0% found this document useful (0 votes)
114 views32 pages

BCRD BCRDE DCRD Centrifugal Downblast Roof Exhausters Catalog 4050

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
114 views32 pages

BCRD BCRDE DCRD Centrifugal Downblast Roof Exhausters Catalog 4050

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 32

INDUSTRIAL PROCESS AND

COMMERCIAL VENTILATION SYSTEMS

Twin City Fan

DOWNBLAST ROOF EXHAUSTERS


Twin City Fan
DCRD | BCRD | BCRD-E (Endurex™ Polymeric Housing)

CATALOG 4050 | FEBRUARY 2017 WWW.TCF.COM


DOWNBLAST
ROOF EXHAUSTERS

Overview
DCRD | BCRD | BCRD-E

Twin City Fan & Blower’s line of quiet, efficient and


economical centrifugal roof exhausters are designed
to offer world-class performance and quality in a
wide variety of commercial and industrial ventilating
applications.

Models DCRD (direct drive) and BCRD (belt driven)


feature spun aluminum construction. Model BCRD-E belt
driven roof exhausters feature a housing constructed of
Twin City Fan & Blower's proprietary Endurex™ polymeric
material that provide significantly improved impact,
weather, corrosion, and UV resistance – see page 5 for
more information.

Typical Applications Include


Agriculture, Air Pollution Control, Automotive, Boilers,

GridSmart
Brick, Car Wash, Commercial Plan & Spec, Composting,
DCRD Ethanol, Food & Beverage, Foundry, General Manufacturing,
TM

Direct Drive Glass, HVAC, Institutional & Hospitality, Metal & Minerals,
EC Motors
Microchip, OEM, Pharmaceutical, Power Generation,
Recycling, Textile, Transportation

Now Available with Wheel Types

GridSmart EC Motors
TM Backward Inclined Centrifugal

Optional Construction
see page 9 Special Coatings, Spark Resistant, UL 705, UL 762, UL
Smoke & Heat

Certifications
AMCA Sound/Air and FEG, UL 705 Listed for Electrical,
UL 762 Listed for Grease-Laden Air, UL Listed for Smoke
Control Systems, OSHPD Seismic Preapproval per OSP-
0395-10, Miami-Dade County Hurricane Rating per NOA
DCRD, BCRD and BCRD-E models are cULus 705 listed for No. 12-0914.12
electrical, File No. E158680.

Twin City Fan & Blower certifies that the Models DCRD, BCRD,
and BCRD-E shown herein are licensed to bear the AMCA Seal.
The ratings shown are based on tests and procedures performed in
accordance with AMCA Publication 211 and AMCA Publication 311
and comply with the requirements of the AMCA Certified Ratings
Program.
Twin City Fan
Fan Efficiency Grade (FEG) certification applies to Model BCRD
Sizes 140D, 160D, 160DHP, 180D, 180DHP, 210D, 210DHP, 240D,
240DHP, 300D, 300DHP, 360D, 360DHP, 420D and 480D, Model
BCRD-E Sizes 140D, 160D, 160DHP, 180D, 180DHP, 210D, 210DHP, For complete product performance, drawings
240D and 240DHP. and available accessories, download our
Fan Selector program at tcf.com.

2 Twin City Fan


TWIN CITY FAN - CATALOG 4050
DOWNBLAST
ROOF EXHAUSTERS

Overview
DCRD | BCRD | BCRD-E

The centrifugal roof exhausters are designed for


roof mounted exhaust of relatively clean air. Typical
applications include general HVAC, warehouse
exhaust, and exhaust for churches, schools, and
offices.

Model DCRD
8" to 19.25" wheel diameters
Airflow to 5,600 CFM
Static pressure to 1" w.g.

Model BCRD
8.5" to 49.21" wheel diameters
Airflow to 28,700 CFM
Static pressure to 3.25" w.g.

Model BCRD-E
8.5" to 27.95" wheel diameters
Airflow to 8,700 CFM DCRD/BCRD BCRD-E Belt Driven
Static pressure to 3.25" w.g. Spun Aluminum Housing EndurexTM Housing

Spun Aluminum Housings Endurex


TM

Weather Resistant Housings

WWW.TCF.COM 3
CONSTRUCTION FEATURES

Models
DCRD | BCRD | BCRD-E
Housings - BCRD & DCRD housings feature heavy gauge
spun aluminum construction of the shroud and top cover.
Shrouds feature a rolled bead edge for rigidity. Motor bands
are constructed of heavy gauge aluminum, rolled and beaded
for rigidity. All housings provide complete protection of the
motor and drive assembly, while allowing quick access to
these components.

Bearings - Heavy-duty re-greaseable pillow block ball


bearings are specifically designed for air handling applications
to provide an average life (L-50) of 500,000 hours or more at
maximum cataloged operating speeds.

Shaft - Precision ground and polished with a first critical speed


of at least 125% of the fan’s maximum operating speed.

Drive - Adjustable pitch V-belt drives with cast iron sheaves


and heat resistant belts are selected at 150% of the driven
motor horsepower.

Motors - ODP, TEFC, and explosion proof, single and three


phase motors are carefully matched to the fan load.

Vibration Isolation - Motor and drive assembly is completely


isolated from the fan supports by rubber isolators to reduce
transmission of noise and vibration.

Wheel - Quiet and efficient non-overloading wheels with


backwardly curved blades are precisely matched to a deep
spun venturi. All wheels are statically and dynamically balanced
to ensure smooth and quiet operation.

Galvanized Bird Screen - Protects the wheel, inlet, and


internal components from entry of birds.

Curb Cap - One-piece curb cap/inlet venturi assembly


provides protection from weather. ­­­­Prepunched mounting holes
provide easy and accurate ­attachment to the roof curb.

Conduit Tubing - A conduit tube is furnished for running


electrical wiring through the curb cap and into the motor
compartment.

Disconnect Switch - Standard on all units. Fans are


provided with a NEMA 1 type disconnect switch mounted
in the motor compartment when ODP or TEFC motors are
used. When explosion proof motors are specified, a NEMA
7/9 disconnect switch will be shipped loose for field mounting
and wiring.

4 TWIN CITY FAN - CATALOG 4050


ENDUREX™ HOUSINGS

Model
BCRD-E
Endurex™ Construction Advantages
BCRD-E housings feature Endurex™ polymeric construction
of the housing and top cover. The polymeric construction of
Endurex™ provides the same long lasting characteristics
as aluminum but with significantly improved impact,
weather, corrosion, and UV resistance. To prove our
confidence in Endurex™ we are providing a limited
lifetime warranty on all Endurex™ housing components.

Impact Resistant - Housing will not dent or crack even


in cold weather to -40oF.

Weather Resistant - Resistant to storm damage caused


by wind, hail and airborne objects.

Corrosion Resistant - Impervious to salt, airborne


chemicals and normal weathering.

UV Resistant - UV inhibitors provide resistance to


ultraviolet light for long years of service.

Resists Shipping Damage - Impossible to dent and


alter housing shape caused by improper handling.

Safe Installation - Provides safe areas to grab for


installation and maintenance without sharp metal edges.

Ease of Maintenance - Removable top cover provides


for belt inspection and maintenance, while the one-piece
construction provides easy removal and access to the Twin City Fan & Blower's proprietary
wheel. Endurex™ polymeric material

UL TESTING, ENDUREXTM HOUSINGS

The Endurex™ housing was tested by UL in accordance Impact Resistance Testing – Tensile and izod impact
with UL 94, 746A, and 746C and is approved as UL 705 tests measured the material’s resistance to real life
listed. The Endurex™ material underwent rigid testing conditions such as falling objects, blows, collisions,
per these standards, surpassing the requirements of the drops, etc.
following:
Functional Support Testing – Flexural and tensile
Ultraviolet Light Exposure Testing – Samples were strength tests to prove the material’s structural stability
exposed to ultra violet light for an equivalent of 500,000 and integrity.
hours (90+ years) to provide the assurance that the
material will last a lifetime.

Flammability Testing – Flame tests performed per UL


94, the most widely accepted flammability performance
standards for plastic materials, gauged the material’s
ability to propagate or extinguish a flame once ignited.
Twin City Fan

WWW.TCF.COM 5
OPTIONS/ACCESSORIES

1
4

1 Self-Flashing Roof Curb Prefabricated roof curbs 3 Backdraft Damper, with automatic or motorized
are available in heavy duty galvanized steel or aluminum operation, feature a felt seal on the edge of the
construction, in heights of 8", 12" or 18". The self- damper blades for quiet operation. Damper frames are
flashing curb is provided with a factory installed 3/16" constructed of 19-gauge galvanized steel and blades
polystyrene gasket. Curbs are provided with 1.5" of are constructed of 26-gauge aluminum.
insulation as standard and feature continuously welded
Motorized dampers are recommended for low CFM
seams for added rigidity and moisture protection.
applications to assure unrestricted airflow. Motorized
Prefabricated curbs are also available in raised cant,
dampers are available with 115, 208, 230, 460, 575
pitched and peak models. Refer to Catalog 4910 for
or 24 volt service. End switches are available. When a
complete details on roof curb options. Minimum 12"
motorized damper option is selected a 12" (or greater)
high curbs are recommended for use with motorized
high roof curb is required.
dampers.

Variable Speed Control is an optional accessory 4 NEMA 4 Disconnect Switch provides positive
2 electrical shutoff when fan cleaning or maintenance of fan
on all DCRD models with 115 volt, open type motors,
and is water and dust tight. Switch is available shipped
to allow the adjustment of airflow for system balancing.
loose for field mounting and wiring or factory mounted
Variable speed controllers are solid-state (Tri-ac)
and wired. NEMA 3R enclosure is also available.
design, and are designed to start the motor on high
speed for better startup characteristics. Variable speed
controls can be shipped separately, factory installed, 5 Tie-Down Brackets A quantity of four brackets are
or field installed on the unit at a later date. Motor must mounted to the fan shroud to allow the fan to be
be ODP 115V, PSC or shaded pole type. secured to the roof in areas where high winds are a
concern. Guy wires are supplied and installed by others.

6 TWIN CITY FAN - CATALOG 4050


OPTIONS/ACCESSORIES

1 5

1 Curb Hinge The curb hinge arrangement provides 4 Canted Roof Curb Prefabricated roof curbs are
easy access to the exhaust fan, backdraft damper available in heavy duty galvanized steel or aluminum
and duct for servicing and cleaning. The curb hinge construction, in heights of 8", 12" or 18". The canted
is of the piano type, running the entire length of the curb is provided with a factory installed wood nailer.
fan's curb base. The curb hinge option ships loose Curbs are provided with 1.5" of insulation as standard
and is designed for use with a standard canted curb and feature continuously welded seams for added
only (1.5" less than fan base). This option cannot be rigidity and moisture protection. Prefabricated curbs
used with self-flashing curbs. are also available in raised cant, pitched and peak
models. Refer to Catalog 4910 for complete details
2 Retaining Chain is available in conjunction with on roof curb options. Minimum 12" high curbs are
recommended for use with motorized dampers.
the curb hinge arrangement to stabilize the unit and
to prevent damage from occurring to the unit while
servicing and cleaning. 5 Insect Screen Provides protection from entry of
insects into wheel, inlet and interior of building.
3 Security Hasp A security hasp is available in
conjunction with the curb hinge arrangement to
prevent removal of the unit from the unit curb cap
and prevent entrance into the building through the
roof’s ductwork.

WWW.TCF.COM 7
OPTIONS/ACCESSORIES

1 Auto Belt Tensioner Spring loaded pulley used


for automatic belt tensioning. Eliminates the need for
regular belt tensioning and extends belt life.
1

2 Miami-Dade Construction All sizes on


model DCRD and sizes 070-360 on model BCRD
are available with optional Miami-Dade Hurricane
Construction. With this option, units are rated for wind
loads up to 150 miles per hour. In conjunction with
independent, licensed Florida Professional Engineers,
these fans have undergone rigorous design, analysis
and testing to ensure they meet the stringent product
requirements of Miami-Dade County. Twin City Fan
& Blower’s NOA (Notice of Acceptance) number is
11-0126.08 and can be found on the Miami-Dade
County website.

2
Twin City Fan

OTHER OPTIONS/ACCESSORIES INCLUDE:

Special Coatings Powered roof exhausters often require Firestat Designed to shut down fan in the event of a fire
special coatings for protective and decorative purposes. to prevent spreading. For use with single phase motors
Available coatings include air-dried enamel, air-dried epoxy, Twin City Fan
only. Available shipped loose for field mounting and wiring
and Heresite (air-dried phenolic). Contact your Twin City or factory mounted and wired.
Fan & Blower sales representative for more information on
available coatings and colors. AMCA Spark B Includes a non-ferrous (aluminum) wheel
and an aluminum rubbing plate around the opening
Straight-Sided Roof Curb Self-flashing style curb with through which the shaft passes.
factory installed wood nailer manufactured with the outside
dimensions of a canted curb (1.50" less than fan curb cap Performance Baffle Inlet plate with customized diameter
inside dimension). Straight-sided curbs are available with to meet specific performance point. Ships loose for field
all the same options as self-flashing and canted curbs. mounting.
Refer to Catalog 4910 for complete details on roof curb
options.

2-Speed Switch Two speed switch is available for 2


speed/2 winding motors to control the fan speed (high
speed, low speed, off). Available on single phase, 1 HP
and below.

8 TWIN CITY FAN - CATALOG 4050


ELECTRONICALLY
COMMUTATED MOTORS

Twin City Fan & Blower offers its own line of custom
engineered Electronically Commutated (EC) motors.
Electronic commutation is the latest motor technology to
be used in direct drive fans. Also known in the industry
as Brush Free or Brushless DC, the EC motors utilize
an electronic circuit board to control the functionality
of the motor. The motor operates off of single phase
AC power, which is converted to DC power within the
motor’s circuitry. Twin City Fan & Blower has motor

GridSmart
options available for 115V, 208-230V or 277V single phase
TM
electrical power. The result is a highly efficient motor,
even at part load, with an expanded speed control range
and a variety of speed control options ECfrom
Motors
which to
choose. EC motors are available in ODP, TENV and TEFC
enclosures.

GridSmart EC Motors
TM

Benefits Model DCRD


• Efficiencies up to 85% With GridSmartTM EC Motor
• Constant efficiency as the motor speed is varied
• Up to 66% energy savings over traditional PSC motors
• Performance range comparable to a belt drive fan with
reduced maintenance benefits of a direct drive fan
• 80% usable turndown range as compared with 40%
maximum on PSC motors
• Soft start gives fans smooth, quiet start
• Lower operating temperatures result in longer life
and reduces energy consumption
• Heavy-duty ball bearings are permanently lubricated Twin City Fan
• Elimination of VFD results in lower initial cost

EC Motor Options
1/6HP to 1HP
• 1/6HP: 115V, single phase
• 1/4HP – 1HP: 115V, 208-230V, 277V, single phase
• ODP or TENV Enclosure
• Motor mounted speed control dial as standard Twin City Fan
• 0-10VDC control leads as standard
• Available with remote mounted speed control dial
1HP & 2HP
• 1HP: 115V, 208-230V, single phase
• 2HP: 208-230V, single phase
• TEFC enclosure (totally enclosed fan cooled)
1HP & 2HP 1/6HP to 1HP
• Available with motor mounted speed dial or 0-10VDC GridSmartTM EC Motors GridSmartTM EC Motors
control lead

WWW.TCF.COM 9
PREFABRICATED ROOF CURBS

Overview

Canted Roof Curbs


• Constructed of 18-gauge galvanized steel with
continuous welded seams
• Large 3" built-in 45° cant to accommodate roofing
material to top of curb. Cant is beveled at corners for
better support of roofing material
• Wood nailer (11∕2") secured to top ledge
• Lined with 11∕2" fiberglass fire-resistant, sound-
absorbing insulation
• Damper shelf standard
• Options: Aluminum (16-gauge) construction, burglar
security bars, metal liner (galvanized or aluminum),
special heights up to 24", single or double pitched
curbs for sloping roofs

Self-Flashing & Straight-Sided Roof Curbs


• Constructed of 18-gauge galvanized steel with
continuous welded seams
• Wide base plate (flashing) to insure watertight seal to roof
• Top ledge covered with 3∕16" polystyrene gasket (self-
flashing) for weather seal and to reduce metal-to-metal
conducted noise
• Wood nailer secured to top ledge (straight-sided)
• Lined with 11∕2" fiberglass fire-resistant, sound-
absorbing insulation
• Damper shelf standard
• Straight-sided roof curbs are constructed with the
same features as the self-flashing curbs, but are
one dimensional to allow for field supplied cants and
roofing material to be brought up to the top of the
curb
• Options: Aluminum (16-gauge) construction, burglar
security bars, metal liner (galvanized or aluminum),
special heights up to 24", single or double pitched
curbs for sloping roofs

Curb Adapters
• Constructed of heavy-gauge galvanized steel with
continuous welded seams
• Top ledge covered with 3∕16" polystyrene gasket to
reduce metal-to-metal conducted noise and act as a
weather seal
• Available in enlarger or reducer (shown) models

10 TWIN CITY FAN - CATALOG 4050


DISCONNECT SWITCHES

Overview

Disconnect switches provide positive electrical shutoff


during fan cleaning or maintenance.

NEMA 1 Disconnect Switch (Standard)


A NEMA 1 disconnect switch is available shipped loose
for field mounting and wiring or factory mounted and NEMA 1 Disconnect Switch
wired with ODP or TEFC motors.

NEMA 3R Disconnect Switch


A NEMA 3R, rain proof, disconnect is available shipped
loose for field mounting and wiring or factory mounted
and wired externally.

NEMA 4 Disconnect Switch


A NEMA 4, water and dust tight, disconnect is available NEMA 3R Disconnect Switch
shipped loose for field mounting and wiring or factory
mounted and wired externally.

NEMA 7/9 Disconnect Switch


A NEMA 7/9 disconnect switch is recommended on
fans with explosion proof motors. The NEMA 7/9 switch
is designed for use with fans operating in hazardous
environments. Available shipped loose for field mounting
and wiring. (Not shown.)
NEMA 4 Disconnect Switch

Twin City Fan

11
TwinWWW.TCF.COM
City Fan
PERFORMANCE DATA

060B ­– 085B DCRD


EC MOTOR PSC MOTOR STATIC PRESSURE (INCHES W.G.)
MTR MTR RPM 0 0.100 0.125 0.250 0.375 0.500 0.625 0.750 0.875 1.000
SIZE SIZE CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
HP HP
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
151 101 84
950
0.00 2.5 0.01 2.5 0.01 2.4
183 145 133
1150
0.01 3.5 0.01 3.2 0.01 3.4
215 183 174 121
1350
0.01 4.6 0.01 4.3 0.01 4.2 0.01 4.4
227 197 189 141
060B 1/8 1425
0.02 5.1 0.02 5.1 0.02 4.8 0.02 5.0
060BE 1/6
238 211 203 159 91
1500
0.02 5.9 0.02 5.9 0.02 5.6 0.02 5.7 0.02 5.9
250 224 217 176 124
1575
0.02 5.9 0.02 6.6 0.02 6.7 0.02 6.2 0.02 5.9
262 238 231 193 147
1650
0.02 7.9 0.02 7.9 0.02 7.9 0.03 6.8 0.02 6.6
278 255 249 214 173 114
--- --- 1750
0.03 8.7 0.03 8.7 0.03 8.7 0.03 7.5 0.03 7.9 0.03 7.4
238 149 123
950
0.01 3.2 0.01 2.9 0.01 2.9
288 219 199
1150
0.01 4.5 0.01 4.0 0.01 4.3
338 281 266 176
1350
0.01 5.6 0.02 5.2 0.02 5.1 0.02 5.2
356 303 289 207
070B 1/8 1425
0.02 6.1 0.03 5.6 0.02 5.4 0.02 5.2
070BE 1/6
375 324 312 235
1500
0.02 6.5 0.02 6.4 0.02 6.2 0.02 6.1
394 346 333 263 177
1575
0.02 7.2 0.02 7.4 0.02 7.0 0.02 6.9 0.02 6.5
412 367 355 289 214
1650
0.02 8.5 0.03 8.5 0.03 8.0 0.03 7.7 0.03 7.1
438 394 383 324 255
--- --- 1750
0.03 9.6 0.03 9.6 0.03 9.5 0.03 8.5 0.03 7.6
294 176 137
950
0.00 3.0 0.01 2.5 0.01 2.7
356 262 236
1150
0.01 4.4 0.01 3.9 0.01 4.1
418 340 319 198
1350
0.01 5.8 0.02 5.2 0.02 5.1 0.01 5.2
442 367 348 240
080B 1/8 1425
0.01 6.4 0.02 5.8 0.02 5.6 0.02 5.6
080BE 1/6
465 395 376 277
1500
0.02 6.9 0.02 6.4 0.02 6.2 0.02 6.0
488 422 404 312
1575
0.02 7.4 0.02 7.2 0.02 6.7 0.02 6.9
512 448 432 345 240
1650
0.02 7.9 0.03 7.9 0.03 7.5 0.03 7.7 0.03 7.3
542 483 468 387 296
--- --- 1750
0.03 8.9 0.03 8.9 0.03 8.4 0.03 8.4 0.03 7.9
401 331 311 185
950
0.02 4.0 0.02 3.4 0.02 3.4 0.02 3.4
485 430 414 328 214
1150
0.04 5.8 0.04 5.7 0.04 5.2 0.04 5.3 0.04 5.0
570 524 512 443 364 268
1350
0.06 7.7 0.06 7.7 0.06 7.7 0.06 6.6 0.06 7.0 0.06 6.7
601 558 547 483 412 328 202
085B 1/8 1425
0.07 8.4 0.07 8.4 0.07 8.4 0.07 7.3 0.07 7.8 0.07 7.3 0.06 7.1
085BE 1/6
633 592 581 522 457 381 291
1500
0.08 8.9 0.08 8.9 0.08 8.9 0.08 7.9 0.09 8.4 0.08 7.6 0.08 7.9
665 626 616 560 499 431 353 244
1575 0.10 8.9 0.10 8.4 0.08 8.4
0.09 9.6 0.09 9.6 0.10 9.6 0.10 8.6 0.10 8.5
696 660 650 596 540 479 407 325
1650 0.10 10.2 0.11 10.2 0.11 10.2 0.11 9.6 0.11 9.1 0.11 9.6 0.10 9.0 0.11 9.1
738 704 695 647 594 538 475 405 321
--- --- 1750
0.12 11.1 0.13 11.1 0.13 11.1 0.13 10.8 0.13 10.1 0.14 10.4 0.13 10.4 0.13 10.1 0.12 10.2
EC Motor is an Electronically Commutated Motor.
PSC Motor is a Permanent Split Capacitor Motor.

NOTES:
1. The AMCA Seal for sound ratings does not apply to units with speed control.
2. Performance certified is for installation Type A: Free inlet, Free outlet.
3. Performance ratings do not include the effects of appurtenances (accessories).
4. Sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301-90.
Type A: Free inlet fan hemispherical sone levels.
5. Highlighted speeds indicate nominal speeds without speed control on PSC motors. All other speeds are intermediate speeds set with the
solid-state speed controller.
6. 1/8 HP motor is 3-speed (1650 RPM/1500 RPM/1350 RPM).
7. Speed control on PSC motors is available for ODP 115/60/1 only. PSC motors are wired at either the 1650 or the 1500 RPM taps.

12 TWIN CITY FAN - CATALOG 4050


PERFORMANCE DATA

090B ­– 120B DCRD


EC MOTOR PSC MOTOR STATIC PRESSURE (INCHES W.G.)
MTR MTR RPM 0 0.100 0.125 0.250 0.375 0.500 0.625 0.750 0.875 1.000
SIZE SIZE CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
HP HP
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
519 430 403 235
950
0.02 4.0 0.02 3.5 0.02 3.5 0.02 3.5
628 558 538 422 273
1150
0.04 5.7 0.04 5.6 0.04 5.3 0.04 5.3 0.04 5.0
737 679 663 574 467 340
1350
0.06 7.6 0.06 7.6 0.06 7.6 0.07 6.8 0.07 6.8 0.07 6.8
778 723 709 627 530 417 253
090B 1/8 1425
0.07 8.3 0.07 8.3 0.08 8.3 0.08 7.4 0.08 7.7 0.08 7.3 0.07 7.2
090BE 1/6
819 767 754 678 589 488 370
1500
0.08 8.9 0.09 8.9 0.09 8.9 0.09 8.1 0.10 8.4 0.09 7.7 0.09 8.0
860 811 798 728 646 553 448 310
1575
0.09 9.6 0.10 9.6 0.10 9.6 0.11 8.7 0.11 8.7 0.11 8.8 0.11 8.6 0.10 8.6
901 854 842 776 701 616 521 413
1650
0.11 10.4 0.11 10.4 0.11 10.4 0.12 9.8 0.13 9.3 0.13 9.8 0.12 9.2 0.12 9.5
956 912 900 840 771 694 609 516 409
--- --- 1750
0.13 11.5 0.13 11.5 0.13 11.5 0.14 11.0 0.15 10.2 0.15 10.8 0.15 10.5 0.15 10.2 0.14 10.3
700 574 538 283
950
0.03 4.6 0.03 4.0 0.03 4.1 0.03 3.6
848 747 719 564 323
1150
0.04 6.6 0.05 6.3 0.05 6.0 0.05 6.0 0.04 5.3
995 911 889 767 623 411
1350
0.07 8.7 0.08 8.7 0.08 8.3 0.08 7.8 0.08 7.5 0.07 7.1
1050 972 951 837 709 534 304
095B 1/8 1425
0.08 9.5 0.09 9.5 0.09 9.5 0.10 8.7 0.10 8.9 0.09 7.8 0.07 7.5
095BE 1/4
1106 1031 1012 905 789 644 443
1500
0.10 10.6 0.11 10.6 0.11 10.6 0.11 9.8 0.11 9.9 0.11 8.4 0.10 8.4
1161 1090 1072 972 864 736 568 368
1575
0.11 11.3 0.12 11.3 0.12 11.3 0.13 11.2 0.13 11.0 0.13 10.5 0.12 9.5 0.10 9.2
1216 1149 1131 1038 936 823 682 497
1650
0.13 13.6 0.14 13.6 0.14 13.6 0.15 12.8 0.15 11.7 0.15 12.4 0.15 10.1 0.13 10.1
1290 1227 1210 1124 1029 929 812 661 483
--- --- 1750
0.16 14.9 0.16 14.9 0.17 14.9 0.18 14.8 0.18 13.2 0.18 13.5 0.18 12.8 0.17 11.5 0.15 11.4
430
500
0.01 1.6
602 391 318
1/15* 700
0.01 3.7 0.02 3.3 0.01 3.1
740 581 534 229
860
0.03 5.4 0.03 4.8 0.03 5.1 0.02 4.4
860 727 691 465
100BE 1/4 100B 1000
0.04 7.0 0.04 6.5 0.04 6.2 0.04 5.9
1/8*
998 885 855 687 467
1160
0.06 9.0 0.07 8.6 0.07 8.5 0.07 8.5 0.06 7.7
1247 1158 1135 1015 877 713 524
1450
0.12 12.9 0.13 12.9 0.13 12.9 0.13 11.6 0.13 12.4 0.13 11.4 0.12 11.6
1/3*
1505 1432 1413 1317 1216 1103 977 834 677 517
1750
0.22 17.5 0.22 17.5 0.22 17.5 0.23 16.7 0.23 16.0 0.23 16.7 0.23 16.6 0.22 15.7 0.21 16.0 0.19 15.9
572
500
0.01 1.8
802 571 489
1/15* 700
0.02 3.9 0.02 3.4 0.02 3.2
985 806 756 450
860
0.03 5.8 0.04 4.8 0.04 4.7 0.04 4.8
1145 995 955 723 418
120BE 1/2 120B 1000
0.05 7.2 0.06 6.7 0.06 6.3 0.07 6.4 0.06 6.4
1/8*
1328 1201 1168 985 768 496
1160
0.08 9.4 0.10 9.4 0.10 9.0 0.10 8.3 0.10 8.0 0.09 8.2
1660 1560 1535 1399 1251 1085 902 682
1450
0.16 13.2 0.18 13.2 0.18 13.2 0.19 11.9 0.20 12.1 0.20 12.5 0.19 11.8 0.18 11.9
1/3*
2004 1922 1901 1793 1678 1557 1427 1284 1132 968
1750
0.29 18.0 0.31 18.0 0.31 18.0 0.33 17.9 0.34 16.4 0.35 16.7 0.35 17.7 0.35 16.7 0.34 15.7 0.33 16.3

EC Motor is an Electronically Commutated Motor.


