ECP200 BASE 2 / 4 User Manual

This document provides the use and maintenance manual for the ECP200 BASE 2/4 electrical control boards for refrigeration installations. It includes 5 chapters that cover an introduction to the product, installation instructions, technical characteristics, warranty information, and parameter programming details. The introduction defines the general purpose and applications of the ECP200 BASE control panels and provides identification data. The installation chapter outlines important information for installers and includes diagrams of the standard installation process. The technical characteristics section lists the power supply details and climatic operating conditions for the control boards.

Uploaded by

roksandic.damir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
307 views28 pages

ECP200 BASE 2 / 4 User Manual

This document provides the use and maintenance manual for the ECP200 BASE 2/4 electrical control boards for refrigeration installations. It includes 5 chapters that cover an introduction to the product, installation instructions, technical characteristics, warranty information, and parameter programming details. The introduction defines the general purpose and applications of the ECP200 BASE control panels and provides identification data. The installation chapter outlines important information for installers and includes diagrams of the standard installation process. The technical characteristics section lists the power supply details and climatic operating conditions for the control boards.

Uploaded by

roksandic.damir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 28

ECP200 BASE 2 / 4

Use and maintenance manual

READ AND KEEP

REV. 01-18 ELECTRICAL BOARDS FOR REFRIGERATING INSTALLATIONS


ENG
ECP200 BASE 2/4

ENGLISH

INTRODUCTION
CHAP. 1
Pag. 3 1.1 General
Pag. 4 1.2 Product ID codes
Pag. 4 1.3 Overall dimensions
Pag. 5 1.4 Identification data
INSTALLATION
CHAP. 2
Pag. 5 2.1 Important information for the installer
Pag. 5 2.2 Standard assembly kit
Pag. 6 2.3 Installing the unit
TECHNICAL CHARACTERISTICS
CHAP. 3
Pag. 7 3.1 Technical characteristics
WARRANTY
CHAP. 4
Pag. 8 4.1 Warranty
PARAMETER PROGRAMMING
CHAP. 5
Pag. 9 5.1 Control panel
Pag. 9 5.2 Frontal keypad
Pag. 10 5.3 LED display
Pag. 11 5.4 General
Pag. 11 5.5 Key to symbols
Pag. 11 5.6 Setting and displaying set points
Pag. 12 5.7 Level 1 programming
Pag: 12 5.8 List of Level 1 variables
Pag. 13 5.9 Level 2 programming
Pag. 13 5.10 List of Level 2 variables
Pag. 15 5.11 Switching on the ECP200 BASE electronic controller
Pag. 15 5.12 Compressor activation/deactivation conditions
Pag. 15 5.13 Manual defrosting
Pag. 16 5.14 Hot gas defrosting
Pag. 16 5.15 Pump down function
Pag. 16 5.16 Password protection
OPTION
CHAP. 6
Pag. 17 6.1 TeleNET monitoring / supervision system
Pag. 17 6.2 Net configuration with Modbus-rtu protocol
Pag. 18 6.3 ALARM RELAY / RS485 switching
TROUBLESHOOTING
CHAP. 7
Pag. 19 7.1 Troubleshooting
APPENDICES
Pag. 20 A.1 EU declaration of conformity
Pag. 21 A.2 ECP200 BASE 4 wiring diagram
Pag. 21 A.3 ECP200 BASE 4A wiring diagram
Pag. 22 A.4 ECP200 BASE 2 wiring diagram
Pag. 22 A.5 ECP200 BASE 2A wiring diagram
Pag. 23 A.6 Connection example (1) - ECP200 BASE4 /BASE4A
Pag. 23 A.7 Connection example (2) - ECP200 BASE4 /BASE4A
Pag. 24 A.8 Connection example (3) - ECP200 BASE2 /BASE2A
Pag. 24 A.9 Connection example (4) - ECP200 BASE2 /BASE2A
CHAP. 1 - Introduction ECP200 BASE 2/4

CHAPTER 1: INTRODUCTION

GENERAL 1.1

DESCRIPTION:
The ECP200 BASE is a new control panel for cold rooms with a single-phase compressor
up to 2HP, specially designed to provide the user with safety, protection, control and ease
of installation.
It allows the user to control all the components on a refrigerating system: compressor,
evaporator fans, defrosting elements, room light and thermostat-holder demisting element.

