Englilsh Manual of Softstarter
Englilsh Manual of Softstarter
ELMARK SOFTSTARTER
ELM2500 SERIES
15~315KW
INSTRUCTION MANUAL
PREFACE
Thank you for your choice of ELMARK SoftStarter.
As the return of your trust we will provide the perfect quality and
wholehearted service to you.
Notes
This instruction manual provides information with respects to
installation, parameter-setting, trouble-diagnosing and proper
operation. This manual should therefore be kept properly and a
careful reading shall be required before any operation attempt to
avoid any accidental casualties or damage(s) to the facilities.
★Special Notice:
▲ Installation, operation, maintenance or checking to this
product shall be required before reading carefully this instruction
manual and ensuring proper use.
▲ Power shall be disconnected before any wiring. Never touch
power terminal with hand or conduct object. Never put or drop
foreign substance into soft starter.
▲ When using the bypass contactor, please connect the motor
according to the recommended diagram in the user’s manual,
that’s in order to keep the output exact consistency of softstarter
and motor. Otherwise softstarter and motor will be damaged.
▲ Connect input terminals R, S and T to urban power supply of
380V; connect output terminals U, V and W to motor.
▲ Grounding terminal PE shall be properly earth connected
(grounding impedance not exceeding 4Ω).
▲ When terminals R, S and T are connected to power supply of
380V and output terminals U, V and W are not connected to
motor, it is normal that the voltage of U, V and W is AC380V. The
voltage is got by leakage current of module. After U, V and W are
connected to motor, the voltage will clear away.
▲ Capacitance can not be connected to the output of soft starter,
but capacitance can be connected to the input of soft starter when
it is used for improving power factor.
CONTENTS
1. Product Model and Consignee Check…………………………. 1
2. Installation…………………………………………………….. 3
3. Functional Block Diagram……………………………………. 6
4. Technical Parameters………………………………………….. 7
5. Wiring…………………………………………………………..8
6. Setting…………………………………………………………..12
7. Function Chart…………………………………………………..15
8. Function in Details………………………………………………. 16
9. State Indication…………………………………………………... 22
Appendix 1. Maintenance…………………………………………... 24
Appendix 2. Fault Diagnosis……………………………………….. 25
Appendix 3. Application environment……………….................... 26
Appendix 4. Modbus communication……………………………..28
1. Product Model and Consignee Check
Please check the product carefully according to the following steps after
unpacking, please contact the supplier immediately if any problem is found.
ELM25015————ELM25055
ELM25075————ELM250200
ELM250220————ELM250315
H F R 2 □□□
2. Installation
For keeping a good product capability, the softstarter must be installed
vertically. Installation space should strictly obey the following requirements.
Good ventilation should be available to the installation environment, which
should avoid direct sunlight for indoor installation.
Environment temperature: -10℃~+50℃
Relative humidity: ≤95% (20℃±5℃)
Environment conditions: Free from flammable gas, explosive gas and
corrosive gas, free from electric dust, to be installed indoors with good
ventilation.
Vibration below 0.5G
If the altitude is above 2000m, the capacity should be decreased accordingly
for application.
Structure Dimension: 15KW-55KW
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
15 ELM25015 30 CJX4-50 10
22 ELM25022 45 CJX4-50 10
30 ELM25030 60 CJX4-80 16
37 ELM25037 76 CJX4-80 16
45 ELM25045 90 CJX4-95 25
55 ELM25055 110 CJX4-115F 25
75 ELM25075 150 CJX4-150F 35
90 ELM25090 180 CJX4-185F 35
110 ELM25010 218 CJX4-225F 50
132 ELM25032 260 CJX4-265F 60
160 ELM25060 320 CJX4-330F 75
200 ELM250200 400 CJX4-500F 90
220 ELM250220 440 CJX4-500F 90
250 ELM250250 500 CJX4-630F 150
280 ELM250280 560 CJX4-630F 150
315 ELM250315 630 CJX4-630F 150
6.Setting
Keypad Panel
Note
Mode “mode” Control box displays function code “HF××”. The current and
key “stop” key switch to each other.
To be used with “mode” key. Under the “HF××” display state,
set “set” press “set” key, the control box will display the corresponding
key value of function code. Press “up” and “down” key to change
its value, and then press “set” to save the changed value.