PSC Motor is a Permanent Split Capacitor Motor.

* 3-phase units are supplied with 1/8 HP 860 RPM, 1/4 HP 1160 RPM and 1/2 HP 1750 RPM motors.
NOTES:
1. The AMCA Seal for sound ratings does not apply to units with speed control.
2. Performance certified is for installation Type A: Free inlet, Free outlet.
3. Performance ratings do not include the effects of appurtenances (accessories).
4. Sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301-90.
Type A: Free inlet fan hemispherical sone levels.
5. Highlighted speeds indicate nominal speeds without speed control on PSC motors. All other speeds are intermediate speeds set with the
solid-state speed controller.
6. Speed control on PSC motors is available for ODP 115/60/1 only.

WWW.TCF.COM 13
PERFORMANCE DATA

130B ­– 160B DCRD


EC MOTOR PSC MOTOR STATIC PRESSURE (INCHES W.G.)
MTR MTR RPM 0 0.100 0.125 0.250 0.375 0.500 0.625 0.750 0.875 1.000
SIZE SIZE CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
HP HP
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
778 415 276
500
0.01 2.2 0.02 1.9 0.01 1.9
1089 865 804 364
1/8 700
0.04 5.2 0.04 4.6 0.04 4.9 0.04 4.5
1338 1163 1114 845 456
860
0.07 7.4 0.07 7.0 0.07 6.7 0.08 6.8 0.07 6.8
1556 1408 1368 1157 895 552
130BE 3/4 130B 1000
0.11 9.4 0.11 9.4 0.12 8.9 0.12 9.4 0.12 9.0 0.11 9.0
1/4
1805 1679 1646 1470 1282 1048 760
1160
0.17 12.1 0.18 12.1 0.18 12.1 0.18 11.5 0.19 12.9 0.19 12.1 0.18 12.7
2256 2156 2131 1998 1856 1709 1550 1362 1139 904
1450
0.33 17.0 0.34 17.0 0.34 17.0 0.35 17.2 0.36 17.1 0.37 18.0 0.37 18.7 0.37 17.2 0.36 18.0 0.34 18.0
1/2
2723 2641 2620 2513 2402 2285 2164 2041 1910 1763
1750
0.58 22 0.59 22 0.59 22 0.60 22 0.62 23 0.62 22 0.63 23 0.64 24 0.65 25 0.65 24
884 502 344
500
0.02 2.9 0.02 2.1 0.02 2.1
1237 999 931 459
1/8 700
0.04 6.3 0.05 5.0 0.05 5.1 0.04 4.6
1520 1334 1283 994 573
140B 860
0.08 9.0 0.08 8.3 0.08 7.8 0.09 7.5 0.08 7.0
1767 1611 1569 1340 1067 688
140BE 3/4 1000
0.13 11.0 0.13 11.0 0.13 10.6 0.13 9.4 0.13 8.7 0.12 9.1
1/4
2050 1917 1882 1695 1488 1248 940
1160
0.20 14.3 0.20 14.3 0.20 14.3 0.21 12.1 0.21 12.3 0.21 11.1 0.19 11.6
2562 2458 2431 2290 2138 1977 1805 1612 1391 1117
1450
0.39 19.6 0.39 19.6 0.39 19.6 0.4 18.9 0.4 17.4 0.41 17.3 0.41 18.4 0.41 17.3 0.39 17.0 0.38 17.0
--- ---
3092 3006 2984 2872 2753 2628 2497 2362 2220 2068
1750
0.68 26 0.69 26 0.69 26 0.70 26 0.70 25 0.71 24 0.71 23 0.72 23 0.72 24 0.72 24
1192 714 571
500
0.03 3.1 0.03 2.4 0.03 2.6
1670 1350 1267 779
1/8 700
0.08 6.0 0.08 5.2 0.08 5.4 0.07 5.3
2051 1788 1725 1378 965
1 150B 860
0.14 8.6 0.14 8.1 0.15 7.7 0.15 8.2 0.13 7.8
2385 2157 2102 1822 1499 1142 766
150BE 1000
0.22 10.9 0.22 10.9 0.23 10.4 0.23 9.8 0.23 9.9 0.21 10.0 0.19 10.1
1/4
2767 2569 2521 2284 2035 1750 1445 1127 777
1160
0.34 13.8 0.35 13.8 0.35 13.8 0.36 12.2 0.36 13.0 0.35 12.8 0.34 12.6 0.31 12.8 0.28 12.6
3339 3175 3134 2935 2740 2535 2315 2068 1816 1557
1 1400
0.60 19.4 0.61 19.4 0.61 19.4 0.62 18.3 0.63 16.6 0.63 17.1 0.63 18.2 0.62 16.9 0.60 16.9 0.58 17.5
--- ---
4174 4042 4010 3847 3688 3532 3375 3210 3040 2859
2 1750
1.17 27 1.18 27 1.18 27 1.20 27 1.21 26 1.22 24 1.23 24 1.24 24 1.24 25 1.23 26
1394 936 792
500
0.04 4.3 0.04 3.6 0.04 3.3
1952 1661 1577 1089
1/4* 700
0.10 8.7 0.12 7.6 0.12 7.1 0.12 6.9
2398 2171 2109 1755 1346 854
1** 860
0.19 11.9 0.21 11.9 0.21 11.4 0.22 10.3 0.22 9.8 0.19 9.9
2788 2597 2546 2265 1941 1585 1197
160BE 160B 1000
0.30 14.2 0.32 14.2 0.32 14.2 0.34 12.2 0.35 13.0 0.34 12.3 0.31 12.9
1/2*
3234 3071 3028 2801 2546 2262 1956 1644 1278
1160
0.46 17.5 0.49 17.5 0.49 17.5 0.52 16.5 0.54 15.7 0.54 16.2 0.54 15.4 0.51 15.8 0.47 15.9
4043 3914 3881 3709 3525 3327 3114 2887 2647 2398
1450
0.91 25 0.94 25 0.94 25 0.98 25 1.01 23 1.04 22 1.06 22 1.06 23 1.06 23 1.05 22
2 ---
4879 4773 4746 4608 4464 4313 4153 3985 3810 3625
1750
1.59 34 1.63 34 1.64 34 1.68 34 1.73 34 1.77 33 1.81 31 1.84 30 1.86 29 1.86 30

EC Motor is an Electronically Commutated Motor. * 3-phase units are supplied with 1/2 HP 860 RPM and 1 HP 1160 RPM motors.
PSC Motor is a Permanent Split Capacitor Motor. ** Performance available with 1 HP 1160 RPM ECODP or 1 HP 1750 RPM
ECTEFC motors. 1160 RPM maximum.

NOTES:
1. The AMCA Seal for sound ratings does not apply to units with speed control.
2. Performance certified is for installation Type A: Free inlet, Free outlet.
3. Performance ratings do not include the effects of appurtenances (accessories).
4. Sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301-90. Type
A: Free inlet fan hemispherical sone levels.
5. Highlighted speeds indicate nominal speeds without speed control on PSC motors. All other speeds are intermediate speeds set with the solid-
state speed controller.
6. Speed control on PSC motors is available for ODP 115/60/1 only.

14 TWIN CITY FAN - CATALOG 4050


PERFORMANCE DATA

170B ­– 180B DCRD


EC MOTOR PSC MOTOR STATIC PRESSURE (INCHES W.G.)
MTR MTR RPM 0 0.100 0.125 0.250 0.375 0.500 0.625 0.750 0.875 1.000
SIZE SIZE CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
HP HP
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
1669 1183 1031
500
0.05 4.0 0.05 3.6 0.05 3.3
2337 2015 1929 1421 845
1/4* 700
0.14 7.8 0.14 7.1 0.14 6.6 0.14 6.1 0.13 6.4
1
2871 2613 2546 2185 1755 1293 750
170B 860
0.25 10.8 0.26 10.8 0.26 10.6 0.27 9.6 0.27 8.7 0.25 9.2 0.21 8.7
3338 3118 3061 2768 2437 2063 1663 1260
170BE 1000
0.40 13.8 0.40 13.8 0.40 13.8 0.42 12.2 0.43 12.4 0.42 11.5 0.41 11.6 0.38 12.2
1/2*
3872 3684 3636 3388 3128 2839 2521 2182 1837 1488
1 1160
0.62 17.4 0.62 17.4 0.63 17.4 0.64 16.5 0.66 15.4 0.67 15.8 0.66 15.7 0.65 14.4 0.63 15.3 0.60 15.4
4606 4449 4409 4205 3995 3777 3542 3289 3021 2738
1380
1.04 22 1.05 22 1.05 22 1.06 22 1.08 21 1.11 20 1.12 20 1.12 21 1.12 21 1.10 19.1
2 --- ---
5341 5205 5171 4997 4819 4638 4451 4256 4048 3829
1600
1.63 28 1.63 28 1.63 28 1.64 28 1.66 28 1.69 27 1.72 26 1.75 25 1.75 26 1.75 27
2165 1660 1512 440
500
0.08 5.1 0.08 4.5 0.08 4.8 0.05 4.2
3031 2693 2601 2096 1496
1/2 700
0.21 9.8 0.22 9.5 0.22 9.0 0.23 9.1 0.21 9.2
3724 3454 3383 3005 2583 2115 1571
1 180B 860
0.38 13.6 0.40 13.6 0.40 13.6 0.41 12.4 0.42 13.6 0.41 12.8 0.37 13.6
4330 4100 4041 3729 3392 3025 2631 2195 1696 879
180BE 1000
0.60 17.6 0.62 17.6 0.62 17.6 0.64 17.1 0.65 16.5 0.66 17.5 0.65 16.8 0.62 17.1 0.57 17.1 0.43 15.3
1
5023 4826 4776 4515 4239 3945 3633 3304 2954 2575
1160
0.94 23 0.96 23 0.96 23 0.98 23 1.00 21 1.02 21 1.02 22 1.02 22 1.01 20 0.97 21
5326 5141 5094 4850 4594 4323 4038 3737 3422 3088
1230
1.12 25 1.14 25 1.14 25 1.17 25 1.19 24 1.20 23 1.22 23 1.22 25 1.22 24 1.20 23
2 --- ---
5629 5454 5410 5181 4942 4691 4428 4151 3862 3561
1300
1.32 27 1.34 27 1.35 27 1.37 27 1.39 27 1.41 25 1.43 25 1.44 26 1.44 26 1.43 25
EC Motor is an Electronically Commutated Motor. * 3-phase units are supplied with 1/2 HP 860 RPM and 1 HP 1160 RPM motors.
PSC Motor is a Permanent Split Capacitor Motor.

NOTES:
1. The AMCA Seal for sound ratings does not apply to units with speed control.
2. Performance certified is for installation Type A: Free inlet, Free outlet.
3. Performance ratings do not include the effects of appurtenances (accessories).
4. Sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301-90. Type
A: Free inlet fan hemispherical sone levels.
5. Highlighted speeds indicate nominal speeds without speed control on PSC motors. All other speeds are intermediate speeds set with the solid-
state speed controller.
6. Speed control on PSC motors is available for ODP 115/60/1 only.

