User Manual
Revision 1.100
English
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 2 of 34
Industrial Electronic Devices
Page Dear customer, we thank you for your attention and we remind you
INDEX 2 that you need to check that the following document is:
UPDATED DOCUMENTATION 2
REVISION LIST 2 Updated
WARNING 2 Related to the product you own
TRADEMARKS 2
SECURITY ALERT 3 To obtain the most recently updated document, note the “document
EXAMPLE OF CONNECTION 4 code” that appears at the top right-hand corner of each page of this
CONNECTION SCHEME 6 document.
CHARACTERISTICS 10
CONFIGURATION 10 With this “Document Code” go to web page
POWER SUPPLY 11 www.adfweb.com/download/ and search for the corresponding code on
FUNCTION MODES 12 the page. Click on the proper “Document Code” and download the
LEDS 13 updates.
RS485 15
RS232 16
ETHERNET 17
REVISION LIST:
USE OF COMPOSITOR SW67671 18
NEW CONFIGURATION / OPEN CONFIGURATION 19
Revision Date Author Chapter Description
SOFTWARE OPTIONS 20
1.001 23/07/2013 Fl All Revision
SET COMMUNICATION 22
1.010 14/07/2014 Fl All Software changed (v1.200)
SET MODBUS ACCESS 25
1.020 18/11/2014 Fl All Software changed (v1.300)
SET BACNET ACCESS 27
1.100 18/04/2017 Ff All Revision
OBJECTS MAP 28
UPDATE DEVICE 29
MECHANICAL DIMENSIONS 31
WARNING:
ORDERING INFORMATIONS 32
ACCESSORIES 32
DISCLAIMER 33
ADFweb.com reserves the right to change information in this manual
OTHER REGULATIONS AND STANDARDS 33 about our product without warning.
WARRANTIES AND TECHNICAL SUPPORT 34 ADFweb.com is not responsible for any error this manual may contain.
RETURN POLICY 34
TRADEMARKS:
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 3 of 34
Industrial Electronic Devices
SECURITY ALERT:
GENERAL INFORMATION
To ensure safe operation, the device must be operated according to the instructions in the manual. When using the device, legal and
safety regulation are required for each individual application. The same applies also when using accessories.
INTENDED USE
Machines and systems must be designed so the faulty conditions do not lead to a dangerous situation for the operator (i.e.
independent limit switches, mechanical interlocks, etc.).
QUALIFIED PERSONNEL
The device can be used only by qualified personnel, strictly in accordance with the specifications.
Qualified personnel are persons who are familiar with the installation, assembly, commissioning and operation of this equipment and
who have appropriate qualifications for their job.
RESIDUAL RISKS
The device is state-of-the-art and is safe. The instruments can represent a potential hazard if they are inappropriately installed and
operated by untrained personnel. These instructions refer to residual risks with the following symbol:
This symbol indicates that non-observance of the safety instructions is a danger for people that could lead to serious injury or
death and / or the possibility of damage.
CE CONFORMITY
The declaration is made by our company. You can send an email to [email protected] or give us a call if you need it.
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 4 of 34
Industrial Electronic Devices
EXAMPLE OF CONNECTION:
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 5 of 34
Industrial Electronic Devices
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 6 of 34
Industrial Electronic Devices
CONNECTION SCHEME:
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 8 of 34
Industrial Electronic Devices
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 9 of 34
Industrial Electronic Devices
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 10 of 34
Industrial Electronic Devices
CHARACTERISTICS:
The HD67671-IP-X-A1 and HD67671-MSTP-X-A1 are converters from BACnet slave to Modbus master and vice-versa.
CONFIGURATION:
You need Compositor SW67671 software on your PC in order to perform the following:
Define the parameter of BACnet line;
Define the parameter of Modbus line;
Define BACnet objects that contains the data read from the Modbus slaves;
Define BACnet objects that contains the data to send to the Modbus slaves;
Update the device.
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 11 of 34
Industrial Electronic Devices
POWER SUPPLY:
The devices can be powered at 8…24V AC and 12…35V DC. For more details see the two tables below.
VAC VDC
Vmin Vmax Vmin Vmax
8V 24V 12V 35V
HD67671-IP-2-A1
HD67671-IP-4-A1
HD67671-MSTP-2-A1
HD67671-MSTP-4-A1
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 12 of 34
Industrial Electronic Devices
FUNCTION MODES:
The device has got two functions mode depending of the position of the ‘Dip2 of Dip-Switch A’:
The first, with ‘Dip2 of Dip-Switch A’ at “OFF” position, is used for the normal working of the device.
The second, with ‘Dip2 of Dip-Switch A’ at “ON” position, is used for uploading the Project and/or Firmware.
For the operations to follow for the updating, see ‘UPDATE DEVICE’ section.
According to the functioning mode, the LEDs will have specifics functions, see ‘LEDS’ section.
Warning:
Dip1 of ‘Dip-Switch A’ must be at ON position to work even if the Ethernet cable is not inserted.
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 13 of 34
Industrial Electronic Devices
LEDS:
HD67671-IP-2-A1, HD67671-IP-4-A1
The device has got six LEDs that are used to give information about the functioning status.
The various meanings of the LEDs are described in the table below.
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 14 of 34
Industrial Electronic Devices
HD67671-MSTP-2-A1, HD67671-MSTP-4-A1
The device has four LEDs that are used to give information of the functioning status.
The various meanings of the LEDs are described in the table below.
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 15 of 34
Industrial Electronic Devices
RS485:
To terminate the RS485 line with a 120Ω resistor it is necessary to put ON dip 1, like in figure.
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 16 of 34
Industrial Electronic Devices
RS232:
The connection from RS232 socket to a serial port (example one from a personal computer) must be made with a NULL MODEM cable (a
serial cable where the pins 2 and 3 are crossed).
It is recommended that the RS232 cable not exceed 15 meters.
HD67671-IP-2-A1 HD67671-MSTP-2-A1
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 17 of 34
Industrial Electronic Devices
ETHERNET:
HD67671-IP-2-A1, HD67671-IP-4-A1
The Ethernet ports are used for BACnet/IP communication and for programming the device.
The BACnet/IP connection must be made using Connector3 and/or Connector4 of HD67671-IP-2-A1 or HD67671-IP-4-A1 with at least
a Category 5E cable. The maximum length of the cable should not exceed 100m. The cable has to conform to the T568 norms relative
to connections in cat.5 up to 100 Mbps. To connect the device to an Hub/Switch is recommended the use of a straight cable, to
connect the device to a PC/PLC/other is recommended the use of a cross cable.
HD67671-MSTP-2-A1, HD67671-MSTP-4-A1
The Ethernet port is used for programming the device.
The Ethernet connection must be made using Connector5 of HD67671-MSTP-2-A1 or HD67671-MSTP-4-A1 with at least a Category
5E cable. The maximum length of the cable should not exceed 100m. The cable has to conform to the T568 norms relative to
connections in cat.5 up to 100 Mbps. To connect the device to an Hub/Switch is recommended the use of a straight cable, to connect
the device to a PC/PLC/other is recommended the use of a cross cable.
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 18 of 34
Industrial Electronic Devices
To configure the Converter, use the available software that runs with Windows called SW67671. It is downloadable from the site
www.adfweb.com and its operation is described in this document (this manual is referenced to the last version of the software present on our
web site). The software works with MSWindows (XP, Vista, Seven, 8, 10; 32/64bit).
When launching the SW67671, the window below appears (Fig. 2).
Note:
It is necessary to have installed .Net Framework 4.
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 19 of 34
Industrial Electronic Devices
The “New Configuration” button creates the folder which contains the entire device’s configuration.
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 20 of 34
Industrial Electronic Devices
SOFTWARE OPTIONS:
By pressing the “Settings” ( ) button there is the possibility to change the language of the software and check the updatings for the
compositor.
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 21 of 34
Industrial Electronic Devices
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 22 of 34
Industrial Electronic Devices
SET COMMUNICATION:
This section define the fundamental communication parameters of two buses, BACnet and Modbus.
By Pressing the “Set Communication” button from the main window for SW67671 (Fig. 2) the window “Set
Communication” appears (Fig. 3).
The window is divided in three sections, one for selecting the type of BACnet (in relation to the device used),
one for the BACnet parameters and the other for the Modbus parameters.
In the section “BACnet Type” is possible to select the type of BACnet to use from:
BACnet/IP (uses Ethernet);
BACnet MS/TP (uses RS485).
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 23 of 34
Industrial Electronic Devices
The means of the fields for the “Modbus Master” section are:
In the field “Serial” the serial port used for the Modbus communication is defined;
In the field “Baudrate” the data rate of the Modbus line is defined;
In the field “Parity” the parity of the Modbus line is defined;
In the field “Stop Bits” the number of Stop-bit of the Modbus line is defined;
In the “TimeOut (ms)” the maximum time that the converter attends for the answer from the slave interrogated is defined;
In the field “Cyclic Delay (ms)” the delay between two requests is defined.
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 24 of 34
Industrial Electronic Devices
If selected “BACnet MS/TP”, the means of the fields for “BACnet” are:
In the field “Baudrate” the data rate of the BACnet line is defined;
In the field “Parity” the parity of the line is defined;
In the field “BACnet Device Name” the name to give to the BACnet node is defined;
In the field “MAC Address” the MAC of BACnet node (from 0 to 254) is defined;
The field “Max Master” specifies the highest allowable address for master nodes. The value shall be less
than or equal to 127;
The field “Max Info Frames” specifies the maximum number of information frames the node may send
before it must pass the token;
In the field “Device Instance” the of the BACnet MS/TP side of the converter is defined;
In the field “Network” the BACnet MS/TP network number is defined;
If the field “BACnet description up to 32 chars” is checked, the description for the BACnet Objects
can be up to 32 chars long.
The means of the fields for the “Ethernet Update” section are:
In the fields “IP ADDRESS” the IP address of the converter is defined;
In the fields “SUBNET Mask” the SubNet Mask of the converter is defined;
In the fields “GATEWAY” the default gateway of the network is defined. This feature can be enabled or
disabled pressing the Check Box field. This feature is used for going out of the net.
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 25 of 34
Industrial Electronic Devices
By Pressing the “Set Modbus Access ” button from the main window for SW67671 (Fig. 2) the window “Set Access” appears (Fig. 4).
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 26 of 34
Industrial Electronic Devices
The window is divided in two parts, the “Modbus Read” that contains the Modbus registers/status readable by the Converter and “Modbus
Write” that contains the Modbus registers/status writeable by the Converter.
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 27 of 34
Industrial Electronic Devices
By Pressing the “Set BACnet Access” button from the main window for SW67671 (Fig. 2) the window “BACnet Set Access” appears (Fig. 5).
OBJECTS MAP:
By Pressing the “Objects Map” button from the main window for SW67671 (Fig. 2) is possible to create a .csv document with the map of
BACnet Objects.
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 29 of 34
Industrial Electronic Devices
UPDATE DEVICE:
By pressing the “Update Device” button, it is possible to load the created Configuration into the
device; and also the Firmware, if necessary.
If you don’t know the actual IP address of the device you have to use this procedure:
Turn OFF the Device;
Put Dip2 of ‘Dip-Switch A’ at ON position;
Turn ON the device
Connect the Ethernet cable;
Insert the IP “192.168.2.205”;
Press the “Ping” button, “Device Found!” must appear”;
Press the “Next” button;
Select which operations you want to do;
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” turn OFF the Device;
Put Dip2 of ‘Dip-Switch A’ at OFF position;
Turn ON the device.
If you know the actual IP address of the device you have to use this procedure:
Turn on the Device with the Ethernet cable inserted;
Insert the actual IP of the Converter;
Press the “Ping” button, must appear “Device Found!”;
Press the “Next” button;
Select which operations you want to do;
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” the device automatically goes at Normal Mode.
Note:
When you install a new version of the software, if it is the first time it is better you do the update of the Firmware in the HD67671
device.
Note:
When you receive the device, for the first time, you also have to update the Firmware in the HD67671 device.
Warning:
If Fig. 8 appears when you try to do the Update try these points before seeking
assistance:
Try to repeat the operations for the updating;
Try with another PC;
Try to restart the PC;
Check the LAN settings;
Check the Wi-Fi settings;
If you are using the program inside a Virtual Machine, try to use in the main
Operating System; Figure 8: “Protection” window
If you are using Windows Seven, Vista, 8 or 10 make sure that you have the
administrator privileges;
In case you have to program more than one device, using the "UDP Update", you have to cancel the ARP table every time you
connect a new device on Ethernet. For do this you have to launch the "Command Prompt" and write the command "arp -d". Pay
attention that with Windows Vista, Seven, 8, 10 you have to launch the "Command Prompt" with Administrator Rights;
Pay attention at Firewall lock.
In the case of HD67671 you have to use the software “SW67671”: www.adfweb.com\download\filefold\SW67671.zip.
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 31 of 34
Industrial Electronic Devices
MECHANICAL DIMENSIONS:
Figure 9a: Mechanical dimensions scheme for HD67671-IP-2-A1 Figure 9b: Mechanical dimensions scheme for HD67671-IP-4-A1
Figure 9c: Mechanical dimensions scheme for HD67671-MSTP-2-A1 Figure 9d: Mechanical dimensions scheme for HD67671-MSTP-4-A1
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 32 of 34
Industrial Electronic Devices
ORDERING INFORMATIONS:
Connectors Type
1: Removable 5mm Screw Terminal
Enclosure Type
A: 1M, 35mm DIN Rail mounting
Modbus port
2: RS232
4: RS485
BACnet type:
IP: BACnet/IP
MSTP: BACnet MS/TP
Device Family
HD67671: BACnet Slave / Modbus Master - Converter
Order Code: HD67671-IP-2-A1 - BACnet/IP slave/ Modbus master – Converter (Modbus over RS232)
Order Code: HD67671-IP-4-A1 - BACnet/IP slave / Modbus master – Converter (Modbus over RS485)
Order Code: HD67671-MSTP-2-A1 - BACnet MS/TP slave / Modbus master – Converter (Modbus over RS232)
Order Code: HD67671-MSTP-4-A1 - BACnet MS/TP slave / Modbus master – Converter (Modbus over RS485)
ACCESSORIES:
Order Code: AC34001 - 35mm Rail DIN - Power Supply 220/240V AC 50/60Hz – 12 V AC
Order Code: AC34002 - 35mm Rail DIN - Power Supply 110V AC 50/60Hz – 12 V AC
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 33 of 34
Industrial Electronic Devices
DISCLAIMER:
All technical content within this document can be modified without notice. The content of the document is a under continual renewal.
For losses due to fire, earthquake, third party access or other accidents, or intentional or accidental abuse, misuse, or use under abnormal
conditions repairs are charged to the user. ADFweb.com S.r.l. will not be liable for accidental loss of use or inability to use this product, such
as loss of business income. ADFweb.com S.r.l. shall not be liable for consequences of improper use.
WEEE INFORMATION
Disposal of old electrical and electronic equipment (as in the European Union and other European countries with separate
collection systems).
This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish. Instead, it
should be taken to an applicable collection point for the recycling of electrical and electronic equipment. If the product is disposed
correctly, you will help prevent potential negative environmental factors and impact of human health, which could otherwise be
caused by inappropriate disposal. The recycling of materials will help to conserve natural resources. For more information about
recycling this product, please contact your local city office, your household waste disposal service or the shop where you purchased
the product.
CE MARKING
The product conforms with the essential requirements of the applicable EC directives.
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 34 of 34
Industrial Electronic Devices
For fast and easy technical support for your ADFweb.com SRL products, consult our internet support at www.adfweb.com.
Otherwise contact us at the address [email protected]
RETURN POLICY:
If while using your product you have any problem and you wish to exchange or repair it, please do the following:
Obtain a Product Return Number (PRN) from our internet support at www.adfweb.com. Together with the request, you need to
provide detailed information about the problem.
Send the product to the address provided with the PRN, having prepaid the shipping costs (shipment costs billed to us will not be
accepted).