Min 2
Min 2
ETAP Page: 1
Location: 12.6.0H Date: 20-11-2023
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: Max Config.: Normal
* Bus1 110.000 105.000 0.0 79.970 54.214 0 0 Bus14 4.483 2.471 25.6 87.6
Bus16 25.447 16.149 150.7 84.4
Bus38 8.618 6.045 52.6 81.9
Bus22 14.198 11.071 90.0 78.9
Bus38 8.618 6.045 52.6 81.9
Bus14 4.483 2.471 25.6 87.6
Bus28 14.122 9.963 86.4 81.7
Bus14 110.000 104.037 -0.1 0 0 0.029 0.200 Bus1 -4.446 -3.670 29.1 77.1
Bus1 -4.446 -3.670 29.1 77.1
Bus15 8.863 7.140 57.4 77.9 -3.560
Bus15 22.000 100.180 -2.1 0 0 8.840 6.630 Bus14 -8.840 -6.630 289.5 80.0
Bus16 110.000 102.305 -0.8 0 0 0.029 0.200 Bus1 -25.016 -16.356 153.3 83.7
Bus18 12.186 7.331 73.0 85.7
Bus17 12.802 8.825 79.8 82.3 -7.120
Bus17 22.000 101.732 -3.6 0 0 12.760 7.911 Bus16 -12.760 -7.911 387.3 85.0
Bus18 110.000 100.894 -1.1 0 0 0.035 0.240 Bus16 -12.063 -8.025 75.4 83.3
Bus19 12.028 7.785 74.5 84.0 -5.000
Bus19 22.000 98.980 -3.3 0 0 12.000 7.133 Bus18 -12.000 -7.133 370.1 86.0
Bus22 110.000 103.065 -0.4 0 0 0.035 0.240 Bus28 -2.572 -2.093 16.9 77.6
Bus1 -14.021 -11.868 93.5 76.3
Bus23 16.558 13.721 109.5 77.0 -7.120
Bus23 22.000 101.804 -3.2 0 0 16.500 12.375 Bus22 -16.500 -12.375 531.7 80.0
Bus28 110.000 103.511 -0.4 0 0 0.029 0.200 Bus22 2.582 1.108 14.2 91.9
Bus1 -13.989 -10.644 89.1 79.6
Bus30 11.378 9.336 74.6 77.3 -5.340
Bus30 22.000 100.740 -2.9 0 0 11.340 8.505 Bus28 -11.340 -8.505 369.3 80.0
Bus38 110.000 103.953 -0.3 0 0 0.070 0.480 Bus1 -8.561 -6.987 55.8 77.5
Bus1 -8.561 -6.987 55.8 77.5
Bus39 8.526 6.747 54.9 78.4 -3.560
Bus39 8.526 6.747 54.9 78.4 -3.560
Bus39 22.000 100.876 -1.7 0 0 17.020 12.765 Bus38 -8.510 -6.383 276.7 80.0
Bus38 -8.510 -6.383 276.7 80.0
* Indicates a voltage regulated bus (voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA