Wireless electricity
sensor family overview
Technical specifications
Our electricity sensor series is comprised of non-invasive, self-powered, miniature PAN-10
wireless current sensors. The sensors clamp onto the electrical outgoing wire from
the circuit breaker and are self-powered by the circuit’s magnetic field. Hundreds
of sensors can be installed in a few hours with no disturbance to daily operations.
Once installed, the sensors become part of the building infrastructure, never
requiring maintenance, service or battery replacement.
PAN-10 and PAN-12 wireless current sensors specifications
PAN-10 sensor PAN-12 sensor
17 x 20 x 32 mm 46.2 x 22.8 x 32.6 mm
Physical dimensions PAN-12
0.67 x 0.79 x 1.26 inch 1.82 x 0.90 x 1.28 inch
Max hot-wire outer 7 mm 18.8 mm
diameter (including insulation) 0.28 inch 0.74 inch
Current measurement range 0 – 63 A 0 – 225 A
Current measurement accuracy Typically <2% at I > 3 A Typically <2% at I > 10 A
Minimum operating current 0.5 – 1 A (typical) 0.7 – 1.2 A (typical)
50 Hz (EU, JPE versions)
AC frequency supported
60 Hz (US, JPW versions)
Key features
434 MHz (EU version)
Transmission frequency 915 MHz (US version) • Non-invasive – snaps and
923 MHz (JPE, JPW versions) fits without disconnection
0 dBm (max – EU, US versions) • No maintenance; self-powered
Transmission power (ERP)
-4 dBm (max – JPE, JPW versions) • High accuracy
Transmission interval 10 seconds
• Wireless – no wiring,
unlike standard CT-based
monitoring systems
• Real-time current data
transmitted every 10 seconds
centricabusinesssolutions.com
Wireless electricity
sensor family overview
PAN-10 and PAN-12 wireless current sensors specifications
Certification1 USA and Canada Australia
Safety: UL 61010-1, UL 61010-2-030, ACMA compliant
CAN/CSA-C22.2 No. 61010-1 (ETL listed)
EMC: FCC Part 15 subpart B, ICES-003 Russia
Radio: FCC Part 15 subpart C, RSS-210, RSS-Gen EAC compliant
Europe Japan
Safety: EN 61010-1, EN 61010-2-030 (CE) Radio: ARIB STD-T108
EMC: EN ETSI 301 489-1, 301 489-3, 613 326-1
Radio: EN ETSI 300 220-1, 300 220-2 CB Certification IEC 61010-1,
IEC 61010-2-030 by
Intertek Testing Services
Flammability rating of external enclosure UL94 V-0
Ingress protection (IP) rating IP5X
Operating temperature -25 – 60°C / -13 – 140°F2
Operating humidity range 5% – 95% non-condensing
Storage temperature -25 – 65°C / -13 – 149°F
PAN-14 wireless high current sensor specifications
33.8 × 29 × 42.5 mm
The PAN-14 high-current sensor
Physical dimensions attaches to any size standard
1.33 × 1.14 × 1.67 inch
0 – 5 A current transformer,
0 – 5 A (up to 10 A peak) allowing measurements at
Current input range
(from external current transformer) any current range or wire gauge.
Current measurement range Determined by external current transformer
PAN-14
Current measurement accuracy Typically <2% at I > 0.1 A (at input from external CT)
Minimum operating current 0.03 – 0.05 A (at input from external CT)
50 Hz (EU, JPE versions)
AC frequency supported
60 Hz (US, JPW versions)
434 MHz (EU version)
Transmission frequency 915 MHz (US version)
923 MHz (JPE, JPW versions)
0 dBm (max)
Transmission power (ERP)
-4 dBm (max – JPE, JPW versions)
Transmission interval 10 seconds
centricabusinesssolutions.com
Wireless electricity
sensor family overview
PAN-14 wireless high current sensor specifications
Certification1 USA and Canada Key features
Safety: UL 61010-1, UL 61010-2-030, CAN/CSA-C22.2 • Connects to any standard 5 A
No. 61010-1 (ETL listed) current transformer
EMC: FCC Part 15 subpart B, ICES-003
Radio: FCC Part 15 subpart C, RSS-210, RSS-Gen • No maintenance; self-powered
• High accuracy
Europe
Safety: EN 61010-1, EN 61010-2-030 (CE) • Wireless sensor and CT are
EMC: EN ETSI 301 489-1, 301 489-3, 613 326-1 closed around the hot wire
Radio: EN ETSI 300 220-1, 300 220-2 with no additional wiring
• Real-time current data
Australia
transmitted every 10 seconds
ACMA compliant
Russia
EAC compliant
Japan
Radio: ARIB STD-T108
CB Certification IEC 61010-1, IEC 61010-2-030
by Intertek Testing Services
Flammability rating of external enclosure UL94 V-0
Ingress protection (IP) rating IP5X
Operating temperature -25 – 60°C / -13 – 140°F
Operating humidity range 5% – 95% non-condensing
Storage temperature -25 – 65°C / -13 – 149°F
PAN-42 wireless power sensor specifications The PAN-42 wireless power
sensor provides high-accuracy
Description 4-wire Wye, 3-wire Delta, single-phase 3-wire, real-time power measurements
single phase 2-wire, or dual-phase 3-wire and advanced power quality
• Voltage: [120/208 V], [240/416 V], or [277/480 V] measurements for main power
• Frequency: 48–62Hz monitoring, sub-metering
• Current input range: 0 – 5 A (up to 10 A peak)
and for the metering of
• Current measurement range: determined
by external CT
large devices.
