Figure 4.14 User I/O Cable Identification and Wire Color Diagram
Part number
Wire Color Diagram
Two Colors = Insulator/Stripe
Three Colors = Insulator/Stripe/Dot
DOC EXPIRES 5/5/2021 3:43:45 PM. Article or Material must comply with the
requirements stipulated by RoHS in its current version
Chapter 4: Installation and Setup
Start Switch Connection (Automation)
Pin Signal Name Signal Type Direction Signal Range Definition Colors
7 ACT_CLEAR 0V True Output 0/24V, 100mA Actuator clear signal Red/Wht
24 AMPLITUDE_OUT Analog Output 0V to 10V Amplitude signal from PS Red/Blk/
Grn
2 CYCLE_ABORT 24V True Input 0/24V, 100mA Red/Blk
3 EXT_RESET 24V True Input 0/24V, 100mA System Reset Grn/Blk
18 EXT_SEEK+ 24V True Input 0/24V, 100mA Red/Blk/
Wht
38 FREQ_OUT Analog Output -10V to +10V Frequency Signal from PS Blk/Wht/Blu
6 G_ALARM 0V True Output 0/24V, 100mA Blk/Wht
14 GEN_ALARM_RELAY_1 Relay Contact Output 40V, 0.25A Contact Closure Red/Grn
29 GEN_ALARM_RELAY_2 Relay Contact Output 40V, 0.25A Contact Closure Wht/Red/
Orn
1 J3_1_INPUT 24V True Input 0/24V, 100mA User definable inputs. Refer Wht/Blk
17 J3_17_INPUT 24V True Input 0/24V, 100mA to Table 4.6 to view available Wht/Blk/
selections. Red
19 J3_19_INPUT 24V True Input 0/24V, 100mA Grn/Blk/
Wht
31 J3_31_INPUT 24V True Input 0/24V, 100mA Wht/Red/
Blu
32 J3_32_INPUT 24V True Input 0/24V, 100mA Blk/Wht/
Grn
33 J3_33_INPUT 24V True Input 0/24V, 100mA Wht/Blk/
Grn
8 J3_8_OUTPUT 24V True Output 0/24V, 100mA User definable outputs. Refer Grn/Wht
22 J3_22_OUTPUT 24V True Output 0/24V, 100mA to Table 4.7 to view available Blk/Red/
selections. Grn
36 J3_36_OUTPUT 24V True Output 0/24V, 100mA Orn/Red
Grn
9 MEM Analog Output -10V to +10V Memory Signal from PS Blu/Wht
11 MEM_CLEAR Open Collector Output 24V, 25mA max Memory Clear signal send to Wht/Red
PS
40 MEMORY_STORE Open Collector Output 24V, 25mA max Memory store from PS Red/Wht/
Blu
34 PB_RELEASE 0V True Output 0/24V, 100mA Red/Wht/
Grn
37 PWR Analog Output 0V to 10V Power Signal from PS Blu/Red/
Grn
21 READY 0V True Output 0/24V, 100mA Blu/Blk/Wht
5 REJECT 0V True Output 0/24V, 100mA Blu/Blk
43 READY_ RELAY_1 Relay Contact Output 40V, 0.25A Contact Closure Blu/Orn/
Red
15 READY_RELAY_2 Relay Contact Output 40V, 0.25A Contact Closure Orn/Grn
26 RUN Open Collector Output 24V, 25mA max Run signal send to PS Orn/Blk/Grn
39 SEEK Open Collector Output 24V, 25mA max Seek Signal send to PS Wht/Blk/Blu
4 SOL_VALVE_SRC 24V Output 0/24V, 125mA SV1 Source Orn/Blk
DOC EXPIRES 5/5/2021 3:43:45 PM. Article or Material must comply with the
requirements stipulated by RoHS in its current version
2000X Distance Power Supply Chapter 4: Installation and Setup
Instruction Manual Start Switch Connection (Automation)
Pin Signal Name Signal Type Direction Signal Range Definition Colors
16 SOL_VALVE_RTN 24V Return Input 0V SV1 Return Blk/Wht/
Red
20 SUSPECT_PART 0V True Output 0/24V, 100mA Orn/Blk/
Wht
10 USER_AMP_IN Analog Input -10V to +10V User Amplitude control signal Blk/Red
25 USER_FREQ_OFFSET Analog Input -10V to +10V User Freq. offset control sig- Grn/Blk/Orn
nal
35 WELD_ON 0V True Output 0/24V, 100mA Start of sonics and trigger Grn/Wht/
Blu
30 WELD_ON_RELAY_1 Relay Contact Output 40V, 0.25A Contact Closure Orn/Wht/
Blu
44 WELD_ON_RELAY_2 Relay Contact Output 40V, 0.25A Contact Closure Blk/Orn/
Red
23 +10V_REF Analog Output 10.0V 10VDC ref. voltage from PS Wht/Red/
Grn
12 24V_RTN 24V Ground Input 0V 24V Return Orn/Red
13 24V_SRC 24V Source Output 24V, 1.25A max 24V Source Blu/Red
27 24V_RTN 24V Ground Input 0V 24V Return Blu/Wht/
Orn
28 24V_SRC 24V Source Output 24V, 1.25A max 24V Source Blk/Wht/
Orn
41 24V_RTN 24V Ground Input 0V 24V Return Grn/Orn/
Red
42 24V_SRC 24V Source Output 24V, 1.25A max 24V Source Orn/Red/
Blu
! CAUTION
Ensure all unused wires are properly isolated. failure to do so may result in Power Supply or
system failure.
NOTICE
Refer to the Branson Automation Guide (EDP 100-214-273) for additional information about
selection and use of Input and Output features listed in the following Table.
DOC EXPIRES 5/5/2021 3:43:45 PM. Article or Material must comply with the
requirements stipulated by RoHS in its current version
Chapter 4: Installation and Setup
Start Switch Connection (Automation)
Input Output
J3_1_INPUT Disabled J3_8_OUTPUT
Disabled
J3_17_INPUT Ext U/S Delay J3_22_OUTPUT Confirm Preset
J3_19_INPUT Display Lock J3_36_OUTPUT Ext Beeper
Sonics Disable Cycle Okay
J3_31_INPUT
Memory Reset No Cycle Alarm
J3_32_INPUT External Start Overload Alarm
J3_33_INPUT Ext Signal Modified Alarm
Sync In Note
Missing Part
External Start
Sync Out
! CAUTION
The power supply can be permanently damaged if it is connected to the incorrect line voltage,
or if the wiring connection is mis-wired. It also presents a safety hazard if mis-wired. Use of
the correct plug or connector helps prevent incorrect connections.
DOC EXPIRES 5/5/2021 3:43:45 PM. Article or Material must comply with the
requirements stipulated by RoHS in its current version
Process Flow and Wiring Tables
12 100-214-273 Rev. 1