PSA15 Differential Protection Datasheet

The document describes a differential protection relay that can be used to investigate protection of equipment with two windings like transformers. The relay connects to a protection and relay test set and allows testing of differential protection characteristics. It contains an industrial Micom P642 relay and displays relay settings and test results. The relay provides adjustable settings to test protection functions like differential, restricted earth fault, overcurrent and thermal overload protection of connected equipment.

Uploaded by

SAYYAM
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views2 pages

PSA15 Differential Protection Datasheet

The document describes a differential protection relay that can be used to investigate protection of equipment with two windings like transformers. The relay connects to a protection and relay test set and allows testing of differential protection characteristics. It contains an industrial Micom P642 relay and displays relay settings and test results. The relay provides adjustable settings to test protection functions like differential, restricted earth fault, overcurrent and thermal overload protection of connected equipment.

Uploaded by

SAYYAM
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Electrical Power Systems

Differential Protection Relay


P SA1 5
For investigations into protection of transformers, autotransformers, generators and other
apparatus with two windings

K ey f e at u res
• An industrial numerical protection relay presented in an educational format
• Demonstrates clearly the characteristics of three-phase differential protection
• Supplied with TecQuipment’s Protection and Relay Test Set (PSL50) and as an optional ancillary to other
selected power systems products
• Needs no extra power source - powered from the TecQuipment Power System range products
• Fully adjustable settings to allow a wide variety of tests and investigations
• Connections via safety sockets
• Modern industrial relay to help teach the latest relay technology

TecQuipment Ltd, Bonsall Street, long eaton, Nottingham NG10 2AN, UK


tecqu ipment. c o m +4 4 115 972 2611 [email protected]

PE/JSL/db 0422 Page 1 of 2


Differential Protection Relay
P SA1 5

Description Learning outcomes


A numerical differential protection relay Investigations into the performance and characteristics of
presented in an educational format. It connects to an industrial differential protection relay.
TecQuipment’s Protection and Relay Test Set (PSL50)
OOperating Conditions
and other modules in the Power System range. It
allows investigations into protection of transformers, O perat ing enviro nment:
autotransformers, generators and other electrical Laboratory environment
apparatus with two windings. The relay shows clearly the
characteristics of three-phase differential protection. This Storage temperature range:
includes high stability during ‘out-of-zone’ faults, zero- –25°C to +55°C (when packed for transport)
sequence current filtering for each winding, high-speed
operation, magnetising inrush restraint, amplitude and O perat ing t emperat u re ra nge:
vector matching. +5°C to +40°C
The relay is housed in a robust enclosure with carrying O perat ing relat ive hu midit y ra nge:
handle. The unit mounts on the desk area of the Protection 30% to 95% (non-condensing)
and Relay Test Set or other Power System product. It
connects using a multi-core cable from the back of the Specifications
relay to the Power System products.
Dimensio ns:
A Micom P642 industrial relay forms the main part of • 300 mm x 550 mm x 278 mm
the unit. The lecturer or student sets up different fault
circuits on the Protection and Relay Test Set or other • Packed 0.16 m3
Power System product. They then use the keypad and Weight:
display on the relay module to program it to the settings
• Net 13.5 kg
needed for the tests. They can also use the Micom S1
software (supplied) and a suitable computer (computer • Packed 30 kg
not included) to program the relay module. The user then
connects the 4 mm shrouded sockets from the relay to the Ma ximu m Inpu t Rat ings:
test circuits on the Power System product. 1 A (a.c.) current input
Most tests need only one relay. However, the Protection 110 VAC Line to line voltage input
and Relay Test Set (PSL50) has two sockets to test two
Su pply:
relay modules at the same time if needed.
Relay operating supply is 110 VAC from Power System
The relay connects to the test circuits through the voltage product through a multi-core interconnecting cable.
and current transformers (VTs and CTs) built into the Power
System products. This helps to show standard electrical Freq u ency:
engineering practice and the importance of CT ratio, 50 or 60 Hz
connection and rating.
Accu racy:
Standard Features ±5%
• Supplied with comprehensive user guide O perat ing t ime:
• Five-year warranty Typically 10 ms to 25 ms

• Manufactured in accordance with the latest European Protection Functions:


Union directives • Differential protection (ANSI 87, 87T)
• Restricted Earth Fault (ANSI 64)
• Definite time overcurrent protection (ANSI 50P, ANSI
50Q and ANSI 50N/G)
• Inverse time overcurrent protection (ANSI 51P, ANSI 51Q
and ANSI 51N/G)
• Negative Sequence Overcurrent (ANSI 46)
• Standby Earth Fault (ANSI 50N/51N)
• Thermal overload protection (ANSI 49)

TecQuipment Ltd, Bonsall Street, long eaton, Nottingham NG10 2AN, UK