BA KR C4 Smallsize-2 en
BA KR C4 Smallsize-2 en
KR C4 smallsize-2
Operating Instructions
KR C4 small-
size-2
Issued: 26.04.2018
Version: BA KR C4 smallsize-2 V7
KR C4 smallsize-2
© Copyright 2018
KUKA Deutschland GmbH
Zugspitzstraße 140
D-86165 Augsburg
Germany
This documentation or excerpts therefrom may not be reproduced or disclosed to third parties without
the express permission of KUKA Deutschland GmbH.
Other functions not described in this documentation may be operable in the controller. The user has
no claims to these functions, however, in the case of a replacement or service work.
We have checked the content of this documentation for conformity with the hardware and software
described. Nevertheless, discrepancies cannot be precluded, for which reason we are not able to
guarantee total conformity. The information in this documentation is checked on a regular basis, how-
ever, and necessary corrections will be incorporated in the subsequent edition.
Subject to technical alterations without an effect on the function.
KIM-PS5-DOC
Translation of the original documentation
Contents
1 Introduction .................................................................................................. 7
1.1 Representation of warnings and notes ...................................................................... 7
1.2 Terms used ................................................................................................................ 7
2 Purpose ........................................................................................................ 9
2.1 Target group .............................................................................................................. 9
2.2 Intended use .............................................................................................................. 9
5 Safety ............................................................................................................ 29
5.1 General ...................................................................................................................... 29
5.1.1 Liability .................................................................................................................. 29
5.1.2 Intended use of the industrial robot ...................................................................... 29
5.1.3 EC declaration of conformity and declaration of incorporation ............................. 30
5.1.4 Terms used ........................................................................................................... 30
5.2 Personnel ................................................................................................................... 32
5.3 Workspace, safety zone and danger zone ................................................................. 33
5.3.1 Determining stopping distances ............................................................................ 33
5.4 Triggers for stop reactions ......................................................................................... 34
5.5 Safety functions ......................................................................................................... 34
5.5.1 Overview of the safety functions ........................................................................... 34
5.5.2 Safety controller .................................................................................................... 35
6 Planning ........................................................................................................ 55
6.1 Electromagnetic compatibility (EMC) ......................................................................... 55
6.2 Installation conditions ................................................................................................ 55
6.3 Connection conditions ............................................................................................... 55
6.4 Power supply connection via X1 Harting connector .................................................. 56
6.5 Overview of interfaces ............................................................................................... 56
6.5.1 Optional interfaces ............................................................................................... 57
6.6 Standard interfaces ................................................................................................... 57
6.6.1 Motor connector X20 ............................................................................................ 57
6.6.2 Safety interface .................................................................................................... 58
6.6.3 Description of safety interface X11 ....................................................................... 58
6.6.3.1 X11 connector contact diagram ....................................................................... 59
6.6.3.2 X11 safety interface ......................................................................................... 59
6.6.3.3 X11 external enabling switch ........................................................................... 61
6.6.3.4 Wiring example for E-STOP circuit and safeguard .......................................... 62
6.6.3.5 Wiring examples for safe inputs and outputs .................................................. 63
7 Transportation ............................................................................................. 71
7.1 Transportation using lifting tackle .............................................................................. 71
7.2 Transportation by pallet truck ..................................................................................... 72
7.3 Transportation with the set of rollers .......................................................................... 72
9 Operation ...................................................................................................... 79
9.1 KUKA smartPAD teach pendant ................................................................................ 79
9.1.1 Front view ............................................................................................................. 79
9.1.2 Rear view .............................................................................................................. 81
10 Maintenance ................................................................................................. 83
10.1 Maintenance symbols ................................................................................................ 83
10.2 Checking CCU_SR relay outputs ............................................................................... 84
10.3 Cleaning the robot controller ...................................................................................... 85
11 Repair ........................................................................................................... 87
11.1 Repair and procurement of spare parts ..................................................................... 87
11.2 Exchanging the external fan ...................................................................................... 87
11.2.1 Removing the external fan .................................................................................... 88
11.2.2 Installing the external fan ...................................................................................... 89
11.2.3 Concluding work ................................................................................................... 90
11.3 Exchanging the drive unit ........................................................................................... 90
11.3.1 Removing the drive unit ........................................................................................ 92
11.3.2 Installing the drive unit .......................................................................................... 92
11.3.3 Concluding work ................................................................................................... 93
11.4 Exchanging control PC components .......................................................................... 93
11.4.1 Exchanging the control PC ................................................................................... 93
11.4.1.1 Removing the control PC ................................................................................. 94
11.4.1.2 Installing the control PC ................................................................................... 95
11.4.1.3 Concluding work .............................................................................................. 95
11.4.2 PC fan ................................................................................................................... 96
1 Introduction
t
Notices These notices serve to make your work easier or contain references to further
information.
Term Description
CIP Safety Common Industrial Protocol Safety
CIP Safety is an Ethernet/IP-based safety inter-
face for connecting a safety PLC to the robot
controller. (PLC = master, robot controller =
slave)
CCU_SR Cabinet Control Unit Small Robot
CIB_SR Cabinet Interface Board Small Robot
EDS Electronic Data Storage (memory card)
EMD Electronic Mastering Device
EMC Electromagnetic compatibility
KCB KUKA Controller Bus
KEB KUKA Extension Bus
KEI KUKA Extension Interface
Term Description
KLI KUKA Line Interface. Connection to higher-level
control infrastructure (PLC, archiving)
KOI KUKA Option Interface
KONI KUKA Option Network Interface
KPC Control PC
KPP_SR KUKA Power Pack Small Robot
KRL KUKA robot programming language (KUKA
Robot Language)
KSB KUKA System Bus. Internal KUKA bus for inter-
nal networking of the controllers with each other
KSI KUKA Service Interface
KSP_SR KUKA Servo Pack Small Robot
KSS KUKA System Software
Manipulator The robot arm and the associated electrical
installations
PMB Power Management Board
RDC Resolver Digital Converter
SATA connections Data bus for exchanging data between the pro-
cessor and the hard drive
(Extended) SIB (Extended) Safety Interface Board
USB Universal Serial Bus. Bus system for connecting
additional devices to a computer
EA External axis (linear unit, Posiflex)
2 Purpose
2
This documentation is aimed at users with the following knowledge and skills:
Advanced knowledge of electrical and electronic systems
Advanced knowledge of the robot controller
Advanced knowledge of the Windows operating system
Use The robot controller is intended solely for operating the following components:
KUKA industrial robots
KUKA linear units
KUKA positioners
An additional KR C4 smallsize drive box is required for operating external axes
(linear units, positioners).
Misuse Any use or application deviating from the intended use is deemed to be misuse
and is not allowed. This includes e.g.:
Use as a climbing aid
Operation outside the permissible operating parameters
Use in potentially explosive environments
Use in underground mining
3 Product description
3.1
t
Overview of the robot controller
1 Drive unit
2 Mains filter
3 Batteries
4 Cabinet Control Unit, Small Robot
5 Main switch
6 Safety Interface Board, Extended (optional)
7 Control PC
1 Motor connector
2 External fan
3 Low-voltage power supply unit
4 Connection panel for options
5 Power supply connection X1
6 Ballast resistor
7 Data connector X21
The robot controller can optionally be equipped with a set of rollers. The set of
rollers enables the robot controller to be easily rolled out of and into a bank of
cabinets.
3.3 Control PC
Functions The control PC (KPC) is responsible for the following functions of the robot
controller:
Graphical user interface
Program creation, correction, archiving, and maintenance
Sequence control
Path planning
Control of the drive circuit
Monitoring
Safety equipment
Communication with external periphery (other controllers, host computers,
PCs, network)
Overview
VGA support is possible via DVI on VGA adapter. The user interface
of the controller can only be displayed on an external monitor if no ac-
tive operator control device (smartPAD, VRP) is connected to the
controller.
Slot assignment
Overview
8 Display port
9 4 USB 2.0 ports
10 LAN Onboard – KUKA Option Network Interface
11 LAN Onboard – KUKA Line Interface
Slot assignment
Description The Cabinet Control Unit, Small Robot (CCU_SR) is the central power distrib-
utor and communication interface for all components of the robot controller.
The CCU_SR consists of the Cabinet Interface Board, Small Robot (CIB_SR)
and the Power Management Board (PMB). All data are transferred via this in-
ternal communication interface to the controller for further processing. If the
mains voltage fails, the control components continue to be powered by batter-
ies until the position data are saved and the controller has shut down. The
charge and quality of the batteries are checked by means of a load test.
The CCU_SR also incorporates sensing, control and switching functions. The
output signals are provided as electrically isolated outputs.
Description The low-voltage power supply unit provides power to the components of the
robot controller.
A green LED indicates the operating state of the low-voltage power supply
unit.
3.6 Batteries
Description In the event of a power failure, or if the power is switched off, the batteries en-
able the robot controller to be shut down in a controlled manner. The batteries
are charged via the CCU_SR and the charge is checked and indicated.
Further information:
KSI: Assembly and operating instructions “Optional interfaces for
KR C4 smallsize-2”
KLI: Assembly and operating instructions “Optional interfaces for KR C4
smallsize-2”
Possible devices of the KUKA Extension Bus are described in the as-
sembly and operating instructions “Optional Interfaces”.
Description The control cabinet is divided into two cooling circuits. The inner zone, con-
taining the control and power electronics, is cooled by the PC fan of the control
PC. In the outer zone, the ballast resistor, the low-voltage power supply unit
and the heat sinks of the drive unit are cooled directly with ambient air by the
external fan.
Description The space for integration of customer options can be used for external cus-
tomer equipment, such as bus modules. It is located on the right-hand side of
the control cabinet and is designed as a top-hat rail. Depending on the cabinet
equipment, the top-hat rail may come completely or partially filled with pre-in-
stalled devices and components.
(>>> 4.2 "Space for integration of customer options" Page 24)
Description The transient limiter is a surge voltage protector consisting of a base module
and a plugged-on protection module.