• Minimum measurable power: 0.025W at device
inputs (per phase) Designed for demanding
electrical applications,
Outputs • Active energy (kWh) – accumulated, per phase supporting industry accuracy
• True RMS voltage and current – per phase standards, PAN-42 enables
• Active and reactive power – per phase the metering of power, voltage,
• Power factor – per phase
current, power factor and power
• Line frequency
quality measurement data.
centricabusinesssolutions.com
Wireless electricity
sensor family overview
PAN-42 wireless power sensor specifications
PAN-42
Accuracy (for voltage, current and active energy) According to ANSI C12.1 (Class 1)3
434 MHz (EU version)
Transmission frequency
915 MHz (US version)
Transmission power (ERP) 0 dBm (max)
Transmission interval 10 seconds
Certification1 USA and Canada
Safety: UL 61010-1, UL 61010-2-030, CAN/CSA-C22.2
No. 61010-1 (ETL listed)
EMC: FCC Part 15 subpart B, ICES-003
Radio: FCC Part 15 subpart C, RSS-210, RSS-Gen
Key features
Europe • Single, dual or
Safety: EN 61010-1, EN 61010-2-030 (CE) 3-phase metering
EMC: EN ETSI 301 489-1, 301 489-3, 613 326-1
• Accurate measurement of
Radio: EN ETSI 300 220-1, 300 220-2
active and reactive power
Australia • Real-time monitoring of
ACMA compliant current, voltage, power and
power quality
Russia
EAC compliant • Easily integrated with
PowerRadarTM, our
CB Certification IEC 61010-1, IEC 61010-2-030 cloud-based energy
by Intertek Testing Services management platform
• Fast and easy installation
Flammability rating of external enclosure UL94 V-0
Ingress protection (IP) rating IP5X
Operating temperature -25 – 60°C / -13 – 140°F
Operating humidity range 5% – 95% non-condensing
Storage temperature -25 – 65°C / -13 – 149°F
centricabusinesssolutions.com
Wireless electricity
sensor family overview
The full portfolio of wireless sensors
We provide a comprehensive range of cost-effective and easy-to-install metering and monitoring tools
that deliver real-time energy data to PowerRadar, our cloud-based energy management platform, or to
the software of choice.
Granular monitoring of individual circuits and devices
PAN-10 PAN-12 PAN-14
Sub-metering and monitoring of main powerlines and large devices
PAN-42
Part numbers of the different versions of our sensors
PAN-10 PAN-12 PAN-14 PAN-42
US: PAN-10-063-US US: PAN-12-225-US US: PAN-14-US US: PAN-42-US
EU: PAN-10-063-EU EU: PAN-12-225-EU EU: PAN-14-EU EU: PAN-42-EU
JP East: PAN-10-063-JPE JP East: PAN-12-225-JPE JP East: PAN-14-JPE
JP West: PAN-10-063-JPW JP West: PAN-12-225-JPW JP West: PAN-14-JPW
1
Please check local regulations for using the hardware outside the countries listed here.
2
Applies to currents up to 125A on PAN-12. The operating temperature for PAN-12’s full current range
(up to 225A) is -25 to 50°C / -13 – 122°F.
3
Assuming CT of class 0.2 or better. centricabusinesssolutions.com
© 2020 Centrica plc. 194 S Wood Ave #200, Iselin, NJ 08830
PowerRadar is a registered trade mark of Panoramic Power Ltd in the United Kingdom and United States of America. DS-EI-2020-3-US-EN