Current Transformer Notes PDF
Current Transformer Notes PDF
A current transformer is a device that is used for the transformation of current from a higher
value into a proportionate current to a lower value. It transforms the high voltage current into
the low voltage current due to which the heavy current flows through the transmission lines is
safely monitored by the ammeter.
The current transformer is used with the AC instrument, meters or control apparatus where
the current to be measured is of such magnitude that the meter or instrument coil cannot
conveniently be made of sufficient current carrying capacity. The current transformer is
shown in the figure below.
The primary and secondary current of the current transformers are proportional to each other.
The current transformer is used for measuring the high voltage current because of the
difficulty of inadequate insulation in the meter itself. The current transformer is used in
meters for measuring the current up to 100 amperes.
The ratio of the primary current and the secondary current is known as a current
transformer ratio of the circuit. The current ratio of the transformer is usually high. The
secondary current ratings are of the order of 5A, 1A and 0.1A. The current primary ratings
vary from 10A to 3000A or more. The symbolic representation of the current transformer is
shown in the figure below.
The working principle of the current transformer is slightly different from the power
transformer. In a current transformer, the load’s impedance or burden on the secondary has
slightly differed from the power transformers. Thus, the current transformer operates on
secondary circuit conditions.
Burden on a Load
The burden of a current transformer is the value of the load connected across the secondary
transformer. It is expressed as the output in volt-amperes (VA). The rated burden is the value
of the burden on the nameplate of the CT. The rated burden is the product of the voltage and
current on the secondary when the CT supplies the instrument or relay with its maximum
rated value of current.
The secondary turns will be 1% and 2% less than the primary turns and the difference being
used in the magnetising core. Thus, if the secondary winding is opened and the current flows
through the primary windings, then there will be no demagnetizing flux due to the secondary
current.
Due to the absence of the counter ampere turns of the secondary, the unopposed primary
MMF will set up an abnormally high flux in the core. This flux will produce core loss with
subsequent heating, and a high voltage will be induced across the secondary terminal.
This voltage caused the breakdown of the insulation and also the loss of accuracy in the
future may occur because the excessive MMF leaves the residual magnetism in the core.
Thus, the secondary of the CT may never be open when the primary is carrying the current.
Is – secondary current
Es – secondary induced voltage
Ip -primary current
Ep – primary induced voltage
Kt – turn ratio, number of secondary turn/number of primary turn
I0 – excitation current
Im – magnetising current
Iw – working component
Φs – main flux
The secondary current lags behinds the secondary induced voltage by an angle θº. The
secondary current relocates to the primary side by reversing the secondary current and
multiply by the turn ratio. The current flows through the primary is the sum of the exciting
current I0 and the product of the turn ratio and secondary current Kt Is.
Current Ratio Errors – The current transformer is mainly due to the energy component of
excitation current and is given as
Where Ip is the primary current. Kt is the turn ratio and is the secondary current.
Phase Angle Error – In an ideal current transformer the vector angle between the primary
and reversed secondary current is zero. But in an actual current transformer, there is a phase
difference between the primary and the secondary current because the primary current has
also supplied the component of exciting current. Thus, the difference between the two phases
is termed as a phase angle error.
1. Wound Transformer – In this transformer the primary winding is composed inside the
transformer. The primary winding had a single turn and connected in series with the
conductor that measured the current. The wound transformer is mainly used for measuring
the current from 1amps to 100 amps.
2. Bar-type Current Transformer – The bar type transformer has only secondary windings.
The conductor on which the transformer is mounted will act as primary windings of the
current transformers.
3. Toroidal Current Transformer – This transformer does not contain primary windings.
The line through which the current flow in the network is attached through a hole or a
window of the transformers. The major advantage of this transformer is that the transformer
has a symmetrical shape due to which it has a low leakage flux, thus less electromagnetic
interference.