4 Technical data
4
Basic data
KR C4 smallsize-2 RAL 7016
Maximum number of servo axes 6
t
Weight approx. 60 kg
Protection rating (IEC 60529) IP54
Sound level < 66 dB (A)
Default color Side panels: anthracite gray (RAL
7016);
Door: KUKA orange 2567
Load on cabinet roof 1500 N with even distribution
Clearance for side-by-side installa- 50 mm (with/without cooling unit)
tion
Power supply
If the robot controller is connected to a power system
connection without a grounded neutral or is operated with incorrect
machine data, this may cause malfunctions in the robot controller and mate-
rial damage to the power supply units. Electrical voltage can cause injuries.
The robot controller may only be operated with grounded-neutral power sup-
ply systems.
Cable lengths For cable designations, standard lengths and optional lengths, please refer to
the operating instructions or assembly instructions of the manipulator and/or
the assembly and operating instructions for KR C4 external cabling for robot
controllers.
The module must be exchanged when the number of switching cycles is ex-
ceeded.
CIB_SR inputs Switching level of the inputs The state for the inputs is not defined for
the voltage range from 5 V to 11 V (transi-
tion range). Either the ON state or the OFF
state is set.
OFF state for the voltage range from -3 V to
5 V (OFF range).
ON state for the voltage range from 11 V to
30 V (ON range).
Load current with 24 V sup- > 10 mA
ply voltage
Load current with 18 V sup- > 6.5 mA
ply voltage
Max. load current < 15 mA
Cable length, terminal - < 50 m, or < 100 m wire length (outgoing
sensor and incoming lines)
Cable cross-section, test > 0.5 mm2
output - input connection
Capacitive load for the test < 200 nF
outputs per channel
Resistive load for the test < 33 Ω
outputs per channel
4.3 Dimensions
Description The diagram (>>> Fig. 4-1 ) shows the dimensions of the robot controller in
conjunction with the optional drive box for operating external axes. If no exter-
nal axes are required, the robot controller stands on its own.
Screw size: M8
Description The following installation options are possible for the drive box:
Stackable with up to 2 further KR C4 smallsize-2 robot controllers
Stackable with the KR C4 smallsize drive box
Side-by-side installation
With set of rollers (not stackable)
The minimum clearances (>>> Fig. 4-4 ) must be observed, irrespective of
the installation type.
The diagram (>>> Fig. 4-5 ) shows the dimensions and drilling locations for
mounting on the safety fence.
Overview The following plates and labels (>>> Fig. 4-6 ) are attached to the robot con-
troller. They must not be removed or rendered illegible. Illegible plates and la-
bels must be replaced.
Item Description
1
Hot surface
During operation of the controller, surface temperatures may be
reached that could result in burn injuries. Protective gloves must be
worn!
Item Description
4
Crushing hazard
Installation of the rear panel poses a crushing hazard. Protective
gloves must be worn!
5
The plates may vary slightly from the examples illustrated above de-
pending on the specific cabinet type or as a result of updates.
On the basis of the information provided by our suppliers, the following com-
ponents of this product contain substances included on the Candidate List of
Substances of Very High Concern (SVHCs) in a concentration exceeding 0.1
percent by mass. None of these substances are released under normal and
reasonably foreseeable conditions of use.
5 Safety
f
5.1 General
y
5.1.1 Liability
Safety infor- Information about safety may not be construed against KUKA Deutschland
mation GmbH. Even if all safety instructions are followed, this is not a guarantee that
the industrial robot will not cause personal injuries or material damage.
No modifications may be carried out to the industrial robot without the autho-
rization of KUKA Deutschland GmbH. Additional components (tools, software,
etc.), not supplied by KUKA Deutschland GmbH, may be integrated into the
industrial robot. The user is liable for any damage these components may
cause to the industrial robot or to other material property.
In addition to the Safety chapter, this document contains further safety instruc-
tions. These must also be observed.
The industrial robot is intended exclusively for the use designated in the “Pur-
pose” chapter of the operating instructions or assembly instructions.
Any use or application deviating from the intended use is deemed to be misuse
and is not allowed. The manufacturer is not liable for any damage resulting
from such misuse. The risk lies entirely with the user.
Operation of the industrial robot in accordance with its intended use also re-
quires compliance with the operating and assembly instructions for the individ-
ual components, with particular reference to the maintenance specifications.
Misuse Any use or application deviating from the intended use is deemed to be misuse
and is not allowed. This includes e.g.:
EC declaration of The system integrator must issue an EC declaration of conformity for the com-
conformity plete system in accordance with the Machinery Directive. The EC declaration
of conformity forms the basis for the CE mark for the system. The industrial
robot must always be operated in accordance with the applicable national
laws, regulations and standards.
The robot controller has a CE mark in accordance with the EMC Directive and
the Low Voltage Directive.
STOP 0, STOP 1 and STOP 2 are the stop definitions according to EN 60204-
1:2006.
Term Description
Axis range Range of each axis, in degrees or millimeters, within which it may move.
The axis range must be defined for each axis.
Stopping distance Stopping distance = reaction distance + braking distance
The stopping distance is part of the danger zone.
Workspace Area within which the robot may move. The workspace is derived from
the individual axis ranges.
User The user of the industrial robot can be the management, employer or
delegated person responsible for use of the industrial robot.
Danger zone The danger zone consists of the workspace and the stopping distances
of the manipulator and external axes (optional).
Term Description
Service life The service life of a safety-relevant component begins at the time of
delivery of the component to the customer.
The service life is not affected by whether the component is used or not,
as safety-relevant components are also subject to aging during storage.
KUKA smartPAD see “smartPAD”
Manipulator The robot arm and the associated electrical installations
Safety zone The safety zone is situated outside the danger zone.
Safe operational stop The safe operational stop is a standstill monitoring function. It does not
stop the robot motion, but monitors whether the robot axes are station-
ary. If these are moved during the safe operational stop, a safety stop
STOP 0 is triggered.
The safe operational stop can also be triggered externally.
When a safe operational stop is triggered, the robot controller sets an
output to the field bus. The output is set even if not all the axes were sta-
tionary at the time of triggering, thereby causing a safety stop STOP 0 to
be triggered.
Safety STOP 0 A stop that is triggered and executed by the safety controller. The safety
controller immediately switches off the drives and the power supply to
the brakes.
Note: This stop is called safety STOP 0 in this document.
Safety STOP 1 A stop that is triggered and monitored by the safety controller. The brak-
ing operation is carried out by the non-safety-oriented section of the
robot controller and monitored by the safety controller. As soon as the
manipulator has stopped, the safety controller deactivates the drives
and the power supply of the brakes.
When a safety STOP 1 is triggered, the robot controller sets an output to
the field bus.
The safety STOP 1 can also be triggered externally.
Note: This stop is called safety STOP 1 in this document.
Safety STOP 2 A stop that is triggered and monitored by the safety controller. The brak-
ing operation is carried out by the non-safety-oriented section of the
robot controller and monitored by the safety controller. The drives
remain activated and the brakes released. As soon as the manipulator is
at a standstill, a safe operational stop is triggered.
When a safety STOP 2 is triggered, the robot controller sets an output to
the field bus.
The safety STOP 2 can also be triggered externally.
Note: This stop is called safety STOP 2 in this document.
Safety options Generic term for options which make it possible to configure additional
safe monitoring functions in addition to the standard safety functions.
Example: SafeOperation
smartPAD Programming device for the robot controller
The smartPAD has all the operator control and display functions
required for operating and programming the industrial robot.
Stop category 0 The drives are deactivated immediately and the brakes are applied. The
manipulator and any external axes (optional) perform path-oriented
braking.
Note: This stop category is called STOP 0 in this document.
Term Description
Stop category 1 The manipulator and any external axes (optional) perform path-main-
taining braking.
Operating mode T1: The drives are deactivated as soon as the robot
has stopped, but no later than after 680 ms.
Operating modes T2, AUT (KR C4), AUT EXT (KR C4), EXT
(VKR C4):
The drives are switched off after 1.5 s.
Note: This stop category is called STOP 1 in this document.
Stop category 1 - The manipulator and any external axes (optional) perform path-oriented
Drive Ramp Stop braking.
Operating mode T1: The drives are deactivated as soon as the robot
has stopped, but no later than after 680 ms.
Operating modes T2, AUT (KR C4), AUT EXT (KR C4), EXT
(VKR C4):
The drives are switched off after 1.5 s.
Note: This stop category is called STOP 1 - DRS in this document.
Stop category 2 The drives are not deactivated and the brakes are not applied. The
manipulator and any external axes (optional) are braked with a path-
maintaining braking ramp.
Note: This stop category is called STOP 2 in this document.
System integrator The system integrator is responsible for safely integrating the industrial
(plant integrator) robot into a complete system and commissioning it.
T1 Test mode, Manual Reduced Velocity (<= 250 mm/s)
T2 Test mode, Manual High Velocity (> 250 mm/s permissible)
External axis Axis of motion that does not belong to the manipulator, yet is controlled
with the robot controller. e.g. KUKA linear unit, turn-tilt table, Posiflex
5.2 Personnel
The following persons or groups of persons are defined for the industrial robot:
User
Personnel
All persons working with the industrial robot must have read and un-
derstood the industrial robot documentation, including the safety
chapter.
User The user must observe the labor laws and regulations. This includes e.g.:
The user must comply with his monitoring obligations.
The user must carry out briefing at defined intervals.
Personnel Personnel must be instructed, before any work is commenced, in the type of
work involved and what exactly it entails as well as any hazards which may ex-
ist. Instruction must be carried out regularly. Instruction is also required after
particular incidents or technical modifications.
Personnel includes:
System integrator
Operators, subdivided into:
Start-up, maintenance and service personnel
Operating personnel
Cleaning personnel
System integrator The industrial robot is safely integrated into a complete system by the system
integrator.
The system integrator is responsible for the following tasks:
Installing the industrial robot
Connecting the industrial robot
Performing risk assessment
Implementing the required safety functions and safeguards
Issuing the EC declaration of conformity
Attaching the CE mark
Creating the operating instructions for the system
The system integrator’s risk assessment may indicate that the stopping dis-
tances must be determined for an application. In order to determine the stop-
ping distances, the system integrator must identify the safety-relevant points
on the programmed path.
When determining the stopping distances, the robot must be moved with the
tool and loads which are also used in the application. The robot must be at op-
erating temperature. This is the case after approx. 1 h in normal operation.
During execution of the application, the robot must be stopped at the point
from which the stopping distance is to be calculated. This process must be re-
peated several times with a safety stop 0 and a safety stop 1. The least favor-
able stopping distance is decisive.
A safety stop 0 can be triggered by a safe operational stop via the safety inter-
face, for example. If a safety option is installed, it can be triggered, for in-
stance, by a space violation (e.g. the robot exceeds the limit of an activated
workspace in Automatic mode).
A safety stop 1 can be triggered by pressing the EMERGENCY STOP device
on the smartPAD, for example.
Stop reactions of the industrial robot are triggered in response to operator ac-
tions or as a reaction to monitoring functions and error messages. The follow-
ing table shows the different stop reactions according to the operating mode
that has been set.
The safety controller is a unit inside the control PC. It links safety-relevant sig-
nals and safety-relevant monitoring functions.
Safety controller tasks:
Switching off the drives; applying the brakes
Monitoring the braking ramp
Standstill monitoring (after the stop)
Velocity monitoring in T1
Evaluation of safety-relevant signals
Setting of safety-oriented outputs
Operating modes The industrial robot can be operated in the following modes:
Manual Reduced Velocity (T1)
Manual High Velocity (T2)
Automatic (AUT)
Automatic External (AUT EXT)
Operat-
Use Velocities
ing mode
Program verification:
Programmed velocity, maxi-
For test operation, pro- mum 250 mm/s
T1 gramming and teach-
ing Jog mode:
Jog velocity, maximum
250 mm/s
Program verification:
T2 For test operation Programmed velocity
Jog mode: Not possible
For industrial robots Program operation:
AUT without higher-level Programmed velocity
controllers Jog mode: Not possible
For industrial robots Program operation:
AUT EXT with higher-level con- Programmed velocity
trollers, e.g. PLC Jog mode: Not possible
Mode selector The user can change the operating mode via the connection manager. The
switch connection manager is a view that is called by means of the mode selector
switch on the smartPAD.
The mode selector switch may be one of the following variants:
With key
It is only possible to change operating mode if the key is inserted.
Without key
The system integrator is responsible for ensuring that such a device is imple-
mented.
The “operator safety” signal is used for monitoring physical safeguards, e.g.
safety gates. Automatic operation is not possible without this signal. In the
event of a loss of signal during automatic operation (e.g. safety gate is
opened), the manipulator stops with a safety stop 1.
Operator safety is not active in modes T1 (Manual Reduced Velocity) and T2
(Manual High Velocity).
The EMERGENCY STOP device for the industrial robot is the EMERGENCY
STOP device on the smartPAD. The device must be pressed in the event of a
hazardous situation or emergency.
Reactions of the industrial robot if the EMERGENCY STOP device is pressed:
The manipulator and any external axes (optional) are stopped with a safe-
ty stop 1.
Before operation can be resumed, the EMERGENCY STOP device must be
turned to release it.
There must always be at least one external EMERGENCY STOP device in-
stalled. This ensures that an EMERGENCY STOP device is available even
when the smartPAD is disconnected.
(>>> 5.5.7 "External EMERGENCY STOP device" Page 38)
Every operator station that can initiate a robot motion or other potentially haz-
ardous situation must be equipped with an EMERGENCY STOP device. The
system integrator is responsible for ensuring this.
There must always be at least one external EMERGENCY STOP device in-
stalled. This ensures that an EMERGENCY STOP device is available even
when the smartPAD is disconnected.
External EMERGENCY STOP devices are connected via the customer inter-
face. External EMERGENCY STOP devices are not included in the scope of
supply of the industrial robot.
The enabling devices of the industrial robot are the enabling switches on the
smartPAD.
There are 3 enabling switches installed on the smartPAD. The enabling
switches have 3 positions:
Not pressed
Center position
Panic position
In the test modes, the manipulator can only be moved if one of the enabling
switches is held in the central position.
Releasing the enabling switch triggers a safety stop 2.
Pressing the enabling switch down fully (panic position) triggers a safety
stop 1.
It is possible to hold 2 enabling switches in the center position simultane-
ously for up to 15 seconds. This makes it possible to adjust grip from one
enabling switch to another one. If 2 enabling switches are held simultane-
ously in the center position for longer than 15 seconds, this triggers a safe-
ty stop 1.
If an enabling switch malfunctions (e.g. jams in the central position), the indus-
trial robot can be stopped using the following methods:
Press the enabling switch down fully.
External enabling devices are required if it is necessary for more than one per-
son to be in the danger zone of the industrial robot.
External enabling devices are not included in the scope of supply of the indus-
trial robot.
The safe operational stop can be triggered via an input on the customer inter-
face. The state is maintained as long as the external signal is FALSE. If the
external signal is TRUE, the manipulator can be moved again. No acknowl-
edgement is required.
Safety stop 1 and safety stop 2 can be triggered via an input on the customer
interface. The state is maintained as long as the external signal is FALSE. If
the external signal is TRUE, the manipulator can be moved again. No ac-
knowledgement is required.
If interface X11 is selected as the customer interface, only the signal Safety
stop 2 is available.
The velocity at the mounting flange is monitored in T1 mode. If the velocity ex-
ceeds 250 mm/s, a safety stop 0 is triggered.
The axis ranges of all manipulator and positioner axes are limited by means of
adjustable software limit switches. These software limit switches only serve as
machine protection and must be adjusted in such a way that the manipula-
tor/positioner cannot hit the mechanical end stops.
The software limit switches are set during commissioning of an industrial ro-
bot.
Depending on the robot variant, the axis ranges of the main and wrist axes of
the manipulator are partially limited by mechanical end stops.
Additional mechanical end stops can be installed on the external axes.
This option is not available for all robot models. Information on spe-
cific robot models can be obtained from KUKA Deutschland GmbH.
The system user is responsible for ensuring that the training of per-
sonnel with regard to the response to emergencies or exceptional sit-
uations also includes how the manipulator can be moved without
drive energy.
Description The following options are available for moving the manipulator without drive
energy after an accident or malfunction:
Release device (optional)
The release device can be used for the main axis drive motors and, de-
pending on the robot variant, also for the wrist axis drive motors.
Information about the options available for the various robot models
and about how to use them can be found in the assembly and oper-
ating instructions for the robot or requested from KUKA Deutschland
GmbH.
All plates, labels, symbols and marks constitute safety-relevant parts of the in-
dustrial robot. They must not be modified or removed.
Labeling on the industrial robot consists of:
Identification plates
Warning signs
Safety symbols
Designation labels
Cable markings
Rating plates
The access of persons to the danger zone of the industrial robot must be pre-
vented by means of safeguards. It is the responsibility of the system integrator
to ensure this.
Physical safeguards must meet the following requirements:
They meet the requirements of EN ISO 14120.
They prevent access of persons to the danger zone and cannot be easily
circumvented.
They are sufficiently fastened and can withstand all forces that are likely
to occur in the course of operation, whether from inside or outside the en-
closure.
They do not, themselves, represent a hazard or potential hazard.
Prescribed clearances, e.g. to danger zones, are adhered to.
Safety gates (maintenance gates) must meet the following requirements:
They are reduced to an absolute minimum.
The interlocks (e.g. safety gate switches) are linked to the operator safety
input of the robot controller via safety gate switching devices or safety
PLC.
Switching devices, switches and the type of switching conform to the re-
quirements of Performance Level d and category 3 according to
EN ISO 13849-1.
Depending on the risk situation: the safety gate is additionally safeguarded
by means of a locking mechanism that only allows the gate to be opened
if the manipulator is safely at a standstill.
The button for acknowledging the safety gate is located outside the space
limited by the safeguards.
Other safety Other safety equipment must be integrated into the system in accordance with
equipment the corresponding standards and regulations.
The following table indicates the operating modes in which the safety functions
are active.
The industrial robot may only be used in perfect technical condition in accor-
dance with its intended use and only by safety-conscious persons. Operator
errors can result in personal injury and damage to property.
It is important to be prepared for possible movements of the industrial robot
even after the robot controller has been switched off and locked out. Incorrect
installation (e.g. overload) or mechanical defects (e.g. brake defect) can cause
the manipulator or external axes to sag. If work is to be carried out on a
switched-off industrial robot, the manipulator and external axes must first be
moved into a position in which they are unable to move on their own, whether
the payload is mounted or not. If this is not possible, the manipulator and ex-
ternal axes must be secured by appropriate means.
smartPAD The user must ensure that the industrial robot is only operated with the smart-
PAD by authorized persons.
If more than one smartPAD is used in the overall system, it must be ensured
that it is clearly recognizable which smartPAD is connected to which industrial
robot. They must not be interchanged.
Modifications After modifications to the industrial robot, checks must be carried out to ensure
the required safety level. The valid national or regional work safety regulations
must be observed for this check. The correct functioning of all safety functions
must also be tested.
New or modified programs must always be tested first in Manual Reduced Ve-
locity mode (T1).
After modifications to the industrial robot, existing programs must always be
tested first in Manual Reduced Velocity mode (T1). This applies to all compo-
nents of the industrial robot and includes e.g. modifications of the external
axes or to the software and configuration settings.
Faults The following tasks must be carried out in the case of faults in the industrial
robot:
Switch off the robot controller and secure it (e.g. with a padlock) to prevent
unauthorized persons from switching it on again.
Indicate the fault by means of a label with a corresponding warning (tag-
out).
Keep a record of the faults.
Eliminate the fault and carry out a function test.
5.8.2 Transportation
Manipulator The prescribed transport position of the manipulator must be observed. Trans-
portation must be carried out in accordance with the operating instructions or
assembly instructions of the robot.
Avoid vibrations and impacts during transportation in order to prevent damage
to the manipulator.
Robot controller The prescribed transport position of the robot controller must be observed.
Transportation must be carried out in accordance with the operating instruc-
tions or assembly instructions of the robot controller.
External axis The prescribed transport position of the external axis (e.g. KUKA linear unit,
(optional) turn-tilt table, positioner) must be observed. Transportation must be carried
out in accordance with the operating instructions or assembly instructions of
the external axis.
Before starting up systems and devices for the first time, a check must be car-
ried out to ensure that the systems and devices are complete and operational,
that they can be operated safely and that any damage is detected.
The valid national or regional work safety regulations must be observed for this
check. The correct functioning of all safety functions must also be tested.
The passwords for the user groups must be changed in the KUKA
System Software before start-up. The passwords must only be com-
municated to authorized personnel.
If additional components (e.g. cables), which are not part of the scope
of supply of KUKA Deutschland GmbH, are integrated into the indus-
trial robot, the user is responsible for ensuring that these components
do not adversely affect or disable safety functions.
Function test The following tests must be carried out before start-up and recommissioning:
General test:
It must be ensured that:
The industrial robot is correctly installed and fastened in accordance with
the specifications in the documentation.
There is no damage to the robot that could be attributed to external forces.
Examples: Dents or abrasion that could be caused by an impact or colli-
sion.
The power supply ratings of the industrial robot correspond to the local
supply voltage and mains type.
The ground conductor and the equipotential bonding cable are sufficiently
rated and correctly connected.
The connecting cables are correctly connected and the connectors are
locked.
Test of the safety functions:
A function test must be carried out for the following safety functions to ensure
that they are functioning correctly:
Local EMERGENCY STOP device
External EMERGENCY STOP device (input and output)
Enabling device (in the test modes)
Operator safety
All other safety-relevant inputs and outputs used
Other external safety functions
Following the start-up procedure, the practical tests for the machine data
must be carried out. The tool must be calibrated (either via an actual cali-
bration or through numerical entry of the data).
Following modifications to the machine data, the safety configuration must
be checked.
After activation of a WorkVisual project on the robot controller, the safety
configuration must be checked.
If machine data are adopted when checking the safety configuration (re-
gardless of the reason for the safety configuration check), the practical
tests for the machine data must be carried out.
System Software 8.3 or higher: If the checksum of the safety configuration
has changed, the safe axis monitoring functions must be checked.
Information about checking the safety configuration and the safe axis
monitoring functions is contained in the Operating and Programming
Instructions for System Integrators.
If the practical tests are not successfully completed in the initial start-up, KUKA
Deutschland GmbH must be contacted.
If the practical tests are not successfully completed during a different proce-
dure, the machine data and the safety-relevant controller configuration must
be checked and corrected.
General practical If practical tests are required for the machine data, this test must always be
test carried out.
For 6-axis robots:
The following methods are available for performing the practical test:
TCP calibration with the XYZ 4-point method
The practical test is passed if the TCP has been successfully calibrated.
Or:
1. Align the TCP with a freely selected point. The point serves as a reference
point.
The point must be located so that reorientation is possible.
The point must not be located on the Z axis of the FLANGE coordinate
system.
2. Move the TCP manually at least 45° once in each of the A, B and C direc-
tions.
The movements do not have to be accumulative, i.e. after motion in one
direction it is possible to return to the original position before moving in the
next direction.
The practical test is passed if the TCP does not deviate from the reference
point by more than 2 cm in total.
For palletizing robots:
Palletizing robots, in this case, are either robots that can be used only as pal-
letizers from the start or robots operated in palletizing mode. The latter must
also be in palletizing mode during the practical test.
First part:
1. Mark the starting position of the TCP.
Also read and note the starting position from the Actual position – Car-
tesian display on the smartHMI.
2. Jog the TCP in the X direction. The distance must be at least 20% of the
robot’s maximum reach. Determine the exact length via the Actual posi-
tion display.
3. Measure the distance covered and compare it with the distance value dis-
played on the smartHMI. The deviation must be < 5%.
4. Repeat steps 1 and 2 for the Y direction and Z direction.
The first part of the practical test is passed if the deviation is < 5% in every di-
rection.
Second part:
Rotate the tool manually about A by 45°: once in the plus direction, once
in the minus direction. At the same time, observe the TCP.
The second part of the practical test is passed if the position of the TCP in
space is not altered during the rotations.
Practical test for If practical tests are required for the machine data, this test must be carried out
axes that are not when axes are present that are not mathematically coupled.
mathematically 1. Mark the starting position of the axis that is not mathematically coupled.
coupled Also read and note the start position from the Actual position display on
the smartHMI.
2. Move the axis manually by a freely selected path length. Determine the
path length from the Actual position display.
Move linear axes a specific distance.
Move rotational axes through a specific angle.
3. Measure the length of the path covered and compare it with the value dis-
played on the smartHMI.
The practical test is passed if the values differ by no more than 5%.
4. Repeat the test for each axis that is not mathematically coupled.
Practical test for If practical tests are required for the machine data, this test must be carried out
robot on KUKA if the robot and KL are mathematically coupled.
linear unit Move the KL manually in Cartesian mode.
The practical test is passed if the TCP does not move at the same time.
Practical test for If practical tests are required for the machine data, this test must be carried out
couplable axes when axes are present that can be physically coupled and uncoupled, e.g. a
servo gun.
1. Physically uncouple the couplable axis.
2. Move all the remaining axes individually.
The practical test is passed if it has been possible to move all the remain-
ing axes.
Description The industrial robot can be set to Start-up mode via the smartHMI user inter-
face. In this mode, the manipulator can be moved in T1 without the external
safeguards being put into operation.
The safety interface used affects “Start-up” mode:
Discrete safety interface
System Software 8.2 or earlier:
Start-up mode is always possible if all input signals at the discrete safety
interface have the state “logic zero”. If this is not the case, the robot con-
troller prevents or terminates Start-up mode.
If an additional discrete safety interface for safety options is used, the in-
puts there must also have the state “logic zero”.
System Software 8.3 or higher:
Start-up mode is always possible. This also means that it is independent
of the state of the inputs at the discrete safety interface.
If an additional discrete safety interface is used for safety options: The
states of these inputs are also irrelevant.
Ethernet safety interface
The robot controller prevents or terminates Start-up mode if a connection to a
higher-level safety system exists or is established.
Effect When the Start-up mode is activated, all outputs are automatically set to the
state “logic zero”.
If the robot controller has a peripheral contactor (US2), and if the safety con-
figuration specifies for this to switch in accordance with the motion enable,
then the same also applies in Start-up mode. This means that if motion enable
is present, the US2 voltage is switched on – even in Start-up mode.
Misuse Any use or application deviating from the intended use is deemed to be misuse
and is not allowed. KUKA Deutschland GmbH is not liable for any damage re-
sulting from such misuse. The risk lies entirely with the user.
General Manual mode is the mode for setup work. Setup work is all the tasks that have
to be carried out on the industrial robot to enable automatic operation. Setup
work includes:
Jog mode
Teaching
Programming
Program verification
The following must be taken into consideration in manual mode:
New or modified programs must always be tested first in Manual Reduced
Velocity mode (T1).
The manipulator, tooling or external axes (optional) must never touch or
project beyond the safety fence.
Workpieces, tooling and other objects must not become jammed as a re-
sult of the industrial robot motion, nor must they lead to short-circuits or be
liable to fall off.
All setup work must be carried out, where possible, from outside the safe-
guarded area.
Setup work in T1 If it is necessary to carry out setup work from inside the safeguarded area, the
following must be taken into consideration in the operating mode Manual Re-
duced Velocity (T1):
If it can be avoided, there must be no other persons inside the safeguard-
ed area.
If it is necessary for there to be several persons inside the safeguarded ar-
ea, the following must be observed:
Each person must have an enabling device.
All persons must have an unimpeded view of the industrial robot.
Eye-contact between all persons must be possible at all times.
The operator must be so positioned that he can see into the danger area
and get out of harm’s way.
Unexpected motions of the manipulator cannot be ruled out, e.g. in the
event of a fault. For this reason, an appropriate clearance must be main-
tained between persons and the manipulator (including tool). Guide value:
50 cm.
The minimum clearance may vary depending on local circumstances, the
motion program and other factors. The minimum clearance that is to apply
for the specific application must be decided by the user on the basis of a
risk assessment.
Setup work in T2 If it is necessary to carry out setup work from inside the safeguarded area, the
following must be taken into consideration in the operating mode Manual High
Velocity (T2):
This mode may only be used if the application requires a test at a velocity
higher than that possible in T1 mode.
Teaching and programming are not permissible in this operating mode.
Before commencing the test, the operator must ensure that the enabling
devices are operational.
The operator must be positioned outside the danger zone.
There must be no other persons inside the safeguarded area. It is the re-
sponsibility of the operator to ensure this.
5.8.5 Simulation
After maintenance and repair work, checks must be carried out to ensure the
required safety level. The valid national or regional work safety regulations
must be observed for this check. The correct functioning of all safety functions
must also be tested.
The purpose of maintenance and repair work is to ensure that the system is
kept operational or, in the event of a fault, to return the system to an operation-
al state. Repair work includes troubleshooting in addition to the actual repair
itself.
The following safety measures must be carried out when working on the indus-
trial robot:
Carry out work outside the danger zone. If work inside the danger zone is
necessary, the user must define additional safety measures to ensure the
safe protection of personnel.
Switch off the industrial robot and secure it (e.g. with a padlock) to prevent
it from being switched on again. If it is necessary to carry out work with the
robot controller switched on, the user must define additional safety mea-
sures to ensure the safe protection of personnel.
If it is necessary to carry out work with the robot controller switched on, this
may only be done in operating mode T1.
Label the system with a sign indicating that work is in progress. This sign
must remain in place, even during temporary interruptions to the work.
The EMERGENCY STOP devices must remain active. If safety functions
or safeguards are deactivated during maintenance or repair work, they
must be reactivated immediately after the work is completed.
Faulty components must be replaced using new components with the same
article numbers or equivalent components approved by KUKA Deutschland
GmbH for this purpose.
