LOAD CALCULATION
PANEL : MDB-1
SYSTEM : 3 Ph. 4W , 380/220 VAC
LOCATION : BUILDING T22-MDB
###
Load Connected Utilization Circuit Breaker
Feeder
ID No. Description Unit Phase Voltage Ib Ir Starter In IC ≥
No. kW % kW Type Pole AT AF
( ø) (V) (A) (A) (A) (kA)
F1 DB-6 BUILDING T22 DISTRIBUTION BOARD - 6 / SPARE 1 220.0 3 400 396.9 80% 176.0 317.5 MCCB 3 496.2 600 630 36
F2 DB-7 BUILDING T21 DISTRIBUTION BOARD - 7 / SPARE 1 220.0 3 400 396.9 80% 176.0 317.5 MCCB 3 496.2 600 630 36
F3 DB-1 BUILDING T24-RENO DISTRIBUTION BOARD - 1 1 220.0 3 400 396.9 80% 176.0 317.5 MCCB 3 496.2 600 630 36
F4 DB-2 BUILDING T24-RENO DISTRIBUTION BOARD - 2 1 120.0 3 400 216.5 80% 96.0 173.2 MCCB 3 270.6 300 400 36
F5 DB-5 BUILDING T24-RENO DISTRIBUTION BOARD - 5 1 120.0 3 400 216.5 80% 96.0 173.2 MCCB 3 270.6 300 400 36
F6 DB-3 BUILDING T24-RENO DISTRIBUTION BOARD - 3 1 100.0 3 400 180.4 80% 80.0 144.3 MCCB 3 225.5 250 250 36
F7 DB-4 BUILDING T24-RENO DISTRIBUTION BOARD - 4 1 100.0 3 400 180.4 80% 80.0 144.3 MCCB 3 225.5 250 250 36
F8 LCP-1 BUILDING T24-RENO LOAD CENTER PANEL-1 1 25.0 3 400 45.1 80% 20.0 36.1 MCCB 3 56.4 60 100 36
F9 LCP-2 BUILDING T24-RENO LOAD CENTER PANEL-2 1 25.0 3 400 45.1 80% 20.0 36.1 MCCB 3 56.4 60 100 36
F10 LCP-3 BUILDING T24-RENO LOAD CENTER PANEL-3 1 25.0 3 400 45.1 80% 20.0 36.1 MCCB 3 56.4 60 100 36
F11 LCP-4 BUILDING T24-RENO LOAD CENTER PANEL-4 1 25.0 3 400 45.1 80% 20.0 36.1 MCCB 3 56.4 60 100 36
F12 LCP-5 BUILDING T24-RENO LOAD CENTER PANEL-5 1 40.0 3 400 72.2 80% 32.0 57.7 MCCB 3 90.2 100 100 36
F13 LCP-6 BUILDING T24-RENO LOAD CENTER PANEL-6 1 40.0 3 400 72.2 80% 32.0 57.7 MCCB 3 90.2 100 100 36
F14 SPACE 1 - 3 400 - - - - MCCB 3 - - 100 36
F15 SPACE 1 - 3 400 - - - - - MCCB 3 - - 100 36
F16 1-CAP-1 Crushing Room Capacitor Bank , No. 1 1 - 3 400 - - - - - ACB 3 - 1,000.0 1,000 36
###
Main Total Load 1,280.0 3 400 2,309.4 80% 1,024.0 1,847.5 - ACB 3 2,309.4 2,500 2,500 50
TRANSFORMER for AVERAGE LOAD 123% 1,574.4 kVA 1000x100
SELECT TR = 1,600 kVA
TRANSFORMER for FULL LOAD 80% 1,280.0 kVA
SELECT TR = 1,600 kVA ITR = 2,309.4 A
CAPACITOR BANK = 30% TR.
= 480 kVAR SELECT 40 kVAR 12 Sets
= 480 kVAR ###
@Fuse = 1.5x[@kVAR/(1.732x0.4)]
= 86.61 A Connect 100 A
@Idisc. ≥ 1.35x[@kVAR/(1.732x0.4)]
77.94 A
Protection = Setsx1.5x[@kVAR/(1.732x0.4)]
= 1,039.26 A
ACB 1,040 AT Connect 1000 AT 1000 AF
CALCULATION LOW VOLT SIDE
Ir (LV)= (kVAx1000)/(1.732x400)
= 2,309.5 A
Icon.= 1.25xIr
= 2,886.8 A
CB MAIN≤ 2,886.8 A Connect 2500 AT 2500 AF
CALCULATION HIGH VOLT SIDE
Ir (HV)= (kVA)/(1.732x22)
= 41.99 A
Icon. ≥ 1.25xIr (HV) 2xIr (HV)
≥ 52.49 A 83.98 A Connect 100 A / Fuse Link 1000 A / W