Power Distribution Monitoring Objects


Reference Manual

800xA - AC800M Connect – Minerals Library

Version 5.1/5b

Based on Project Minerals Library, CoE Cement and Minerals


Prep. ATBPA/Ch. Tschumi, M.Schmid, 09.06.2010
P.Topfmeyer, N.Beringer
Appr. ATBPA/M.Knabenhans 01.04.2010
Doc. kind Reference Manual Doc. Item

Title Power Distribution Monitoring Objects des. des.

800xA Minerals Library version 5.1/5b Resp. dept. CHIND / ATBPA


Document identity Lang. Rev. ind. Sheet 1
3BHS 253000 en N
ABB Switzerland Ltd No. of sh. 73
Template: Design Description_1,1_A4h_en_standard.dot; Filename: 08 Minerals Library Power Distribution Monitoring Objects.docx; Print: 5/11/2015 2:08:00 PM; Save: 5/6/2015 10:48:00 AM; CHIND No. 3BHS102547 ZAB E01 Rev
A. -; I-Q
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

CONTENT
1. SUMMARY ................................................................................................................ 4
2. COMMON DATA ....................................................................................................... 4
2.1 BASIC DESCRIPTION ..................................................................................... 4
2.2 CONTROL ....................................................................................................... 5
2.2.1 Library location .................................................................................... 5
2.2.2 Point of Control ................................................................................... 5
2.2.3 Simulation Mode ................................................................................. 5
2.3 OPERATION.................................................................................................... 6
2.3.1 Graphic Element CB............................................................................ 6
2.3.1.1 Presentation ........................................................................ 6
2.3.1.2 Status .................................................................................. 7
2.3.1.3 Labels .................................................................................. 8
2.3.1.4 Properties ............................................................................ 9
2.3.1.5 Dynamic Colored Single Line ............................................... 9
2.3.2 Graphic Element CBValueAndUnit .................................................... 16
2.3.2.1 Presentation ...................................................................... 16
2.3.2.2 Labels ................................................................................ 16
2.3.2.3 Properties .......................................................................... 16
2.3.3 Graphic Element CommunicationStatus ............................................ 16
2.3.3.1 Presentation ...................................................................... 16
2.3.3.2 Status ................................................................................ 16
2.3.3.3 Properties .......................................................................... 16
2.3.4 Graphic Element Name_Link_CB ...................................................... 18
2.3.4.1 Presentation ...................................................................... 18
2.3.4.2 Status ................................................................................ 18
2.3.4.3 Labels ................................................................................ 18
2.3.4.4 Properties .......................................................................... 18
3. CircuitBreaker ........................................................................................................ 19
3.1 BASIC DESCRIPTION ................................................................................... 19
3.2 CONTROL ..................................................................................................... 19
3.2.1 Graphical Representation.................................................................. 19
3.2.2 Parameter description ....................................................................... 20
3.2.3 Data Type description ....................................................................... 22
3.2.4 Project Constants .............................................................................. 23
3.3 OPERATION.................................................................................................. 24
3.3.1 Graphic Elements.............................................................................. 24
3.3.2 Faceplate .......................................................................................... 25
3.3.2.1 Default View ...................................................................... 26
3.3.2.2 Extended View ................................................................... 28
3.3.3 Faceplate Control Permission ........................................................... 35
3.4 Alarms and Events ......................................................................................... 36
3.4.1.1 Object Status and Mode .................................................... 36
4. ABB_REF542Plus_IntCtrl ...................................................................................... 37
4.1 BASIC DESCRIPTION ................................................................................... 37
4.2 CONTROL ..................................................................................................... 37
4.2.1 Parameter description ....................................................................... 37
4.2.2 Data Type description ....................................................................... 38
4.3 OPERATION.................................................................................................. 39
5. CircuitBreakerABBREF542Plus ............................................................................ 40
5.1 BASIC DESCRIPTION ................................................................................... 40
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 2
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

5.2 CONTROL ..................................................................................................... 41


5.2.1 Parameter description ....................................................................... 41
5.2.2 Data Type description ....................................................................... 43
5.2.3 Project Constants .............................................................................. 43
5.3 OPERATION.................................................................................................. 46
5.3.1 Graphic elements .............................................................................. 46
5.3.1.1 Graphic Element CBValueAndUnit..................................... 46
5.3.2 Faceplate for Circuit Breaker Operation ............................................ 47
5.3.3 Faceplate for Modbus Operation ....................................................... 48
5.3.3.1 Default View ...................................................................... 49
5.3.3.2 Extended View ................................................................... 50
5.3.4 Faceplate Control Permission ........................................................... 50
5.4 Application examples ..................................................................................... 51
5.4.1 How to configure the Modbus interface ............................................. 51
6. Power Factor Correction Control (PFCC) Control Module .................................. 53
6.1 BASIC DESCRIPTION ................................................................................... 53
6.1.1 Features ............................................................................................ 53
6.1.2 Function description .......................................................................... 54
6.1.2.1 Grid change trip ................................................................. 54
6.1.2.2 Stepping sequence ............................................................ 54
6.1.2.3 Step Up ............................................................................. 54
6.1.2.4 Step Down ......................................................................... 54
6.1.2.5 Over compensation step down ........................................... 55
6.1.2.6 Over compensation trip ...................................................... 55
6.1.2.7 Input value filter ................................................................. 55
6.2 CONTROL ..................................................................................................... 56
6.2.1 Parameter description ....................................................................... 56
6.2.2 Data Type description ....................................................................... 58
6.3 OPERATION.................................................................................................. 59
6.3.1 Graphic Element ............................................................................... 59
6.3.1.1 Presentation ...................................................................... 59
6.3.1.2 Status ................................................................................ 59
6.3.1.3 Properties .......................................................................... 60
6.3.2 Faceplate .......................................................................................... 61
6.3.2.1 Extended View ................................................................... 62
6.3.2.2 Trending ............................................................................ 67
6.3.3 Faceplate Control Permission ........................................................... 68
6.4 Application Example ...................................................................................... 69
6.4.1 PFCC Enable Configuration .............................................................. 70
6.4.2 Single incoming feeder, bus coupler open (PFC E21_1S1) ............... 71
6.4.3 Dual incoming feeder, bus coupler closed (PFC E21_1S21) ............. 72
7. DOCUMENT REVISION HISTORY.......................................................................... 73

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 3
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

1. SUMMARY
This document contains a detailed description of the following Power Distribution
Monitoring Objects:
·CircuitBreaker
·CircuitBreakerABBREF542Plus
·ABB_REF542Plus_IntCtrl
·MOT1REF542Plus
·PFCCtrl

2. COMMON DATA

2.1 BASIC DESCRIPTION


The Power Distribution Monitoring objects provide access and control for supervision and
control of power distribution equipment such as switchgear, and protection relays using
serial connectivity (e.g. Profibus or Modbus).
The objects are designed as composite control modules containing one module for the
communication. This module can be modified to adapt to the requirements of the
equipment.

All Power Distribution Monitoring objects have the following common basic functions:
· Manual control from the Operator Station (via the faceplate)
· Local control from Electrical Panel in the E-Room
· Detailed status, alarm and interlock indication on the Operator Station
· Single Line Display Graphic Elements
· Faceplates
· Tracking of control mode and status changes on the Operator station
· Full integration into Minerals Library of group control concept – GCC – Group
Control Connection
· Supervision of the Profibus / Modbus Communication
· Out of service function. Enables the operator to take single circuit breakers out of
control (No Action from the group, Faceplate, etc)

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 4
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

2.2 CONTROL

2.2.1 Library location


The Control Module Types for Power Distribution Monitoring objects and their
corresponding Structured Data Types are located in the library BMIEnergy 1.5-23 for
Control Builder Professional.

2.2.2 Point of Control


Power Distribution Monitoring objects have the 4 different POC (Point Of Control) SEQ,
CEN, LOC, and Out Of Service. All modes are selectable from the operator station.
The POC defines from where the circuit breaker will be controlled, e.g. from the central
control room, by opening / closing every circuit breaker separately (CEN) or from the field
(LOC).
In order to control an object from a certain POC, it must be selected first.
The different possible POC are:
Sequence:
The object is controlled from a superior application program e.g. from a drive group
sequence. Sequence can be set from the operator station or by the application program.
Central:
The object is controlled from the operator station by means of the open/close push
buttons on the faceplate.
Local:
The object is controlled from the MVD Panel directly. The Circuit Breaker Control module
will only follow and indicate the status in the MVD Panel. Whether the CBTrip Interlock
remains active depends on the MVD Panel design.

Out of Service:
The object is not in service and cannot be operated from any location. It also means that
the object will be skipped when running a superior group sequence.
Out of Service mode can be set and re-set from the operator station only.

2.2.3 Simulation Mode


The group object has the possibility to bet set in simulation mode from the operator
station. In this case, all the circuit breaker objects belonging to it will be forced to
simulation mode as well.
In simulation mode, feedbacks (e.g. open, close position) are simulated and commands
and alarms are disabled. This mode is used to test Group Sequence logic and Interlocks.

Even with disabled commands there is still possibility that digital/analog


output signals can be activated.
For safety always disconnect the Profibus, Modulebus or any other
interface to the field before switching to Simulation Mode.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 5
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

2.3 OPERATION
There are different graphic elements available for power monitorng objects as shown
below.
Graphic Element Description Example

Displays object status information for a


circuit breaker in a single line diagram.
CB
Different indication types such as feeder or
bus coupler are possible.

Displays objects actual analog values such


CBValueAndUnit
as voltage, current or power.
CommunicationStatus Displays the communication status.
Name_Link_CB Displays the object name and status.

2.3.1 Graphic Element CB


This is the main graphic element to present and operate a circuit breaker. It shows the
status, interlocks and alarms. Many different indication types are available.

2.3.1.1 Presentation
A01_Feeder A02_FeederDual A03_Incomer A04_IncomerDual

A05_Cable A08_Feeder
A06_Coupler A07_Riser
Connector DiscOnly

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 6
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

A09_Feeder B02_BusSectionizer B03_BusSectionizer


B01_BusCoupler
WithoutES WithCB WithoutCB

C01_InsertableCB C02_InsertableCB C03_InsertableCB C04_InsertableCB


Feeder FeederWithES Incomer IncomerWithES

C05_InsertableCB C07_InsertableCB D02_CB


D01_CB_Feeder
Coupler BusCoupler FeederWithES

D04_CB
D03_CB Incomer D05_CB Coupler D07_CB BusCoupler
IncomerWithES

E01_EarthSwitch
Only

2.3.1.2 Status
Examples Object status Symbol color

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 7
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

2.3.1.3 Labels

OFF, object ready to operate grey

Isolator 1 closed, CB open and ready CB filled grey


to operate Isolator filled green

CB filled green
Isolator 1 closed, CB closed
Isolator 1 filled green

CB filled green
Earth switch 1 closed, CB closed
Earth switch 1 filled yellow

Isolator 1 filled grey with thick


OFF, warning on isolator
orange frame

CB filled grey with thick red


OFF, failure on CB
frame

Description Example
Point of Control
Sequence
Point of Control
Central

Point of Control Local

Out of Service

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 8
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Description Example
Blocked Interlock or
Functional Back Signal

Interlock is set

General Circuit
Breaker Alarm

Field is earthed and


secure

2.3.1.4 Properties
Name DataType Default Value Description
Busbar Integer 3 1 = Busbar A (upper busbar) , 2 = Busbar
B (lower busbar), 3 = Busbar A and B, 4 =
Busbar A and B
CBGenAlarmLabelPos Integer 3 1 = Top left, 2 = Top center, 3 = Top right,
4 = Center left, 5 = Center center, 6 =
Center right, 7 = Bottom left, 8 = Bottom
center, 9 = Bottom right
EnableBusbar Boolean True Show bus bar
EnableConnectionOnBusbar Boolean True Show connection (small dot) on busbar.
EnableControlPointSequence Boolean False Show control point sequence label when
control point sequence is active
IndicationType Enum A01_Feeder Indication type selection
OffColor Enum A01_HVLine Symbol on color. Only used for
CB.StatusAppearance (General Property)
is set to 2.
OnColor Enum A01_HVLine Symbol on color. Only used for
CB.StatusAppearance (General Property)
is set to 1 or 2.
ReturnStatusBusbarA (1) PropertyRef null Return status bus bar A
ReturnStatusBusbarB (1) PropertyRef null Return status bus bar B
ReturnStatusCable (1) PropertyRef null Return status cable
StatusBusbarA (1) Integer 101 Bus bar A status
StatusBusbarB (1) Integer 101 Bus bar B status
StatusCable (1) Integer 101 Cable status
SubscriptionRate Integer 0 The update rate for all aspect object
properties subscribed for
SymbolSize Integer 16 Symbol size: 8 = little, 12 = small, 16 =
normal, 20 = large, 24 = XXL; Line
thickness: 1 pixel when symbol size is
smaller than 28, 2 pixel when symbol size
is larger or equal than 28 and smaller than
32, 3 pixel when symbol size is larger or
equal than 52.
(1): This properties are only used when common setting StatusAppearance = 2, please refer to [1]
Minerals Library Overview (3BHS 161555).

2.3.1.5 Dynamic Colored Single Line


When using CB StatusAppearance = 2 it is possible to link multiple CB Graphic Elements
PG2 together. The status (line color) will then be applied to all connected CB Graphic
Elements according to the object state (CB open or closed).

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 9
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Incomer closed Incomer open

To link the status use the StatusLink properties listed below.


Name DataType Default Value Description
ReturnStatusBusbarA PropertyRef null Return status for bus bar A
ReturnStatusBusbarB PropertyRef null Return status for bus bar B
ReturnStatusCable PropertyRef null Return status for cable
StatusBusbarA Integer 101 Bus bar A status
StatusBusbarB Integer 101 Bus bar B status
StatusCable Integer 101 Cable status

The table below shows the Busbar and Cable property connection for each indication
type.
Example Indication Types Definition
All feeders:
· A01_Feeder
· A02_FeederDual
· A05_CableConnector Bus bar A: Upper bus bar
· A08_Feeder DiscOnly Bus bar B: Lower bus bar
Cable: lower straight line
· A09_FeederWithoutES
· B01_BusCoupler
Note: The actually used bus
· C01_InsertableCBFeeder bar depends on the Busbar
· C02_InsertableCBFeederWithES property.
· D01_CB_Feeder
· D02_CB FeederWithES
· E01_EarthSwitch Only
All incomers:
· A03_Incomer Bus bar A: Upper bus bar
Bus bar B: Lower bus bar
· A04_IncomerDual
Cable: lower straight line
· C03_InsertableCBIncomer
· C04_InsertableCBIncomerWithES Note: The actually used bus
· D03_CB Incomer bar depends on the Busbar
· D04_CB IncomerWithES property.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 10
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Example Indication Types Definition

Sectionizer and bus-couplers:


Bus bar A: Left bus bar
· B02_BusSectionizerWithCB
Bus bar B: Right bus bar
· B03_BusSectionizerWithoutCB
Cable: n/a
· C07_InsertableCBBusCoupler
· D07_CBBusCoupler

Risers and couplers:


· A06_Coupler Bus bar A or B: Upper line
Cable: lower line
· A07_Riser
· C05_InsertableCBCoupler
Note: The actually used bus
· C06_InsertableCBRiser
bar depends on the Busbar
· D05_CBCoupler property.
· D06_CBRiser

ReturnStatusBusbarA, ReturnStatusBusbarB and ReturnStatusCable returns a value


different from 101 (status is off) when the object is feeder to bus bar A/B or cable,
respectively.
StatusBusbarA, StatusBusbarB and StatusCable are input properties for bus bar A/B or
cable, respectively.
The following table defines the property value for StatusBusbarA, StatusBusbarB and
StatusCable. StatusLink properties of data type PropertyRef are using the same
definition. Connect them only to expression variable from type integer.
Other values, than the listed below, are not supported and will lead to an invalid status
indication.
Property Value Definition
101 off (OffColor)
100 on (OnColor)
0 earthed
1 high voltage 01 on
2 high voltage 02 on
3 high voltage 03 on
4 medium voltage 01 on
5 medium voltage 02 on
6 medium voltage 03 on
7 low voltage 01 on
8 low voltage 02 on
9 low voltage 03 on
10 UPS on
11 control voltage on
50 earth off
51 high voltage 01 off
52 high voltage 02 off
53 high voltage 03 off
54 medium voltage 01 off
55 medium voltage 02 off
56 medium voltage 03 off
57 low voltage 01 off

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 11
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Property Value Definition


58 low voltage 02 off
59 low voltage 03 off
60 UPS off
61 control voltage off
99 HV line (black)
The smaller the property value, the higher the priority. If property value is 100 or 101 (or
higher) the OnColor or OffColors, respectively, is used.
There are a few examples in the table below:
Example Property Settings ReturnStatus
OffColor: C01_MediumVoltage01Off
OnColor: C04_MediumVoltage01On
ReturnStatusBusbarA: 101 (off)
ReturnStatusBusbarB: 101 (off)
StatusBusbarA: 100 (on)
ReturnStatusCable: 101 (off)
StatusBusbarB: 101 (off)
StatusCable: 101 (off)

OffColor: C01_MediumVoltage01Off
OnColor: C04_MediumVoltage01On
ReturnStatusBusbarA: 101 (off)
ReturnStatusBusbarB: 101 (off)
StatusBusbarA: 100 (on)
ReturnStatusCable: 4 (medium voltage 01 on)
StatusBusbarB: 101 (off)
StatusCable: 101 (off)

OffColor: C01_MediumVoltage01Off
OnColor: C04_MediumVoltage01On
ReturnStatusBusbarA: 101 (off)
ReturnStatusBusbarB: 101 (off)
StatusBusbarA: 100 (on)
ReturnStatusCable: 0 (earthed)
StatusBusbarB: 101 (off)
StatusCable: 101 (off)

OffColor: C01_MediumVoltage01Off
OnColor: C04_MediumVoltage01On
ReturnStatusBusbarA: 101 (off)
ReturnStatusBusbarB: 0 (earthed)
StatusBusbarA: 100 (on)
ReturnStatusCable: 101 (off)
StatusBusbarB: 101 (off)
StatusCable: 101 (off)

OffColor: C01_MediumVoltage01Off
OnColor: C04_MediumVoltage01On
ReturnStatusBusbarA: 101 (off)
ReturnStatusBusbarB: 101 (off)
StatusBusbarA: 1 (high voltage 01 on)
ReturnStatusCable: 101 (off)
StatusBusbarB: 101 (off)
StatusCable: 101 (off)

To connect several CB graphics element’s bus bar or cable status together you must
follow the steps below:
1. Make sure that all CB graphics element’s property settings are as desired. Check
particularly the properties Busbar, OffColor and OnColor.
2. Create for every return property you like to use an expression variable (data type =
integer) on the graphic display and set the expression to 101 (off).

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 12
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Connect these variables to the appropriate graphic item properties


(ReturnStatusBusbarA, ReturnStatusBusbarB or ReturnStatusCable).
3. Create for every shared bus bar or cable one expression variable (data type =
integer). As expression use the Min()-function to search the smallest return value.
The syntax for the Min()-function allows only two arguments. For more than two
arguments use a cascade like the following: “Min(Min(ReturnValue01,
ReturnValue02), ReturnValue03)”.
Connect this expression variable to the appropriate graphic item properties
(StatusBusbarA, StatusBusbarB or StatusCable).

2.3.1.5.1 Example
Below is an example for a dynamic colored single line display with two incomers, two
feeders and a bus coupler.

All used expression variables for the example are shown below. Note that all expression
variables for the return status are set to 101 (status off).

Color settings for all CB graphic items:

Bellow are the individual property settings for the five CB graphic items. Note that not used
return status properties (ReturnStatusBusbarA, ReturnStatusBusbarB and
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 13
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

ReturnStatusCable) are set to “null”. Not connected status properties (StatusBusbarA,


StatusBusbarB and StatusCable) are set to “101” (status off).
Graphic Item Property Settings

Incomer 1

Incomer 2

Feeder 1

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 14
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Graphic Item Property Settings

Feeder 2

Coupler

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 15
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

2.3.2 Graphic Element CBValueAndUnit

2.3.2.1 Presentation

2.3.2.2 Labels
Description Indication
Signal Blocked / Forced

Example:

2.3.2.3 Properties
Name DataType Default Value Description
CBValue Enum A1_Voltage Select the desired value
EnableDisplayBackground Boolean False Show display background color as symbol
Color background
EnableUnit Boolean True Show unit
NumberOfDigits Integer 4 Number of presented digits
SubscriptionRate Integer 0 The update rate for all aspect object
properties subscribed for
UnitSize Integer 8 Unit size in pixel: 7 = Small, 8 = Standard,
10 = Large, 12= XXL
ValueSize Integer 12 Value size in pixel: 8 = Small, 10 Medium,
12 = Standard, 14 = Large, 16 = XXL
For common settings please refer to [1] Minerals Library Overview (3BHS 161555).

2.3.3 Graphic Element CommunicationStatus

2.3.3.1 Presentation
IndicationType Description Example
0 Text with colored background

10 Square in front of text

20 Colored text

2.3.3.2 Status
Example Object status Symbol color
Normal Position
(EnableNormalPos = False then fully Gray dimmed (semitransparent)
transparent)

Normal Position Green


(Appearance Type: Alarm or Value interlock)

Abnormal Position Red

2.3.3.3 Properties
Name DataType Default Value Description
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 16
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Name DataType Default Value Description


AppearanceType Integer 0 0 = Alarm, 2 = Value, 3 = Value custom
color, 10 = Alarm interlock, 12 Value
interlock
ColorAbnormalPos Color Lime Used for AppearanceType 3 = Value
custom color
ColorNormalPos Color RGB(159,159, Used for AppearanceType 3 = Value
159) custom color
EnableFont Boolean False True enables the Font property. If false,
default Font is used and TextSize as well
as TextBold are enabled.
EnableLogicalColor Boolean True To use an individual color, set it to false
EnableNormalPos Boolean True Hide symbol in normal position
Font Font Font( "Arial" Text font when EnableFont is true
,10 ,Regular,
Bold)
IndicationType Integer 0 0 = Text with background color, 10 =
Square in front of text, 20 = Text colored
NormalPos Boolean True Used for AppearanceType 2 = Value, 3 =
Value custom color
SubscriptionRate Integer 0 The update rate for all aspect object
properties subscribed for
SymbolSize Integer 12 Symbol size in pixel: 8 = Litle, 10 = Small,
12 = Standard, 16 = Large, 20 = XXL
TextBold Boolean True Switch Text Style between normal and
bold, only available if EnableFont is set to
false
TextIndAbnormalPos String "ComError" TextIndTrAbnormalPos
TextIndTrNormalPos String "ComError" TextIndTrNormalPos
TextSize Integer 10 Text size in pixel: 8 = Small, 10 =
Standard, 12 = Large, 16 = XXL. Only
available if EnableFont is set to false.
TextSource Integer 2 0 = None, 1 = TextIndAbnormalPos /
TextIndNormalPos Properties, 2 = NLS
Text
For common settings please refer to [1] Minerals Library Overview (3BHS 161555).

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 17
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

2.3.4 Graphic Element Name_Link_CB

2.3.4.1 Presentation

2.3.4.2 Status
Object status Symbol color

CB off Gray

CB closed Green filled

CB closed with warning Green filled with thick orange frame

CB not ready for start because of


failure in at least one of the Gray with thick red frame
connected consumers

2.3.4.3 Labels
Description Example
Point of Control
Sequence

Point of Control Central

Point of Control Local

Out of Service

Blocked Interlock or
Functional Back Signal

2.3.4.4 Properties
Name DataType Default Value Description
EnableControlPointSequence Boolean False Show control point sequence label when
control point sequence is active
SubscriptionRate Integer 0 The update rate for all aspect object
properties subscribed for
SymbolSize Integer 22 Symbol size in pixel: 18 = Little, 20= Small,
22 = Standard, 24 = Large, 26 = XXL
Text String "Name" Object name
TextBold Boolean True Text style is bold
TextSize Integer 10 Textl size in pixel: 8= Small, 10 =
Standard, 12 = Large, 16 = XXL
TextSource Integer 2 0 = None, 1 = Manual, 2 = OPC, 3 = NLS
For common settings please refer to [1] Minerals Library Overview (3BHS 161555).

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 18
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3. CircuitBreaker

3.1 BASIC DESCRIPTION


The Control Module Type CircuitBreaker is used to control a motorized Circuit Breaker
(configuration of 1 CB and up to 2 Isolators) in a drive group or standalone.
Next to the common basic functions for energy management objects, the following
functions are supported for Circuit Breaker:
· Operation modes
· Selection of individual Breaker for operation
· Open / Close order to operate the breaker
· Indication of Breaker status
· Indication of Switches
· Current, Voltage and Power indication
· User definable Warning indication
· 3 additional interface inputs for CB; for e.g. Trip, General Alarm & Ready
· Closed and Open position inputs with feedback time supervision; for CB, Isolator
or Earth Switch (ESW)
· 3 Process interlocks pre CB and 2 pre Isolator.
· Calculation and indication of CB Close time (in hours) and number of CB Trips and
closing operations

NOTE: The CircuitBreaker Control Module does not have a PCC Bus

3.2 CONTROL

3.2.1 Graphical Representation

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 19
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.2.2 Parameter description


Name Data Type Initial value Description
1 Name string[24] 'Name' INIT: Tag name of the circuit breaker (allowed deliminators are "."
and "-", no blanks ":" or ";" allowed)
2 Description string[40] 'Description' IN: Description text of the circuit breaker
3 IO CircuitBreak IN/OUT: Circuit Breaker Data Variable
erData
4 Group GrpDrvCon default IN/OUT: Connection to control module GROUP (sequencer)
5 GrpCBClsStep dint cBMI.DINT_0 IN: CB Close step no 1..999, if set to 0 -> not part of group
sequence
6 GrpCBOpnStep dint cBMI.DINT_0 IN: CB Open step no 1001..1999, if set to 0 -> not part of group
sequence
7 GrpIsol1ClsStep dint cBMI.DINT_0 IN: Isol1 Close step no 1..999, if set to 0 -> not part of group
sequence
8 GrpIsol1OpnStep dint cBMI.DINT_0 IN: Isol1 Open step no 1001..1999, if set to 0 -> not part of group
sequence
9 GrpIsol2ClsStep dint cBMI.DINT_0 IN: Isol2 Close step no 1..999, if set to 0 -> not part of group
sequence
10 GrpIsol2OpnStep dint cBMI.DINT_0 IN: Isol2 Open step no 1001..1999, if set to 0 -> not part of group
sequence
11 GrpCBClsDelay time cBMI.Time2s IN: CB Close delay when closed from group sequence
12 GrpCBOpnDelay time cBMI.Time2s IN: CB Open delay when opened from group sequence
13 GrpIsol1ClsDelay time cBMI.Time2s IN: Isol1 Close delay when closed from group sequence
14 GrpIsol1OpnDelay time cBMI.Time2s IN: Isol2 Open delay when opened from group sequence
15 GrpIsol2ClsDelay time cBMI.Time2s IN: Isol1 Close delay when closed from group sequence
16 GrpIsol2OpnDelay time cBMI.Time2s IN: Isol2 Open delay when opened from group sequence
17 EnQuickStop bool false IN false: Enable Group Quick stop for the Circuit breaker
18 IOStatus1 dint cBMI.DINT_0 IN: Status signal of related IO-Board
19 IOStatus2 dint cBMI.DINT_0 IN: Status signal of related IO-Board
20 IOStatus3 dint cBMI.DINT_0 IN: Status signal of related IO-Board
21 IOStatus4 dint cBMI.DINT_0 IN: Status signal of related IO-Board / Serial Interface
22 CBEnabled bool true INIT: Enable CB (only valid if CBType is default=51)
23 Isol1Enabled bool false INIT: Enable Isol1 (only valid if CBType is default=51)
24 Isol2Enabled bool false INIT: Enable Isol2 (only valid if CBType is default=51)
25 CBReady bool true IN true: Circuit Breaker Ready for Operation
26 IgnoreCBRdyForOpn bool true IN true: if true the ready signal has no influence on CB open
Cmd commands
27 CBTrip bool false IN false: Circuit Breaker Common Trip
28 CBGeneralAlarm bool false IN false: Circuit Breaker Relay General Alarm
29 CBClosed bool false IN false: Circuit Breaker Closed
30 CBOpen bool false IN false: Circuit Breaker Open
31 CBInserted bool true IN false: Circuit Breaker Inserted
32 CBIsolated bool false IN false: Circuit Breaker Isolated
33 Isol1Ready bool true IN true: Isolator 1 Ready for Operation
34 IgnoreIsol1RdyForOp bool false IN false: if true the ready signal has no influence on Isolator 1
nCmd open commands
35 Isol1Closed bool false IN false: Isolator 1 Closed
36 Isol1Open bool false IN false: Isolator 1 Open
37 Isol2Ready bool true IN true: Isolator 2 Ready for Operation
38 IgnoreIsol2RdyForOp bool false IN false: if true the ready signal has no influence on Isolator 2
nCmd open commands
39 Isol2Closed bool false IN false: Isolator 2 Closed
40 Isol2Open bool false IN false: Isolator 2 Open
41 ESW1Closed bool false IN false: Earth Switch 1 Closed
42 ESW1Open bool false IN false: Earth Switch 1 Open
43 ESW2Closed bool false IN false: Earth Switch 2 Closed
44 ESW2Open bool false IN false: Earth Switch 2 Open
45 FieldEarthAndSecure bool false IN false: Field Earthed and Secured
46 CBTime time cBMI.Time2s IN: Maximum delay time for Circuit Breaker Response
47 IsolTime time cBMI.Time10s IN: Maximum delay time for Isolator Response
48 LocalControl bool cBMIEnergy.CB. IN false: Circuit Breaker Relay in Local Control (Commands from
LocalControl_Inv Seq and Cen are ignored)
erted
49 Current RealIO default IN: Circuit Breaker Current
50 ShowCurrent bool true IN: Enabling of Current indication on Faceplate
51 Voltage RealIO default IN: Circuit Breaker Voltage
52 ShowVoltage bool true IN: Enabling of Voltage indication on Faceplate
53 Power RealIO default IN: Circuit Breaker Power
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 20
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Name Data Type Initial value Description