APPLICATIONS:
- Complete management of single-phase static or ventilated refrigeration systems up to
2HP, with off-cycle or electrical defrosting and with direct or pump-down compressor
stop.
- Control of single-phase evaporator unit only with freon solenoid enable signal or remote
condensing unit enable signal.

MAIN CHARACTERISTICS:
- Cold room temperature displaying and regulation with decimal point.
- Evaporator temperature displaying from parameter.
- Plant control activation/deactivation.
- Plant alarms signaling (probe error, minimum and maximum temperature alarm,
compressor protection).
- LED indicators and large display illustrate system status.
- User-friendly keypad.
- Evaporator fans management.
- Manual and automatic defrost (static, through heaters, through cycle reversal).
- Direct or pump-down management and control of condensing unit up to 2HP.
- Cold room light activation through key on the panel or through door-switch.
- Direct control of compressor, defrosting elements, evaporator fans, room light with
outputs directly connectable to the various units.
- Auxiliary relay with parameter-configured.
- Possibility, as an alternative to an auxiliary relay, of a RS485 port for connection to the
TeleNET supervision net or to a net with MODBUS-RTU protocol.

Rev. 01-18 USE AND MAINTENANCE MANUAL Page 3


ECP200 BASE 2/4 CHAP. 1 - Introduction

1.2 PRODUCT ID CODES

ECP200 BASE 2 Controls and manages compressor and


room light.

ECP200 BASE 2 A Controls and manages compressor and


room light. Alarms relay.

ECP200 BASE 4 Controls and manages compressor,


defrosting elements, evaporator fans and
room light.

ECP200 BASE 4 A Controls and manages compressor,


defrosting elements, evaporator fans and
room light. Alarms relay.

1.3 OVERALL DIMENSIONS

Page 4 USE AND MAINTENANCE MANUAL Rev. 01-18


CHAP. 2 - Installation ECP200 BASE 2/4

IDENTIFICATION DATA 1.4


The unit described in this manual has an ID plate on the side showing all the relevant
identification data:

• Name of Manufacturer
• Code of the electrical board
• Serial number
• Date
• Power supply
• IP protection rating
• Operating temperature

CHAPTER 2: INSTALLATION

IMPORTANT INFORMATION FOR THE INSTALLER 2.1

1. Install the device in places where the protection rating is observed and try not to
damage the box when drilling holes for wire/pipe seats.

2. Do not use multi-polar cables in which there are wires connected to inductive/power
loads or signalling wires (e.g. probes/sensors and digital inputs).

3. Do not fit power supply wiring and signal wiring (probes/sensors and digital inputs) in
the same raceways or ducts.

4. Minimise the length of connector wires so that wiring does not twist into a spiral shape
as this could have negative effects on the electronics.

5. Fit a general protection fuse upstream from the electronic controller.

6. All wiring must be of a cross-section suitable for relevant power levels.

7. When it is necessary to make a probe/sensor extension, the wires must have a cross-
section of at least 1mm2. Probes extension or shortening could alter their factory
calibration; therefore to check and calibrate the probes through an external thermometer.

STANDARD ASSEMBLY KIT 2.2

For the purposes of assembly and use, the electronic ECP200 BASE control unit comes
with:

• N° 3 seals, to be fitted between the fixing screws and the box back panel;
• N° 1 user’s manual.

Rev. 01-18 USE AND MAINTENANCE MANUAL Page 5


ECP200 BASE 2/4 CHAP. 2 - Installation

2.3 INSTALLING THE UNIT

Fig. 1: Undo the 4 screws on the front of the panel.

Fig. 2: Use the three existing holes to fix the box back panel
to the wall: use three screws of a length suitable for the
thickness of the wall to which the panel will be attached. Fit a
rubber washer (supplied) between each screw and the box
backing.