Cleaning and preventive maintenance work is to be carried out in accordance
with the operating instructions.
Robot controller Even when the robot controller is switched off, parts connected to peripheral
devices may still carry voltage. The external power sources must therefore be
switched off if work is to be carried out on the robot controller.
The ESD regulations must be adhered to when working on components in the
robot controller.
Voltages in excess of 50 V (up to 780 V) can be present in various compo-
nents for several minutes after the robot controller has been switched off! To
prevent life-threatening injuries, no work may be carried out on the industrial
robot in this time.
Water and dust must be prevented from entering the robot controller.
Counterbal- Some robot variants are equipped with a hydropneumatic, spring or gas cylin-
ancing system der counterbalancing system.
The hydropneumatic and gas cylinder counterbalancing systems are pressure
equipment and, as such, are subject to obligatory equipment monitoring and
the provisions of the Pressure Equipment Directive.
The user must comply with the applicable national laws, regulations and stan-
dards pertaining to pressure equipment.
Inspection intervals in Germany in accordance with Industrial Safety Order,
Sections 14 and 15. Inspection by the user before commissioning at the instal-
lation site.
The following safety measures must be carried out when working on the coun-
terbalancing system:
The manipulator assemblies supported by the counterbalancing systems
must be secured.
Work on the counterbalancing systems must only be carried out by quali-
fied personnel.
Hazardous The following safety measures must be carried out when handling hazardous
substances substances:
Avoid prolonged and repeated intensive contact with the skin.
Overview If certain components in the industrial robot are operated, safety measures
must be taken to ensure complete implementation of the principle of “single
point of control” (SPOC).
The relevant components are:
Submit interpreter
PLC
OPC server
Remote control tools
Tools for configuration of bus systems with online functionality
KUKA.RobotSensorInterface
Since only the system integrator knows the safe states of actuators in the pe-
riphery of the robot controller, it is his task to set these actuators to a safe
state, e.g. in the event of an EMERGENCY STOP.
T1, T2 In modes T1 and T2, the components referred to above may only access the
industrial robot if the following signals have the following states:
Submit inter- If motions, (e.g. drives or grippers) are controlled with the submit interpreter or
preter, PLC the PLC via the I/O system, and if they are not safeguarded by other means,
then this control will take effect even in T1 and T2 modes or while an EMER-
GENCY STOP is active.
If variables that affect the robot motion (e.g. override) are modified with the
submit interpreter or the PLC, this takes effect even in T1 and T2 modes or
while an EMERGENCY STOP is active.
Safety measures:
In T1 and T2, the system variable $OV_PRO must not be written to by the
submit interpreter or the PLC.
Do not modify safety-relevant signals and variables (e.g. operating mode,
EMERGENCY STOP, safety gate contact) via the submit interpreter or
PLC.
If modifications are nonetheless required, all safety-relevant signals and
variables must be linked in such a way that they cannot be set to a dan-
OPC server, These components can be used with write access to modify programs, outputs
remote control or other parameters of the robot controller, without this being noticed by any
tools persons located inside the system.
Safety measure:
If these components are used, outputs that could cause a hazard must be de-
termined in a risk assessment. These outputs must be designed in such a way
that they cannot be set without being enabled. This can be done using an ex-
ternal enabling device, for example.
Tools for configu- If these components have an online functionality, they can be used with write
ration of bus access to modify programs, outputs or other parameters of the robot control-
systems ler, without this being noticed by any persons located inside the system.
WorkVisual from KUKA
Tools from other manufacturers
Safety measure:
In the test modes, programs, outputs or other parameters of the robot control-
ler must not be modified using these components.
Name/Edition Definition
6 Planning
Description If connecting cables (e.g. field buses, etc.) are routed to the control PC from
outside, only shielded cables with an adequate degree of shielding may be
used. The cable shield must be connected with maximum surface area to the
PE rail in the cabinet using shield terminals (screw-type, no clamps).
The dimensions and installation conditions of the robot controller are specified
in the section “Technical data”.
(>>> 4.3 "Dimensions" Page 24)
(>>> 4.5 "Installation conditions" Page 25)
Technical data Technical data of the power supply connection: (>>> 4 "Technical data"
Page 21)
Cable lengths For cable designations, standard lengths and optional lengths, please refer to
the operating instructions or assembly instructions of the manipulator and/or
the assembly and operating instructions for KR C4 external cabling for robot
controllers.
Description A Harting connector bypack is supplied with the robot controller. The customer
can connect the robot controller to the power supply via connector X1.
Overview The robot controller is equipped with the following cables as standard:
Device connection cable
Motor cable, data cable
smartPAD cable
Peripheral cables
Peripheral/bus cables depending on the customer variant and/or options are
connected to the connection panel for options.
Interfaces
Representation The connector pin allocation is represented in tabular form. Pins that are not
assigned are not listed here.
All contactor, relay and valve coils that are connected to the robot
controller by the user must be equipped with suitable suppressor di-
odes. RC elements and VCR resistors are not suitable.
Description The motors and brakes of the robot axes are connected to the robot controller
via motor connector X20.
Motor connector
Pin Description
X20
1 Motor M1 U1
6 Motor M1 V1
11 Motor M1 W1
2 Motor M2 U1
7 Motor M2 V1
12 Motor M2 W1
Pin Description
3 Motor M3 U1
8 Motor M3 V1
13 Motor M3 W1
4 Motor M4 U1
9 Motor M4 V1
14 Motor M4 W1
5 Motor M5 U1
10 Motor M5 V1
15 Motor M5 W1
21 Motor M6 U1
22 Motor M6 V1
23 Motor M6 W1
18 Brake, axes 1-3, 24 V
24 Brake, axes 1-3, GND
19 Brake, axes 4-6, 24 V
25 Brake, axes 4-6, GND
20 PE
Description EMERGENCY STOP devices must be connected via safety interface X11 or
linked together by means of higher-level controllers (e.g. PLC).
Wiring Take the following points into consideration when wiring safety interface X11:
System concept
Safety concept
Contact diagram,
connector X11
In the cabling for the input signals and test signals in the system, suit-
able measures must be taken to prevent a cross-connection between
the voltages (e.g. separate cabling of input signals and test signals).
In the cabling for the output signals and test signals in the system,
suitable measures must be taken to prevent a cross-connection be-
tween the output signals of a channel (e.g. separate cabling).
Connector pin
Pin Description Function
allocation X11
1 CIB_SR test output A Makes the pulsed voltage avail-
3 able for the individual interface
(test signal)
inputs of channel A.
5
7 These signals may only be
mapped with the safe inputs of
9
channel A.
19 CIB_SR test output B Makes the clocked voltage
21 available for the individual
(test signal)
interface inputs of channel B.
23
25 These signals may only be
mapped with the safe inputs of
27
channel B.
8 Safe operational stop, channel Safe operational stop input for
A all axes
26 Safe operational stop, channel Activation of standstill monitor-
B ing
Stop 0 is initiated if the acti-
vated monitoring is violated.
10 Safety stop 2, channel A Safety stop 2 input for all axes
28 Safety stop 2, channel B Triggering of stop 2 and activa-
tion of standstill monitoring at
standstill of all axes.
Stop 0 is initiated if the acti-
vated monitoring is violated.
Signal “Peri The signal “Peri enabled” is set to 1 (active) if the following conditions are met:
enabled” (PE) Drives are switched on.
Safety controller motion enable signal present.
The message “Operator safety open” must not be active.
This message is not active in the modes T1 and T2.
“Peri enabled” in conjunction with the signal “Safe operational stop”
In the case of activation of the signal “Safe operational stop” during the
motion:
Error -> braking with Stop 0. “Peri enabled” eliminated.
Activation of the signal “Safe operational stop” with the manipulator sta-
tionary:
Release the brakes, switch drives to servo-control and monitor for restart.
“Peri enabled” remains active.
Signal “Motion enable” remains active.
US2 voltage (if present) remains active.
Signal “Peri enabled” remains active.
“Peri enabled” in conjunction with the signal “Safety stop 2”
In the case of activation of the signal “Safety stop 2”:
Stop 2 of the manipulator.
Signal “Drive enable” remains active.
Brakes remain released.
Manipulator remains under servo-control.
Monitoring for restart active.
Signal “Motion enable” is deactivated.
US2 voltage (if present) is deactivated.
Signal “Peri enabled” is deactivated.
Description External enabling switches can be connected to the robot controller via inter-
face X11.
Connector pin
Pin Description Function
allocation X11
11 CCU_SR test output A Makes the pulsed voltage avail-
13 able for the individual interface
(test signal)
inputs of channel A.
These signals may only be
mapped with the CCU_SR.
Safety stop 1 (drives switched off Input open Input open No operational
when axis at standstill) state
Safety stop 2 (safe operational stop, Input open Input closed Not pressed
drives switched on)
Safety stop 1 (drives switched off Input closed Input open Panic position
when axis at standstill)
Axes enabled (axis jogging possible) Input closed Input closed Center position
Description The EMERGENCY STOP devices are connected to X11 in the robot control-
ler.
EMERGENCY
The EMERGENCY STOP devices on the robot controller
STOP must be integrated into the EMERGENCY STOP circuit
of the system by the system integrator.
Failure to do this may result in death, severe injuries or considerable damage
to property.
Safety gate A dual-channel acknowledge button must be installed outside the physical
safeguard. The closing of the safety gate must be confirmed by pressing the
acknowledge button before the industrial robot can be started again in Auto-
matic mode.
The inputs of the SIB are of dual-channel design with external testing. The
dual-channel operation of the inputs is monitored cyclically.
The following diagram illustrates the connection of a safe input to a floating
contact provided by the customer.
Test outputs A and B are fed with the supply voltage of the SIB. Test outputs
A and B are sustained short-circuit proof. The test outputs must only be used
to supply the SIB inputs, and for no other purpose.
The wiring example described can be used to achieve compliance with Cate-
gory 3 and Performance Level (PL) d according to EN ISO 13849-1.
