The document provides technical specifications for a 500kV fault current limiter. It lists 27 required specifications including a rated voltage of 500kV, rated current of 3150A, rated opening time of less than 1.5ms, and environmental resistance level of Ej. All 27 proposed specifications from the manufacturer NR Electric meet or exceed the required specifications, including a rated opening time of less than 1.5ms. The document guarantees the fault current limiter will perform as specified.

Uploaded by

ICHAL ASMIR
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
122 views7 pages

TPG A 2 FAULT CURRENT LIMITER 500 KV - NARI

The document provides technical specifications for a 500kV fault current limiter. It lists 27 required specifications including a rated voltage of 500kV, rated current of 3150A, rated opening time of less than 1.5ms, and environmental resistance level of Ej. All 27 proposed specifications from the manufacturer NR Electric meet or exceed the required specifications, including a rated opening time of less than 1.5ms. The document guarantees the fault current limiter will perform as specified.

Uploaded by

ICHAL ASMIR
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

TECHNICAL PARTICULAR AND GUARANTEE

TPG.A^-B.FCL.500 kV : FAULT CURRENT LIMITER 500 kV DYNAMIC TYPE FAST SWITCH

DESCRIPTION UNIT REQUIRED PROPOSED & GUARANTEED


NO

A GENERAL

(to be mentioned) NR Electric Co. Ltd.


1 Manufacturer

Dynamic Type Fast Switch Dynamic Type Fast Switch


2 Technology Outdoor, three-phase, floor-to-ceiling tank Outdoor, three-phase, floor-to-ceiling tank
type type

3 Rating Value
kV 500 500
{a) Rated voltage
A >3000 3150
(b) Rated current
Hz 50 50
(c) Rated frequency
a 15 15
(d) Rated current-limiting impedance
20 20
(e) Maximum current-limiting onset time ms

4 Rated insulation level

kV 1000 1000
(a) BIL (kV, peak Turn to turn insulation),
kV 1550 1550
(b) BIL (kV, peak Insulation to ground).

■■■

/●. V ,

g:S.-'plGNATURE MANUFACJURER'S signature


h Ud

( Page 1 of 7
( )
TECHNICAL PARTICULAR AND GUARANTEE

TPG.A^-B.FCL.500 kV ; FAULT CURRENT LIMITER SOO kV DYNAMIC TYPE FAST SWITCH

NO DESCRIPTION UNIT REQUIRED PROPOSED & GUARANTEED

B FAST SWITCH

5
Rated continuous operating cunent (maximum ambient A a3000 3150
temperature)

kV 500 500
6 Rated break voltage
<1.5 <1.5
7 Rated opening time ms

8 <20 <20
Rated closing time ms

9 Rated short-circuit current kA 63 63

10 mm/kV 25 25
Creepage ratio distance
450 450
11 The power frequency tolerant voltage of the fracture /1min kV

kV 1000 1000
12 The fault lightning shock withstands voltage of the fracture
kV 680 680
13 The ground power frequency tolerant voltage/1 min
kV 1550 1550
14 Withstands voltage of lightning strikes to ground
4 4
15 Number of fractures Set/Per phase

K <65 <65
16 Temperature rises
<100 <100
17 Loop contact resistance (between entry and exit lines) pO

BIDDER'S SI JURE
MANUFACJWR’S'SIGNATURE
r,
iV

( rf
) ( ) Page 2 of 7
TECHNICAL PARTICULAR AND GUARANTEE

TPG.A.2-B.FCL.500 kV : FAULT CURRENT LIMITER 500 kV DYNAMIC TYPE FAST SWITCH

NO DESCRIPTION UNIT REQUIRED PROPOSED & GUARANTEED

C CURRENT LIMITING REACTOR

18 Reactance value mH 47.75 47.75

“C (to be mentioned) 0.13300


19 DC resistance value (O, 75°C).

20 Wiring form K Paralleled on both sides of the fast switch Paralleled on both sides of the fast switch

minute(s) 20kA/2s 20kA/2s


21 Thermally stable current and duration
22 kA 50 50
Dynamically stabilizes current peaks

23 Inter-tum lightning shock voltage kV 1000 1065(ATTHE SEA LEVEL)

24 Temperature rise limit (thermally stable current), (to be mentioned)

(a) The average temperature rise of the windings K 70 70(550A@50Hz)

(b) The hottest temperature rises (relative to ambient K 80 80(550A@50Hz)


temperature)
K 10 <10
(c) Temperature difference between windings
25 Heat resistance rating of the insulation material
H-class H-class
(a) Heat resistance rating of inter-turn insulation
F-class F-class
(b) Overall insulation heat resistance rating

BIDDER'S SIGNATURE
MANUFA^J^f^RS'SlGNATURE

( ) ( ) Page 3 of 7
TECHNICAL PARTICULAR AND GUARANTEE

TPG.A^-B.FCL.500 kV : FAULT CURRENT LIMITER 500 kV DYNAMIC TYPE FAST SWITCH

DESCRIPTION UNIT REQUIRED PROPOSED & GUARANTEED


NO

26 Environmental resistance Ej level Ej level

27 Weather resistance C level 2 C level 2

(to be mentioned) 180°


28 Angle between the entry and exit terminals
29 Pillar insulators are mainly parameter

(a) Rated lightning shock withstand voltage (kV, kV 1550 1650(AT THE SEA LEVEL)
peak,Insulation to ground),

(b) Rated AC withstand voltage (dryMet) (kV, rms,Insulation to kV rms 680 725(ATTHESEA LEVEL)
ground),
(to be mentioned) 18130
(c) The creepage distance of the insulator to ground mm

N Manufacturer provided 16000


(d) Insulator flexural strength
30 The terminal blocks allow force

N 3500 3500
(a) Horizontal longitudinal
N 2500 2500
(b) Vertical orientation
N 2500 2500
(c) Horizontal landscape
2.5 2.5
(d) Static safety factor (three forces acting simultaneously).
PLATE/AL
31 Terminal shape/material (to be mentioned)

BIDDER’S SIGNATURE MANUFA R'S'SIGNATURE

( ) Page 4 of 7
( )
TECHNICAL PARTICULAR AND GUARANTEE

TPG.A.2-B.FCL.500 kV ; FAULT CURRENT LIMITER 500 kV DYNAMIC TYPE FAST SWITCH

NO DESCRIPTION UNIT REQUIRED PROPOSED & GUARANTEED

32 Reactor size

(to be mentioned) 2.15


(a) Outer diameter m

(to be mentioned) 1.33


(b) Inner diameter m

(to be mentioned) COiL:3.224 TOTAL9.051


(c) Height m

(to be mentioned) 13
(d) Number of packages pcs

33 Reactor weight kg (to be mentioned) COiL:5640 TOTAL;9210

34 Winding protection requirements

The windings are increased with FRP The windings are increased with FRP
protective false layer, and the outer protective false layer, and the outer
surface is first sandblasted, and then the surface is first sandblasted, and then the
(a) Winding outer surface protective layer treatment method anti-ultraviolet primer and topcoat are anti-ultraviolet primer and topcoat are
sprayed, and the outermost surface is sprayed, and the outermost surface is
sprayed with anti-fouling coating. sprayed with anti-fouling coating.

(b) Air duct and inner layer protection treatment method


Continuous wire winding with no welding Continuous wire winding with no welding
(c) Leader section processing method head in the middle head in the middle

(d) Rain protection measures Install rain caps and rain grilles Install rain caps and rain grilles

MANUFA F{ER'S'6t_QNATURE

( ) ( ) Page 5 of 7
TECHNICAL PARTICULAR AND GUARANTEE

TPGJVJ-B.FCL.500 kV : FAULT CURRENT LIMITER 500 kV DYNAMIC TYPE FAST SWITCH

UNIT REQUIRED PROPOSED & GUARANTEED


NO DESCRIPTION

0-5 0-5
35 Inductance value deviation %

Altitude correction withstand test voltage (power 1500m altitude modifier 1500m altitude modifier
36
ftequency/lightning)
The deviation of each phase reactance The deviation of each phase reactance
from the three-phase average is not from the three-phase average is not
37 Three-phase inductance deviation
greater than ±2%. greater than ±2%.

38 Installation arrangement Single phase outdoor installation Single phase outdoor installation

D CONTROL AND PROTECTION DEVICE


VDC 110 110
39 Power supply
S3 £3
40 Fastest short-circuit current detection operating time ms

Hz 50 50
41 Rated frequency
Static: S60 Static : <60
W
42 Device DC power consumption Operating : S70 Operating: S70

>10 >10
K
43 Sampling frequency
110 110
VDC
44 Binary input circuit voltage
V IRIG-B IRIG-B
45 Time synchronization interface

'S ^SIGNATURE MANUFA' R'^'SIGNATURE

( ) Page 6 of 7
)
TECHNICAL PARTICULAR AND GUARANTEE

TPG.A^-B.FCL.500 kV : FAULT CURRENT LIMITER 500 kV DYNAMIC TYPE FAST SWITCH

NO DESCRIPTION UNIT REQUIRED PROPOSED & GUARANTEED

46 Test Certificates : To be submitted

KETOP/XIHARI
- Issued by

- Reference lEC 60255/IEC62271-100

2019.10.17/2021.05.25
- Date of test report

To be submitted See Attachments


47 Catalogue, drawings, manual and other references

BIDDER’S SIGNATURE
MANUFA©|^f^|R'S'$|GNATURE
%
Jt^
-) ( ) Page 7 of 7