This document provides information about BACnet/IP Slave and Modbus Master converters, including connection schemes, characteristics, configuration, functions, LED indicators, and ordering details. The converters allow communication between BACnet networks and Modbus devices, with features like triple electrical isolation, two BACnet ports, and an operating temperature range of -40°C to 85°C. Configuration is done through an integrated web server using the Compositor SW67671 software.

Uploaded by

techhustler2
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
24 views34 pages

MN67671 Eng

This document provides information about BACnet/IP Slave and Modbus Master converters, including connection schemes, characteristics, configuration, functions, LED indicators, and ordering details. The converters allow communication between BACnet networks and Modbus devices, with features like triple electrical isolation, two BACnet ports, and an operating temperature range of -40°C to 85°C. Configuration is done through an integrated web server using the Compositor SW67671 software.

Uploaded by

techhustler2
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 34

User Manual BACnet Slave / Modbus Master

Document code: MN67671_ENG Revision 1.100 Page 1 of 34


Industrial Electronic Devices

User Manual
Revision 1.100
English

BACnet/IP Slave / Modbus Master -


Converter
(Order Code: HD67671-IP-2-A1, HD67671-IP-4-A1)
BACnet MS/TP Slave / Modbus Master - For others BACnet products see also the following link:
Converter Converter BACnet slave to
(Order Code: HD67671-MSTP-2-A1, HD67671-MSTP-4-A1) www.adfweb.com?Product=HD67056 (M-Bus Master)
www.adfweb.com?Product=HD67086 (M-Bus Wireless)
www.adfweb.com?Product=HD67170 (SNMP Manager)
For Website information:
www.adfweb.com?Product=HD67670 (DMX)
www.adfweb.com?Product=HD67671 www.adfweb.com?Product=HD67671 (Modbus Master)
www.adfweb.com?Product=HD67672 (Modbus Slave)
For Price information: www.adfweb.com?Product=HD67673 (Modbus TCP Master)
www.adfweb.com?Product=HD67674 (Modbus TCP Slave)
www.adfweb.com?Price=HD67671-IP-2-A1
www.adfweb.com?Product=HD67675 (PROFIBUS Master)
www.adfweb.com?Price=HD67671-IP-4-A1 www.adfweb.com?Product=HD67676 (PROFIBUS Slave)
www.adfweb.com?Price=HD67671-MSTP-2-A1 www.adfweb.com?Product=HD67677 (CAN)
www.adfweb.com?Price=HD67671-MSTP-4-A1 www.adfweb.com?Product=HD67678 (CANopen)
www.adfweb.com?Product=HD67679 (PROFINET)
www.adfweb.com?Product=HD67680 (DeviceNet Master)
Benefits and Main Features: www.adfweb.com?Product=HD67681 (DeviceNet Slave)
www.adfweb.com?Product=HD67682 (EtherNet/IP)
Triple electrical isolation www.adfweb.com?Product=HD67683 (NMEA 2000)
www.adfweb.com?Product=HD67684 (Ethernet)
Two BACnet ports
www.adfweb.com?Product=HD67685 (J1939)
Temperature range: -40°C/85°C (-40°F/185°F) www.adfweb.com?Product=HD67693 (SNMP Agent)
www.adfweb.com?Product=HD67802 (KNX)
www.adfweb.com?Product=HD67833 (DALI)

Do you have an your customer protocol?


www.adfweb.com?Product=HD67003
Do you need to choose a device? do you want help?
www.adfweb.com?Cmd=helpme
User Manual

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 2 of 34
Industrial Electronic Devices

INDEX: UPDATED DOCUMENTATION:

Page Dear customer, we thank you for your attention and we remind you
INDEX 2 that you need to check that the following document is:
UPDATED DOCUMENTATION 2
REVISION LIST 2 Updated
WARNING 2 Related to the product you own
TRADEMARKS 2
SECURITY ALERT 3 To obtain the most recently updated document, note the “document
EXAMPLE OF CONNECTION 4 code” that appears at the top right-hand corner of each page of this
CONNECTION SCHEME 6 document.
CHARACTERISTICS 10
CONFIGURATION 10 With this “Document Code” go to web page
POWER SUPPLY 11 www.adfweb.com/download/ and search for the corresponding code on
FUNCTION MODES 12 the page. Click on the proper “Document Code” and download the
LEDS 13 updates.
RS485 15
RS232 16
ETHERNET 17
REVISION LIST:
USE OF COMPOSITOR SW67671 18
NEW CONFIGURATION / OPEN CONFIGURATION 19
Revision Date Author Chapter Description
SOFTWARE OPTIONS 20
1.001 23/07/2013 Fl All Revision
SET COMMUNICATION 22
1.010 14/07/2014 Fl All Software changed (v1.200)
SET MODBUS ACCESS 25
1.020 18/11/2014 Fl All Software changed (v1.300)
SET BACNET ACCESS 27
1.100 18/04/2017 Ff All Revision
OBJECTS MAP 28
UPDATE DEVICE 29
MECHANICAL DIMENSIONS 31
WARNING:
ORDERING INFORMATIONS 32
ACCESSORIES 32
DISCLAIMER 33
ADFweb.com reserves the right to change information in this manual
OTHER REGULATIONS AND STANDARDS 33 about our product without warning.
WARRANTIES AND TECHNICAL SUPPORT 34 ADFweb.com is not responsible for any error this manual may contain.
RETURN POLICY 34

TRADEMARKS:

All trademarks mentioned in this document belong to their respective


owners.

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 3 of 34
Industrial Electronic Devices

SECURITY ALERT:

GENERAL INFORMATION
To ensure safe operation, the device must be operated according to the instructions in the manual. When using the device, legal and
safety regulation are required for each individual application. The same applies also when using accessories.

INTENDED USE
Machines and systems must be designed so the faulty conditions do not lead to a dangerous situation for the operator (i.e.
independent limit switches, mechanical interlocks, etc.).

QUALIFIED PERSONNEL
The device can be used only by qualified personnel, strictly in accordance with the specifications.
Qualified personnel are persons who are familiar with the installation, assembly, commissioning and operation of this equipment and
who have appropriate qualifications for their job.

RESIDUAL RISKS
The device is state-of-the-art and is safe. The instruments can represent a potential hazard if they are inappropriately installed and
operated by untrained personnel. These instructions refer to residual risks with the following symbol:

This symbol indicates that non-observance of the safety instructions is a danger for people that could lead to serious injury or
death and / or the possibility of damage.

CE CONFORMITY
The declaration is made by our company. You can send an email to [email protected] or give us a call if you need it.

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 4 of 34
Industrial Electronic Devices

EXAMPLE OF CONNECTION:

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 5 of 34
Industrial Electronic Devices

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 6 of 34
Industrial Electronic Devices

CONNECTION SCHEME:

Figure 1a: Connection scheme for HD67671-IP-2-A1


ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 7 of 34
Industrial Electronic Devices

Figure 1b: Connection scheme for HD67671-IP-4-A1

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 8 of 34
Industrial Electronic Devices

Figure 1c: Connection scheme for HD67671-MSTP-2-A1

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 9 of 34
Industrial Electronic Devices

Figure 1d: Connection scheme for HD67671-MSTP-4-A1

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 10 of 34
Industrial Electronic Devices

CHARACTERISTICS:

The HD67671-IP-X-A1 and HD67671-MSTP-X-A1 are converters from BACnet slave to Modbus master and vice-versa.

They allows the following characteristics:


Up to 2000 BACnet objects (Read+Write);
Triple isolation between BACnet - Power Supply, BACnet - Modbus, Power Supply - Modbus.
Two-directional information between BACnet bus and Modbus bus;
Mountable on 35mm Rail DIN;
Wide power supply input range: 8…24V AC or 12…35V DC;
Wide temperature range: -40°C / 85°C [-40°F / +185°F].

CONFIGURATION:

You need Compositor SW67671 software on your PC in order to perform the following:
Define the parameter of BACnet line;
Define the parameter of Modbus line;
Define BACnet objects that contains the data read from the Modbus slaves;
Define BACnet objects that contains the data to send to the Modbus slaves;
Update the device.

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 11 of 34
Industrial Electronic Devices

POWER SUPPLY:

The devices can be powered at 8…24V AC and 12…35V DC. For more details see the two tables below.

VAC VDC
Vmin Vmax Vmin Vmax
8V 24V 12V 35V

Consumption at 24V DC:

Device Consumption [W/VA]


HD67671-IP-X-A1 3.5
HD67671-MSTP-X-A1 3.5

Caution: Not reverse the polarity power

HD67671-IP-2-A1
HD67671-IP-4-A1
HD67671-MSTP-2-A1
HD67671-MSTP-4-A1

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 12 of 34
Industrial Electronic Devices

FUNCTION MODES:

The device has got two functions mode depending of the position of the ‘Dip2 of Dip-Switch A’:
The first, with ‘Dip2 of Dip-Switch A’ at “OFF” position, is used for the normal working of the device.
The second, with ‘Dip2 of Dip-Switch A’ at “ON” position, is used for uploading the Project and/or Firmware.

For the operations to follow for the updating, see ‘UPDATE DEVICE’ section.

According to the functioning mode, the LEDs will have specifics functions, see ‘LEDS’ section.

Warning:
Dip1 of ‘Dip-Switch A’ must be at ON position to work even if the Ethernet cable is not inserted.

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 13 of 34
Industrial Electronic Devices

LEDS:

HD67671-IP-2-A1, HD67671-IP-4-A1
The device has got six LEDs that are used to give information about the functioning status.
The various meanings of the LEDs are described in the table below.

LED Normal Mode Boot Mode


1: ON [supply voltage ] ON: Device powered ON: Device powered
(green) OFF: Device not powered OFF: Device not powered
Blinks quickly: Boot state
2: Modbus comm. (green) Change state when Modbus replies arrive
Blinks very slowly (~0.5Hz): update in progress
Blinks quickly: Boot state
3: Device state (green) Blinks slowly (~1Hz)
Blinks very slowly (~0.5Hz): update in progress
Blinks quickly: Boot state
4: Not used (green) OFF
Blinks very slowly (~0.5Hz): update in progress
Blinks quickly: Boot state
5: Ethernet1 Tx (green) Blinks when it is transmitting Ethernet frames
Blinks very slowly (~0.5Hz): update in progress
Blinks quickly: Boot state
6: Ethernet2 Tx (green) Blinks when it is transmitting Ethernet frames
Blinks very slowly (~0.5Hz): update in progress

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 14 of 34
Industrial Electronic Devices

HD67671-MSTP-2-A1, HD67671-MSTP-4-A1
The device has four LEDs that are used to give information of the functioning status.
The various meanings of the LEDs are described in the table below.

LED Normal Mode Boot Mode


Blinks quickly: Boot state
1: Device State Blinks slowly (~1Hz)
Blinks very slowly (~0.5Hz): update in progress

ON: Ethernet cable connected ON: Ethernet cable connected


2: Link Ethernet
OFF: Ethernet cable disconnected OFF: Ethernet cable disconnected

Blinks quickly: Boot state


3: BACnet communication Blinks quickly when a BACnet request is received
Blinks very slowly (~0.5Hz): update in progress
Blinks quickly: Boot state
2: Modbus comm. (green) Change state when Modbus replies arrive
Blinks very slowly (~0.5Hz): update in progress

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 15 of 34
Industrial Electronic Devices

RS485:

To terminate the RS485 line with a 120Ω resistor it is necessary to put ON dip 1, like in figure.

The maximum length of the cable should be 1200m (4000 feet).

Here some codes of cables:


Belden: p/n 8132 - 2x 28AWG stranded twisted pairs conductor + foil shield + braid shield;
Belden p/n 82842 - 2x 24AWG stranded twisted pairs conductor + foil shield + braid shield;
Tasker: p/n C521 - 1x 24AWG twisted pair conductor + foil shield + braid shield;
Tasker: p/n C522 - 2x 24AWG twisted pairs conductor + foil shield + braid shield.

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 16 of 34
Industrial Electronic Devices

RS232:

The connection from RS232 socket to a serial port (example one from a personal computer) must be made with a NULL MODEM cable (a
serial cable where the pins 2 and 3 are crossed).
It is recommended that the RS232 cable not exceed 15 meters.

HD67671-IP-2-A1 HD67671-MSTP-2-A1

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 17 of 34
Industrial Electronic Devices

ETHERNET:

HD67671-IP-2-A1, HD67671-IP-4-A1
The Ethernet ports are used for BACnet/IP communication and for programming the device.
The BACnet/IP connection must be made using Connector3 and/or Connector4 of HD67671-IP-2-A1 or HD67671-IP-4-A1 with at least
a Category 5E cable. The maximum length of the cable should not exceed 100m. The cable has to conform to the T568 norms relative
to connections in cat.5 up to 100 Mbps. To connect the device to an Hub/Switch is recommended the use of a straight cable, to
connect the device to a PC/PLC/other is recommended the use of a cross cable.

HD67671-MSTP-2-A1, HD67671-MSTP-4-A1
The Ethernet port is used for programming the device.
The Ethernet connection must be made using Connector5 of HD67671-MSTP-2-A1 or HD67671-MSTP-4-A1 with at least a Category
5E cable. The maximum length of the cable should not exceed 100m. The cable has to conform to the T568 norms relative to
connections in cat.5 up to 100 Mbps. To connect the device to an Hub/Switch is recommended the use of a straight cable, to connect
the device to a PC/PLC/other is recommended the use of a cross cable.

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 18 of 34
Industrial Electronic Devices

USE OF COMPOSITOR SW67671:

To configure the Converter, use the available software that runs with Windows called SW67671. It is downloadable from the site
www.adfweb.com and its operation is described in this document (this manual is referenced to the last version of the software present on our
web site). The software works with MSWindows (XP, Vista, Seven, 8, 10; 32/64bit).

When launching the SW67671, the window below appears (Fig. 2).

Note:
It is necessary to have installed .Net Framework 4.

Figure 2: Main window for SW67671

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 19 of 34
Industrial Electronic Devices

NEW CONFIGURATION / OPEN CONFIGURATION:

The “New Configuration” button creates the folder which contains the entire device’s configuration.

A device’s configuration can also be imported or exported:


To clone the configurations of a Programmable “BACnet slave / Modbus master -
Converter” in order to configure another device in the same manner, it is necessary to
maintain the folder and all its contents;
To clone a project in order to obtain a different version of the project, it is sufficient to
duplicate the project folder with another name and open the new folder with the
button “Open Configuration”.

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 20 of 34
Industrial Electronic Devices

SOFTWARE OPTIONS:

By pressing the “Settings” ( ) button there is the possibility to change the language of the software and check the updatings for the
compositor.

In the section “Language” it is possible to change the language of the


software.

In the section “Connection Options”, it is possible to check if there are some


updatings of the software compositor in ADFweb.com website.
Checking the option “Check Software Update at Start of Program”, the
SW67671 check automatically if there are updatings when it is launched.

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 21 of 34
Industrial Electronic Devices

In the section “Software Settings”, it is possible to enable/disable some


keyboard’s commands for an easier navigation inside the tables contained in
the different sections of the software.

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 22 of 34
Industrial Electronic Devices

SET COMMUNICATION:

This section define the fundamental communication parameters of two buses, BACnet and Modbus.

By Pressing the “Set Communication” button from the main window for SW67671 (Fig. 2) the window “Set
Communication” appears (Fig. 3).
The window is divided in three sections, one for selecting the type of BACnet (in relation to the device used),
one for the BACnet parameters and the other for the Modbus parameters.

In the section “BACnet Type” is possible to select the type of BACnet to use from:
BACnet/IP (uses Ethernet);
BACnet MS/TP (uses RS485).

If selected “BACnet/IP” the means of the fields for “BACnet” are:


In the fields “IP ADDRESS” the IP address of BACnet/IP side of the converter is defined;
In the fields “SUBNET Mask” the SubNet Mask of BACnet/IP side of the converter is defined;
In the fields “GATEWAY” the default gateway of the network is defined. This feature can be enabled
or disabled pressing the Check Box field. This feature is used for going out of the net;
In the field “Port” the port used for BACnet communication is defined. The default port used for
BACnet communication is 47808, but is possible to insert any value (except 10000 and 10001);
In the field "BACnet Device Name" the name of BACnet/IP side of the converter is defined;
In the field “Device Identifier” the ID of BACnet/IP side of the converter is defined;
If the field “BACnet description up to 32 chars” is checked, the description for the BACnet Objects
can be up to 32 chars long;
If the field “Enable BBMD” is checked, the BACnet/IP Broadcast Management Device function is
enabled;
If the field “Accept FDR” is checked, the converter accepts the Foreign Device Registration.