Make all the electrical connections as illustrated in the diagram for the corresponding
model (see relative table in APPENDICES).
To effect correct electrical connection and maintain the protection rating, use
appropriate wire/raceway grips to ensure a good seal. 
Route the wiring inside the unit in as tidy a fashion as possible: be especially careful to keep power
wires away from signal wires. Use clips to hold wires in place.

Fig. 3: Close the front panel, making sure that all the wires are
inside the box and that the box seal sits in its seat properly.
Tighten the front panel using the 4 screws, making sure the O-rings
on the head of each screw are used.
Power up the panel and carry out thorough reading/programming of
all the parameters.

Be careful not to over-tighten the closure screws as this could warp the box and
compromise proper operation of the membrane-type keypad.
Install short-circuit overload safety devices on all the power cables connected to the
ECP200 controller so as to prevent damage to the device. Work and/or maintenance 
must ONLY be carried out on the unit after disconnecting the panel from the power supply and
from any inductive/power loads: doing so allows the worker to do his job safely.

Page 6 USE AND MAINTENANCE MANUAL Rev. 01-18


CHAP. 3 - Technical characteristics ECP200 BASE 2/4

CHAPTER 3: TECHNICAL CHARACTERISTICS

TECHNICAL CHARACTERISTICS 3.1

Power supply
Voltage 230 V~  10% 50/60Hz
Max power (only electronics) ~ 7 VA
Rated current
16A
(With all loads connected)
Climatic conditions
Working temperature -5 ÷ +50°C
Storage temperature -10 ÷ +70°C
Relative ambient humidity Lower than 90% Hr
General characteristics
Type of sensors that can be connected NTC 10K 1%
Resolution 0,1 °C.
Sensor read precision ± 0,5 °C
Read range -45 ÷ +45 °C
Output characteristics (free voltage contact)
Description Installed relay Card output characteristics BASE 2 BASE4

Compressor (Relay 30A AC1) 10A 250V~ (AC3) (2HP) X X


(100000 cycles)
Elements (Relay 30A AC1) 16A 250V~ (AC1) X

Fans (Relay 16A AC1) 2,7A 250V~ (AC3) X

Room light (Relay 16A AC1) 16A 250V~ (AC1) X X


X X
Alarm / Aux (Optional) (Relay 8A AC1) 8(3)A 250V~ optional optional
Dimensional characteristics
Dimensions 19.3cm x 7.9cm x 20.3cm (HxPxL)
Insulation / mechanical characteristics
Box protection rating IP65
Box material ABS autoestinguente
Type of insulation Class II

Rev. 01-18 USE AND MAINTENANCE MANUAL Page 7


ECP200 BASE 2/4 CHAP. 4 – Warranty

CHAPTER 4: WARRANTY

4.1 WARRANTY

ECP200 BASE series products are covered by a 24-months warranty against all
manufacturing defects as from the date indicated on the product ID code.
In case of defect the product must be appropriately packaged and sent to our production
plant or to any authorized Service Center with the prior request of the Return Authorization
Number.
Customers are entitled to have defective products repaired, spare parts and labour
included. The costs and the risks of transport are at the total charge of the Customer.
Any warranty action does not extend or renew its expiration.
The Warranty does not cover:
 Damages resulting from tampering, impact or improper installation of the product and
its accessories.
 Installation, use or maintenance that does not comply with the instructions provided
with the product.
 Repair work carried out by unauthorized personnel.
 Damage due to natural phenomena such as lightning, natural disasters, etc…
In all these cases the costs for repair will be charged to the customer.
The intervention service in warranty can be refused when the equipment is modified or
transformed.
Under no circumstances Pego S.r.l. will be liable for any loss of data and information,
costs of goods or substitute services, damage to property, people or animals, loss of sales
or earnings, business interruption, any direct, indirect, incidental, consequential,
damaging, punitive, special or consequential damages, in any way whatsoever caused,
whether they are contractual, extra contractual or due to negligence or other liability arising
from the use of the product or its installation.
Malfunction caused by tampering, bumps, inadequate installation automatically declines
the warranty. It is compulsory to observe all the instructions in this manual and the
operating conditions of the product.
Pego S.r.l. disclaims any liability for possible inaccuracies contained in this manual if due
to errors in printing or transcription.
Pego S.r.l. reserves the right to make changes to its products which it deems necessary
or useful without affecting its essential characteristics.
Each new release of the PEGO product user manual replaces all the previous ones.
As far as not expressly indicated, is applicable the Law and in particular the art. 1512 C.C.
(Italian Civil Code).
For any controversy is elected and recognized by the parties the jurisdiction of the Court of
Rovigo.

Page 8 USE AND MAINTENANCE MANUAL Rev. 01-18


CHAP. 5 - Parameter programming ECP200 BASE 2/4

CHAPTER 5: PARAMETER PROGRAMMING

CONTROL PANEL 5.1

  

    

 FRONT KEYPAD 5.2


 AUXILIARY RELAY CONTROL (on the version with alarm relay, it manually
controls the relay if parameter AU=1)

 UP / MUTE BUZZER ALARM

 STAND BY (the system shuts down and the LED flashes)

 Room temperature SETTING

Rev. 01-18 USE AND MAINTENANCE MANUAL Page 9


ECP200 BASE 2/4 CHAP. 5 - Parameter programming

 DOWN / MANUAL DEFROST

 ROOM LIGHT

5.3 LED DISPLAY

 Cold room temperature / parameters

 Stand-by (flashes on stand-by. Outputs are deactivated)

 Room light (flashes if door switch activated)

 Cold (indicates activation of compressor)

Fans

Defrosting

Ausiliary

Alarm/warning

Page 10 USE AND MAINTENANCE MANUAL Rev. 01-18


CHAP. 5 - Parameter programming ECP200 BASE 2/4

GENERAL 5.4

To enhance safety and simplify the operator’s work, the ECP200 BASE has two
programming levels; the first level (Level 1) is used to configure the frequently-modified
SETPOINT parameters. The second programming level (Level 2) is for general parameter
programming of the various controller work modes.

It is not possible to access the Level 2 programming directly from Level 1: you must exit
the programming mode first.

KEY TO SYMBOLS 5.5

For purposes of practicality the following symbols are used:

• () the UP key is used to increase values and mute the alarm.

• () the DOWN key is used to decrease values and force defrosting.

SETTING AND DISPLAYING THE SET POINTS 5.6

1. Press the SET key to display the current SETPOINT (temperature).


2. Hold down the SET key and press the () or () keys to modify the SETPOINT.
Release the SET key to return to cold room temperature display: the new setting will be
saved automatically.

Rev. 01-18 USE AND MAINTENANCE MANUAL Page 11


ECP200 BASE 2/4

LEVEL 1 PROGRAMMING (User level)


5.7
To gain access to the Level 1 configuration menu proceed as follows:
1. Press the () and () keys simultaneously and keep them pressed for a few seconds
until the first programming variable appears on the display.
2. Release the () and () keys.
3. Select the variable to be modified using the () or () key.
4. When the variable has been selected it is possible:
• To display the setting by pressing SET key.
• To modify the setting by pressing the SET key together with the () or () key.
When configuration values have been set you can exit the menu by pressing the () and
() keys simultaneously for a few seconds until the cold room temperature reappears.
5. The new settings are saved automatically when you exit the configuration menu.

5.8 LIST OF LEVEL 1 VARIABLES (User level)

VARIABLES MEANING VALUE DEFAULT

r0 Temperature difference compared to main SETPOINT 0.2 - 10 °C 2°C


d0 Defrost interval (hours) 0 - 24 hours 4 hours
End-of-defrost setpoint.
Defrost is not executed if the temperature read by the
d2 -35 - 45 °C 15°C
defrost sensor is greater than d2
(If the sensor is faulty defrosting is timed)
d3 Max defrost duration (minutes) 1 - 240 min 25 min
Drip duration (minutes)
At the end of defrost the compressor and fans remain at
d7 0 - 10 min 0 min
standstill for time d7, the defrost LED on the front panel
flashes.
Fan pause after defrost (minutes)
Allows fans to be kept at standstill for a time F5 after
F5 dripping. This time begins at the end of dripping. If no 0 - 10 min 0 min
dripping has been set the fan pause starts directly at the end
of defrost.
Minimum temperature alarm
Allows user to define a minimum temperature for the room
A1 being refrigerated. Below value A1 an alarm trips: the alarm - -45°C
LED flashes, displayed temperature flashes and the buzzer
sounds to indicate the problem.
Maximum temperature alarm
Allows user to define a maximum temperature for the room
A2 being refrigerated. Above value A2 an alarm trips: the alarm - +45°C
LED flashes, displayed temperature flashes and the buzzer
sounds to indicate the problem.

Displays
evaporator
Evaporator sensor temperature display
tEu temperature read only
(displays nothing if dE =1)
(displays nothing
if dE =1)

Page 12 USE AND MAINTENANCE MANUAL Rev. 01-18


CHAP. 5 - Parameter programming ECP200 BASE 2/4

LEVEL 2 PROGRAMMING (Installer level) 5.9

To access the second programming level press the UP () and DOWN () keys and the
LIGHT key simultaneously for a few seconds.
When the first programming variable appears the system automatically goes to stand-by.
1. Select the variable to be modified by pressing the UP () and DOWN () keys.
When the parameter has been selected it is possible to:
2. View the setting by pressing the SET key.
3. Modify the setting by holding the SET key down and pressing the () or () key.
4. When configuration settings have been completed you can exit the menu by pressing
the () and () keys simultaneously and keeping them pressed until the room
temperature reappears.
5. Changes are saved automatically when you exit the configuration menu.
6. Press the STAND-BY key to enable electronic control.

LIST OF LEVEL 2 VARIABLES (Installer level) 5.10

VARIABLES MEANING VALUES DEFAULT


0 = normally open
AC Door switch status (with door closed) 0
1 = normally closed
0 = Fans run continuously
Fan status with compressor off
F3 1 = Fans only run when 1
compressor is working
0 = Fans run during defrost
F4 Fan pause during defrost 1 = Fans do not run during 1
defrost
Sensor presence
If the evaporator sensor is disabled
defrosts are carried out cyclically with 0 = evaporator sensor present
dE 0
period d0: defrosting ends when an 1 = no evaporator sensor
external device trips and closes the remote
defrost contact or when time d3 expires.
Defrost type, cycle inversion (hot gas) or 1 = hot gas
d1 0
with heater elements 0 = element
Net address for connection to TeleNET 0 ÷ 31 (with AU=3)
Ad 0
supervision system or Modbus 1 ÷ 247 (with AU=7)
Minimum and maximum temperature
Ald 1…240 min 120 min
signalling and alarm display delay

Rev. 01-18 USE AND MAINTENANCE MANUAL Page 13


ECP200 BASE 2/4 CHAP. 5 - Parameter programming

Minimum time between shutdown and


C1 subsequent switching on of the 0…15 min 0 min
compressor.
CAL Cold room sensor value correction -10…+10 0

0 = NO
Pc Compressor protection contact status 0 = NO
1 = NC
Compressor safety time for door
switch: when the door is opened the
doC evaporator fans shut down and the 0…5 min 0
compressor will continue working for time
doC, after which it will shut down.
Compressor restart time after door
opening. when the door is opened and 0…240 min
tdo after tdo time, it’s setted back the normal 0
functioning giving door open alarm (Ed) 0 = disabled
With tdo=0 the parameter is disabled.
FAN shutdown TEMPERATURE
The fans will stop if the temperature value
Fst -45…+45°C +45°C
read by the evaporator sensor is higher
than this value.
Fd Fst differential 0…+10°C 2°C

LSE Minimum value attributable to setpoint. -45... HSE °C -45°C

HSE Maximum value attributable to setpoint. +45... LSE °C +45°C


0 = activates when alarm is
on
tA NO – NC alarm relay switching 1
1 = deactivates when alarm is
on
0 = alarm relay
1 = manual auxiliary relay
controlled via AUX key
2 = automatic auxiliary relay
managed by StA temp.
setting with 2°C differential
3 = relay disabled / TeleNET
function
4 = pump down function
(see CHAP 5.15)
AU Auxiliary/alarm relay control 0
5 = free voltage contact for
condensing unit (AUX relay
and compressor relay in
parallel)
6 = contact for casing element
control (AUX relay closed
with compressor output
inactive).
7 = relay disabled / Modbus-
RTU function
StA Temp. setting for aux. relay -45…+45°C 0
Man in cold room alarm
Select input INP1 on the board as 0 = compressor protection
In1 0
compressor protection alarm or as man in 1 = man in room alarm
cold room alarm (contact NC).