54 ShowPower bool true IN: Enabling of Power indication on Faceplate
55 OrdCBCls bool false OUT pulse: Close Order for Circuit Breaker
56 OrdCBOpn bool false OUT pulse: Open Order for Circuit Breaker
57 IntCBCls bool true OUT: Close Interlock for Circuit Breaker (normally true)
58 OrdIsol1Cls bool false OUT pulse: Close Order for Isolator 1
59 OrdIsol1Opn bool false OUT pulse: Open Order for Isolator 1
60 OrdIsol2Cls bool false OUT pulse: Close Order for Isolator 2
61 OrdIsol2Opn bool false OUT pulse: Open Order for Isolator 2
62 LocAlarmAck bool false OUT: Alarm reset pulse (e.g. to reset alarms in the Circuit Breaker
Relay)
63 IntCBClsTxt string[25] cBMI.Empty_str IN: Description Text Interlock Signal CB Close, for NLS support
use ||IL_NLS_ preffix and no space in the text
64 IntCBOpnTxt string[25] cBMI.Empty_str IN: Description Text Interlock Signal CB Open, for NLS support
use ||IL_NLS_ preffix and no space in the text
65 IntCBTripTxt string[25] cBMI.Empty_str IN: Description Text Interlock Signal CB Trip, for NLS support use
||IL_NLS_ preffix and no space in the text
66 IntIsol1ClsTxt string[25] cBMI.Empty_str IN: Description Text Interlock Signal Isol1 Close, for NLS support
use ||IL_NLS_ preffix and no space in the text
67 IntIsol1OpnTxt string[25] cBMI.Empty_str IN: Description Text Interlock Signal Isol1 Open, for NLS support
use ||IL_NLS_ preffix and no space in the text
68 IntIsol2ClsTxt string[25] cBMI.Empty_str IN: Description Text Interlock Signal Isol2 Close, for NLS support
use ||IL_NLS_ preffix and no space in the text
69 IntIsol2OpnTxt string[25] cBMI.Empty_str IN: Description Text Interlock Signal Isol2 Open, for NLS support
use ||IL_NLS_ preffix and no space in the text
70 EnSeq bool cBMIEnergy.CB. IN true: Point of control Sequence enable
EnSeq
71 EnCen bool cBMIEnergy.CB. IN true: Point of control Central enable
EnCen
72 EnLoc bool cBMIEnergy.CB. IN false: POC change to Loc by Operator or Program enable.
EnLoc (LocalControl from Cabinet also possible if false)
73 ExtendedInfo dint cBMI.DINT_0 IN: Mux 1 = ConsumerExt, 2 = Alarm List, 4 = Event List, 8 =
DetailGraphic, 16 = Status, 32 = Trend, 64 = Faceplate
74 Class dint 1 INIT: Alarm/Event class 1 ... 9999 (process section)
75 TripTr dint 3 INIT: Trip Treatment; 1,2,3 = ALPrio# (1=lowest)
76 AlarmTr dint 2 INIT: General Alarm Treatment; 1,2,3 = ALPrio# (1=lowest)
77 DiscrTr dint 2 INIT: Discrepancy Treatment; 1,2,3 = ALPrio# (1=lowest)
78 InterlockTr dint cBMI.AE.Interloc INIT: Interlock Treatment; 1,2,3 = ALPrio# (1=lowest)
kTr
79 ModeTr bool cBMIEnergy.CB. IN true: True enables events on mode and point of control change
ModeTr
80 StatusTr bool cBMIEnergy.CB. IN true: True enables events on status (open/close) change
StatusTr
81 IOStatTxt string[25] cBMIEnergy.CB.I IN: Description text for Input/Output board failure (IOStatus), for
OS_txt NLS support use ||AE_NLS_ preffix and no space in the text
82 IOStat4Txt string[25] cBMI.Empty_str IN: Description text for IOStatus4 failure usally used for serial
interface supervision, for NLS support use ||AE_NLS_ preffix and
no space
83 WarningTxt string[25] cBMIEnergy.CB. IN: Description Text for General Warning, for NLS support use
Warning_txt ||AE_NLS_ preffix and no space in the text
84 GeneralAlarmTxt string[25] cBMIEnergy.CB. IN: Description Text for General Alarm, for NLS support use
GnrlAlarm_txt ||AE_NLS_ preffix and no space in the text
85 CircuitBreakerTxt string[15] cBMIEnergy.CB. IN: Description Text for Circuit Breaker, for NLS support use
CircuitBreak_txt ||AE_NLS_ preffix and no space in the text
86 Isolator1Txt string[15] cBMIEnergy.CB.I IN: Description Text for Isolator 1, for NLS support use ||AE_NLS_
sol1_txt preffix and no space in the text
87 Isolator2Txt string[15] cBMIEnergy.CB.I IN: Description Text for Isolator 2, for NLS support use ||AE_NLS_
sol2_txt preffix and no space in the text
88 ESW1Txt string[15] cBMIEnergy.CB. IN: Description Text for Earth Switch 1, for NLS support use
ESW1_txt ||AE_NLS_ preffix and no space in the text
89 ESW2Txt string[15] cBMIEnergy.CB. IN: Description Text for Earth Switch 2, for NLS support use
ESW2_txt ||AE_NLS_ preffix and no space in the text
90 ClosedTxt string[10] cBMIEnergy.CB. IN: Description Text for Closed, for NLS support use ||IL_NLS_
Closed_txt preffix and no space in the text
91 OpenTxt string[10] cBMIEnergy.CB. IN: Description Text for Open, for NLS support use ||IL_NLS_
Open_txt preffix and no space in the text
92 ReadyTxt string[10] cBMIEnergy.CB. IN: Description Text for Ready, for NLS support use ||AE_NLS_
Ready_txt preffix and no space in the text
93 TripTxt string[10] cBMIEnergy.CB. IN: Description Text for Trip, for NLS support use ||AE_NLS_
Trip_txt preffix and no space in the text
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 21
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Name Data Type Initial value Description


94 DiscrepancyTxt string[10] cBMIEnergy.CB. IN: Description Text for Discrepancy, for NLS support use
Disc_txt ||AE_NLS_ preffix and no space in the text
95 GrpCBClsOverride bool false IN false: If true, CB Cls backsignal to Group is set constant 1
96 GrpCBOpnOverride bool false IN false: If true, CB Opn backsignal to Group is set constant 1
97 GrpIsol1ClsOverride bool false IN false: If true, Isol1 Cls backsignal to Group is set constant 1
98 GrpIsol1OpnOverride bool false IN false: If true, Isol1 Opn backsignal to Group is set constant 1
99 GrpIsol2ClsOverride bool false IN false: If true, Isol2 Cls backsignal to Group is set constant 1
100 GrpIsol2OpnOverride bool false IN false: If true, Isol2 Opn backsignal to Group is set constant 1
101 AlarmAck bool false IN pulse: Alarm acknowledge
102 CBType dint 51 INIT: Obsolete; Used to enable CB, Isol1, Isol2 depending on
Type. (Default = 51 UNIGEAR Cable Connector)

3.2.3 Data Type description


Together with the CircuitBreaker Control Module Type a Structured Data Type
CircuitBreakerData is available. This makes it possible to create one Global Variable in
the application for each motor instance.
CircuitBreakerData contains two components :
CircuitBreakerInput, CircuitBreakerOutput
CircuitBreakerData; components
Name Data Type Attribute Initial Description
s Value
1 In CircuitBreakerInput retain Input variables to the CirCuit Breaker
2 Out CircuitBreakerOutput retain Output variables to the CirCuit Breaker

CircuitBreakerInput; components
Name Data Attributes Initial Description
Type value
1 PreSelCB bool retain true IN true: true = CB is pre-selected, usally connected to
PreBinData.PreSel
2 PreSelIsol1 bool retain true IN true: true = Isolator 1 is pre-selected, usally
connected to PreBinData.PreSel
3 PreselIsol2 bool retain false IN true: true = Isolator 2 is pre-selected, usally
connected to PreBinData.PreSel
4 CBSeqCls bool retain hidden false IN pulse: CB external close command, changes POC
to Seq and closes the CB
5 CBSeqOpn bool retain hidden false IN pulse: CB external open command, changes POC
to Seq and opens the CB
6 Isol1SeqCls bool retain hidden false IN pulse: Isol 1 external close command, changes
POC to Seq and closes the Isol 1
7 Isol1SeqOpn bool retain hidden false IN pulse: Isol 1 external open command, changes POC
to Seq and opens the Isol 1
8 Isol2SeqCls bool retain hidden false IN pulse: Isol 2 external close command, changes
POC to Seq and closes the Isol 2
9 Isol2SeqOpn bool retain hidden false IN pulse: Isol 2 external open command, changes POC
to Seq and opens the Isol 2
10 SetSeq bool retain hidden false IN pulse: external POC change to Seq
11 SetCen bool retain hidden false IN pulse: external POC change to Cen
12 SetLoc bool retain hidden false IN pulse: external POC change to Loc
13 IntCBCls bool retain true IN true: Interlock Signal CB Close, prevents closing in
Seq and Cen
14 IntCBOpn bool retain true IN true: Interlock Signal CB Open, prevents opening in
Seq and Cen
15 IntCBTrip bool retain true IN true: Safety Interlock Signal CB Trip
16 IntIsol1Cls bool retain true IN true: Interlock Signal Isol1 Close, prevents closing
in Seq and Cen
17 IntIsol1Opn bool retain true IN true: Interlock Signal Isol1 Open, prevents opening
in Seq and Cen
18 IntIsol2Cls bool retain true IN true: Interlock Signal Isol2 Close, prevents closing
in Seq and Cen
19 IntIsol2Opn bool retain true IN true: Interlock Signal Isol2 Open, prevents opening
in Seq and Cen
20 Warning bool retain false IN: When enabled show the WarningTxt in the
Faceplate

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 22
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

CircuitBreakerOutput; components
Name Data Attributes Initial Description
Type value
1 Seq bool retain nosort Indication of point of operation SEQuence.
2 Cen bool retain nosort Signal indicating that the drive is in central operation
mode.
3 Loc bool retain nosort Signal indicating that the drive is in local operation
mode.
4 OutOfSrv bool retain nosort Signal indicating that the dirve is Out Of Service
5 TripCB bool retain nosort TRIPped indication, can be used to start redundant
equipment.
6 CBReadyCls bool retain nosort Indication that Circuit Breaker is Ready to Close
7 CBReadyOpn bool retain nosort Indication that Circuit Breaker is Ready to Open
8 Isol1ReadyCls bool retain nosort Indication that Isolator 1 is Ready to Close
9 Isol1ReadyOpn bool retain nosort Indication that Isolator 1 is Ready to Open
10 Isol2ReadyCls bool retain nosort Indication that Isolator 2 is Ready to Close
11 Isol2ReadyOpn bool retain nosort Indication that Isolator 2 is Ready to Open
12 SumReady bool retain nosort Signal indicating that the all CB and Isol are Ready
for Operation.
13 PosCBCls bool retain nosort Signal indicating that the CB is closed.
14 PosCBOpn bool retain nosort Signal indicating that the CB is open.
15 PosIsol1Cls bool retain nosort Signal indicating that the Isolator 1 is closed.
16 PosIsol1Opn bool retain nosort Signal indicating that the Isolator 1 is open.
17 PosIsol2Cls bool retain nosort Signal indicating that the Isolator 2 is closed.
18 PosIsol2Opn bool retain nosort Signal indicating that the Isolator 2 is open.
19 OrdCBCls bool retain nosort Close Order Pulse for Circuit Breaker.
20 OrdCBOpn bool retain nosort Open Order Pulse for Circuit Breaker.
21 IntCBCls bool retain nosort Close Interlock for Circuit Breaker (normally true)
22 OrdIsol1Cls bool retain nosort Close Order Pulse for Isolator 1.
23 OrdIsol1Opn bool retain nosort Open Order Pulse for Isolator 1.
24 OrdIsol2Cls bool retain nosort Close Order Pulse for Isolator 2.
25 OrdIsol2Opn bool retain nosort Open Order Pulse for Isolator 2.
26 CBClsCnt dint coldretain Accumulated no of closings of the Circuit Breaker
nosort
27 CBTripCnt dint coldretain Accumulated no of (load) trips for CB
nosort
28 CBClsTimeCnt real coldretain Accumulated closed time of the Circuit Breaker
nosort
29 Name string[ retain nosort Name of the CB, Used for displaying CB's in Load
24] Faceplate
30 LastReset date_ coldretain Last Reset of Close and Trip Cnt in System Time
and_ti
me

3.2.4 Project Constants


Name Data Type Default Value
1 cBMIEnergy.CB.CBGeneralAlarm_Inverted bool (bool): false
2 cBMIEnergy.CB.CBReady_Inverted bool (bool): false
3 cBMIEnergy.CB.CBTrip_Inverted bool (bool): false
4 cBMIEnergy.CB.CircuitBreak_Txt string (string): 'CB'
5 cBMIEnergy.CB.Closed_Txt string (string): 'Closed'
6 cBMIEnergy.CB.Disc_Txt string (string): 'Discrep'
7 cBMIEnergy.CB.EnCen bool (bool): true
8 cBMIEnergy.CB.EnLoc bool (bool): false
9 cBMIEnergy.CB.EnSeq bool (bool): true
10 cBMIEnergy.CB.ESW1_Txt string (string): 'Earth Switch 1'
11 cBMIEnergy.CB.ESW2_Txt string (string): 'Earth Switch 2'
12 cBMIEnergy.CB.FieldErathAndSec_Txt string (string): 'Field Earthed and Secured'
13 cBMIEnergy.CB.GnrlAlarm_Txt string (string): 'General Alarm'
14 cBMIEnergy.CB.Inserted_Txt string (string): 'Inserted'
15 cBMIEnergy.CB.IntCBTrip_ActiveInAlarm bool (bool): true
16 cBMIEnergy.CB.IOS_Txt string (string): 'I/O Error'
17 cBMIEnergy.CB.Isol1_Txt string (string): 'Isolator 1'
18 cBMIEnergy.CB.Isol1Ready_Inverted bool (bool): false
19 cBMIEnergy.CB.Isol2_Txt string (string): 'Isolator 2'
20 cBMIEnergy.CB.Isol2Ready_Inverted bool (bool): false
21 cBMIEnergy.CB.Isolated_Txt string (string): 'Isolated'

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 23
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Name Data Type Default Value


22 cBMIEnergy.CB.LocalControl_Inverted bool (bool): false
23 cBMIEnergy.CB.ModeTr bool (bool): true
24 cBMIEnergy.CB.NotFieldErathAndSec_Txt string (string): 'Field Not Earthed and Not Secured'
25 cBMIEnergy.CB.Open_Txt string (string): 'Open'
26 cBMIEnergy.CB.Ready_Txt string (string): 'not Ready'
27 cBMIEnergy.CB.StatusTr bool (bool): true
28 cBMIEnergy.CB.Suppr_External_DiscrepancyAl bool (bool): false
29 cBMIEnergy.CB.Trip_Txt string (string): 'Tripped'
30 cBMIEnergy.CB.Warning_txt string (string): 'Warning'
Some of these Constants are used as initial Values for the Control Module Parameter.
cBMIEnergy.CB.Suppr_External_DiscrepancyAl can be set to disable the Discrepancy
Alarm for the Circuit Breakers for all cases where the Position changes while no
Command was sent from the Controller (useful if external Interfaces are switching the
Breakers). If the CB Control Module itself wants to change the Breaker’s position, the
Discrepancy alarm is still issued (Command Timeout case). Note that in this release, the
Discrepancy Alarm is always disabled if the CB is in Local Mode.
cBMIEnergy.CB.IntCBTrip_ActiveInAlarm can be set to keep sending Commands to
Breakers with Discrepancy Alarms. Note that there is also an Interlock IntCBCls going out
to the Circuit Breaker, which is supposed to be used as a Fundamental Interlock.

Name Data Type Default Value


1 cBMIEnergy.LogTxt.CBTxt string (string): 'CB'
2 cBMIEnergy.LogTxt.ESW1Txt string (string): 'ESW1'
3 cBMIEnergy.LogTxt.ESW2Txt string (string): 'ESW2'
4 cBMIEnergy.LogTxt.IntCBTrip string (string): 'IntCBTrip'
5 cBMIEnergy.LogTxt.Iso1Txt string (string): 'Iso1'
6 cBMIEnergy.LogTxt.Iso2Txt string (string): 'Iso2'
7 cBMIEnergy.LogTxt.PosCls string (string): 'Cls'
8 cBMIEnergy.LogTxt.PosOpn string (string): 'Opn'
These Constants are used to generate the Event (Log) Messages.

3.3 OPERATION

3.3.1 Graphic Elements


Graphic Element Description Example

Displays object status information for a


circuit breaker in a single line diagram.
CB
Different indication types such as feeder or
bus coupler are possible.

Displays objects analog values:


Possible values:
CBValueAndUnit · Voltage
· Current
· Power
Name_Link_CB Displays the object name and status.
For more information see chapter 2.3 OPERATION.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 24
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.2 Faceplate
The following aspect view buttons are available on Circuit Breaker Faceplates
Icon Aspect View
Alarm List

Event List

Operators Note

Faceplate Documentation, reference to this document

The following command buttons are available on Circuit Breaker Faceplates


Icon Description Icon Description

Close Selected Switch Acknowledge alarm

Open Selected Switch Select CB for further operation


Only available in POC Central
Change control point to
sequence: Select Isolator 1 for further
The object is controlled automatically operation
from the application program in the Only available in POC Central
controller
Change control point to central: Select Isolator 2 for further
The object is controlled manually operation
from the Faceplate with the buttons Only available in POC Central
Change control point to local
The object is controlled locally in the field
via a local panel with push buttons.
The start/run interlocks are not taken into
account.
The safety interlock and alarms remain
effective

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 25
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.2.1 Default View

Tagname
&
Description

Point of Control

Object status

Actual
Measurement
Current Indication
Voltage Indication
Extended Info Power Indication

Extended View
for detailed
information and
settings

If a “Current”, “Voltage” or “Power” analog input signal is connected to the relevant


Parameter, the actual values appear in the Faceplate (Default and Extended View).

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 26
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.2.1.1 Extended Info


More information to parent object (Trends, Alarm/Event Lists) and direct links to
Objects Web interfaces or Object Overlap Displays are available in the Extended Info
box.

Icon Description
Show parent objects alarm list.

Show parent objects event list.

Show parent objects trend display

Show parent objects faceplate

Show Overlap Graphic Display

Show Device Extended Status

Open Device Web Page

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 27
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.2.2 Extended View

Additional information for the Circuit Breaker is structured in tabs. The available tabs
and a short description of the contained information are shown below.
Tab Description
Status
Interlock Interlock indication and interlock blocking
Alarm Alarm indication and alarm blocking
Group Corresponding Drive Group issues
Maintenance Maintenance issues

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 28
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.2.2.1 Status

The Circuit Breaker Configuration (CBType parameter) is done on every WarmStart, no


configuration change will be taken into account online.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 29
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Interlocks

Reference Table, Interlocks


Type of interlock Description
CB Cls Operator blockable closing interlock Prevents the Circuit Breaker from closing as
Not active in POC Local long as the interlock is on.
CB Opn Operator blockable opening interlock Prevents the Circuit Breaker from opening as
Not active in POC Local long as the interlock is on.
CB Trip Operator blockable trip interlock Trips the Circuit Breaker and prevents the CB
Not active in POC Local from closing as long as the trip interlock is on
Isol1 Cls Operator blockable closing interlock Prevents the Isolator 1 from closing as long as
Not active in POC Local the interlock is on.
Isol1 Opn Operator blockable opening interlock Prevents the Isolator 1 from opening as long
Not active in POC Local as the interlock is on.
Isol2 Cls Operator blockable closing interlock Prevents the Isolator 2 from closing as long as
Not active in POC Local the interlock is on.
Isol2 Opn Operator blockable opening interlock Prevents the Isolator 2 from opening as long
Not active in POC Local as the interlock is on.

Description
B Indication that the corresponding interlock has been blocked / overridden. Yellow means
that the interlock is blocked (disabled). When it is activated a yellow `B` is indicated next
to the graphic element and on the Base Control.

F All interlocks are low active. When the interlock signal is “false” the interlock is active.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 30
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.2.2.2 Alarms
There is a build in Alarm indication on the Extended Faceplate Alarm tab.
Following Alarms can be indicated:
Ø IOS Indication of I/O sub-system fault used by this specific motor (no
alarm generated)
Ø CB Gen Indication of internal CB General Alarm fault
Ø CB Trip Indication of internal CB Common Trip fault
Ø CB Dis Circuit Breaker Discrepancy check on opening / closing
Ø Isol1 Dis Isolator 1 Discrepancy check on opening / closing
Ø Isol2 Dis Isolator 2 Discrepancy check on opening / closing

Additionally, Circuit Breaker incorporates the following Warnings (these do not trip the
breaker):
· General Warning : User Defined Warning

In total, 3 AlarmCond Blocks are used:


· Trip : for Circuit Breaker Common Trip
· Alarm : for Circuit Breaker Relay General Alarm
· Discrepancy : for Circuit Breaker, Isolator 1 and Isolator 2 Discrepancy check on
closing / opening
First incoming (within the same cycle the highest prio) input will be freezed for indication
and alarm.
All alarms have individual descriptive text string as parameter in the control module.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 31
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Reference Table, Alarms


Type of alarm Description
IOS Input/Output error Indication of I/O sub-system fault used by this
specific motor (no alarm generated)
CB Gen Circuit Breaker internal Indication of internal CB fault and protection
CB Trip interface signals trip
CB Dis Circuit Breaker Discrepancy Indication of CB position discrepancy
check on opening / closing
Isol1 Dis Isolator 1 Discrepancy check Indication of Isolator 1 position discrepancy
on opening / closing
Isol2 Dis Isolator 2 Discrepancy check Indication of Isolator 2 position discrepancy
on opening / closing

F All alarms are High active. When the alarm signal is “true” the alarm is active.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 32
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.2.2.3 Group

This CB will be the second object in the


Drive Group to be started, with a delay of
2s.

This Isol1 will be the first object in the


Drive Group to be stopped, with a delay
of 2s.

Number of steps in the corresponding


Drive Group

Link to the corresponding Drive Group

Reference Table, Group


Description Delay
CB Close Sequential close order of the CB Close delay of the CB, GrpCBClsDelay
Step within the Group
CB Open Sequential open order of the CB Open delay of the CB, GrpCBOpnDelay
Step within the Group
Isol1 Close Sequential close order of the Close delay of the Isol1, GrpIsol1ClsDelay
Step Isol1 within the Group
Isol1 Open Sequential open order of the Open delay of the Isol1, GrpIsol1OpnDelay
Step Isol1 within the Group
Isol2 Close Sequential close order of the Close delay of the Isol2, GrpIsol2ClsDelay
Step Isol2 within the Group
Isol2 Open Sequential open order of the Open delay of the Isol2, GrpIsol2OpnDelay
Step Isol2 within the Group
No of Max number of steps in the Drive n.a.
Steps Group

F When a Circuit Breaker Component is not a member of a Drive Group, the Close Step
and Open Step are “0”

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 33
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.2.2.4 Maintenance

Last Reset Time

F “Simulation” and “Allow Alarm during Simulation” Checkbox and Reset Counters
button are only accessible when you are logged on as a System Engineer

Reference Table, Maintenance


Description
Out of Service When this box is checked the CB is put out of service and is not taken
into account anymore by the corresponding Group
Allow Alarm during Alarming during simulation can be enabled for testing the simulated
Simulation interface signals of an individual CB while the rest of the group
remains in simulation
CBType Warning This Warning Text is only visible if the Control Modules CBType
Parameter is different to the Graphic Element IndicationType Property
CB Trip Number of Circuit breaker Trips
CB Close Number of Circuit breaker Open -> Close operations
CB Close Time Time in hours that CB has been closed
Reset Counters Reset button, to reset all counters
Last Reset Time Shows the Date and Time the CB Counters were last reset

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 34
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.3 Faceplate Control Permission


Using User Roles and Permissions, each Circuit Breaker Faceplate Control can be
configured according the Plant specific Access Rights concept.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 35
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.4 Alarms and Events


For general information about Alarm & Event list, please consult Chapter 2.4 in the
Consumer Objects Reference Manual.
For a description of the Alarms, please refer to Section 3.3.2.2.2

3.4.1.1 Object Status and Point of Control


Object status and modes are presented on the event list. Whenever the object changes its
status or point of control, the complete information of the object at the time of the change
is logged in the event list. The following message structure applies:
[POC] + [CB STATUS] + [DIS1 STATUS] + [DIS2 STATUS] + Blk/Dbl

[POC] Description
Seq Point of Control Sequence (from Group of Application)
Cen Point of Control Central (from Faceplate)
Loc Point of Control Local (from Field / Local Panel)
Out Circuit Breaker is Out of Service

[CB STATUS] Description


Cls Circuit Breaker is closed
Opn Circuit Breaker is open
Isol Circuit Breaker is isolated (racked out)
Flt Circuit Breaker Position is faulty (Opn and Cls)
Int Circuit Breaker Position is between Open and Close
Unk Circuit Breaker Rack Position unknown

[DS1 STATUS] Description


Cls Disconnector 1 is closed
Opn Disconnector 1 is open
Flt Disconnector 1 Position is faulty (Opn and Cls)
Int Disconnector 1 Position is between Open and Close

[DS2 STATUS] Description


Cls Disconnector 2 is closed
Opn Disconnector 2 is open
Flt Disconnector 2 Position is faulty (Opn and Cls)
Int Disconnector 2 Position is between Open and Close

Blk is added to the Message if any Interlock is blocked, otherwise Dbl is added to the
Event.

The following are additional Status Messages possible:


ESW1 & ESW2 Open and Closed Position
Field Earthed and Secured (if connected as Interface Signal from Field)

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 36
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

4. ABB_REF542Plus_IntCtrl

4.1 BASIC DESCRIPTION


The Control Module Type ABB_REF542Plus_IntCtrl is used to control the ModBus
Communication. This Control Module takes care for the Communication Layer and the
data mapping. ABB_REF542Plus_IntCtrl combines the following functions:
· ModBus Master Control for all REF542Plus Slaves on one Bus
(Recommended Configuration is 10 Slaves per bus)
· Decoding of Status, Trip and Alarm Bits from REF542Plus
· Coding of Commands to REF542Plus
· Communication Supervision and Alarms
· Events for all possible REF542Plus Trips and Alarms.
The control module is designed to support the REF542Plus control code and ModBus
mapping as defined as standard for the BU Minerals by ATBPE and ATBPA (LBU
Switzerland)

4.2 CONTROL

4.2.1 Parameter description


No Name Data Type Initial Value Description
1 Name string[20] 'Name' INIT: Tag name of the ModbusSlave (allowed deliminators are "."
and "-", no blanks ":" or ";" allowed)
2 Description string[40] 'Description' IN: Description text of the Modbus Slave (allowed deliminators
are "." and "-", no blanks ":" or ";" allowed)
3 IO ABB_REF542 ABB REF542 Plus Interface Record
Plus_Interface
4 ModBusLink BMIModBus IN/OUT: Modbus Slave/Master InterLink
SlaveInterLink
5 InterfaceType dint 1 IN: Interface for the ABB REF 542 Plus 1: BU Minerals
UNIGEAR; 2: BU Minerals ZX2
6 Class dint 1 INIT: AE Class 1 ... 9999 (Section)
7 ModbusChannel string[40] '0.3' INIT: HW Channel Address of the Modbus Inteface in HW Tree
as string
8 ModbusSlavePos string[40] '1' INIT: Slave Number of the Modbus Device as string
9 ReadCurrentAnd bool FALSE IN: false reads 21 words, true reads 13 words
VoltOnly
10 Read_ADDR string[40] '%IW10#000' INIT: Mobus Address for Read Base Addr
11 Command_ADDR string[40] '%QW10#00 INIT: Modbus Address for Write Base Address
0'
12 SlaveErrorTime time 30s INIT: Incase slave does not receive new data within the
SlaveErrorTime a Communication Alarm is generated, and all
values are reset
13 EnAutoRestart bool FALSE IN false: Enabling of Automatic Restart of ModBus Slave after
Communication Error
14 SlaveTimeOutTime time 2s INIT: Time till the master cont. with next slave in case slave is not
responding / if slave is not enable or reports an error time is
ignore
15 SalveReconnectDelay time 1s INIT: Time the slave wait before first sending after the connection
is o.k.
16 Simulation bool FALSE Simulation Mode for Drives from Group

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 37
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

4.2.2 Data Type description


Together with the ABB_REF542Plus_IntCtrl Control Module Type, 2 Structured Data
Type: ABB_REF542Plus_Interface and BMIModBusSlaveInterLink for the
Communication are available.

ABB_REF542Plus_Interface; components
Name Data Type Attribu Initial Description
tes Value
1 Commands ABB_REF542Plus_ retain IN : Command variables to the CB, Isolator
Commands
2 Status1 ABB_REF542Plus_ retain OUT : State variables for the CB, Isolator, ESW
Status1
3 Status2 ABB_REF542Plus_ retain OUT : State variables for the CB, Isolator, ESW
Status2
4 Status3 ABB_REF542Plus_ retain OUT : State variables for the CB, Isolator, ESW
Status3
5 Trips1 ABB_REF542Plus_ retain OUT : Trips variables for the CB, Isolator, ESW
Trips1
6 Trips2 ABB_REF542Plus_ retain OUT : Trips variables for the CB, Isolator, ESW
Trips2
7 Alarms1 ABB_REF542Plus_ retain OUT : Alarms variables for the CB, Isolator, ESW
Alarms1
8 Alarms2 ABB_REF542Plus_ retain OUT : Alarms variables for the CB, Isolator, ESW
Alarms2
9 Current ABB_REF542Plus_ retain OUT : Current variable for the 3 Phases
Current
10 Voltage ABB_REF542Plus_ retain OUT : Voltage variable for the 3 Phases
Voltage
11 Power ABB_REF542Plus_ retain OUT : Power variable for the 3 Phases
Power
12 Frequency ABB_REF542Plus_ retain OUT : Frequency variable
Frequency
13 Energy ABB_REF542Plus_ retain OUT : Energy variable ; Active, Reactive
Energy
14 ModBus BMIModBusSlave retain ModBus Communication
Slave

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 38
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

BMIModBusSlaveInterLink; components
Name Data Attributes Initial Description
Type Value
1 CommandPending bool retain nosort
hidden
2 FirstScanAfterWar bool retain nosort FALSE
mStart hidden
3 FirstSlavePos dint nosort 999
hidden
4 LastSlavePos dint nosort 0
hidden
5 IdenticalSlavePos bool nosort FALSE
hidden
6 ActReadData dint retain nosort
RequestSlaveNo hidden
7 ActReadData dint retain nosort
ReceivedSlaveNo hidden
8 NextReadData dint retain nosort 999
RequestSlaveNo hidden
9 ActSendData dint retain nosort
RequestSlaveNo hidden
10 ActSendDataDone dint retain nosort
SlaveNo hidden
11 NextSendData dint retain nosort 999
RequestSlaveNo hidden
12 NextSendData date_ retain nosort
RequestTime and_ti hidden
me
13 NewestSendData date_ retain nosort
RequestTime and_ti hidden
me
14 EventMaster bool nosort FALSE Event the Slave Requests from the Master
Actions
15 StartAllSlaves bool retain nosort Starts All Slaves on a Bus
16 StopAllSlaves bool retain nosort Stops All Slaves on a Bus

4.3 OPERATION

The Faceplate to Monitor, Start and Stop the ModBus is available in the Wrapper Object. See
section 5.3.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 39
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

5. CircuitBreakerABBREF542Plus

5.1 BASIC DESCRIPTION


The Control Module Type CircuitBreakerABBREF542Plus provides a composite Control
Module with serial interface to implement the supervision and operation of power network
switchgear equipment. The example below presents an ABB REF542+ with Modbus
communication.

Composite CircuitBreakerABBREF542Plus composed by :


o CircuitBreaker for operating motorized Circuit Breaker products
o ABB_REF542Plus_IntCtrl for monitoring the Modbus Communication
o 3 AIC & 1 Energy Counter for displaying the most significant information on the operator
display

The Control Module can easily be adapted to other equipment and communication types.
Next to the common basic functions for energy monitoring objects, the following functions
are supported:
· Operation modes
· Selection of individual Breaker for operation
· Open / Close order to operate the breaker
· Communication link error
· Indication of Breaker status
· Indication of Switches
· Indication of Voltage, Current, Power
· Extended Info Button added to Circuit Breaker FPL to access complete REF542
Trip, Alarm and Status information

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 40
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

5.2 CONTROL

5.2.1 Parameter description


# Name Data Type Initial Value Description
1 Name string[24] INIT: Tag name of the circuit breaker composit object (allowed
deliminators are "." and "-", no blanks ":" or ";" allowed)
2 CBName string[24] INIT: Tag name of the circuit breaker (allowed deliminators are
"." and "-", no blanks ":" or ";" allowed)
3 Description string[40] 'Description' IN: Description text of the circuit breaker
4 IO CircuitBreake IN/OUT: Circuit Breaker Data Variable
rABBREF542
PlusData
5 ModBus_Link BMIModBusS IN/OUT: Modbus Slave/Master InterLink
laveInterLink
6 InterfaceType dint 1 IN: Interface for the ABB REF 542 Plus 1: BU Minerals
UNIGEAR; 2: BU Minerals ZX2
7 ModBusTask string IN: Connection to Modbus Task(s)
8 Modbus_Name string[24] 'Name' INIT: Tag name of the ModBus Interface (used for Modbus Com
Error Alarm (e.g. MOT1 or CircuitBreaker)
9 Modbus_Channel string[40] '0.3' INIT: HW Channel Address of the Modbus Interface in HW Tree
as string
10 Modbus_SlavePos string[40] '1' INIT: Slave Number of the Modbus Device as string
11 ModBus_ReadCurrentA bool false IN: false reads 21 words, true reads 13 words
ndVoltOnly
12 ModBus_SlaveErrorTim time 30s INIT: In case slave does not receive new data within the
e SlaveErrorTime a Communication Alarm is generated, and all
values are reset
13 ModBus_EnAutoRestar bool false IN false: Enabling of Automatic Restart of ModBus Slave after
t Communication Error
14 ModBus_SlaveTimeOut time 2s INIT: Time till the master cont. with next slave in case slave is
Time not responding / if slave is not enable or reports an error time is
ignore
15 ModBus_SalveReconn time 1s INIT: Time the slave wait before first sending after the connection
ectDelay is o.k.
16 Voltage_Name string[24] INIT: Tag name of the AIC for the Voltage (allowed deliminators
are "." and "-", no blanks ":" or ";" allowed)
17 Voltage_Description string[40] IN: Description text of the AIC
18 Voltage_Max real 50 INIT: Scaling Parameter Range Max.
19 Voltage_Unit string[5] 'kV' INIT: Scaling Parameter Unit.
20 Voltage_Fraction dint 2 INIT: Fraction (Number of Decimals).
21 Current_Name string[24] INIT: Tag name of the AIC for the Current (allowed deliminators
are "." and "-", no blanks ":" or ";" allowed)
22 Current_Description string[40] IN: Description text of the AIC
23 Current_Max real 2000 INIT: Scaling Parameter Range Max.
24 Current_Unit string[5] 'A' INIT: Scaling Parameter Unit.
25 Current_Fraction dint 0 INIT: Fraction (Number of Decimals).
26 Power_Name string[20] INIT: Tag name of the AIC for the Power (allowed deliminators
are "." and "-", no blanks ":" or ";" allowed)
27 Power_Description string[40] IN: Description text of the AIC
28 Power_Max real 100 INIT: Scaling Parameter Range Max.
29 Power_Unit string[5] 'MW' INIT: Scaling Parameter Unit.
30 Power_Fraction dint 2 INIT: Fraction (Number of Decimals).
31 Counter_Name string[24] INIT: Tag name of the Energy Counter (allowed deliminators are
"." and "-", no blanks ":" or ";" allowed)
32 Group GrpDrvCon default IN/OUT: Connection to control module GROUP (sequencer)
33 GrpCBClsStep dint cBMI.DINT_0 IN: CB Close step no 1..999, if set to 0 -> not part of group
sequence
34 GrpCBOpnStep dint cBMI.DINT_0 IN: CB Open step no 1001..1999, if set to 0 -> not part of group
sequence
35 GrpIsol1ClsStep dint cBMI.DINT_0 IN: Isol1 Close step no 1..999, if set to 0 -> not part of group
sequence
36 GrpIsol1OpnStep dint cBMI.DINT_0 IN: Isol1 Open step no 1001..1999, if set to 0 -> not part of group
sequence
37 GrpIsol2ClsStep dint cBMI.DINT_0 IN: Isol2 Close step no 1..999, if set to 0 -> not part of group
sequence
38 GrpIsol2OpnStep dint cBMI.DINT_0 IN: Isol2 Open step no 1001..1999, if set to 0 -> not part of group
sequence
39 GrpCBClsDelay time cBMI.Time2s IN: CB Close delay when closed from group sequence

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 41
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

# Name Data Type Initial Value Description


40 GrpCBOpnDelay time cBMI.Time2s IN: CB Open delay when opened from group sequence
41 GrpIsol1ClsDelay time cBMI.Time2s IN: Isol1 Close delay when closed from group sequence
42 GrpIsol1OpnDelay time cBMI.Time2s IN: Isol2 Open delay when opened from group sequence
43 GrpIsol2ClsDelay time cBMI.Time2s IN: Isol1 Close delay when closed from group sequence
44 GrpIsol2OpnDelay time cBMI.Time2s IN: Isol2 Open delay when opened from group sequence
45 EnQuickStop bool false IN false: Enable Group Quick stop for the Circuit breaker
46 IOStatus1 dint cBMI.DINT_0 IN: Status signal of related IO-Board
47 IOStatus2 dint cBMI.DINT_0 IN: Status signal of related IO-Board
48 IOStatus3 dint cBMI.DINT_0 IN: Status signal of related IO-Board
49 CBEnabled bool true INIT: Enable CB (only valid if CBType is default=51)
50 Isol1Enabled bool false INIT: Enable Isol1 (only valid if CBType is default=51)
51 Isol2Enabled bool false INIT: Enable Isol2 (only valid if CBType is default=51)
52 IgnoreCBRdyForOpnC bool true IN true: if true the ready signal has no influence on CB open
md commands
53 IgnoreIsol1RdyForOpn bool false IN false: if true the ready signal has no influence on isolator 1
Cmd open commands
54 IgnoreIsol2RdyForOpn bool false IN false: if true the ready signal has no influence on isolator 2
Cmd open commands
55 CBTime time cBMI.Time2s IN: Maximum delay time for Circuit Breaker Response
56 IsolTime time cBMI.Time10s IN: Maximum delay time for Isolator Response
57 ShowCurrent bool true IN: Enabling of Current indication on Faceplate
58 ShowVoltage bool true IN: Enabling of Voltage indication on Faceplate
59 ShowPower bool true IN: Enabling of Power indication on Faceplate
60 IntCBClsTxt string[25] cBMI.Empty_str IN: Description Text Interlock Signal CB Close
61 IntCBOpnTxt string[25] cBMI.Empty_str IN: Description Text Interlock Signal CB Open
62 IntCBTripTxt string[25] cBMI.Empty_str IN: Description Text Interlock Signal CB Trip
63 IntIsol1ClsTxt string[25] cBMI.Empty_str IN: Description Text Interlock Signal Isol1 Close
64 IntIsol1OpnTxt string[25] cBMI.Empty_str IN: Description Text Interlock Signal Isol1 Open
65 IntIsol2ClsTxt string[25] cBMI.Empty_str IN: Description Text Interlock Signal Isol2 Close
66 IntIsol2OpnTxt string[25] cBMI.Empty_str IN: Description Text Interlock Signal Isol2 Open
67 EnSeq bool cBMIEnergy.CB. IN true: Point of control Sequence enable
EnSeq
68 EnCen bool cBMIEnergy.CB. IN true: Point of control Central enable
EnCen
69 EnLoc bool cBMIEnergy.CB. IN false: POC chng to Loc by Operator or Program enable.
EnLoc (LocalContol form Relay even possible if false)
70 ExtendedInfo dint cBMIEnergy.ABB IN: Mux 1 = ConsumerExt, 2 = Alarm List, 4 = Event List, 8 =
REF542Plus.Ext DetailGraphic, 16 = Status, 32 = Trend, 64 = Faceplate
endedInfo
71 Class dint 1 INIT: Alarm/Event class 1 ... 9999 (process section)
72 TripTr dint 3 INIT: Trip Treatment; 1,2,3 = ALPrio# (1=lowest)
73 AlarmTr dint 2 INIT: General Alarm Treatment; 1,2,3 = ALPrio# (1=lowest)
74 DiscrTr dint 2 INIT: Discrepancy Treatment; 1,2,3 = ALPrio# (1=lowest)
75 ModeTr bool cBMIEnergy.CB. IN true: True enables events on mode and point of control
ModeTr change
76 StatusTr bool cBMIEnergy.CB. IN true: True enables events on status (open/close) change
StatusTr
77 IOStatTxt string[25] cBMIEnergy.CB.I IN: Description text for Input/Output board failure (IOStatus)
OS_txt
78 GeneralAlarmTxt string[25] cBMIEnergy.CB. IN: Description Text for General Alarm
GnrlAlarm_txt
79 CircuitBreakerTxt string[15] cBMIEnergy.CB. IN: Description Text for Circuit Breaker
CircuitBreak_txt
80 Isolator1Txt string[15] cBMIEnergy.CB.I IN: Description Text for Isolator 1
sol1_txt
81 Isolator2Txt string[15] cBMIEnergy.CB.I IN: Description Text for Isolator 2
sol2_txt
82 ESW1Txt string[15] cBMIEnergy.CB. IN: Description Text for Earth Switch 1
ESW1_txt
83 ESW2Txt string[15] cBMIEnergy.CB. IN: Description Text for Earth Switch 2
ESW2_txt
84 ClosedTxt string[10] cBMIEnergy.CB. IN: Description Text for Closed
Closed_txt
85 OpenTxt string[10] cBMIEnergy.CB. IN: Description Text for Open
Open_txt
86 ReadyTxt string[10] cBMIEnergy.CB. IN: Description Text for Ready
Ready_txt

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 42
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

# Name Data Type Initial Value Description


87 TripTxt string[10] cBMIEnergy.CB. IN: Description Text for Trip
Trip_txt
88 DiscrepancyTxt string[10] cBMIEnergy.CB. IN: Description Text for Discrepancy
Disc_txt
89 GrpCBClsOverride bool false IN false: If true, CB Cls backsignal to Group is set constant 1
90 GrpCBOpnOverride bool false IN false: If true, CB Opn backsignal to Group is set constant 1
91 GrpIsol1ClsOverride bool false IN false: If true, Isol1 Cls backsignal to Group is set constant 1
92 GrpIsol1OpnOverride bool false IN false: If true, Isol1 Opn backsignal to Group is set constant 1
93 GrpIsol2ClsOverride bool false IN false: If true, Isol2 Cls backsignal to Group is set constant 1
94 GrpIsol2OpnOverride bool false IN false: If true, Isol2 Opn backsignal to Group is set constant 1
95 AlarmAck bool false IN pulse: Alarm acknowledge
96 CBType dint 51 INIT: Obsolete; Used to enable CB, Isol1, Isol2 depending on
Type. (Default = 51 UNIGEAR Cable Connector)

5.2.2 Data Type description


Together with the CircuitBreakerABBREF542Plus Control Module Type Structured Data
Type CircuitBreakerABBRREF542PlusData and BMIModBusSlaveInterLink for the
Communication are available. This makes it possible to create one Global Variable in the
application for each CB instance.
CircuitBreakerABBRREF542PlusData contains several structured components :
CircuitBreaker, ABB_REF542Plus_Interface.

CircuitBreakerABBRREF542PlusData; components
Name Data Type Attributes Initial Description
Value
1 Ctrl CircuitBreakerData retain Variables to the CirCuit Breaker
2 ABB_REF542 ABB_REF542 retain Interface for Serial Communication
Plus_Interface Plus_Interface
3 Voltage AISData retain Indication for Voltage
4 Current AISData retain Indication for Current
5 Power AISData retain Indication for Power
6 Energy PulseCountData retain Indication for Energy Counter

5.2.3 Project Constants


Name Data Default Value
Type
cBMIEnergy.ABBREF542Plus.Alarms1.ARCSupLoopBB string (string): 'ARC Supervision Bus Bar 1 Chamber'
1 1
cBMIEnergy.ABBREF542Plus.Alarms1.ARCSupLoopBB string (string): 'ARC Supervision Bus Bar 2 Chamber'
2 2
3 cBMIEnergy.ABBREF542Plus.Alarms1.ARCSupLoopCB string (string): 'ARC Supervision CB Chamber'
4 cBMIEnergy.ABBREF542Plus.Alarms1.AuxGasPressAl string (string): 'Auxilliary Gas Pressure Alarm'
5 cBMIEnergy.ABBREF542Plus.Alarms1.AuxMCBTripCom string (string): 'Auxilliary MCB Trip Common'
6 cBMIEnergy.ABBREF542Plus.Alarms1.CB1GasPressAl string (string): 'CB1 Gas Pressure Alarm'
7 cBMIEnergy.ABBREF542Plus.Alarms1.CB1SprgNotLoad string (string): 'CB1 Spring Not Loaded'
8 cBMIEnergy.ABBREF542Plus.Alarms1.CB1TripFault string (string): 'CB1 Trip Fault'
9 cBMIEnergy.ABBREF542Plus.Alarms1.CoilSupDist string (string): 'Coil Supervision Disturbed'
10 cBMIEnergy.ABBREF542Plus.Alarms1.MCBTripCom string (string): 'MCB Tripped Common'
11 cBMIEnergy.ABBREF542Plus.Alarms1.TafoOilLevelAl string (string): 'Trafo Oil Level Alarm'
cBMIEnergy.ABBREF542Plus.Alarms1.TapChgMotorMC string (string): 'OLTC Motor MCB Trip'
12 BTrip
13 cBMIEnergy.ABBREF542Plus.Alarms1.Thermal49Al string (string): 'Thermal Protection 49 Alarm '
14 cBMIEnergy.ABBREF542Plus.Alarms1.TrafoBuchholzAl string (string): 'Trafo Buchholz Alarm'
15 cBMIEnergy.ABBREF542Plus.Alarms1.TrafoMCBTrip string (string): 'Trafo MCB Trip'
16 cBMIEnergy.ABBREF542Plus.Alarms1.TrafoTempAl string (string): 'Trafo Temperature Alarm'
17 cBMIEnergy.ABBREF542Plus.Alarms2.CB2GasPressAl string (string): 'CB2 Gas Pressure Alarm'
18 cBMIEnergy.ABBREF542Plus.Alarms2.CB2SprgNotLoad string (string): 'CB2 Spring Not Loaded'
19 cBMIEnergy.ABBREF542Plus.Alarms2.CB2TripFault string (string): 'CB2 Trip Fault'
cBMIEnergy.ABBREF542Plus.Alarms2.ExtClosingInterlo string (string): 'External Closing Interlock (Prevents to
20 ck Close)'
21 cBMIEnergy.ABBREF542Plus.Alarms2.ExtUserDefAl string (string): 'User defined External Alarm'
22 cBMIEnergy.ABBREF542Plus.Alarms2.RiserMCBTripCo string (string): 'Riser VT MCB open'

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 43
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Name Data Default Value


Type
m
cBMIEnergy.ABBREF542Plus.Alarms2.SPADSelfMonitor string (string): 'Self Monitoring SPAD, SPAU'
23 ing
24 cBMIEnergy.ABBREF542Plus.Alarms2.UserDefined1 string (string): 'User Defined Alarm 21'
25 cBMIEnergy.ABBREF542Plus.Alarms2.UserDefined2 string (string): 'User Defined Alarm 22'
26 cBMIEnergy.ABBREF542Plus.Alarms2.UserDefined3 string (string): 'User Defined Alarm 23'
27 cBMIEnergy.ABBREF542Plus.Alarms2.UserDefined4 string (string): 'User Defined Alarm 24'
28 cBMIEnergy.ABBREF542Plus.Alarms2.UserDefined5 string (string): 'User Defined Alarm 25'
29 cBMIEnergy.ABBREF542Plus.Alarms2.UserDefined6 string (string): 'User Defined Alarm 26'
30 cBMIEnergy.ABBREF542Plus.Alarms2.UserDefined7 string (string): 'User Defined Alarm 27'
31 cBMIEnergy.ABBREF542Plus.Alarms2.UserDefined8 string (string): 'User Defined Alarm 28'
32 cBMIEnergy.ABBREF542Plus.Alarms2.VTMCBTripCom string (string): 'VT MCB Tripped Open'
33 cBMIEnergy.ABBREF542Plus.ExtendedInfo dint (dint): 71
34 cBMIEnergy.ABBREF542Plus.ModBusAlarm string (string): 'Modbus Com Error'
35 cBMIEnergy.ABBREF542Plus.ReadRequest string (string): 'Read Request Slave: '
36 cBMIEnergy.ABBREF542Plus.SendRequest string (string): 'Send Request Slave: '
37 cBMIEnergy.ABBREF542Plus.Status3.UserDefined1 string (string): 'Other INC. Trafo open'
38 cBMIEnergy.ABBREF542Plus.Status3.UserDefined10 string (string): 'User Defined Status 10'
39 cBMIEnergy.ABBREF542Plus.Status3.UserDefined11 string (string): 'User Defined Status 11'
40 cBMIEnergy.ABBREF542Plus.Status3.UserDefined12 string (string): 'User Defined Status 12'
41 cBMIEnergy.ABBREF542Plus.Status3.UserDefined13 string (string): 'User Defined Status 13'
42 cBMIEnergy.ABBREF542Plus.Status3.UserDefined14 string (string): 'User Defined Status 14'
43 cBMIEnergy.ABBREF542Plus.Status3.UserDefined15 string (string): 'User Defined Status 15'
44 cBMIEnergy.ABBREF542Plus.Status3.UserDefined16 string (string): 'User Defined Status 16'
45 cBMIEnergy.ABBREF542Plus.Status3.UserDefined2 string (string): 'Tap changers in man.'
46 cBMIEnergy.ABBREF542Plus.Status3.UserDefined3 string (string): 'Bus Coupler open'
47 cBMIEnergy.ABBREF542Plus.Status3.UserDefined4 string (string): 'Emergency Operation'
48 cBMIEnergy.ABBREF542Plus.Status3.UserDefined5 string (string): 'Other INC. Trafo 1T2 Open'
49 cBMIEnergy.ABBREF542Plus.Status3.UserDefined6 string (string): '1T2 - Tap Changers in man. '
50 cBMIEnergy.ABBREF542Plus.Status3.UserDefined7 string (string): 'Riser Earth.Swithc closed'
51 cBMIEnergy.ABBREF542Plus.Status3.UserDefined8 string (string): 'Riser Earth.Swithc open'
52 cBMIEnergy.ABBREF542Plus.Status3.UserDefined9 string (string): '2of3 overbridge'
53 cBMIEnergy.ABBREF542Plus.Trips1.Trip50Iggg string (string): 'Protection Trip I>>>(50)'
54 cBMIEnergy.ABBREF542Plus.Trips1.Trip51Ig string (string): 'Protection Trip I>(51)'
55 cBMIEnergy.ABBREF542Plus.Trips1.Trip51Igg string (string): 'Protection Trip I>>(51)'
56 cBMIEnergy.ABBREF542Plus.Trips1.Trip51NIEgg string (string): 'Earth Fault Prot. Trip IE>>(51N)'
57 cBMIEnergy.ABBREF542Plus.Trips1.Trip67Idg string (string): 'Directional Overcurr. Trip I>(67)'
58 cBMIEnergy.ABBREF542Plus.Trips1.Trip67Idgg string (string): 'Directional Overcurr. Trip I>>(67)'
59 cBMIEnergy.ABBREF542Plus.Trips1.Trip67NIEdg string (string): 'Earth Fault Direct. Prot. Trip I>(67N)'
60 cBMIEnergy.ABBREF542Plus.Trips1.Trip67NIEdgg string (string): 'Earth Fault Direct. Prot. Trip I>>(67N)'
61 cBMIEnergy.ABBREF542Plus.Trips1.TripARCBB1 string (string): 'Electrical ARC Prot. Trip BB1'
62 cBMIEnergy.ABBREF542Plus.Trips1.TripARCBB2 string (string): 'Electrical ARC Prot. Trip BB2'
cBMIEnergy.ABBREF542Plus.Trips1.TripCBInsufGasPre string (string): 'CB Insufficient Gas Pressure'
63 ss
cBMIEnergy.ABBREF542Plus.Trips1.TripSBEF51G string (string): 'Secondary Bus Bar Earth Fault Prot.
64 Trip 51G'
65 cBMIEnergy.ABBREF542Plus.Trips1.TripSPAD87T string (string): 'Protection Trip SPAD 87T'
66 cBMIEnergy.ABBREF542Plus.Trips1.TripThermal49 string (string): 'Thermal Protection Trip 49'
67 cBMIEnergy.ABBREF542Plus.Trips1.UserDefined1 string (string): 'User Defined Trip 12'
68 cBMIEnergy.ABBREF542Plus.Trips1.UserDefined2 string (string): 'User Defined Trip 12'
cBMIEnergy.ABBREF542Plus.Trips2.IntType_1_UNISAF string (string): 'User Defined Trip 21'
69 E.UserDefined1
cBMIEnergy.ABBREF542Plus.Trips2.IntType_1_UNISAF string (string): 'User definied External Trip'
70 E.UserDefined2
cBMIEnergy.ABBREF542Plus.Trips2.IntType_1_UNISAF string (string): 'User definied External Trip'
71 E.UserDefined3
cBMIEnergy.ABBREF542Plus.Trips2.IntType_1_UNISAF string (string): 'User definied External Trip'
72 E.UserDefined4
cBMIEnergy.ABBREF542Plus.Trips2.IntType_1_UNISAF string (string): 'User definied Ext. CB Trip Comm'
73 E.UserDefined5
cBMIEnergy.ABBREF542Plus.Trips2.IntType_1_UNISAF string (string): 'External Emergency Trip'
74 E.UserDefined6
cBMIEnergy.ABBREF542Plus.Trips2.IntType_1_UNISAF string (string): 'Trip due to external Interlock (prevents
75 E.UserDefined7 closing)'
cBMIEnergy.ABBREF542Plus.Trips2.IntType_1_UNISAF string (string): 'User defined External Trip'
76 E.UserDefined8
77 cBMIEnergy.ABBREF542Plus.Trips2.IntType_2_ZX2.Us string (string): 'User Defined Trip 21'
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 44
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Name Data Default Value


Type
erDefined1
cBMIEnergy.ABBREF542Plus.Trips2.IntType_2_ZX2.Us string (string): 'Arc-Supervision CB-BB-B'
78 erDefined2
cBMIEnergy.ABBREF542Plus.Trips2.IntType_2_ZX2.Us string (string): 'Arc-Supervision BBI-B'
79 erDefined3
cBMIEnergy.ABBREF542Plus.Trips2.IntType_2_ZX2.Us string (string): 'Arc-Supervision BBII-B'
80 erDefined4
cBMIEnergy.ABBREF542Plus.Trips2.IntType_2_ZX2.Us string (string): 'Arc-Supervision CB-BB-A'
81 erDefined5
cBMIEnergy.ABBREF542Plus.Trips2.IntType_2_ZX2.Us string (string): 'Arc-Supervision BBI-A'
82 erDefined6
cBMIEnergy.ABBREF542Plus.Trips2.IntType_2_ZX2.Us string (string): 'Arc-Supervision BBII-A'
83 erDefined7
cBMIEnergy.ABBREF542Plus.Trips2.IntType_2_ZX2.Us string (string): 'User Defined TripExternal Trip'
84 erDefined8
85 cBMIEnergy.ABBREF542Plus.Trips2.TrafoBuchholzTrip string (string): 'Trafo Buchholz Trip'
86 cBMIEnergy.ABBREF542Plus.Trips2.TrafoPressRefTrip string (string): 'Trafo Pressure Relief Trip'
87 cBMIEnergy.ABBREF542Plus.Trips2.TrafoTempTrip string (string): 'Trafo Temperature Trip'
88 cBMIEnergy.ABBREF542Plus.Trips2.Trip27Ulll string (string): 'Undervoltage Trip 27'
89 cBMIEnergy.ABBREF542Plus.Trips2.Trip59Uggg string (string): 'Overvoltage Trip 59'
90 cBMIEnergy.ABBREF542Plus.Trips2.TripEmergencyStop string (string): 'Emergnecy Stop Trip'
91 cBMIEnergy.ABBREF542Plus.Trips2.TripNalfFuse string (string): 'Nalf Fuse Blown'
92 cBMIEnergy.ABBREF542Plus.Trips2.TripUnderVoltCoil string (string): 'Undervoltage Aux. Contact'
Most of these Constants define the Event Texts.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 45
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

5.3 OPERATION

5.3.1 Graphic elements


Graphic Element Description Example
Displays objects analog values:
Possible values:
· Current L1, L2 or L3
· Voltage L12, L23 or L31
CBValueAndUnit
· Active or reactive power
· Active or reactive energy
· Power factor
· Frequency
CommunicationStatus Displays the communication status.
For more information see chapter 2.3 OPERATION.

5.3.1.1 Graphic Element CBValueAndUnit


Fraction and unit source for the CBValueAndUnit graphic element depends on the
CBValue property:
Value Unit / Fraction Source
Current L1 CM Parameter: Current_Unit and Current_Fraction
Current L2 CM Parameter: Current_Unit and Current_Fraction
Current L3 CM Parameter: Current_Unit and Current_Fraction
Voltage L12 CM Parameter: Voltage_Unit and Voltage_Fraction
Voltage L23 CM Parameter: Voltage_Unit and Voltage_Fraction
Voltage L31 CM Parameter: Voltage_Unit and Voltage_Fraction
Active Power CM Parameter: Power_Unit and Power_Fraction
Reactive Power Common Property: “BMI NG Value Parameters”
Active Energy Common Property: “BMI NG Value Parameters”
Reactive Energy Common Property: “BMI NG Value Parameters”
Power Factor Common Property: “BMI NG Value Parameters”
Frequency Common Property: “BMI NG Value Parameters”
Common Property aspect “BMI NG Value Parameters”:

For more information see chapter 2.3 OPERATION.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 46
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

5.3.2 Faceplate for Circuit Breaker Operation


The Circuit Breaker faceplate is described in chapter 3.3.3. When using the Circuit
Breaker together with the ModBus Interface additional Information becomes available:
· Link to REF542Plus Status Display
· REF542Plus Alarm and Event List

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 47
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

5.3.3 Faceplate for Modbus Operation


This faceplate is only used for ModBus Supervision and Maintenance

The following aspect view buttons are available on ABBREF542Plus Faceplates


Icon Aspect View
Alarm List

Event List

Operators Note

Faceplate Documentation, reference to this document

The following command buttons are available on ABBREF542Plus Faceplates


Icon Description Icon Description

Start ModBus Interface Acknowledge alarm

Stop ModBus Interface

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 48
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

5.3.3.1 Default View

Tagname
&
Description

ModBus Task
&
Name

ModBus
Interface Status

ModBus Slave
Information

Extended View
for detailed
information and
settings

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 49
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

5.3.3.2 Extended View

The faceplate extended view, gives the possibility to Block the ModBus Communication
Alarm.

The CommStatus Tab shows the Status Output of the ModBus Communication Blocks. In
case of problems with the communication, compare these numbers with the Manual
(search in Control Builder Help for “error codes”).

5.3.4 Faceplate Control Permission


The Faceplate sets the Values found in BMIModBusIntAct which is part of
ABB_REF542Plus_IntCtrl:
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 50
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

5.4 Application examples

5.4.1 How to configure the Modbus interface


Here an example of a Circuitbreaker ABBREF542Plus’ Modbus related Parameters
Name Data Type Value Description
Name string[24] 'E20_1S1_QU1' TagName of the Wrapper Object
CBName string[24] 'E20_1S1_U1' TagName of the Circuit Breaker
Description string[40] 'Incomer 33 kV' IN: Description text of the circuit
breaker
IO CircuitBreakerABB IO.GR_E20._E20_1 IN/OUT: Circuit Breaker Data Variable
REF542PlusData S1_U1
ModBus_Link BMIModBusSlaveI E2X_1S1_ModBus Variable common to all CB Modules on
nterLink the same Bus
CBType dint 100 see CBType Table

InterfaceType dint 1 1: UNIGEAR, 2: ZX2

ModBusTask string 'N01.Modbus' Define a separate Modbus Task for all


the CB’s in the Controller and give its
name here!
Modbus_Name string[24] 'E20_1S1_U1_Com' TagName of the Modbus Interface (can
be equal to the Wrapper Object Name)
Modbus_Channel string[40] '0.3' Position of the Modbus Interface on the
Controller
Modbus_SlavePos string[40] '1' Modbus Slave Address of the Circuit
Breaker

Note that the ModBusTask and the Modbus_Link Parameters must be equal for all CBs
connected to the same Modbus interface!
Some examples for the Modbus_Channel Parameter:

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 51
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

PM third Com port:


Channel ‘0.3’

CI853 first port:


Channel ‘2.1’

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 52
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6. Power Factor Correction Control (PFCC) Control Module

6.1 BASIC DESCRIPTION


The Power Factor Correction Control Control Module Type allows the control of MV-
Switchgear RC Bank in order to monitor and control the Power Factor of the grid connect.

6.1.1 Features
· Communication between PFCC Module and the connected MV-Switchgear (up to 8
MV-Circuit Breaker Control Modules)
· Stepping Up / Down according the allowed hierarchical harmonics sequence
· Selectable Control Type:
o Stepping Up / Down by automatically choosing the best available RC Bank to
reach Cos Phi target
o Stepping Up / Down according individual predefined thresholds for reactive
Power
· Manual / Auto Mode
o Manual: PFCC must be started manually when ever the network characteristic is
changed, e.g. bus bar coupling CB open / close
o Auto: Automatic trip and restart of the PFCC when ever the network
characteristic is changed, e.g. bus bar coupling CB open / close
· Network support with parallel Infeed Trafo on the same Busbar
· Reactive power hysteresis up / down
· Step up / down delay time
· Additional over compensation step down delay time for prevention of over
compensation
· Prevents fast reclosing of CB
· Trending of RC Bank Use
· Tracking of Starting / Stopping time
· Tracking of Manual Mode / Automatic Mode change
· Monitoring of
o Actual Power,
o Actual Reactive Power,
o Actual Reactive Power used from the RC Bank
o and Actual Power Factor
· Issuing of warnings and alarms. For example in the case of:
o Over Compensation

All of this information is available to the operator through standard interfaces from the
BMI Energy Library:
· Graphical Elements (see §6.3.1)
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 53
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

· Faceplate (see extended Faceplate §6.3.2)


· Multi-Trends (see extended Faceplate §6.3.2.2)

6.1.2 Function description


ControllerType 0: The PFCC monitors the reactive power and switches RC banks CB on
and off to reach the target cos phi
Controller Type 1: Similar to Type 0 but allow binary switching, that is, switch on higher
priority RC Banks even if this will lead to short time overcompensation
Controller Type 2: The PFCC monitors the reactive power and switches RC banks CB on
and off according predefined thresholds for the total reactive Power

6.1.2.1 Grid change trip


When ever the InFeed CB or coupling CB changes its position all RC Bank CB’s will trip.
Important: This has to be controlled by the IO.In.PFC_Enable parameter see
application examples §6.4.

6.1.2.2 Stepping sequence


The electrically possible stepping sequence (previous CB) is maintained by the
CB_PFC_Q#_PD parameters in the control module. Usually filters with a lower harmonic
order must be closed before filters with a higher order.
Important: Define the CB_PFC_Q#_PD according to the information from engineer
that did the layout of the compensation.

6.1.2.3 Step Up
Controller Type 0: Whenever the measured reactive power is higher than the nominal
compensation of the next switchable RC bank minus the hysteresis up value for a duration
longer than the step up time, then the next CB will close
Controller Type 1: Similar to Type 0 but the already compensated reactive power is added
to the measured reactive power. This allows for finer control using Steps with different
compensation values if short-time over-compensation is allowed.
Controller Type 2: Whenever the measured reactive power is higher than the defined
threshold value for a duration longer than the step up time, then the next CB will close

6.1.2.4 Step Down


Controller Type 0: Whenever the measured reactive power is lower than the hysteresis
down value for a duration longer than the step down time, then the next CB will open
Controller Type 1: Similar to Type 0 but after switching on a RC Bank (step up action), the
StepDownOvercompensationTime is applied for StepDownOvercompensationTime to
force faster step down
Controller Type 2: Whenever the measured reactive power is lower than the defined
threshold value for a duration longer than the step down time, then the next CB will open

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 54
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.1.2.5 Over compensation step down


As long as the measured reactive power is lower then the triggering value for
overcompensation CB’s will be opened in sequence with the step down over
compensation time
Remark: This function is not active for Controller Type 2.

6.1.2.6 Over compensation trip


In case overcompensation is present for a time longer then the alarm delay time defined in
the over compensation DIS all CB’s will trip
Remark: This function is not active for Controller Type 2.

6.1.2.7 Input value filter


In order to filter load peaks the low pass filter on the Power and Reactive Power AIS can
be set according to the application needs. The PFC uses the filtered value for its
calculations.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 55
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.2 CONTROL

6.2.1 Parameter description


No Name Data Type Initial Description
Value
1 Name string[20] EDIT: Name of the Module
2 Description string[40] EDIT: Description of the Module
3 IO PFCCtrlData IN(OUT): PFC Ctrl Data Type
4 Class dint 1 EDIT: AE Class 1 ... 9999 (Section)
AlarmTr dint 3 INIT: Alarm Treatment: -1 no AE; 0 = Event ; 1,2,3 =
5 ALPrio# (1=lowest)
WarnTr dint 2 INIT: Warning Treatment: -1 no AE; 0 = Event ; 1,2,3 =
6 ALPrio# (1=lowest)
EnMan bool True IN: True : enable Manual Mode : Operator must start PFC
7 MOdule even after PFC_Enable = true
EnAuto bool False IN: True : enables automatic Mode : PFC Module started
8 automatically when PFC_Enable = true
9 P_Total_Value real 0.0 IN: actual active Power Value [MW] on the BusBar
Q_Total_Value real 0.0 IN: actual reactive Power Value [MVar] on the BusBar, has
to have the ability to become negative in case of
10 overcompensation
EnCosPhi_Total_Value bool False IN: True enables the reading of CosPhi_Total_Value
11 Parameter otherwise calculated from P and Q
CosPhi_Total_Value real 0.0 IN: actual CosPhi Value on the BusBar, has to have the
12 ability to become negative in case of overcompensation
EnCompAtPrimarySide bool False IN: set to true in case P and Q only available at 2nd side
and comp. is required for Primary Side, below 3 parameters
13 are required
S_Nominal_HV_Trafo real 1.0 IN: Nominal Rated Power [MVA] of infeed HV Trafo to be
compensated, required when P / Q from 2nd side and
14 comp. required for primary side
Uk_HV_Trafo real 0 IN (0..100%): Nominal ShortCircuit Impendance of HV
Trafo, required when P / Q from 2nd side and comp.
15 required for primary side
Nb_of_HV_Trafo int 1 IN: Number of HV Trafo feeding the same MV BusBar in
parallel, required when P / Q from 2nd side and comp.
16 required for primary side
17 ControllerType dint 0 IN: 0 Standard, 1 Binary Switching, 2 Individual Thresholds
CB_PFC_Q1 CircuitBreaker IN(OUT): Connection to CB of the 1.Lowest Harmonic RC
18 Data Bank to be controlled by the PFC (i.e F3)
CB_PFC_Q1_PD bool True IN: CB Position of Lower Harmonic RC Bank required to
19 switch on Q1. Always true.
20 PFC_Q1_MVar real IN: Reactive Power of the 1.Harmonic RC Bank
CB_PFC_Q2 CircuitBreaker IN(OUT): Connection to CB of the 2.Lowest Harmonic RC
21 Data Bank to be controlled by the PFC (i.e F5)
CB_PFC_Q2_PD bool False IN: CB Position of Lower Harmonic RC Bank required to
22 switch on Q2. Typically Qxx.Out.PosCBCls
23 PFC_Q2_MVar real IN: Reactive Power of the 2.Harmonic RC Bank
CB_PFC_Q3 CircuitBreaker Default IN(OUT): Connection to CB of the 3.Lowest Harmonic RC
24 Data Bank to be controlled by the PFC (i.e F7)
CB_PFC_Q3_PD bool False IN: CB Position of Lower Harmonic RC Bank required to
25 switch on Q3. Typically Qxx.Out.PosCBCls
26 PFC_Q3_MVar real 2 IN: Reactive Power of the 3.Harmonic RC Bank
CB_PFC_Q4 CircuitBreaker Default IN(OUT): Connection to CB of the 4.Lowest Harmonic RC
27 Data Bank to be controlled by the PFC (i.e F9)
CB_PFC_Q4_PD bool False IN: CB Position of Lower Harmonic RC Bank required to
28 switch on Q4. Typically Qxx.Out.PosCBCls
29 PFC_Q4_MVar real 2 Reactive Power of the 4.Harmonic RC Bank
CB_PFC_Q5 CircuitBreaker Default IN(OUT): Connection to CB of the 5.Lowest Harmonic RC
30 Data Bank to be controlled by the PFC (i.e F11)
CB_PFC_Q5_PD bool False IN: CB Position of Lower Harmonic RC Bank required to
31 switch on Q5. Typically Qxx.Out.PosCBCls
32 PFC_Q5_MVar real 2 IN: Reactive Power of the 5.Harmonic RC Bank
CB_PFC_Q6 CircuitBreaker Default IN(OUT): Connection to CB of the 6.Lowest Harmonic RC
33 Data Bank to be controlled by the PFC (i.e F13)
CB_PFC_Q6_PD bool False IN: CB Position of Lower Harmonic RC Bank required to
34 switch on Q6. Typically Qxx.Out.PosCBCls
35 PFC_Q6_MVar real 2 IN: Reactive Power of the 6.Harmonic RC Bank

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 56
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

No Name Data Type Initial Description


Value
CB_PFC_Q7 CircuitBreaker Default IN(OUT): Connection to CB of the 7.Lowest Harmonic RC
36 Data Bank to be controlled by the PFC (i.e F15)
CB_PFC_Q7_PD bool False IN: CB Position of Lower Harmonic RC Bank required to
37 switch on Q7. Typically Qxx.Out.PosCBCls
38 PFC_Q7_MVar real 2 IN: Reactive Power of the 7.Harmonic RC Bank
CB_PFC_Q8 CircuitBreaker Default IN(OUT): Connection to CB of the 8.Lowest Harmonic RC
39 Data Bank to be controlled by the PFC (i.e F17)
CB_PFC_Q8_PD bool False IN: CB Position of Lower Harmonic RC Bank required to
40 switch on Q8. Typically Qxx.Out.PosCBCls
41 PFC_Q8_MVar real 2 IN: Reactive Power of the 8.Harmonic RC Bank
Q_OverCompensated_ string[20] EDIT: Tag name of the DIC (. - ok, no blanks allowed!)
42 Name
Q_OverCompensated_ string[35] 'PFC INIT: Alarm Message description (e.g. Pull Rope Switch,
AETxt Tripped: Level High) for NLS support use ||AE_NLS_ preffix and no
Q<Q space in the text
Triggering
43 Value'
44 PFC_Enable_Name string[20] EDIT: Tag name of the DIC (. - ok, no blanks allowed!)
PFC_Enable_AETxt string[35] 'PFC INIT: Alarm Message description (e.g. Pull Rope Switch,
Tripped Level High) for NLS support use ||AE_NLS_ preffix and no
due to lost space in the text
45 of enable'
46 P_Total_Name string[20] EDIT: Tag name of the AIC (. - ok, no blanks allowed!)
P_Total_Description string[40] 'Actual IN: Description text of the AIC
Power on
this
47 Busbar'
48 P_Total_min real 0.0 INIT: Scaling Parameter Range.
49 P_Total_Max real 100.0 INIT: Scaling Parameter Range Max.
50 P_Total_Unit string[5] 'MW' INIT: Scaling Parameter Unit.
51 P_Total_Fraction dint 2 INIT: Fraction (Number of Decimals).
52 Q_Total_Name string[20] INIT: Tag name of the AIC (. - ok, no blanks allowed!)
Q_Total_Description string[40] 'Actual IN: Description text of the AIC
Reactive
Power on
this
53 Busbar'
54 Q_Total_min real -16.0 INIT: Scaling Parameter Range.
55 Q_Total_Max real 16.0 INIT: Scaling Parameter Range Max.
56 Q_Total_Unit string[5] 'MVar' INIT: Scaling Parameter Unit.
57 Q_Total_Fraction dint 2 INIT: Fraction (Number of Decimals).
58 CosPhi_Total_Name string[20] INIT: Tag name of the AIC (. - ok, no blanks allowed!)
CosPhi_Total_Description string[40] 'Actual IN: Description text of the AIC
CosPhi on
this
59 Busbar'
60 CosPhi_Total_min real -1 INIT: Scaling Parameter Range.
61 CosPhi_Total_Max real 1 INIT: Scaling Parameter Range Max.
62 CosPhi_Total_Unit string[5] '' INIT: Scaling Parameter Unit.
63 CosPhi_Total_Fraction dint 2 INIT: Fraction (Number of Decimals).
64 PFC_Actual_Q_Name string[20] INIT: Tag name of the AIC (. - ok, no blanks allowed!)
PFC_Actual_Q_Description string[40] 'Actual IN: Description text of the AIC
Reactive
Power
65 from PFC'

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 57
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.2.2 Data Type description


Together with PFCC Control Module Type a Structured Data Type PFCCtrlData is
available.
Remarks : as shown below it is a combined Type containing 2 DIS and 4 AIS
PFCCtrlData; components
Name Data Type Attribu Initial Description
tes Value
In PFCCtrl retain IN variables to the PFCCtrl Control Module to be
1 Input written in the Application
Out PFCCtrl retain OUT variables from the PFCCtrl Control Module to
2 Output be read in the Application
Q_OverComp DISData retain Indication for Q_OverCompensated
3 ensated
4 PFC_Enable DISData retain Indication for PFC_Enable
5 P_Total AISData retain Indication for P_Total
6 Q_Total AISData retain Indication for Q_Total
7 CosPhi_Total AISData retain Indication for CosPhi_Total
PFC_Actual_Q AISData retain Indication for PFC Actual used Q
8 nosort

PFCCtrlInput; components
Name Data Attribu Initial Description
Type tes Value
1 PFC_Enable bool retain false In true : enabling of PFC_Module
SetAuto bool retain false In True : start automatically the PFC Module when
2 PFC_Enable = true
SetMan bool retain true In True : Operator must start PFC MOdule after
3 PFC_Enable = true
4 AlarmAck bool retain false In True : Acknowledge Alarms of DIC's and AIC's

PFCCtrlOutput; components
Name Data Attribu Initial Description
Type tes Value
CBs_RFS bool retain OUT: Summarized CB's not Tripped Status and
1 nosort no CB's in Local
CBsReadyOpn bool retain OUT: Summarized CB's ReadyOpn Status
2 nosort
CBsReadyCls bool retain OUT: Summarized CB's ReadyCls Status
3 nosort
Started bool retain OUT: PFC Module is acting
4 nosort
Man bool coldre OUT: Manual Mode : Operator must start PFC
tain MOdule even after PFC_Enable = true
5 nosort
Auto bool coldre OUT: Automatic Mode : PFC Module started
tain automatically when PFC_Enable = true
6 nosort
Q_Primary real retain OUT: Show to Reactive Power on the Primary
7 nosort Side

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 58
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.3 OPERATION

6.3.1 Graphic Element


Graphical Element is available for PFCC objects. It permits direct access to relevant
information from Operator Display:
Graphic
Description Example
Element
Displays object
PFC
name and status.

The PFCC Object is moreover extended by graphical Elements of


· Circuit Breakers with dynamic status indication
· 4*AIS for direct access to Trending / Eventing / Alarming
· 2*DIS for direct access to Eventing / Alarming

6.3.1.1 Presentation
The graphic element PFC displays the object name and object status.

6.3.1.2 Status
Object status Symbol color

PFCC OFF Gray

PFCC Green Arrow oriented to the Top


Stepping Up
PFCC Green Arrow oriented to the Bottom
Stepping Down

PFCC ON Green filled

PFCC ON,
Green filled with thick orange frame
with warning

PFCC stopped
Gray with thick red frame
with failure

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 59
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.3.1.3 Properties
Name DataType Default Dynamicity Description
Value
SubscriptionRate Integer 0 Dynamic The update rate for all aspect object
properties subscribed for
SymbolSize Integer 22 Dynamic Symbol size in pixel: 18 = Little, 20 =
Small, 22 = Standard, 24 = Large, 26 =
XXL
Text String "Description" Dynamic PFCC Description
TextBold Boolean True Dynamic Text style is bold
TextSize Integer 10 Dynamic Text size in pixel: 8: Little, 9 = Small, 10
= Standard, 12 = Large, 14 = XXL
TextSource Integer 2 Dynamic 0 = None, 1 = Manual, 2 = OPC, 3 =
NLS
For common settings please refer to [1] Minerals Library Overview (3BHS 161555).

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 60
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.3.2 Faceplate
The following aspect view buttons are available on Load Faceplates
Icon Aspect View
Alarm List

Event List

BMI Triple Trend Display (see chapter trending)

Operators Note

Faceplate Documentation, reference to this document

Tagname
&
Description

PFCC Status &


Mode

Dynamic Status indication of


all CB’s connected to the RC
Bank and controlled by PFCC
Direct Link to the CB’s
Faceplate

Display of PFCC
Measurement Direct Link to Actual
PFCC Measurement
Faceplate

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 61
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.3.2.1 Extended View

Actual Status Description


Step Up in xx s Time till the next RC bank in sequence will be switched on when the
reactive power is above the trigger value.
Sequence is defined in the Control Module by the Previous Drive
parameter to prevent in any case a wrong switching of CB’s
Step Down in xx s Time till the RC bank in sequence will switch off when the actual
reactive power is below the hysteresis down trigger value

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 62
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 63
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.3.2.1.1 RC Bank

Indication of the nominal Reactive Power Available in each RC Bank

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 64
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.3.2.1.2 Parameters

Actual Status Description


Step Up Time Time the reactive power needs to be over the hysteresis limit in order
to close the CB
Step Down Time Time the reactive power needs to be below the hysteresis limit in
order to open the CB
Step Down Time Over Time for step down actions in case of over compensation warning
Comp.
Reclosing Time Time during which the re-closing of a RC Bank is prohibited
This is a safety feature for the Self-unloading of the RC Bank
-> should be programmed in the CB relay in addition
(for Local Operation) !
Hysteresis Up For a step up action the reactive power - next RC bank value must be
bigger then the hysteresis
Example :
- Next available RC Bank 2.0 MVar
- Q on the Busbar : 2.5 MVar
- Hysteresis Up : 1.00MVar
-> PFCC will only close next available RC Bank when Q on the Busbar
raise until 2.0+1.0 = 3.0MVar and stay above for Step Up time
Hysteresis Down For a step down action the reactive power must be lower then the
hysteresis
Example :
- Q on the Busbar : 1.1 MVar
- Q Triggering Value for Over Copmensation : 0.2 MVar
- Hysteresis Down : 1.00MVar
-> PFCC will only open the last switched on RC when Q on the Busbar
falls below 1.00MVar and stay below for Step Down time
Q triggering Value for Triggering value for overcompensation warning and alarm.
Over Compensation The time delay for warning and alarm can be set on the over
compensation DIS.
Warning will activate over compensation step down, and alarm will trip
all the CB’s

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 65
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

For Controller Type 2, the tab “Parameters” looks slightly different:

Actual Status Description


Step Threshold Up Threshold value for stepping up
Step Threshold Down Threshold value for stepping down

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 66
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.3.2.2 Trending

The Trending is accessible from the Faceplate, giving a historical overview of the load
main values:
· Actual Active Power on this busbar (Green)
· Actual Reactive Power on this busbar (Pink)
· Actual CosPhi on this busbar (light Blue)
· Actual Reactive Power from PFC (dark Blue)

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 67
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.3.3 Faceplate Control Permission

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 68
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.4 Application Example

This example shows the correct configuration of the PFCC Control for this Grid.
4 PFCC control Module are needed. One for each possible configuration :
· E21_1S1 : InFeed Trafo E21_1T1 with coupler open
· E21_1S2 : InFeed Trafo E21_1T2 with coupler open
· E21_1S12 : One of the InFeed Trafo E21_1T1 / E21_1T2 with coupler closed
· E21_1S21 : Two InFeed Trafo in parallel with coupler closed
Structure in CBM

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 69
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.4.1 PFCC Enable Configuration

Indeed, each PFCC Control Module must have exclusive configuration, only one PFCC Module can be active at a time !

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 70
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.4.2 Single incoming feeder, bus coupler open (PFC E21_1S1)

Blue: previous drive definition, all CB’s are connected to the same BusBar ( --- )

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 71
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.4.3 Dual incoming feeder, bus coupler closed (PFC E21_1S21)

Red: parameters required for parallel operation of the incoming feeders with transformers ( --- )
Blue: previous drive definition, all CB’s are connected to the same BusBar ( --- )

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 72
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

7. DOCUMENT REVISION HISTORY


Rev. Page (P) Description Date/Initials
ind. Chapt. (C)
A Initial Version for Minerals Library Release 5.0/0 16.01.2006/NB
B Document Number Corrected 01.07.2008/KN
C Chapter 2 Corrected / Extended Status Added 03.09.2008/KN
D Added Project Constants 08.04.2009/LK
clean-up for 5.0/2 Release 24.04.2009/LK
E Updated for 5.1/1 Release 27.10.2009/CT
F Updated for Process Graphics 2, 5.1/1 Release 10.11.2009/MS
G Updated for 5.1/2 Release 10.02.2010/MS
H Updated with PFCCtrl 09.06.2010/NB
I Updated for 5.1/3 Release 25.10.2010/CT
J Chapt. 6 Updated for PFC Controller Type = 2 03.03.2011/JR
K Update for 5.1/4 Release 17.04.2013/LK
L Update CB Events and POC for 5.1/4a Release 13.09.2013/LK
M Update for 5.1/5 Release 13.08.2014/LK
N Correct terminology Mode <> POC 06.05.2015/LK

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Power Distribution Monitoring Objects
Objects
800xA Minerals Library version 5.1/5b
Document number Lang. Rev. ind. Pages 73
ABB Switzerland Ltd 3BHS 253000 en N No. of p. 73