▲ “up” key Under “HF××” display state, press “up”, “down” key to select
▼
“down” other function code. After enter the function code, they are
key used to change the value of the function code.
run “run”
key Press “run” key for startup.
Under any state, press “stop/reset” key, it will have priority to
Stop/Reset “stop/res
be valid. Press twice for free stop of the softstarter. And it
et” key also can reset the softstarter when malfunction happens.
Special Display Content and Interpretation
Display Items Interpretation
Show reset process; under single control mode, it
-HF-
displays such content after reset normally;
RUN startup state
STOP Stop state
OUT Run state
SST Soft-stop state
Startup interval status (it is displayed in the startup
DEL_
interval)
Count Down Delay state
Main adjustable parameters:Startup torque compensation
Ramp ascending time
Soft-stop time (ramp descending time)
startup current limited
Startup mode: voltage ramp soft startup
current limiting soft startup
kick soft startup
Stop mode: voltage ramp soft stop mode
Free stop mode
D D
U
Ue
C C
U0
B B
t (HF07) T
Si ze N u m b er R ev i s io n
A
A4
Set HF01 to 1 and set startup current limit percent Is(HF09)and Torque
1 2 3
D ate:
Fi l e:
1 8 -S ep -2 0 0 4
F: \ HG Y µÄ ÎÄ µµ \È íÆ ð ¶¯ \ ²¨Ð Îͼ .d d b
Sh eet of
D raw n B y :
4
compensation voltage (HF04). The current of the motor will increase until the
voltage ramp reaches Is, then it will stop, and the speed will accelerate to its
full speed. After that, the current will decrease to below the rated current Ie,
1 2 3 4
I
C C
Is
B
Ie B
A
Current Limit Startup Feature Curve (2) Title
A
Size N u mb er R ev is io n
A4
D ate: 1 8 -S ep -2 0 0 4 Sh eet o f
File: F:\HG Y µÄ ÎÄ µµ \È íÆ ð ¶¯ \²¨Ð Îͼ .d d b D raw n B y :
ΔKick startup
1 2 3 4
Set HF01 to 2, and set ramp start time t(HF07) and torque compensation
(HF04), kick time t(HF06). The motor will start rapidly along with the
increasing voltage, then the voltage will increase in an ramp way, and the
speed will accelerate to its full speed. It is better for startup motor with big
1 2 3 4
U
C Ue C
US
U0
B B
t (HF06) T
Kick Startup Feature Curve (3)
HF02 A
Startup delay time 0-600S 0S
Title
A
Size N u mb er R ev is io n
Startup delay time is set for startup preparation, and the motor will not start in
A4
D ate:
File:
1 8 -S ep -2 0 0 4
F:\HG Y µÄ ÎÄ µµ \È íÆ ð ¶¯ \²¨Ð Îͼ .d d b
Sh eet o f
D raw n B y :
1 2 3 4
this interval. Count down mode is used for display, and the time can be set
from 0 to 600 seconds. And it will output a normal open –normal close
contact dot signal. By applying the signal, a warning signal may be effected
for safety attention! The manufacturer value is set to 0S
0V,and the motor will run with inertia till its stop, as shown in Figure (4):
D D
U
C
Ue C
B B
T
Ti t le
A A
Si ze N u m b er R ev i s io n
Soft stop means that the voltage of starter will reduce gradually from Ue to
0V when the voltage drops. The soft stop can help resist “water hammer
domino effect ”, as shown in Figure (5):
1 2 3 4
D D
Ue
C C
B B
t (HF08) T
S i ze
A4
N u m b er R ev i s io n
A
D ate: 2 0 -S ep -2 0 0 4 S h eet of
F i l e: F : \ HG Y µÄ ÎÄ µµ \È íÆ ð ¶¯ \ ²¨Ð Îͼ .d d b D raw n B y :
5% 4
9.State Indication
9.1 Fault Indication
Protection Display in the Counter measures
function panel
Over current OC1/OC2 Please decrease HF04 and increase HF07 in
the voltage ramp startup. Please refer to
Appendix 2 in the current limited startup.
Out-phase P.F. Please check if power input is normal.
Please check the cooling channel of soft starter regularly, make sure it
isn’t blocked by trash and dust.
Keep and install soft starter in a place far from strong eroding, high
powder, high temperature or high humidity. Soft starter should avoid
strong vibration.
Clean it regularly and check whether it works properly.