Dynamic testing The switch-off capability of the inputs is tested cyclically. For this, the test
outputs TA_A and TA_B are switched off alternately.
The switch-off pulse length is defined for the SIBs as t1 = 625 μs (125 μs
– 2.375 ms).
The duration t2 between two switch-off pulses on one channel is 106 ms.
The input channel SIN_x_A must be supplied by the test signal TA_A. The
input channel SIN_x_B must be supplied by the test signal TA_B. No other
power supply is permissible.
It is only permitted to connect sensors which allow the connection of test
signals and which provide floating contacts.
The signals TA_A and TA_B must not be significantly delayed by the
switching element.
Switch-off pulse
diagram
Safe output On the SIB, the outputs are provided as dual-channel floating relay outputs.
The following diagram illustrates the connection of a safe output to a safe input
provided by the customer with external test facility. The input used by the cus-
tomer must be monitored externally for cross-connection.
1 SIB
2 Robot controller
3 Interface X11 or X13
4 Output wiring
5 System side
6 Safe input (Fail Safe PLC, safety switching device)
7 Test output channel B
8 Test output channel A
9 Input X, channel A
10 Input X, channel B
The wiring example described can be used to achieve compliance with Cate-
gory 3 and Performance Level (PL) d according to EN ISO 13849-1.
Connector pin
Pin Description
allocation X19
11 TD+
12 TD-
2 RD+
3 RD-
8 smartPAD plugged in (A) 0 V
9 smartPAD plugged in (B) 24 V
5 24 V PS2
6 GND
Connector pin
Pin Description
allocation X21
1 +24 V with battery back-up
2 GND
5 +24 V without battery backup
6 GND
9 TD+
11 TD-
10 RD+
Pin Description
12 RD-
- PE
Description For the X21 US2 RDC interface, the buffered US1 voltage is used to supply
power to the RDC of the robot. The US2 voltage is implemented as switchable
using safe technology. This deactivates actuators via a Beckhoff board, for ex-
ample, when the drives are deactivated.
This function exists in the following three variants and is set in the safety con-
figuration:
Switched by an external PLC:
The contactor is switched directly by an external input (US2 signal in the
PROFIsafe/CIP Safety/FSoE telegram). This variant is available only if
PROFIsafe/CIP Safety/FSoE is in use.
Switched by the KRC:
The contactor is switched if the “FF signal” and the non-safe
“US2_CONTACTOR_ON” signal from the robot controller are set. In this
way, the non-safe part of the robot controller can also switch the contactor.
Deactivated:
The contactor is always off.
If, due to a fault in the system cabling, there is a cross connection between
US1 and US2, this will not be noticed during normal operation. The result is
that load voltage US2 is no longer switched off which can lead to a dangerous
state in the system.
In the cabling for the voltages US1 and US2 in the system, suitable
measures must be taken to prevent a cross-connection between the
voltages (e.g. separate cabling of US1 and US2 or a cable with rein-
forced insulation between the two voltages).
If the US2 option is used, the signaling of the US2 states must be
checked (at US2) before the process periphery is started up.
Connector pin
Pin Description
allocation X21
1 +24 V with battery back-up
2 GND
5 US2 +24 V switched
6 GND
9 TD+
11 TD-
10 RD+
12 RD-
- PE
Voltage US2 is switched via contactors Q5 and Q6. The fuse is located on the
CCU_SR.
External PLC In this configuration, the US2 contactor can be checked by deactivating the in-
put “Peripheral contactor (US2)” in the PROFIsafe or CIP Safety telegram.
KRC In this configuration, the US2 contactor can be checked by opening the oper-
ator safety device (safeguard) in “Automatic” or “Automatic External” mode
and releasing the enabling switch in “T1” or “T2” mode.
Fig. 6-13: Equipotential bonding between the manipulator and the robot
controller
The safety functions of the robot controller conform to Category 3 and Perfor-
mance Level d according to EN ISO 13849-1.
For controller variants that are not listed here, please contact KUKA
Deutschland GmbH.
7
T
Transportation
s
No cables may be connected to the robot controller.
The door of the robot controller must be closed.
The robot controller must be upright.
Procedure 1. Attach the lifting tackle with a lifting frame to all 4 transport eyebolts on the
control cabinet.
1 Eyebolts
2 Correctly attached lifting frame
3 Correctly attached lifting tackle
4 Incorrectly attached lifting tackle
Description The robot controller rollers may only be used to roll the cabinet into and out of
a row of cabinets – not to transport the cabinet over longer distances. The floor
must be level and free from obstacles, as there is a permanent risk of toppling.
8.1 Start-up
Overview A connecting cable set is supplied with the industrial robot. In the standard
version this consists of:
Motor cables to the manipulator
Data cables to the manipulator
The following cables may be provided for additional applications:
Motor cables for external axes
Peripheral cables
Procedure
The robot controller is preconfigured for the specific in-
dustrial robot. If cables are interchanged, the manipula-
tor and the external axes (optional) may receive incorrect data and can thus
cause personal injury or material damage. If a system consists of more than
one manipulator, always connect the connecting cables to the manipulators
and their corresponding robot controllers.
1. Route and connect the motor cables to the manipulator junction box sep-
arately from the data cables.
2. Route and connect the motor cables of the external axes.
3. Route the data cables to the manipulator junction box separately from the
motor cable. Plug in connector X21.
4. Connect the peripheral cables.
Fig. 8-2: Equipotential bonding between the manipulator and the robot
controller
Description To prevent the batteries from discharging before the controller has been start-
ed up for the first time, the robot controller is supplied with connector X305 dis-
connected from the CCU_SR.
Description The robot controller is connected to the mains via a Harting connector X1.
Procedure Connect the robot controller to the power supply via X1.
Connector pin
Pin Description
allocation X1
1 L1
2 L2
Pin Description
3 L3
PE PE
Description The system configuration of the industrial robot must be configured using
WorkVisual in the following cases:
New installation of KUKA System Software
Observe compatibility.
Exchanging If a device is exchanged, at least one KCB, KSB or KEB device is replaced by
devices a device of the same type. Any number of KCB, KSB and KEB devices can be
exchanged until all devices in the KCB, KSB and KEB have been replaced si-
multaneously by devices of the same type. Simultaneous exchange of two
identical components of the KCB is not possible. Only one of the identical com-
ponents may be exchanged at any one time.
Description The industrial robot can be set to Start-up mode via the smartHMI user inter-
face. In this mode, the manipulator can be moved in T1 without the external
safeguards being put into operation.
When Start-up mode is possible depends on the safety interface that is used.
Discrete safety interface
Start-up mode is always possible. This also means that it is independent of the
state of the inputs at the discrete safety interface.
If an additional discrete safety interface is used for safety options: The states
of these inputs are also irrelevant.
Ethernet safety interface
The robot controller prevents or terminates Start-up mode if a connection to a
higher-level safety system exists or is established.
Description The industrial robot can be set to Start-up mode via the smartHMI user inter-
face. In this mode, the manipulator can be moved in T1 without the external
safeguards being put into operation.
The safety interface used affects “Start-up” mode:
Discrete safety interface
System Software 8.2 or earlier:
Start-up mode is always possible if all input signals at the discrete safety
interface have the state “logic zero”. If this is not the case, the robot con-
troller prevents or terminates Start-up mode.
If an additional discrete safety interface for safety options is used, the in-
puts there must also have the state “logic zero”.
In Start-up mode, the system switches to the following simulated input image:
The external EMERGENCY STOP is not active.
The safety gate is open.
No safety stop 1 has been requested.
No safety stop 2 has been requested.
No safe operational stop has been requested.
Only for VKR C4: E2/E22 is closed.
If SafeOperation or SafeRangeMonitoring is used, Start-up mode also influ-
ences other signals.
9 Operation
Function The smartPAD is the teach pendant for the industrial robot. The smartPAD has
all the operator control and display functions required for operating and pro-
gramming the industrial robot.
The smartPAD has a touch screen: the smartHMI can be operated with a fin-
ger or stylus. An external mouse or external keyboard is not necessary.
Overview
Item Description
1 Button for disconnecting the smartPAD
2 Mode selector switch. The switch may be one of the following vari-
ants:
With key
Without key
The mode selector switch is used to call the connection manager.
The operating mode can be changed by using the connection man-
ager.
9 Status keys. The status keys are used primarily for setting param-
eters in technology packages. Their exact function depends on the
technology packages installed.
10 Start key: The Start key is used to start a program.
11 Start backwards key: The Start backwards key is used to start a
program backwards. The program is executed step by step.
12 STOP key: The STOP key is used to stop a program that is run-
ning.
13 Keyboard key
Displays the keyboard. It is generally not necessary to press this
key to display the keyboard, as the smartHMI detects when key-
board input is required and displays the keyboard automatically.
Overview
10 Maintenance
Description
t Maintenance work must be performed at the specified maintenance intervals
after commissioning at the customer’s plant.
Maintenance
The overview may contain maintenance symbols that are not relevant
symbols for the maintenance work on this product. The maintenance illustra-
tions provide an overview of the relevant maintenance work.
Oil change
Tighten screw/nut
Clean component
Exchange battery
Precondition The robot controller must be switched off and secured to prevent unau-
thorized persons from switching it on again.
Precondition The robot controller must be switched off and secured to prevent unau-
thorized persons from switching it on again.
Power supply lead disconnected.
Observe the ESD guidelines.
Work regulations The manufacturer’s instructions must be observed when using cleaning
agents for cleaning work.
It must be ensured that no cleaning agents enter electrical components.
Do not use compressed air during cleaning work.
Do not spray with water.
11 Repair
Repair Repairs to the robot controller may only be carried out by KUKA customer sup-
port personnel or by customers who have taken part in a relevant course of
training held by KUKA Deutschland GmbH.
Repairs within modules may only be carried out by specially trained KUKA
Deutschland GmbH personnel.
Procurement of The article numbers of the spare parts are listed in the spare parts catalog.
spare parts KUKA Deutschland GmbH supplies the following types of spare parts for re-
pairs to the robot controller:
New parts
Once the new part has been installed, the part that has been removed can
be disposed of.
Exchange parts
Once the exchange part has been installed, the part that has been re-
moved is returned to KUKA Deutschland GmbH.
A “Robot Repair Card” is supplied with the exchange parts. The Re-
pair Card must be completed and returned to KUKA Deutschland
GmbH.
Description The following instructions describe the exchange of the external fan on a robot
controller.
Overview The instructions are subdivided into the following work steps:
2 Concluding work
(>>> 11.2.3 "Concluding work" Page 90)
Precondition The robot controller must be switched off and secured to prevent unau-
thorized persons from switching it on again.
The power cable must be de-energized.
Work safety
When work is performed on this system, live parts and
unintentional robot motions can cause injuries and dam-
age to property. If work is carried out on an operable system, the main switch
on the control cabinet must be turned to the OFF position and secured with
a padlock to prevent unauthorized persons from switching it on again.
Warn all persons concerned before putting the system back into operation.
Procedure 1. Install the new fan together with its holder and fasten.
After the external fan has been exchanged, the following tasks must be carried
out:
General tasks Boot the controller and look out for irregularities.
Description The following instructions describe the exchange of the drive unit on a robot
controller.
Overview The instructions are subdivided into the following work steps:
2 Concluding work
(>>> 11.3.3 "Concluding work" Page 93)
Precondition The robot controller must be switched off and secured to prevent unau-
thorized persons from switching it on again.
Power supply lead disconnected.
Observe the ESD guidelines.
Wait 5 minutes until the intermediate circuit has discharged.
Work safety
When work is performed on this system, live parts and
unintentional robot motions can cause injuries and dam-
age to property. If work is carried out on an operable system, the main switch
on the control cabinet must be turned to the OFF position and secured with
a padlock to prevent unauthorized persons from switching it on again.
Warn all persons concerned before putting the system back into operation.
2. Unscrew the 2 knurled screws on the front of the drive unit with a hexagon
wrench.
1 Handgrips
2 Knurled screws
Procedure 1. Place the new drive unit on the support rails and fasten with the knurled
screws.
1 Handgrips
2 Knurled screws
2. Plug in the connections of the drive unit in accordance with the connector
and cable labeling.
After the drive unit has been exchanged, the following tasks must be carried
out:
General tasks Check that all of the connectors on the drive unit are fitted securely before
starting up the controller.
Boot the controller and look out for irregularities.
Description The following instructions describe the exchange of the control PC on a robot
controller.
Overview The instructions are subdivided into the following work steps:
2 Concluding work
(>>> 11.4.1.3 "Concluding work" Page 95)
Work safety
When work is performed on this system, live parts and
unintentional robot motions can cause injuries and dam-
age to property. If work is carried out on an operable system, the main switch
on the control cabinet must be turned to the OFF position and secured with
a padlock to prevent unauthorized persons from switching it on again.
Warn all persons concerned before putting the system back into operation.
Procedure
1 Knurled nut
2 Tilt the PC
3 Lift the PC
1. Shut down the robot controller with the settings Cold start and Reload
files.
2. Turn off the robot controller using the main switch and take measures to
prevent it from being turned on again unintentionally.
3. Disconnect the power cable from the supply.
4. Unplug the power supply and all connections to the control PC.
5. Slacken the knurled nuts.
6. Remove the control PC and lift it out towards the top.
Procedure
1 Knurled nut
2 Tilt the PC
3 Lift the PC
After the control PC has been exchanged, the following tasks must be carried
out:
General tasks Boot the controller and look out for irregularities.
11.4.2 PC fan
Description The following instructions describe the exchange of the PC fan on a robot con-
troller.
Overview The instructions are subdivided into the following work steps:
2 Concluding work
(>>> 11.4.2.3 "Concluding work" Page 98)
Precondition The robot controller must be switched off and secured to prevent unau-
thorized persons from switching it on again.
The power cable must be de-energized.
Work safety
When work is performed on this system, live parts and
unintentional robot motions can cause injuries and dam-
age to property. If work is carried out on an operable system, the main switch
on the control cabinet must be turned to the OFF position and secured with
a padlock to prevent unauthorized persons from switching it on again.
Warn all persons concerned before putting the system back into operation.
Procedure 1. Fasten the inner fan grille to the new fan with the expanding rivets.
The fan grille must be fastened to the side with the identification plate.
See (>>> Fig. 11-13 )
After the PC fan has been exchanged, the following tasks must be carried out:
General tasks Boot the controller and look out for irregularities.
Description The following instructions describe the exchange of the SSD hard drive on a
KR C4 controller.
Overview The instructions are subdivided into the following work steps:
2 Concluding work
(>>> 11.4.5.3 "Concluding work" Page 101)
Precondition The robot controller must be switched off and secured to prevent unau-
thorized persons from switching it on again.
The power cable must be de-energized.
Work safety
When work is performed on this system, live parts and
unintentional robot motions can cause injuries and dam-
age to property. If work is carried out on an operable system, the main switch
on the control cabinet must be turned to the OFF position and secured with
a padlock to prevent unauthorized persons from switching it on again.
Warn all persons concerned before putting the system back into operation.
Procedure
1 SATA connector
2 Power supply connector
3 Knurled screws on the underside
Once the hard drive has been exchanged, the following options are
available in addition to configuration using WorkVisual:
Load the archive of the previous installation.
Restore the complete image using the KUKA Recovery Tool.
1 SATA connector
2 Power supply connector
3 Knurled screws on the underside
Procedure 1. Insert the new SSD hard drive into the controller.
2. Plug in the SATA and power supply connectors.
3. Fasten the hard drive with the knurled screws.
4. Install the operating system and the KUKA System Software (KSS).
5. The system configuration of the industrial robot must be configured using
WorkVisual.
Once the hard drive has been exchanged, the following options are
available in addition to configuration using WorkVisual:
Load the archive of the previous installation.
Restore the complete image using the KUKA Recovery Tool.
After the SSD hard drive has been exchanged, the following tasks must be
carried out:
General tasks Boot the controller and look out for irregularities.
Description The following instructions describe the exchange of the batteries on a robot
controller.
Overview The instructions are subdivided into the following work steps:
Precondition The robot controller must be switched off and secured to prevent unau-
thorized persons from switching it on again.
The power cable must be de-energized.
Work safety
When work is performed on this system, live parts and
unintentional robot motions can cause injuries and dam-
age to property. If work is carried out on an operable system, the main switch
on the control cabinet must be turned to the OFF position and secured with
a padlock to prevent unauthorized persons from switching it on again.
Warn all persons concerned before putting the system back into operation.
2. Remove both battery blocks from the battery holder on the side panel of
the robot controller.
3. Insert the new battery blocks and plug in the battery connection cables.
2. Remove both battery blocks from the battery holder on the side panel of
the robot controller.
Procedure
The battery blocks must both be exchanged together.
1. Insert the new battery blocks and plug in the battery connection cables.
After the batteries have been exchanged, the following tasks must be carried
out:
General tasks Check that all of the connectors on the batteries are fitted securely before
starting up the controller.
Boot the controller and look out for irregularities.
Description The following instructions describe the exchange of the low-voltage power
supply unit on a robot controller.
Overview The instructions are subdivided into the following work steps:
2 Concluding work
(>>> 11.6.3 "Concluding work" Page 106)
Precondition The robot controller must be switched off and secured to prevent unau-
thorized persons from switching it on again.
Power supply lead disconnected.
Observe the ESD guidelines.
Wait 5 minutes until the intermediate circuit has discharged.
Work safety
When work is performed on this system, live parts and
unintentional robot motions can cause injuries and dam-
age to property. If work is carried out on an operable system, the main switch
on the control cabinet must be turned to the OFF position and secured with
a padlock to prevent unauthorized persons from switching it on again.
Warn all persons concerned before putting the system back into operation.
Procedure 1. Unscrew the 4 screws from the rear panel of the robot controller and re-
move the rear panel.
Fig. 11-19: Removing the rear panel and low-voltage power supply unit
2. Unplug the connections of the low-voltage power supply unit inside the
cabinet:
Power supply connector X2
CCU_SR power infeed connector X1
PE connector XPE
3. Unscrew 3 fastening screws of the low-voltage power supply unit.
4. Tilt the low-voltage power supply unit forward and lift it out vertically.
Procedure 1. Insert the new low-voltage power supply unit and fasten with 3 screws.
2. Plug in the connections of the low-voltage power supply unit inside the
cabinet:
Power supply connector X2
CCU_SR power infeed connector X1
PE connector XPE
3. Mount the rear panel on the rear of the controller and fasten with 4 screws.
Fig. 11-20: Removing the rear panel and low-voltage power supply unit
After the low-voltage power supply unit has been exchanged, the following
tasks must be carried out:
General tasks Check that all of the connectors on the low-voltage power supply unit are
fitted securely before starting up the controller.
Boot the controller and look out for irregularities.
Description The following instructions describe the exchange of the mains filter on a robot
controller.
Overview The instructions are subdivided into the following work steps:
2 Concluding work
(>>> 11.7.3 "Concluding work" Page 108)
Precondition The robot controller must be switched off and secured to prevent unau-
thorized persons from switching it on again.
Power supply lead disconnected.
Observe the ESD guidelines.
Wait 5 minutes until the intermediate circuit has discharged.
Work safety
When work is performed on this system, live parts and
unintentional robot motions can cause injuries and dam-
age to property. If work is carried out on an operable system, the main switch
on the control cabinet must be turned to the OFF position and secured with
a padlock to prevent unauthorized persons from switching it on again.
Warn all persons concerned before putting the system back into operation.
Fig. 11-21
Procedure
Fig. 11-22
After the mains filter has been exchanged, the following tasks must be carried
out:
General tasks Check that all of the connectors on the mains filter are fitted securely be-
fore starting up the controller.
Boot the controller and look out for irregularities.
Description The following instructions describe the exchange of the ballast resistor on a
robot controller.
Overview The instructions are subdivided into the following work steps:
Precondition The robot controller must be switched off and secured to prevent unau-
thorized persons from switching it on again.