Figure 3: “Set Communication” window

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 23 of 34
Industrial Electronic Devices

The means of the fields for the “Modbus Master” section are:
In the field “Serial” the serial port used for the Modbus communication is defined;
In the field “Baudrate” the data rate of the Modbus line is defined;
In the field “Parity” the parity of the Modbus line is defined;
In the field “Stop Bits” the number of Stop-bit of the Modbus line is defined;
In the “TimeOut (ms)” the maximum time that the converter attends for the answer from the slave interrogated is defined;
In the field “Cyclic Delay (ms)” the delay between two requests is defined.

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 24 of 34
Industrial Electronic Devices

If selected “BACnet MS/TP”, the means of the fields for “BACnet” are:
In the field “Baudrate” the data rate of the BACnet line is defined;
In the field “Parity” the parity of the line is defined;
In the field “BACnet Device Name” the name to give to the BACnet node is defined;
In the field “MAC Address” the MAC of BACnet node (from 0 to 254) is defined;
The field “Max Master” specifies the highest allowable address for master nodes. The value shall be less
than or equal to 127;
The field “Max Info Frames” specifies the maximum number of information frames the node may send
before it must pass the token;
In the field “Device Instance” the of the BACnet MS/TP side of the converter is defined;
In the field “Network” the BACnet MS/TP network number is defined;
If the field “BACnet description up to 32 chars” is checked, the description for the BACnet Objects
can be up to 32 chars long.

The means of the fields for the “Ethernet Update” section are:
In the fields “IP ADDRESS” the IP address of the converter is defined;
In the fields “SUBNET Mask” the SubNet Mask of the converter is defined;
In the fields “GATEWAY” the default gateway of the network is defined. This feature can be enabled or
disabled pressing the Check Box field. This feature is used for going out of the net.

These information are used for programming the Converter.

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 25 of 34
Industrial Electronic Devices

SET MODBUS ACCESS:

By Pressing the “Set Modbus Access ” button from the main window for SW67671 (Fig. 2) the window “Set Access” appears (Fig. 4).

Figure 4: “Set Access” window

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 26 of 34
Industrial Electronic Devices

The window is divided in two parts, the “Modbus Read” that contains the Modbus registers/status readable by the Converter and “Modbus
Write” that contains the Modbus registers/status writeable by the Converter.

The meaning of the fields in the window are the follows:


In the field “Slave ID” the address of the Modbus device to read/write is defined;
In the field “Type” the data type of the Register to read/write is defined. It is possible to choose between the following:
o Coil Status;
o Input Status (only readable);
o Holding Register;
o Input Register (only readable).
In the field “Address” the starting address of the register/status to read/write is defined;
In the field “NPoint” the number of consecutive registers/status to read/write is defined;
In the field “Poll Time” the time (expressed in milliseconds) used to read/write the register/status is defined. If ‘0’, the request isn’t
sent;
If the field “On Change” is checked, the Modbus writing request is made only if BACnet data are changed; otherwise it is sent
cyclically, using the “Poll Time”. This feature is used only on “Modbus Write” section;
In the field “Max Error” the number of consecutive errors that the Master waits before discarding the row from the cycle of requests
is defined;
In the field “Position” the position (byte) where taking/saving the data from/to the internal arrays of the converter is defined;
The field “Start Bit” is used for the “Binary” BACnet objects and it allows to select which bit of the selected Position using;
By checking the field “Float Conv” it is possible to enable the conversion of the value read in one or two modbus registers, expressed
like Integer value, into a Float value. Instead, if the field is enable inside Modbus Write section, the converter converts the Float value
that is arrived with BACnet into a Integer value. This command is usefull if the BACnet master uses only Analog-Input and Analog-
Output, but on Modbus side it is necessary to have Integer values;
In the field “Endian” it is possible to select if the values in the registers follow the Bin-Endian or Little-Endian format. This field has
valence only if the NPoint has a value of two. This field is used only if “Float Conv” is checked;
In the “Operation” field it is possible to select a post-operation to do to the value before saving it in the case of "Modbus Read" or
write it in the case of "Modbus Write". This field is used only if “Float Conv” is checked;
If the field “Swap W” is checked, the words of the value read/written are exchanged between them;
In the field “Mnemonic” a description of the data inserted in the row is defined.

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 27 of 34
Industrial Electronic Devices

SET BACNET ACCESS:

By Pressing the “Set BACnet Access” button from the main window for SW67671 (Fig. 2) the window “BACnet Set Access” appears (Fig. 5).

The window is divided in two parts, the


“BACnet in Read” that contains the BACnet
objects readable by a BACnet Master (the
Modbus registers/status associated to these
objects are read by Modbus master); and
“BACnet in Write” that contains the BACnet
objects writeable by a BACnet Master (the
Modbus registers associated to these objects
are written by Modbus Master).

The meaning of the fields in the window are


the follows:
In the field “Data Type” it is possible
to select the BACnet object data type;
In the field “Eng. Unit”, with double
click the window “Select the BACnet
Engineering Unit” appears (Fig. 6);
In the field “Position” it is possible to
select the position (byte) where
taking/saving the data from/to the
internal arrays of the converter;
The field “Start Bit” is used for the
“Binary” BACnet objects and it allows
to select which bit of the selected
Position using;
The field “Length” is used to define
the dimension in bytes of the BACnet
Object. For “Binary” Objects, this field
must be set to ‘1’.

Figure 5: “BACnet Set Access” window


ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 28 of 34
Industrial Electronic Devices

It is possible to insert directly the Unit (using its unique number) by


compiling the “Selected BACnet Engineering Unit” field; or by
selecting with the fields “Select the Type” and “Select unit” the
Type/Unit desired. If the second way is used, is necessary to press the
“Select Engineering Unit” button for confirm the choice.

Figure 6: “Select the BACnet Engineering Unit” window

OBJECTS MAP:

By Pressing the “Objects Map” button from the main window for SW67671 (Fig. 2) is possible to create a .csv document with the map of
BACnet Objects.

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 29 of 34
Industrial Electronic Devices

UPDATE DEVICE:

By pressing the “Update Device” button, it is possible to load the created Configuration into the
device; and also the Firmware, if necessary.

If you don’t know the actual IP address of the device you have to use this procedure:
Turn OFF the Device;
Put Dip2 of ‘Dip-Switch A’ at ON position;
Turn ON the device
Connect the Ethernet cable;
Insert the IP “192.168.2.205”;
Press the “Ping” button, “Device Found!” must appear”;
Press the “Next” button;
Select which operations you want to do;
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” turn OFF the Device;
Put Dip2 of ‘Dip-Switch A’ at OFF position;
Turn ON the device.

If you know the actual IP address of the device you have to use this procedure:
Turn on the Device with the Ethernet cable inserted;
Insert the actual IP of the Converter;
Press the “Ping” button, must appear “Device Found!”;
Press the “Next” button;
Select which operations you want to do;
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” the device automatically goes at Normal Mode.

At this point the configuration/firmware on the device is correctly updated.

Figure 7: “Update device” windows


ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 30 of 34
Industrial Electronic Devices

Note:
When you install a new version of the software, if it is the first time it is better you do the update of the Firmware in the HD67671
device.

Note:
When you receive the device, for the first time, you also have to update the Firmware in the HD67671 device.

Warning:
If Fig. 8 appears when you try to do the Update try these points before seeking
assistance:
Try to repeat the operations for the updating;
Try with another PC;
Try to restart the PC;
Check the LAN settings;
Check the Wi-Fi settings;
If you are using the program inside a Virtual Machine, try to use in the main
Operating System; Figure 8: “Protection” window
If you are using Windows Seven, Vista, 8 or 10 make sure that you have the
administrator privileges;
In case you have to program more than one device, using the "UDP Update", you have to cancel the ARP table every time you
connect a new device on Ethernet. For do this you have to launch the "Command Prompt" and write the command "arp -d". Pay
attention that with Windows Vista, Seven, 8, 10 you have to launch the "Command Prompt" with Administrator Rights;
Pay attention at Firewall lock.

In the case of HD67671 you have to use the software “SW67671”: www.adfweb.com\download\filefold\SW67671.zip.

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 31 of 34
Industrial Electronic Devices

MECHANICAL DIMENSIONS:

Figure 9a: Mechanical dimensions scheme for HD67671-IP-2-A1 Figure 9b: Mechanical dimensions scheme for HD67671-IP-4-A1

Figure 9c: Mechanical dimensions scheme for HD67671-MSTP-2-A1 Figure 9d: Mechanical dimensions scheme for HD67671-MSTP-4-A1
ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 32 of 34
Industrial Electronic Devices

ORDERING INFORMATIONS:

The ordering part number is formed by a valid combination of the following:


HD67671 - IP - 2 - A 1

Connectors Type
1: Removable 5mm Screw Terminal

Enclosure Type
A: 1M, 35mm DIN Rail mounting

Modbus port
2: RS232
4: RS485

BACnet type:
IP: BACnet/IP
MSTP: BACnet MS/TP

Device Family
HD67671: BACnet Slave / Modbus Master - Converter

Order Code: HD67671-IP-2-A1 - BACnet/IP slave/ Modbus master – Converter (Modbus over RS232)
Order Code: HD67671-IP-4-A1 - BACnet/IP slave / Modbus master – Converter (Modbus over RS485)
Order Code: HD67671-MSTP-2-A1 - BACnet MS/TP slave / Modbus master – Converter (Modbus over RS232)
Order Code: HD67671-MSTP-4-A1 - BACnet MS/TP slave / Modbus master – Converter (Modbus over RS485)

ACCESSORIES:

Order Code: AC34001 - 35mm Rail DIN - Power Supply 220/240V AC 50/60Hz – 12 V AC
Order Code: AC34002 - 35mm Rail DIN - Power Supply 110V AC 50/60Hz – 12 V AC

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 33 of 34
Industrial Electronic Devices

DISCLAIMER:

All technical content within this document can be modified without notice. The content of the document is a under continual renewal.
For losses due to fire, earthquake, third party access or other accidents, or intentional or accidental abuse, misuse, or use under abnormal
conditions repairs are charged to the user. ADFweb.com S.r.l. will not be liable for accidental loss of use or inability to use this product, such
as loss of business income. ADFweb.com S.r.l. shall not be liable for consequences of improper use.

OTHER REGULATIONS AND STANDARDS:

WEEE INFORMATION
Disposal of old electrical and electronic equipment (as in the European Union and other European countries with separate
collection systems).
This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish. Instead, it
should be taken to an applicable collection point for the recycling of electrical and electronic equipment. If the product is disposed
correctly, you will help prevent potential negative environmental factors and impact of human health, which could otherwise be
caused by inappropriate disposal. The recycling of materials will help to conserve natural resources. For more information about
recycling this product, please contact your local city office, your household waste disposal service or the shop where you purchased
the product.

RESTRICTION OF HAZARDOUS SUBSTANCES DIRECTIVE


The device respects the 2002/95/EC Directive on the restriction of the use of certain hazardous substances in electrical
and electronic equipment (commonly referred to as Restriction of Hazardous Substances Directive or RoHS).

CE MARKING
The product conforms with the essential requirements of the applicable EC directives.

ADFweb.com S.r.l.
User Manual BACnet Slave / Modbus Master
Document code: MN67671_ENG Revision 1.100 Page 34 of 34
Industrial Electronic Devices

WARRANTIES AND TECHNICAL SUPPORT:

For fast and easy technical support for your ADFweb.com SRL products, consult our internet support at www.adfweb.com.
Otherwise contact us at the address [email protected]

RETURN POLICY:

If while using your product you have any problem and you wish to exchange or repair it, please do the following:
Obtain a Product Return Number (PRN) from our internet support at www.adfweb.com. Together with the request, you need to
provide detailed information about the problem.
Send the product to the address provided with the PRN, having prepaid the shipping costs (shipment costs billed to us will not be
accepted).

If the product is within the warranty of twelve months, it will be repaired or exchanged and returned within three weeks. If the product is no
longer under warranty, you will receive a repair estimate.

ADFweb.com S.r.l.
Via Strada Nuova, 17
IT-31010 Mareno di Piave
TREVISO (Italy)
Phone +39.0438.30.91.31
Fax +39.0438.49.20.99
www.adfweb.com