Page 14 USE AND MAINTENANCE MANUAL Rev. 01-18


CHAP. 5 - Parameter programming ECP200 BASE 2/4

0 = only display set point


1 = display set point, AUX,
light access
Password type of protection 2 = access in programming
P1 3
( active when PA is not equal 0) not permitted
3 = access in second level
programming not
permitted
Password 0...999
PA 0
(see P1 for the type of protection) 0 = not active
7
reL Software release indicates software version
(Read only)

SWITCHING ON THE ECP200 BASE ELECTRONIC CONTROLLER 5.11


After wiring the electronic controller correctly, power up at 230 V AC; the display panel will
immediately emit a beep and all the LEDs will come on simultaneously for a few seconds.

COMPRESSOR ACTIVATION/DEACTIVATION CONDITIONS 5.12


The ECP200 BASE controller activates the compressor when cold room temperature
exceeds setting+differential (r0); it deactivates the compressor when cold room
temperature is lower than the setting. If the Pump-down function is selected (Parameter
AU=4) refer to chapter 5.15 for the compressor activation / deactivation conditions.

MANUAL DEFROSTING 5.13

To defrost just press the dedicated key (see section 5.2) to activate the elements relay.
Defrosting will not take place if the end-of-defrost temperature setting (d2) is lower than
the temperature detected by the evaporator sensor. Defrosting ends when the end-of-
defrost temperature (d2) or maximum defrost time (d3) is reached.

Rev. 01-18 USE AND MAINTENANCE MANUAL Page 15


ECP200 BASE 2/4

5.14 HOT GAS DEFROSTING

Set parameter d1=1 to defrost in cycle inversion mode.


The compressor relay and defrost relay are activated throughout the defrost phase.
To ensure proper control of the system the installer must use the defrost output: this must
allow opening of the cycle inversion solenoid valve and closure of the liquid solenoid valve.
For capillary systems (without thermostat valve) it is only necessary to control the cycle
inversion solenoid valve via the defrost relay control.

5.15 PUMP DOWN FUNCTION

Pump down function is activated when parameter AU=4.


Connect pump down pressostat on the digital input 1-3. The compressor is directly
controlled by pressostat.
Connect evaporator solenoid valve on the AUX relay. The solenoid is controlled directly by
thermostat.

5.16 PASSWORD FUNCTION

When parameter PA is setting with value different to 0 the protection function is activated.
See parameter P1 for the different protection.
When PA is setting the protection start after two minutes of inactivity. On display appear
000. With up/down modify the number, with set key confirm it.
Use universal number 100 if you don’t remember the password.

Page 16 USE AND MAINTENANCE MANUAL Rev. 01-18


CHAP. 6 - Optional kits ECP200 BASE 2/4

CHAPTER 6: OPTIONAL KIT

TeleNET MONITORING/SUPERVISION SYSTEM 6.1


For TeleNET connections to enable RS485 as indicated at chapter 6.3 and follow the
scheme below. Refer to TeleNET user manual for instrument configuration.

WARNING: During configuration, at entry “Module” to select the entry "Instrument ECP
Base Series / ECP Expert Series ".

NET CONFIGURATION WITH MODBUS-RTU PROTOCOL 6.2


For RS485 connections with Modbus-RTU protocol, to enable RS485 output as indicated
at chapter 6.3 and follow the scheme below.
Refer to MODBUS-RTU_ECP200T1 user manual (available on Pego Internet web site) for
MODBUS-RTU communication protocol specification.

