Generator Data Sheet of BHEL

This document provides specifications for a generator to be used in a 2x600MW thermal power plant project in India. Key details include: - The generator will be made by BHEL, rated at 600MW and 705.9MVA, with a rated voltage of 21kV and speed of 3000rpm. - Performance metrics at rated load include an efficiency of 98.79% and regulation of 28.8% at unity power factor. - The generator can withstand a 3-phase short circuit current of 29.24kA for 3 seconds and a stator ground fault current of 15A for 1 second. - Maximum temperatures of components are not to exceed 120°C at rated operating

Uploaded by

bramhanand verma
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
387 views

Generator Data Sheet of BHEL

This document provides specifications for a generator to be used in a 2x600MW thermal power plant project in India. Key details include: - The generator will be made by BHEL, rated at 600MW and 705.9MVA, with a rated voltage of 21kV and speed of 3000rpm. - Performance metrics at rated load include an efficiency of 98.79% and regulation of 28.8% at unity power factor. - The generator can withstand a 3-phase short circuit current of 29.24kA for 3 seconds and a stator ground fault current of 15A for 1 second. - Maximum temperatures of components are not to exceed 120°C at rated operating

Uploaded by

bramhanand verma
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 21

DOC. NO.

: 4033-0483
GENERATOR DATA SHEET REV : 01
DATE : 06.01.2011

PROJECT : 2x600MW TPP AT DERANG, ANGUL, ORISSA


CUSTOMER : JINDAL INDIA THERMAL POWER LIMITED
CONSULTANT: TATA CONSULTING ENGINEERS LIMITED, MUMBAI
CL. NO. PARAMETER UNIT VALUE

1.0.0 GENERATOR AND ACCESSORIES

1.1.0 General
1.1.1 Make -- BHEL
1.1.2 Type -- THDF 115/67
1.1.3 Reference Standards -- IEC-34
1.1.4 Enclosure -- Generator : IP-54
Exciter : IP-40
1.1.5 Type of cooling
a) Stator winding -- Direct Water Cooled
b) Stator core -- Direct H2 Cooled
c) Rotor -- Direct H2 Cooled
1.1.6 Rated coolant pressure Hydrogen Bar 5 Bar (g)
1.1.7 Rated speed RPM 3000
1.2.0 Main Ratings
1.2.1 Rated output MW/MVA 600 MW , 705.9 MVA
1.2.2 a) i) Max. Continuous Rating MW/MVA 600 MW , 705.9 MVA
ii) Temp limits Within Class B
1.2.2 b) i) Generator rating at Turbine VWO condition MW/MVA 630 MW , 741.2 MVA
ii) Temp limits Within Class F
1.2.3 Rated power factor -- 0.85 (Lag)
1.2.4 Rated terminal voltage kV 21
1.2.5 Rated stator current Amps. 19407
1.2.6 Phase --- 3
1.2.7 Rated frequency Hz 50
1.2.8 Excitation at rated output and power factor
a) Voltage Volts. 413
b) Current Amps. 5192
1.2.9 a) Short Circuit Ratio (S.C.R.) at rated output 0.57
b) Permissible (±) tolerance in S.C.R.  15 %
1.3.0 Performance

1.3.1 Efficiency at

D:\user\akg\600MW_Derang\4033-0483_GDS_Derang_R01.doc
Page 1 of 14
DOC. NO. : 4033-0483
GENERATOR DATA SHEET REV : 01
DATE : 06.01.2011

PROJECT : 2x600MW TPP AT DERANG, ANGUL, ORISSA


CUSTOMER : JINDAL INDIA THERMAL POWER LIMITED
CONSULTANT: TATA CONSULTING ENGINEERS LIMITED, MUMBAI
CL. NO. PARAMETER UNIT VALUE

a) 100% load 98.79


b) 75% load 98.84
c) 50% load 98.76
d) 25% load 98.16
1.3.2 Regulation at rated output, speed and voltage
a) Unity power factor % 28.8
b) 0.85 power factor lagging % 36.2
c) 0.85 power factor leading % 23.6
1.3.3 At generator rated output, rated speed and power
factor, the permissible variation range in
a) Terminal voltage % 5
b) Frequency % +3 / -5
c) Absolute sum of combined voltage and % 5
frequency variation (Refer Curve No.
TG-THDF115/67-015)
1.3.4 Voltage rise during sudden rejection of full load at
rated power factor
a) With A.V.R. % 15%
b) Without A.V.R. % 36.2%
1.3.5 Generator reactive capability
a) Max. Inductive loading (zero lag) MVAR 530
b) Max. Capacitive loading (zero lead) MVAR 330
c) Capacitive loading at rated load and voltage MVAR 260
1.3.6 Permissible unbalanced loading subject to current
not exceeding the rated current in any phase
a) Maximum continuous negative sequence % 8
current-I2
b) Maximum value of I22t for transient operation 8
under system fault (where I2 in p.u. and t in
seconds.)
1.3.7 Generator asynchronous operation
a) Permissible load % f.l. Refer Curve No. TG-
THDF 115/67-018
b) Duration Min. Refer Curve No. TG-
THDF 115/67-018
1.3.8 Short circuit withstand
a) 3-phase terminal fault

D:\user\akg\600MW_Derang\4033-0483_GDS_Derang_R01.doc
Page 2 of 14
DOC. NO. : 4033-0483
GENERATOR DATA SHEET REV : 01
DATE : 06.01.2011

PROJECT : 2x600MW TPP AT DERANG, ANGUL, ORISSA


CUSTOMER : JINDAL INDIA THERMAL POWER LIMITED
CONSULTANT: TATA CONSULTING ENGINEERS LIMITED, MUMBAI
CL. NO. PARAMETER UNIT VALUE

i) Current kA 29.24 (Steady State)


ii) Duration Secs. 3.0 Secs
a) Stator ground fault
i) Current A 15 Amps
ii) Duration Secs. 1.0 Sec
1.3.9 Overload performance
a) Stator current % f.l. 150
b) Time Sec. 30
1.3.10 Generator pull out power at rated voltage MW 982
1.3.11 Maximum continuous generator capability under 67% of rated load
one H2 cooler section out of operation
1.3.12 Generator capability on variation of coolant Refer Curve No. TG-
pressure THDF 115/67-017
1.3.13 Minimum H2 gas pressure & corresponding MW Bar, 510 MW at H2
MW Pressure of 4.0 bar(g)
1.3.14 Rotor overspeed capability % 120% for 2 min
1.4.0 Temperatures
1.4.1 Ambient temperature
a) Cooling water at inlet to heat exchanger Deg. C 38
b) Ambient air Deg. C Not Applicable
1.4.2 Coolant temperatures
a) Cooled H2 gas Deg. C 45
b) Hot H2 gas Deg. C 78
c) Stator Water inlet Deg. C 50
d) Stator Water outlet Deg. C 76
1.4.3 Maximum temperature at rated conditions.

a) Stator winding Deg. C 120


b) Stator core
i) In contact with insulated winding Deg. C 120
ii) Not in contact with insulated winding Deg. C 120
c) Rotor winding Deg. C 105
d) Collector rings if any Deg. C NA
1.5.0 Miscellaneous Parameters

D:\user\akg\600MW_Derang\4033-0483_GDS_Derang_R01.doc
Page 3 of 14
DOC. NO. : 4033-0483
GENERATOR DATA SHEET REV : 01
DATE : 06.01.2011

PROJECT : 2x600MW TPP AT DERANG, ANGUL, ORISSA


CUSTOMER : JINDAL INDIA THERMAL POWER LIMITED
CONSULTANT: TATA CONSULTING ENGINEERS LIMITED, MUMBAI
CL. NO. PARAMETER UNIT VALUE

1.5.1 Saturation constant 1.17


1.5.2 Wave form factor < 0.1 (as per ANSI
C50.10)
1.5.3 Telephone Harmonic Distortion (THD) Less than 5 %
1.5.4 Stored energy constant (H)
a) Generator + Exciter KW Sec. 0.80
/KVA
b) Complete turbo- generator KW Sec. 3.43
/KVA
1.5.5 Fly wheel effect (GD2)
a) Generator + exciter Kg-Sq.m (43864+2154)=46018
b) Turbine Kg-Sq.m 150132
c) Complete TG unit Kg-Sq.m 196150
1.5.6 Acceleration time (Ti) Sec. 1.6 (Generator + Exciter)
1.5.7 Critical Speed (Generator + Exciter)
b) 1st r.p.m. RPM 672
nd
c) 2 r.p.m. RPM 1295
rd
c) 3 r.p.m. RPM 2060
d) Critical speed above Synchronous speed RPM 3986
1.6.0 Reactances etc. (in % at rated MVA and kV)
1.6.1 Direct axis reactances Saturated Unsat.
a) Synchronous, Xd % 174.1 204.0
b) Transient, Xd’ % 24.5 25.75
c) Sub-transient, Xd’’ % 17.8 21.4
d) Leakage Reactance (stator) % 15.9
e) Leakage reactance (rotor) % 11.9
f) Synchronous Impedance Ohms 1.27
1.6.2 Quadrature axis reactances
a) Synchronous, Xq % --- 193.7
b) Transient, Xq’ % 65.9 73.2
’’
c) Sub-transient, Xq % 19.0 23.5
1.6.3 Negative sequence reactance, X2 18.4 22.5
1.6.4 Zero sequence reactance, Xo % 9.8 10.9

D:\user\akg\600MW_Derang\4033-0483_GDS_Derang_R01.doc
Page 4 of 14
DOC. NO. : 4033-0483
GENERATOR DATA SHEET REV : 01
DATE : 06.01.2011

PROJECT : 2x600MW TPP AT DERANG, ANGUL, ORISSA


CUSTOMER : JINDAL INDIA THERMAL POWER LIMITED
CONSULTANT: TATA CONSULTING ENGINEERS LIMITED, MUMBAI
CL. NO. PARAMETER UNIT VALUE

1.6.5 Potier reactance, Xp 24.8


1.6.6 Permissible tolerance in all guaranteed reactance %  15%
values
1.6.7 Effective winding capacitance to earth
a) Per phase µF 0.377
b) All phase connected to earth µF 1.131
1.6.8 Effective surge impedance to neutral per phase 32.0
Ohm
1.6.9 Armature resistance per phase at
a) 25 Deg. C Ohm 0.0009578
b) 75 Deg. C Ohm 0.001142
1.6.10 Field resistance per phase at
a) 25 Deg. C Ohm 0.06565
b) 75 Deg. C Ohm 0.0783
1.7.0 Time Constants
1.7.1 Direct axis transient
a) Open circuit time constant, Td’o Sec. 6.19
b) Short circuit time constant, Td’ Sec. 0.78
1.7.2 Direct axis subtransient
a) Open circuit time constant, Td’’o Sec. 0.04
b) Short circuit time constant, Td’’ 0.03
1.7.3 Quadrature axis transient
a) Open circuit time constant, Tq’o Sec. 2.5
b) Short circuit time constant, Tq’ Sec. 0.84
1.7.4 Quadrature axis sub-transient
a) Open circuit time constant, Tq’’o Sec. 0.20
b) Short circuit time constant, Tq’’ Sec. 0.07
1.7.5 Armature short circuit time constant, Ta Sec. 0.30
1.8.0 Short Circuit Current (in p.u.)

1.8.1 Sub-transient current


a) 3-phase short circuit P.U. 9.7
b) 2-phase short circuit P.U. 8.3

D:\user\akg\600MW_Derang\4033-0483_GDS_Derang_R01.doc
Page 5 of 14
DOC. NO. : 4033-0483
GENERATOR DATA SHEET REV : 01
DATE : 06.01.2011

PROJECT : 2x600MW TPP AT DERANG, ANGUL, ORISSA


CUSTOMER : JINDAL INDIA THERMAL POWER LIMITED
CONSULTANT: TATA CONSULTING ENGINEERS LIMITED, MUMBAI
CL. NO. PARAMETER UNIT VALUE

c) 1-phase to neutral short circuit P.U. 11.3


1.8.2 Transient current
a) 3-phase short circuit P.U. 4.1
b) 2-phase short circuit P.U. 4.0
c) 1-phase to neutral short circuit P.U. 5.7
1.8.3 Steady state current
a) 3-phase short circuit P.U. 1.51
b) 2-phase short circuit P.U. 2.34
c) 1-phase to neutral short circuit P.U. 3.86
1.9.0 Design and Construction
1.9.1 Stator core
a) Type of mounting Horizontal
b) Grade of steel
i) Thickness mm 0.50
ii) Loss figure W / Kg 1.1 W/kg (At 1 Tesla)
iii) Steel Grade M270-50A or
Equivalent.
iv)Type of core varnish Stabolite-40
c) Generator air gap mm 105
1.9.2 Stator winding
a) Is winding transposed? Yes/No Yes
b) Phase connections Double Star
c) Insulation
i) Class Class-F
ii) Type Micalastic
iii) Corona protection Yes
d) Dielectric test voltage kV 43
e) Impulse voltage strength kVp 89
f) Insulation Class
i) Slot Class-F
ii) End coil Class-F
1.9.3 Terminals

D:\user\akg\600MW_Derang\4033-0483_GDS_Derang_R01.doc
Page 6 of 14
DOC. NO. : 4033-0483
GENERATOR DATA SHEET REV : 01
DATE : 06.01.2011

PROJECT : 2x600MW TPP AT DERANG, ANGUL, ORISSA


CUSTOMER : JINDAL INDIA THERMAL POWER LIMITED
CONSULTANT: TATA CONSULTING ENGINEERS LIMITED, MUMBAI
CL. NO. PARAMETER UNIT VALUE

a) No. of terminal brought out


i) Phase 3
ii) Neutral 3
b) Type of terminal bushings Epoxy Type
c) Net space available for mounting bushing Outer Diameter : 800
current transformers MM
Inner Diameter : 450
MM
Length : 400 MM
d) Bushing CT furnished? Yes/No No
e) If yes state no. and specification of bushing Not applicable
C.T.
f) Dielectric test voltage kV 85
1.9.4 Rotor
a) Material for
i) Rotor forging 26NiCrMoV145
ii) Retaining ring X8CrMnN1818K
iii) Rotor wedge CuNi2Si
iv) Stator Frame Structural Steel
v) Bearing Body Carbon Steel
1.9.5 Rotor winding
a) Insulation
i) Class Class-F
ii) Type Epoxy Glass fiber
b) Turns per pole 49
c) Dielectric test voltage kV 5.0
1.9.6 Bearing
a) Type Sleeve Bearing
b) Oil quantity per bearing Cu.M/hr. 21.0
2
c) Oil pressure Kg/cm (g) 0.5 bar
1.10.0 Seal Oil system
1.10.1 No. of streams One

1.10.2 Seal oil pumps


a) Number 2 AC + 1DC

D:\user\akg\600MW_Derang\4033-0483_GDS_Derang_R01.doc
Page 7 of 14
DOC. NO. : 4033-0483
GENERATOR DATA SHEET REV : 01
DATE : 06.01.2011

PROJECT : 2x600MW TPP AT DERANG, ANGUL, ORISSA


CUSTOMER : JINDAL INDIA THERMAL POWER LIMITED
CONSULTANT: TATA CONSULTING ENGINEERS LIMITED, MUMBAI
CL. NO. PARAMETER UNIT VALUE

b) Capacity Cu.M/hr. 25.2


c) Discharge pressure Kg/cm2(g) 8-10 bar
1.10.3 Pump motor A.C Motor D.C Motor
a) KW rating KW 15 15
b) Voltage rating. Volts 400 220 DC
1.10.4 Vapour Extraction Unit (Bearing)
a) Type Centrifugal type
b) Capacity Cu.M/hr. 396
c) Motor size KW/V 0.75 / 400 Volts
1.10.5 Seal Oil/Water Cooler Plate type
(if applicable)
a) No. x Capacity 2x100%
b) Material of Construction (Specify Standard/
Code & grade if required)
i) Plate SS 316
ii) Tube plate --
iii) Water box ---
c) Quantity of cooling water per cooler Cu.M/hr. 59.4
d) Pressure drop across cooler on water side m.w.c. 3.5
e) Designed heat load KW 204
f) Heat transfer area Sq.m As per design
requirements
g) Cooling water temperature
i) Inlet Deg. C 38
ii) Outlet Deg. C 41
h) Maximum cooling water pressure allowable Kg/cm2(g) 8 bar (g)
2
i) Cooler water side hydrostatic test pressure Kg/cm (g) 24
1.11.0 Gas System
1.11.1 Volume of H2 space in generator Cu. M 85
1.11.2 Cooling gas flow Cu.M/Sec 24
1.11.3 Purity of H2 required
a) Normal % 98
b) Minimum % 96

D:\user\akg\600MW_Derang\4033-0483_GDS_Derang_R01.doc
Page 8 of 14
DOC. NO. : 4033-0483
GENERATOR DATA SHEET REV : 01
DATE : 06.01.2011

PROJECT : 2x600MW TPP AT DERANG, ANGUL, ORISSA


CUSTOMER : JINDAL INDIA THERMAL POWER LIMITED
CONSULTANT: TATA CONSULTING ENGINEERS LIMITED, MUMBAI
CL. NO. PARAMETER UNIT VALUE

1.11.4 H2 Leakage per day at rated pressure (Specify Cu-m 18


Unit)
1.11.5 Volume at NTP required for
a) H2 to displace CO2 to bring the casing to Cu. M 638
rated pressure
b) CO2 to displace H2 Cu. M 212.5
c) Air to displace CO2 Cu. M 255
d) CO2 to displace Air Cu. M 170
1.11.6 No. x Capacity of Cylinders furnished
a) H2 Nos., Cu.M 120 X 7
b) CO2 Nos., Cu.M 40 x 12
c) N2 Nos., Cu.M 12 X 7
1.11.7 H2 Gas/Water Cooler
a) No. x Capacity 2 X 50 % (Twin Type-
Two elements in one
twin cooler)
b) Material of Construction (Specify Standard/
Code & grade)
i) Type Plug-in
ii) Tube plate Carbon Steel ( IS :
2062 Gr. B)
iii) Water box Carbon Steel ( IS :
2062 Gr. B)
c) Quantity of cooling water per cooler Cu.M/hr. 137.5 Cu.M/hr. per
cooler element
d) Pressure drop across cooler on water side m.w.c. 9.5
e) Designed heat load KW 5090 (Rated Load)
f) Heat transfer area Sq. M 1208
2
g) Overall Heat transfer co-efficient Kcal/m .hr.De 301
g.C
h) Cooling water temperature
i) Inlet (max.) Deg. C 38
ii) Outlet Deg. C 46
2
1.11.8 Maximum cooling water pressure allowable Kg/cm (g) < 4.0
2
1.11.9 Cooler water side hydrostatic pressure Kg/cm (g) < 4.0
1.12.0 Excitation System
1.12.1 Nominal exciter response ratio

D:\user\akg\600MW_Derang\4033-0483_GDS_Derang_R01.doc
Page 9 of 14
DOC. NO. : 4033-0483
GENERATOR DATA SHEET REV : 01
DATE : 06.01.2011

PROJECT : 2x600MW TPP AT DERANG, ANGUL, ORISSA


CUSTOMER : JINDAL INDIA THERMAL POWER LIMITED
CONSULTANT: TATA CONSULTING ENGINEERS LIMITED, MUMBAI
CL. NO. PARAMETER UNIT VALUE

a) With generator at no load >2.0


b) With generator at rated load >2.0
1.12.2 Excitation System Voltage response time Sec. 0.5
1.12.3 Ceiling current Amps. 8830
1.12.4 Ceiling voltage Volts. 702
1.12.5 Ceiling duty duration Sec. 10
1.12.6 “Rapid defluxing” time and the technique used Sec. < 2.7 Sec, Field
Suppression
Technique followed by
Field Discharge
1.12.7 Type of de-excitation system Through Discharge
Resistor
1.12.8 Field reversal capability Yes, Field inversion by
driving Thyristor Bridge
to Inverter Mode
1.12.9 Excitation system time constant 0.02 Secs
1.12.10 Auxiliary power requirement 400 Volts, 3 Phase, 50
Hz : 5 KVA during testing.
Station DC 220V : 15 A
continuous (2 Feeders)
230 Volts, 1 Phase, 50
Hz – 1 KVA Continuous
1.12.11 Forced Cooling System requirement Not Applicable
1.12.12 Base field voltage Volts 413
1.12.13 Natural frequency of T.G. torsional oscillations First = 15.49 Hz
Second = 25.98 Hz
Third = 39.27Hz
1.12.14 Space requirement including clearance Typically : 4260(w) X
800 (D) X 2300 (H) in
mm. Clearance of 1
meter all around for
working.
1.12.15 Shelf life of the solid state spares Typically 5 Years, for
AVR Modules
1.12.16 Time for which spare parts (including solid state) 15 Years, for AVR
will be kept available Modules.
1.13.0 Automatic Voltage Regulator
1.13.1 Make BHEL-EDN
1.13.2 Type Micro processor based
DVR
1.13.3 Power Supply to regulator Volts. 220VDC +10%, -15%

D:\user\akg\600MW_Derang\4033-0483_GDS_Derang_R01.doc
Page 10 of 14
DOC. NO. : 4033-0483
GENERATOR DATA SHEET REV : 01
DATE : 06.01.2011

PROJECT : 2x600MW TPP AT DERANG, ANGUL, ORISSA


CUSTOMER : JINDAL INDIA THERMAL POWER LIMITED
CONSULTANT: TATA CONSULTING ENGINEERS LIMITED, MUMBAI
CL. NO. PARAMETER UNIT VALUE

1.13.4 Range of voltage adjustments


a) Auto 90% Ugn to 110% Ugn
b) Manual 0 to 105% Ifn
1.13.5 Range of operation
a) Frequency Hz 47.5 to 52.5
b) Temperature Deg. C 50
1.13.6 Accuracy +/- 0.5%
1.13.7 Dead Band Negligible
1.13.8 Response time to apply field forcing voltage with a < or = 20mS
5%drop
1.14.0 Brushless Excitation
1.14.1 Pilot Exciter
a) Make BHEL
b) Type ELP50/42-30/16
c) Reference Standard IEC 34-1
d) Type of drive Direct
e) Rated output KVA 65
f) Rated power factor ---
g) Rated voltage Volts. 220
h) Rated current Amps. 195
i) Rated speed RPM 3000
j) No. of phase & frequency Nos./Hz 3 x 400
k) Insulation class & type Class-F/ Enamelled
Glass
l) Stator winding resistance per phase at 25 Ohm 0.00275
Deg. C
m) Stator winding resistance per phase at 75 Ohm 0.00327
Deg. C
1.14.2 Main Exciter
a) Make BHEL
b) Type ELR70/90-30/6-20N
c) Reference Standard IEC 34-1
d) Type of drive Direct
e) Rated output KVA 3780

D:\user\akg\600MW_Derang\4033-0483_GDS_Derang_R01.doc
Page 11 of 14
DOC. NO. : 4033-0483
GENERATOR DATA SHEET REV : 01
DATE : 06.01.2011

PROJECT : 2x600MW TPP AT DERANG, ANGUL, ORISSA


CUSTOMER : JINDAL INDIA THERMAL POWER LIMITED
CONSULTANT: TATA CONSULTING ENGINEERS LIMITED, MUMBAI
CL. NO. PARAMETER UNIT VALUE

f) No. of phase & frequency Nos./Hz 3 x 150


g) Rated power factor -----
h) Rated voltage at generator output and power Volts. 413
factor
i) Rated current at generator output and power Amps. 5192
factor
j) Field current at generator rated output and Amps. 110
power factor
k) Exciter rectified field voltage with manual
control

i) Maximum Volts. 122


ii) Minimum Volts. 5
l) No. of poles 6
m) Winding resistance At 25 At 75 Deg.
Deg. C C
i) Armature (per phase) Ohm 0.00046 0.00054
(phase-
phase)
ii) Field Ohm 0.59 0.70
n) Class and type of insulation
i) Armature Epoxy Glass lapped /
Class-F
ii) Field Epoxy Nomex / Class-F
o) Nominal exciter response ratio > 2.0
p) Type of cooling Air to water
1.14.3 Rotating rectifier assembly
a) Make BHEL
b) Type Silicon Diode
c) Reference Standard IEC 34-1
d) Type of connection Three Phase
e) No. of bridge arms 6
f) No. of parallel paths per bridge arm 10
g) No. of rectifier cells in each parallel path 2 (in parallel)
h) Minimum nos. of parallel paths per bridge 8
arm required for rated output
i) Spare capacity of rectifier on the basis of 20 %
guaranteed full load %

D:\user\akg\600MW_Derang\4033-0483_GDS_Derang_R01.doc
Page 12 of 14
DOC. NO. : 4033-0483
GENERATOR DATA SHEET REV : 01
DATE : 06.01.2011

PROJECT : 2x600MW TPP AT DERANG, ANGUL, ORISSA


CUSTOMER : JINDAL INDIA THERMAL POWER LIMITED
CONSULTANT: TATA CONSULTING ENGINEERS LIMITED, MUMBAI
CL. NO. PARAMETER UNIT VALUE

j) Diode rating
i) Rated average forward current Amps. 690
ii) Maximum repetitive peak inverse voltage Volts. 2600
k) Fuses
i) Total no. of fuses 60
ii) Type of connection BOLTED
iii) Rating of each fuse 800 Amps, 800 Volts
iv) Type of fuse failure indicator Stroboscope
l) Overload rating of the rectifier cell
i) Current Amps. 690
ii) Duration Sec. Continuous
O
m) Maximum junction temperature of the rectifier C 90
cell
n) Method of over voltage protection RC Network
o) Make and type of cooling fans Make : Siemens /
Indalco make
Type : Extruded
Section
1.14.4 Air/Water Cooler
a) No. x Capacity 2 X 50 %
b) Material of Construction (Specify Standard/
Code & grade)
i) Type Plug-in-Type
ii) Tube plate Carbon Steel (IS 2062,
Gr.B)
iii) Water box Carbon Steel (IS 2062,
Gr.B)
c) Quantity of cooling water per cooler Cu.M/hr. 100
d) Pressure drop across cooler on water side m.w.c. 2.4
e) Designed heat load KW 500
f) Heat transfer area Sq. M 429
g) Cooling water temperature
i) Inlet (max.) Deg. C 39
ii) Outlet Deg. C 41.2
2
1.14.5 Maximum cooling water pressure allowable Kg/cm (g) 10

D:\user\akg\600MW_Derang\4033-0483_GDS_Derang_R01.doc
Page 13 of 14
DOC. NO. : 4033-0483
GENERATOR DATA SHEET REV : 01
DATE : 06.01.2011

PROJECT : 2x600MW TPP AT DERANG, ANGUL, ORISSA


CUSTOMER : JINDAL INDIA THERMAL POWER LIMITED
CONSULTANT: TATA CONSULTING ENGINEERS LIMITED, MUMBAI
CL. NO. PARAMETER UNIT VALUE

1.14.6 Cooler water side hydrostatic pressure Kg/cm2(g) < 3.0


1.15.0 Generator
1.15.1 Iron Loss
a) At no load KW 730
b) At full load KW 876
1.15.2 Stator copper loss KW 1285
1.15.3 Rotor copper loss
a) At no load KW 307
b) At full load KW 2110
1.15.4 Stray load loss KW 1820
1.15.5 Friction and windage loss KW 1025
1.15.6 Excitation losses
a) Exciter constant loss KW 305
b) Exciter & Rotary rectifier variable loss KW 74
c) Collector-brush contact loss KW ---
1.15.7 Total losses KW 7349
1.16.0 Main Weights
1.16.1 Weight of the Generator Stator Tonnes 298
1.16.2 Weight of the Generator Rotor Tonnes 75
1.16.3 Weight of the Complete Generator (Stator plus Tonnes 492
Rotor)
1.16.4 i) Overall Diameter of stator
ii) Length of Stator(overall) Refer Generator
iii) Length of the rotor(overall) Outline Drg.
iv) Diameter of rotor Barrel
1.17.0 Generator Performance Curves
1.17.1 Generator capability curve TG:THDF115/67-010
1.17.2 Open and short circuit characteristics TG:THDF115/67-011
1.17.3 Load excitation curves and estimated `V’ curves TG:THDF115/67-012
1.17.4 Negative sequence current characteristics TG:THDF115/67-013
1.17.5 Permissible loading at rated power factor during TG:THDF115/67-015
voltage and frequency variation
1.17.6 Capability diagram at reduced H2 pressure TG:THDF115/67-017
1.17.7 Asynchronous capability of generator TG:THDF115/67-018

D:\user\akg\600MW_Derang\4033-0483_GDS_Derang_R01.doc
Page 14 of 14
PERMISIBLE LOADING DURING VOLTAGE AND FREQUENCY DEVIATIONS
(AT RATED POWER FACTOR)

GENERATOR TYPE : THDF 115/67

B.H.E.L. TG:THDF115/67- 015


Date: 18.07.07
ASYNCHRONOUS CAPABILITY
OF
TURBOGENERATOR TYPE THDF 115/67

0.8

0.7

0.6

0.5
LOAD, P.U. -------->

0.4

0.3

CONTINUOUS
0.2

0.1

0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 8 8.5 9 9.5 10
TIME, MINUTES-------->

CURVE NO. TG-THDF115/67-018


Worked By : Asha Gupta Approved By : S D Nagar REV-00, DATE-16.01.2009