table 3: Torsional shear in various storey in Y-direction in kN.


Column Line First Storey Second Storey Third Storey Fourth Storey

A 50.53 48.77 41.76 25.98

B 30.75 29.68 25.41 15.81

C 10.97 10.59 9.07 5.64

D 5.28 5.09 4.36 2.71

E 17.14 16.55 14.17 8.81

F 29.01 28.00 23.98 14.91

G 40.88 39.46 33.78 21.02