Rev. 01-18 USE AND MAINTENANCE MANUAL Page 17


ECP200 BASE 2/4 CAP. 6 - Opzioni

6.3 ALARM RELAY / RS485 SWITCHING

Open the front of the box as described in Chap. 2.3 (page 6): rotate it downwards 180° to
gain access to the electronic board

Undo the 6 CPU board fixing screws: remove the board from the frontal part of the box in
ABS.

Configure the jumper from JUMPER JP2


(placed on the front of electrical board near
the display far down on the right) following
one of the ensuing options.

RS485 output selection:


Insert the jumper JP2 on 3-2 position and set
the 2nd level variable AU=3 (TeleNET) or
AU=7 (Modbus-RTU).
The connection clamps are RS485_(A) and
RS485_(B) on board of electrical board.
Remember besides to assign an univocal net
address in the current instruments net. (Ad
2nd level parameter).
Warning! with this configuration auxiliary relay
is disabled.

AUX/Alarm relay selection:


Insert the jumper JP2 in 2-1 position and set
the 2nd level variable AU to a value different
from 3 and 7 according to the needed
function. Clamps of configurable relay clean
contact are on AUX/ALL output, on board of
electronic board.
Warning! with this configuration RS485
connection is disabled.

Page 18 USE AND MAINTENANCE MANUAL Rev. 01-18


CHAP. 7 - Troubleshooting ECP200 BASE 2/4

CHAPTER 7: TROUBLESHOOTING

TROUBLESHOOTING 7.1
In the event of any anomalies the ECP200 BASE warns the operator by displaying alarm codes
and sounding the warning buzzer inside the control panel. If an alarm is tripped the display will
show one of the following messages.

ALARM CODE POSSIBLE CAUSE SOLUTION

 Check that cold room temperature


sensor is working properly
E0 Cold room temperature sensor not working properly
 If the problem persists replace the
sensor

 Check that defrost sensor is


Defrost sensor not working properly working properly
E1
(In this case defrosts will last time d3)  If the problems persists replace
the sensor
Eeprom alarm
E2 An EEPROM memory alarm has been detected  Switch unit off and back on
(All outputs except the alarm one are deactivated)
 Reset the alarm input inside the
E8 Man in cold room alarm
cold room
 Check that compressor is working
Compressor protection tripped (e.g. thermal
properly
protection or max pressure switch)
Ec  Check compressor absorption
(All outputs except the alarm one – where applicable
– are deactivated)  If the problem persists contact the
technical assistance service

 Check door switch status


Open door Alarm. When the door is opened and after
 Check door switch connections
Ed tdo time, it’s setted back the normal functioning
giving door open alarm (Ed)  If the problem persists contact the
technical assistance service

 Check that the compressor is


Temperature Minimum or maximum temperature alarm.
working properly.
shown on The temperature inside the cold room has exceeded
display is  Sensor not reading temperature
the min. or max. temperature alarm setting (see
flashing variables A1 and A2, user programming level) properly or compressor start/stop
control not working.

Rev. 01-18 USE AND MAINTENANCE MANUAL Page 19


Appendices
ECP200 BASE 2/4

APPENDICES

A.1 EU DECLARATION OF CONFORMITY

LA PRESENTE DICHIARAZIONE DI CONFORMITA’ E’ RILASCIATA SOTTO LA RESPONSABILITA’ ESCLUSIVA


DEL FABBRICANTE:
THIS DECLARATION OF CONFORMITY IS ISSUED UNDER THE EXCLUSIVE RESPONSIBILITY OF THE
MANUFACTURER:

PEGO S.r.l. Via Piacentina 6/b, 45030 Occhiobello (RO) – Italy –

DENOMINAZIONE DEL PRODOTTO IN OGGETTO / DENOMINATION OF THE PRODUCT IN OBJECT

MOD.: ECP200 BASE 2 - ECP200 BASE 2 A - ECP200 BASE 4 - ECP200 BASE 4 A

IL PRODOTTO DI CUI SOPRA E’ CONFORME ALLA PERTINENTE NORMATIVA DI ARMONIZZAZIONE


DELL’UNIONE EUROPEA:
THE PRODUCT IS IN CONFORMITY WITH THE RELEVANT EUROPEAN HARMONIZATION LEGISLATION:

Direttiva Bassa Tensione (LVD): 2014/35/UE


Low voltage directive (LVD): 2014/35/EU
Direttiva EMC: 2014/30/UE
Electromagnetic compatibility (EMC): 2014/30/EU

LA CONFORMITA’ PRESCRITTA DALLA DIRETTIVA E’ GARANTITA DALL’ADEMPIMENTO A TUTTI GLI EFFETTI


DELLE SEGUENTI NORME:
THE CONFORMITY REQUIRED BY THE DIRECTIVE IS GUARANTEED BY THE FULFILLMENT TO THE
FOLLOWING STANDARDS:

Norme armonizzate: EN 60730-1:2016, EN 60730-2-9:2010,EN 61000-6–1:2007, EN 61000-6–3:2007


European standards: EN 60730-1:2016, EN 60730-2-9:2010, EN 61000-6–1:2007, EN 61000-6–3:2007

IL PRODOTTO E’ COSTITUITO PER ESSERE INCORPORATO IN UNA MACCHINA O PER ESSERE ASSEMBLATO
CON ALTRI MACCHINARI PER COSTITUIRE UNA MACCHINA CONSIDERATE DALLA DIRETTIVA: 2006/42/CE
“Direttiva Macchine”.
THE PRODUCT HAS BEEN MANUFACTURED TO BE INCLUDED IN A MACHINE OR TO BE ASSEMBLED
TOGHETER WITH OTHER MACHINERY TO COMPLETE A MACHINE ACCORDING TO DIRECTIVE: EC/2006/42
“Machinery Directive”.

Firmato per nome e per conto di: Luogo e Data del rilascio:
Signed for and on behalf of: Place and Date of Release:

Occhiobello (RO), 08/01/2018

Page 20 USE AND MAINTENANCE MANUAL Rev. 01-18


Appendices ECP200 BASE 2/4

ECP200 BASE4 WIRING DIAGRAM A.2

Voltage free contact

ECP200 BASE4A WIRING DIAGRAM A.3

Optional
(See option
chapter)

Voltage free contact

Rev. 01-18 USE AND MAINTENANCE MANUAL Page 21


ECP200 BASE 2/4 Appendices

A.4 ECP200 BASE2 WIRING DIAGRAM

Voltage free contact

A.5 ECP200 BASE2A WIRING DIAGRAM

Optional
(See option
chapter)

Voltage free contact

Page 22 USE AND MAINTENANCE MANUAL Rev. 01-18


Appendices ECP200 BASE 2/4

CONNECTION EXAMPLE (1) - ECP200 BASE4 /BASE4A A.6


Connection with outputs powered for direct control of functions.

CONNECTION EXAMPLE (2) - ECP200 BASE4 /BASE4A A.7


Mixed connection with on/off contact to enable towards condensing unit power
board and fan, light and defrost outputs powered for direct control.

Rev. 01-18 USE AND MAINTENANCE MANUAL Page 23


ECP200 BASE 2/4 Appendices

A.8 CONNECTION EXAMPLE (3) - ECP200 BASE2 /BASE2A

Connection with outputs powered for direct control of functions.

A.9 CONNECTION EXAMPLE (4) - ECP200 BASE2 /BASE2A

Mixed connection with on/off contact powered to enable towards room power board
and light output powered for direct control.

Page 24 USE AND MAINTENANCE MANUAL Rev. 01-18


ECP200 BASE 2/4

NOTES

Rev. 01-18 USE AND MAINTENANCE MANUAL Page 25


ECP200 BASE 2/4

NOTES

Page 26 USE AND MAINTENANCE MANUAL Rev. 01-18


ECP200 BASE 2/4

NOTES

Rev. 01-18 USE AND MAINTENANCE MANUAL Page 27


ECP200 BASE 2/4

PEGO s.r.l.
Via Piacentina, 6/b 45030 Occhiobello ROVIGO - ITALY
Tel. +39 0425 762906 Fax +39 0425 762905
e.mail: [email protected] – www.pego.it

AFTER-SALES ASSISTANCE CENTRE


Tel. +39 0425 762906 e.mail: [email protected]

Distributor: