This document provides derating values in kA for various ABB low voltage protective devices installed in the KAIA power system. It lists molded case circuit breakers, molded case circuit breakers with electronic release, air circuit breakers, and miniature circuit breakers along with their frame/trip ratings and corresponding derating values in single line or panel wise configuration. The derating values allow determining the adjusted current carrying capacity of a device when installed in the KAIA power system.

Uploaded by

Amr Abdelsayed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
72 views

Abb Deration Table

This document provides derating values in kA for various ABB low voltage protective devices installed in the KAIA power system. It lists molded case circuit breakers, molded case circuit breakers with electronic release, air circuit breakers, and miniature circuit breakers along with their frame/trip ratings and corresponding derating values in single line or panel wise configuration. The derating values allow determining the adjusted current carrying capacity of a device when installed in the KAIA power system.

Uploaded by

Amr Abdelsayed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

ABB DERATING VALUE FOR LV DEVICES IN KAIA (B-122735)

KAIA (B-122735)

MOLDED CASE SWITCH


DERATING VALUE
ABB LV PROTECTIVE DEVICE
(PANEL WISE)
REMARKS
FRAME / TRIP
TYPE MODEL SDB
RATING
XT3D 250AF 228
XT4D 250AF 238
40AT 35
50AT 43
63AT 55
XT2 160A 80AT 70
MOLDED CASE CIRCUIT BREAKER
(THERMAL MAGNETIC RELEASE)

100AT 87
125AT 109
160AT 139
40AT 34
50AT 42
63AT 53
80AT 66
XT4 100AT 85
160/250A 125AT 105
160AT 137
200AT 175
225AT 190
250AT 230
XT2N 160, In=63AT 63
XT2 XT2N 160, In=100AT 100
MOLDED CASE CIRCUIT

(ELECTRONIC RELEASE)

XT2N 160, In=160AT 160


XT4S 160, In=40AT 40
BREAKER

XT4S 160, In=63AT 63


XT4 XT4S 160, In=100AT 88
XT4S 160, In=160AT 160
XT4S 250, In=250AT 238
T5 T5N 400, In=400AT 355
T6 T6S 630, In=630AT 540
800AF 800
1000AF 1000
E1 B/N
1250AF 1250
(ELECTRONIC RELEASE)
AIR CIRCUIT BREAKER

1600AF 1600
1600AF 1600
E2 B
2000AF 2000
1000AF 1000
1250AF 1250
E2 N
1600AF 1600
2000AF 2000
1250AF 1250
E2 L
1600AF 1600
----------

Page 1of1
ABB DERATING VALUE FOR LV DEVICES IN KAIA (B-122735)

KAIA (B-122735)
ABB LV PROTECTIVE DEVICE
FRAME / TRIP REMARKS
MINIATURE CIRCUIT BREAKER

TYPE MODEL PDB LDB


RATING
16A 14.6 14.6
20A 18.2 18.2
S200
32A 29.1 29.1
40A 36.4 36.4
16A 14.2 14.2
S800 20A 17.8 17.8
40A 35.6 35.6
XT1D 160AF 153 153
MOLDED

SWITCH

XT3D 250AF 228 228


CASE

XT4D 250AF 238 238

Page 1of1