Check input wire and output wire of soft starter regularly. Check whether
the grounded wire is reliable, and whether terminals become flexible.
Renew startup contact implement (relay) regularly.
Check whether there is imprint or parts damage caused by overheating.
Check whether the wire is aging.
Note: When soft starter breaks down or doesn’t work properly, please handle
it according to this manual; Contact the manufacturer when you fail to solve
the problems. Users are not allowed for any repair by themselves.
Appendix 2. Fault Diagnosis
State
Problems Troubleshooting
explanation
1.Check whether the bypass contactor is blocked
Motor sounds
Soft starter is in at the closed place;
buzz, when
standby state 2.Check whether the silicon controlled rectifier
power is on (SCR) is spark-through or damaged.
No control
power supply 1.Check whether work voltage is normal.
state
Soft starter is
short circuit 1.Check whether the bypass contactor is blocked
between input at the closed place;
and output 2.Check whether the silicon controlled rectifier
terminal (SCR) is sparked through or damaged
connection
The above problems must be handled by professionals. Users are not allowed
for any repair by themselves.
Appendix 3. Application environment (for reference)
Startup mode Parameters setting Startup
Machinery
Load type time
type Voltage Current Torque Current
(S)
Ramp limited (%) (%)
Standard
Water pump ● 10% 300% 10 30
load
A little
Fan ● 20% 10 30
heave load
compressor Standard
● 10% 350% 10 30
(piston-type) load
compressor Standard
● 15% 10 30
(centrifugal) load
Standard
Convey ● 10% 300% 10 30
load
A little
Mixer ● 15% 350% 20 40
heave load
Modbus protocol does not require a special interface while a typical physical interface is RS485.
You can read reference books or ask for the details of MODBUS from manufactures.
II. Modbus Protocol
1. Overall Description
(1) Transmission mode
1) ASCII Mode
When controllers are setup to communicate on a Modbus network using ASCII mode,
each 8–bit byte in a message is sent as two ASCII characters. For example, 31H (hexadecimal
data)include two ASCII characters’3(33H)’,’1(31H)’.
In RTU mode, one Byte is expressed by hexadecimal format. For example, 31H is delievered to
data packet.
(2) Format
1) ASCII mode
Start Address Function Data LRC check End
: Inverter Function Data Data … Data High-order Low-order Return Line Feed
(0X3A) Address Code Length 1 … N byte of LRC byte of LRC (0X0D) (0X0A)
2)RTU mode
Start Address Function Data CRC check End
Inverter Function N Low-order High-order byte
T1-T2-T3-T4 T1-T2-T3-T4
Address Code data byte of CRC of CRC
3) Protocol Converter
It is easy to turn a RTU command into an ASCII command followed by the lists:
1) Use the LRC replacing the CRC.
2) Transform each byte in RTU command into a corresponding two byte ASCII. For example:
transform 0x03 into 0x30, 0x33 (ASCII code for 0 and ASCII code for 3).
3) Add a ‘colon’ ( : ) character (ASCII 3A hex) at the beginning of the message.
4) End with a ‘carriage return – line feed’ (CRLF) pair (ASCII 0D and 0A hex).
So we will introduce RTU Mode in followed part. If you use ASCII mode, you can use the up lists to convert.
(3) Address and meaning
The part introduces inverter running, inverter status and related parameters setting.
Description of rules of function codes parameters address:
1) Use the function code as parameter address
1. General Series:
High-order byte: 01~09 (hexadecimal)
Low-order byte: 00~3C
For example: F114 (display on the board), parameter address is 010E (hexadecimal).
2. Softstarter series
High-order byte: 00
Low-order byte: 00~3C
For example: HF14 (display on the board), parameter address is 000E (hexadecimal).
Note: in this situation, it allowes to read six function codes and write only one function code.
Some function codes can only be checked but cannot be modified; some function codes can
neither be checked nor be modified; some function codes can not be modified in run state; some
function codes can not be modified both in stop and run state.
In case parameters of all function codes are changed, the effective range, unit and related
instructions shall refer to user manual of related series of inverters. Otherwise, unexpected results
may occur.
2) Use different parameters as parameter address
(The above address and parameters descriptions are in hexadecimal format, for example, the
decimal digit 4096 is represented by hexadecimal 1000).
1. Running status parameters
Parameters Address Parameter Description(read only)
1001 The following is softstarter status.
The high-order byte is 0, and low-order byte is the status of softstarter.
0. standby
1. running
2. OC1 protection
3. OC2 protection
4. PF protection
5. OH protection
6. OL protection
1002 Output current
2. Control commands
Parameters Address Parameters Description(write only)
2000 Command meaning:
0003:Deceleration stop
0004:Free stop
0008:Run(no directions)
0009:Fault reset
3. Communication parameters
Parameters Address Parameters Description(read only)
3000 Command meaning:
0000:no error
0001:illegal function
0002: illegal address
0003: illegal parameters
0004: LRC error
0005: CRC error
0006:system locked
4. Response
Command Description Parameters Description
Response when reading 1、return code value in normal response
parameters 2、not allowed to read return FFFF(hex)
Response when writing 0001:operate successfully
parameters 0002:less than min value
0006:system locked
The following is response command when read/write parameters:
Eg1: In RTU mode, change acc time (F007) to 10.0s in NO.01 softatarter.
Host Query
Register Register Preset Preset Data
Address Function CRC Lo CRC Hi
Address Hi Address Lo Data Hi Lo
01 06 F0 07 00 0A 8B 0C
Function code F007 Value: 10.0S
Slave Response
Register Register Response Response
Address Function CRC Lo CRC Hi
Address Hi Address Lo Data Hi Data Lo
01 06 F0 07 00 04 0A C8
Function code F007 Do not allow to change
Eg 2:Read status and output voltage from N0.2 softstarter.
Host Query
First Register First Register Register Register
Address Function CRC Lo CRC Hi
Address Hi Address Lo count Hi count L0
02 03 10 00 00 02 C0 F8
Communication Parameters Address 1000H
Slave Response:
Byte Data Data Data Data CRC CRC
Address Function
Count Hi Lo Hi Lo Lo Hi
02 03 04 00 02 00 00 68 F3
OC1 protection output current
01 06 20 00 00 01 43 CA
Communication parameters address 2000H Forward running
Slave Response:
Register Register Write Write
Address Function CRC Lo CRC Hi
Hi Lo status Hi status Lo
01 06 20 00 00 01 43 CA
Writing parameters successfully
Eg4: Read the value of F017 from NO.2 softstarter
Host Query:
Register Register Register Register CRC
Address Function CRC Lo
Address Hi Address Lo Count Hi Count L0 Hi
02 03 F0 11 00 01 E7 3C
Communication Parameter Address F011H Reading one Register.
Slave Response:
02 03 F0 11 00 04 27 3F
The actual value is 4.
3. Additional Remarks
0:Odd 1:Even
HF19 Parity Check 0
2:No checkout
0 1200 1 2400
HF20 Baud Rate 2 4800 3 9600 2
4 19200
You can read device status and function code value or preset functions value of soft starter regardless of
value of HF00.
Please set functions code related to communication consonant with the PLC/PC communication
parameters, when soft starter communicate with PLC/PC.
Ⅳ physical interface
1 interface
Hardware uses communication MAX485, the following are the pin of 485
interface.
PLC/PC
Field Bus
Command
Given
Status Info
Actual Value
C ontrol
alue
ELMARK ELMARK
soft soft
starter starter
Daisy chain the devices together. Do not use 'spur' lines, or a star configuration. Terminating Resistors of 120
Ohms should be used on the ends of long modbus/485 loops. In the first example below, the terminator
Correct wrong
1
2
Soft starter
1 2 3 4
3
Modbus Devices Soft starter
4
Modbus Devices
wrong
4
soft starter 1 2 3
Modbus Devices
Please note that for the same time in half-duplex connection, only one inverter can have communication with
PC/PLC. Should two or more than two inverters upload data at the same time, then bus competition will
occur, which will not only lead to communication failure, but higher current to certain elements as well.
No direct grounding shall be allowed for any point of RS485 network. All the equipment in the network shall
be well grounded via their own grounding terminal. Please note that grounding wires will not form closed
loop in any case.
Please think over the drive capacity of PC/PLC and the distance between PC/PLC and inverter when wiring.
Add a repeaters if drive capacity is not enough. Modbus repeaters may be used to extend the length of the
loop, but introduce delay in the device response time. Using repeaters on slow devices may cause timeout
problems.
All wiring connections for installation shall have to be made when the inverter is disconnected from
power supply.
080901