Power supply lead disconnected.
Observe the ESD guidelines.
Wait 5 minutes until the intermediate circuit has discharged.
Work safety
When work is performed on this system, live parts and
unintentional robot motions can cause injuries and dam-
age to property. If work is carried out on an operable system, the main switch
on the control cabinet must be turned to the OFF position and secured with
a padlock to prevent unauthorized persons from switching it on again.
Warn all persons concerned before putting the system back into operation.
1 Fastening screw
2 Connections
1 Fastening screw
2 Connections
1 Fastening screw
2 Connections
After the ballast resistor has been exchanged, the following tasks must be car-
ried out:
General tasks Check that all of the connectors on the ballast resistor are fitted securely
before starting up the controller.
Boot the controller and look out for irregularities.
Description The following instructions describe the exchange of the CCUsr on a robot con-
troller.
Overview The instructions are subdivided into the following work steps:
2 Concluding work
Precondition The robot controller must be switched off and secured to prevent unau-
thorized persons from switching it on again.
Power supply lead disconnected.
Observe the ESD guidelines.
Work safety
When work is performed on this system, live parts and
unintentional robot motions can cause injuries and dam-
age to property. If work is carried out on an operable system, the main switch
on the control cabinet must be turned to the OFF position and secured with
a padlock to prevent unauthorized persons from switching it on again.
Warn all persons concerned before putting the system back into operation.
Connections
Con-
Item Description
nector
1 X46 KSB RoboTeam (yellow)
2 X48 KSB EtherCAT interface (green), optional
3 X45 KSB RoboTeam (red)
4 X29 EDS connection, memory card
5 X23 Fast Measurement inputs 1 to 5
6 X4 KPC supply and power supply fan
7 X307 UL lamp (optional)
8 X12 USB
9 X500 Not used
10 X501 Not used
11 X21 Power supply to RDC/EMD
12 X402 Safe inputs 1 to 3
13 X403 Safe inputs 4 to 7
14 X404 Safe inputs 8 to 9
15 X401 Mastering reference switch
16 X407 Safe input 11, teach pendant plugged in
17 X406 Safe outputs 12 to 15
18 X34 KCB RDC interface (white)
19 X31 KCB KPC interface (blue)
20 X32 KCB KPP interface (orange)
21 X33 I/O board (optional)
22 X41 KSB KPC interface (yellow)
23 X47 KSB spare (red)
24 X44 KSB KEI (white)
25 X43 KSB - KSI (blue)
26 X42 KSB - KOI (orange)
27 X3 Power supply to KPP_SR logic/brakes
28 X5 Power supply to options
29 X22 Power supply to options
30 X305 Battery infeed
31 X6 I/O board power supply without battery backup
(optional)
32 X301 24 V supply, spare
33 X1 Supply
34 X15 Power supply to power supply fan
35 X14 Power supply to external fan
36 X308 External power supply
37 X1700 Board connection to the PMB_SR
38 X405 Safe contactor output 10, single-channel input 10
39 X306 smartPAD power supply
40 X302 I/O board power supply with battery backup
(optional)
41 X25 Alarm contact, Power OK, power supply unit
1. Unlock the data cable connectors. Unplug all connections to the CCU_SR.
2. Remove the screw from the fastening plate and remove the plate together
with the CCU_SR.
1 Tabs
2 Screw of fastening plate with CCU_SR
Procedure 1. Check the new CCU_SR for mechanical damage. Insert the fastening
plate with the CCU_SR and screw it down.
1 Tabs
2 Screw of fastening plate with CCU_SR
2. Plug in all the connections in accordance with the connector and cable la-
beling. Lock the data cable connectors.
After the CCUsr has been exchanged, the following tasks must be carried out:
General tasks Check that all of the connectors on the CCUsr are fitted securely before
starting up the controller.
Boot the controller and look out for irregularities.
12
2
Troubleshooting
T
Overview
t
Overview
A defective fuse is indicated by a red LED next to the fuse. Once the
cause of the fault has been eliminated, defective fuses must be re-
placed with fuses with the value specified in the operating instructions
or printed on the module.
13.1 Decommissioning
s
Description This section describes all the work required for decommissioning the robot
controller if the robot controller is to be removed from the system. After decom-
missioning, it is prepared for storage or for transportation to a different loca-
tion.
Following its removal, the robot controller may only be transported with lifting
tackle and a fork lift truck or pallet truck.
Precondition The removal site must be accessible with a crane or with a fork lift truck for
transportation.
The crane and fork lift truck have an adequate carrying capacity.
There is no hazard posed by system components.
13.2 Storage
Precondition If the robot controller is to be put into long-term storage, the following points
must be observed:
The place of storage must be as dry and dust-free as possible.
Avoid temperature fluctuations.
Avoid wind and drafts.
Avoid condensation.
Observe and comply with the permissible temperature ranges for storage.
Select a storage location in which the packaging materials cannot be dam-
aged.
Only store the robot controller indoors.
Procedure 1. Clean robot controller. No dirt may remain on or in the robot controller.
2. Inspect the robot controller, both internally and externally, for damage.
3. Remove batteries and store in accordance with the manufacturer’s instruc-
tions.
4. Remove any foreign bodies.
5. Remove any corrosion expertly.
6. Attach all covers to the robot controller and check that the seals are cor-
rectly in place.
7. Seal off electrical connections with suitable covers.
8. Cover the robot controller with plastic film and seal it against dust.
If necessary, add a desiccant beneath the sheeting.
13.3 Disposal
When the robot controller reaches the end of its useful life, it can be disman-
tled, and the materials can be disposed of properly by type.
The following table provides an overview of the materials used in the robot
controller. Some of the plastic components are marked with a material desig-
nation and must be disposed of accordingly.
Subassembly, com-
Material, designation Note
ponent
Steel Screws and washers, -
robot controller hous-
ing
PUR Cable sheaths -
ETFE Flexible tube -
Copper Electrical cables, wires -
EPDM Seals and covers -
CuZn (gold-plated) Connectors, contacts Dispose of without dis-
mantling
Steel (ST 52-3) Allen screws, washers -
PE Cable straps -
Electrical components Bus modules, boards, Dispose of as electri-
sensors cal scrap without dis-
assembling
14
4
KUKA Service
A
Availability KUKA Customer Support is available in many countries. Please do not hesi-
tate to contact us if you have any questions.
Index
Numbers Control PC, functions 12
2006/42/EU2006 52 Control PC, installing 95
2014/30/EU2014 52 Control PC, removing 94
2014/68/EU2014 52 Control unit 22
95/16/EC 52 Cooling, cabinet 18
Counterbalancing system 50
A
Accessories 29 D
Ambient conditions 21 Danger zone 30
Ambient temperature 21 DC 12
ANSI/RIA R.15.06-2012 53 Declaration of conformity 30
Applied norms and regulations 52 Declaration of incorporation 29, 30
Automatic mode 49 Decommissioning 51, 123
Axis limitation, mechanical 40 defective fuses 121
Axis range 30 Device connection cable 56
Dimensions 24
B Dimensions of boreholes 25
Ballast resistor, exchanging 108 Dimensions, smartPAD holder 26
Ballast resistor, installing 111 Disposal 51, 123
Ballast resistor, removing 110 Drive Configuration 12
Batteries 16 Drive unit 12
Batteries, exchanging 101 Drive unit, exchanging 90
Batteries, installing 103 Drive unit, installing 92
Batteries, removing 102 Drive unit, removing 92
Batteries, storage temperature 21 Dynamic testing 64
Battery discharge protection, reversing 75
Brake defect 42 E
Brake release device 41 EA 8
Braking distance 30 EC declaration of conformity 30
EDS 7
C Electromagnetic compatibility (EMC) 53
Cabinet Control Unit LED display 117 Electromagnetic compatibility, EMC 55
Cabinet Control Unit Small Robot, fuses 121 EMC 7
Cabinet Control Unit, Small Robot 15 EMC Directive 30, 52
Cabinet cooling 18 EMD 7
Cabinet Interface Board, Small Robot 15, 23 EMERGENCY STOP 80
Cable lengths 22, 55 EMERGENCY STOP device 37, 38, 42
CCU_SR 7, 15 EMERGENCY STOP devices to X11 62
CCU_SR functions 15 EMERGENCY STOP wiring example 62
CCU_SR LED display, overview 117 EMERGENCY STOP, external 38, 45
CCU_SR relay outputs, checking 84 EMERGENCY STOP, local 45
CCUsr, exchanging 111 EN 60204-12006/A12009 53
CCUsr, installing 114 EN 61000-6-22005 53
CCUsr, removing 112 EN 61000-6-42007 + A12011 53
CE mark 30 EN 614-12006+A12009 53
Charge 16 EN ISO 10218-12011 53
CIB_SR 7, 23 EN ISO 121002010 53
CIB_SR inputs 23 EN ISO 13849-12015 52
CIB_SR outputs 23 EN ISO 13849-22012 52
CIP Safety 7 EN ISO 138502015 52
Cleaning work 50 Enabling device 38, 42
Connecting cables 29 Enabling device, external 39
Connecting cables, connecting 73 Enabling switch 81
Connection conditions, planning 55 Enabling switch, external, X11 61
Connection manager 80 Enabling switches 38
Control PC 12 Environmental conditions 21
Control PC components, exchanging 93 Equipotential bonding 68
Control PC, exchanging 93 Exchanging devices 76
Training 9
Transient limiter, description 19
Transportation 43, 71
Transportation, lifting tackle 71
Transportation, pallet truck 72
Transportation, set of rollers 72
Troubleshooting 117
Turn-tilt table 29
U
US2 47
US2 function, checking 68
USB 8
USB connection 81
Use, contrary to intended use 29
Use, improper 29
User 30, 32
V
Velocity monitoring 39
Vibration excitation 22
Vibration resistance 22
W
Warnings 7
Workspace 30, 33
X
X11, contact diagram 59
X11, enabling switch 61
X11, safety interface 59
X19, KUKA smartPAD 66
X20, motor connector 57
X21 US2, RDC interface 67
X21, RDC interface 66