The Advanced Intelligent NAC Module is an addressable module used with Axis AX Series fire alarm panels. It provides an individually programmable notification appliance circuit to switch external power sources to groups of notification appliances. Each module supervises wiring for faults and reports back to the panel. It can be set to a group address to activate multiple modules from a single command and mounts in standard electrical boxes.

Uploaded by

Felipe Feitosa
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
33 views

Inteligent NAC Module

The Advanced Intelligent NAC Module is an addressable module used with Axis AX Series fire alarm panels. It provides an individually programmable notification appliance circuit to switch external power sources to groups of notification appliances. Each module supervises wiring for faults and reports back to the panel. It can be set to a group address to activate multiple modules from a single command and mounts in standard electrical boxes.

Uploaded by

Felipe Feitosa
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Intelligent NAC Module

Advanced Intelligent NAC Module is an addressable module for


use with the Axis AX Series Intelligent Fire Alarm Control Panel’s
SLC Loops. Each module incorporates an independent,
individually programmable, notification appliance circuit (NAC),
providing cost-effective solutions in areas requiring multiple
notification appliance circuits. Each NAC module allows switching
of an external power supply, such as a 24 VDC regulated power
source or audio amplifier to a group of notification appliances.

The notification appliance circuit can be wired either Class A or B.


Each module also supervises the wiring for opens, shorts and
grounds and reports this status back to the intelligent fire alarm
control panel. Typical input power to the NAC module would be
from the main FACP, a power supply booster or an amplifier.

To increase the already rapid response activation, each module


can be set to a group address, allowing all NAC modules assigned
to a common group address to be activate from a single command
poll from the intelligent fire alarm control panel.

An eight position programming DIP switch is provided on each


NAC module for NAC circuit addressing and wiring classification
definition. An additional four position programming DIP switch is Features
provided for group addressing. The NAC module mounts to the
front of a standard 4” square or 2-gang electrical outlet box. Class A or B Wiring
Displayed on the front of each module is a single red status LED Horn/Strobe or Speaker Control
that flashes when the module is polled.
Flexible Programmability
Compatible with the Axis AX Series Dynamix I/O relationship Durable Construction
programming, the NAC module can be individually assigned to
activate from any input zone or address. In addition, the NAC Cost-Effective & Trouble-Free Installation
module can be programmed with various output relationships, 25/70 VRMS Speaker Capability
timing functions, gated functions, etc. to perform project specific
control operations.
Listings and Approvals
ETL ANSI/UL 864 Listed: 101564744NYM-001
UL file: UOXX.S7003 / ML file: S24460
CSFM Approved: 7300-1713:108
NYC MEA: 294-95-E

[903-004] 1.5 Page 1 of 2


us.advancedco.com

Wiring Diagram

Specification
Voltage 17-28 VDC, with Communication Pulses 5-9 VDC
Operating Current 1 mA (Quiescent) 1 mA (Alarm) 6 mA (With LED's)
Line Impedance 50 Ω
Wiring Classification Class A or B
End-of-Line Resistor 47 KΩ, 0.5 Watt (Class “B” Only)
Circuit Voltage Input 24 VDC or 25/70 VRMS
Max NAC Circuit Output 24VDC @ 1 Amp (Use Regulated DC Listed Supply)
Max Speaker Circuit Output 24VDC, 25 /70.7VRMS @ 500mA
Wiring Terminals Screw In-Out Terminals
Mounting 4” Square or 2-Gang Electrical Outlet Box
Dimensions (Diameter & Height) 4 1/2”W x 4 1/2”H x 1”D
Weight 2.8 oz
Operating Temperature 32 o -120 o F (0o -49 o C)
Humidity 10 - 93% (Non-Condensing)

Order Codes and Options


55000-825ADV Notification Appliance Circuit Module

Check if this document is up to date | Give us feedback


Advanced, 100 South Street, Hopkinton, MA. 01748 T: +508 435 9995 E: [email protected] W: us.advancedco.com
As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice.

[903-004] 1.5 Page 2 of 2