Twin City Fan

WWW.TCF.COM 15
PERFORMANCE DATA

070D BCRD/BCRD-E
STATIC PRESSURE (INCHES W.G.)
0 0.125 0.25 0.375 0.50 0.625 0.75 0.875 1.00 1.125 1.25 1.375
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
180 85
795
0.01 4.0 0.01 4.0
254 197 120
1125
0.02 7.4 0.02 7.4 0.02 7.4
311 263 214 145
1375
0.03 4.4 0.03 6.5 0.03 8.4 0.03 9.1
359 316 279 234 169
1/4 1590
0.05 5.5 0.05 6.3 0.05 7.4 0.05 8.2 0.04 8.4
401 362 329 290 251 187
1775
0.06 6.5 0.06 6.6 0.06 6.8 0.06 7.3 0.06 7.9 0.06 7.9
440 403 372 340 303 267 206
1945
0.08 7.4 0.08 7.4 0.08 7.0 0.08 6.9 0.08 7.7 0.08 8.0 0.08 7.8
475 441 411 383 350 316 282 222
2100
0.10 8.6 0.10 8.7 0.10 8.1 0.11 7.9 0.11 8.4 0.11 9.0 0.11 9.2 0.10 9.1
MAXIMUM MOTOR FRAME SIZE: 48

075D BCRD/BCRD-E
STATIC PRESSURE (INCHES W.G.)
0 0.125 0.25 0.375 0.50 0.625 0.75 0.875 1.00 1.125 1.25 1.375
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
322 217
940
0.02 3.7 0.02 3.5
363 278
1060
0.02 4.4 0.02 4.5
404 327 214
1180
0.03 5.0 0.03 4.7 0.03 4.7
445 372 291
1300
0.04 5.5 0.04 5.2 0.05 5.3
486 419 355 242
1/4 1420
0.05 6.0 0.06 6.0 0.06 5.6 0.06 5.4
527 467 412 327 167
1540
0.06 6.6 0.07 6.6 0.07 6.2 0.08 6.5 0.06 5.6
568 514 459 393 296
1660
0.08 7.5 0.09 7.5 0.09 7.0 0.09 7.4 0.09 6.7
609 560 504 456 378 260
1780
0.10 8.5 0.11 8.5 0.11 8.0 0.11 7.9 0.12 8.4 0.11 7.5
650 605 550 510 445 365 225
1900
0.12 9.4 0.13 9.4 0.14 9.2 0.14 8.7 0.14 9.2 0.14 8.9 0.12 8.1
MAXIMUM MOTOR FRAME SIZE: 48

085D BCRD/BCRD-E
STATIC PRESSURE (INCHES W.G.)
0 0.125 0.25 0.375 0.50 0.625 0.75 0.875 1.00 1.125 1.25 1.50
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
325 229
715
0.01 4.1 0.01 2.6
444 388 297
975
0.02 7.4 0.02 5.6 0.02 4.7
546 504 445 368 232
1200
0.03 9.9 0.04 9.6 0.04 6.5 0.04 6.4 0.03 4.8
660 627 587 533 472 393
1450
0.06 13.1 0.06 13.1 0.06 10.9 0.07 8.7 0.07 9.1 0.07 6.9
728 699 665 622 570 513 441 332
1/4 1600
0.08 14.7 0.08 14.7 0.08 13.5 0.09 10.8 0.09 9.9 0.09 10.2 0.09 8.2 0.08 7.4
796 770 740 705 661 613 560 496 412
1750
0.10 16.1 0.11 16.1 0.11 16.1 0.11 13.2 0.11 11.1 0.12 11.2 0.12 11.5 0.12 9.4 0.11 8.3
855 831 804 773 737 693 648 598 538 464
1880
0.13 16.8 0.13 16.8 0.13 16.8 0.14 15.1 0.14 12.7 0.14 11.5 0.14 12.1 0.14 11.9 0.14 10.5 0.14 8.9
944 922 898 872 843 808 769 728 685 635 578
2075
0.17 18.4 0.18 18.4 0.18 18.4 0.18 17.7 0.18 15.8 0.19 13.6 0.19 12.5 0.19 13.0 0.19 13.3 0.19 12.4 0.19 10.8
1037 1017 996 973 949 921 890 854 817 779 738 639
2280
0.23 19.3 0.23 19.3 0.24 19.3 0.24 19.3 0.24 18.1 0.24 16.2 0.25 14.7 0.25 13.7 0.25 13.7 0.26 14.1 0.26 14.0 0.25 11.9
MAXIMUM MOTOR FRAME SIZE: 48

NOTES:
1. Performance certified is for Installation Type A: Free inlet, free outlet.
2. Power rating (BHP) does not include transmission losses.
3. Performance ratings do not include the effects of appurtenances (accessories).
4. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
5. Values shown are for installation Type A: Free inlet fan hemispherical sone levels.

16 TWIN CITY FAN - CATALOG 4050


PERFORMANCE DATA

100D BCRD/BCRD-E
STATIC PRESSURE (INCHES W.G.)
0 0.125 0.25 0.375 0.50 0.625 0.75 0.875 1.00 1.125 1.25 1.375
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
725 591 448
775
0.03 4.8 0.03 4.2 0.03 3.9
865 749 651 498
925
0.05 6.5 0.06 5.7 0.06 6.3 0.06 5.4
1/4
1169 1080 999 924 856 755
1250
0.13 10.0 0.14 10.1 0.14 8.7 0.14 9.3 0.15 10.0 0.15 8.2
1412 1337 1267 1202 1139 1081 1024 946 812
1510
0.23 14.0 0.24 14.0 0.24 12.3 0.25 11.6 0.25 11.8 0.26 12.7 0.26 12.7 0.26 10.8 0.25 10.4
1487 1416 1349 1285 1225 1167 1114 1057 970 834
1590
0.26 14.9 0.27 14.9 0.28 13.6 0.29 12.6 0.29 12.5 0.30 13.3 0.30 14.1 0.30 13.5 0.30 11.0 0.29 11.2
1/3
1557 1489 1424 1363 1305 1248 1196 1145 1085 990 851
1665
0.30 16.1 0.31 16.1 0.32 14.9 0.33 13.8 0.33 13.3 0.34 13.6 0.34 14.5 0.35 15.0 0.35 13.7 0.34 12.1 0.33 12.2
MAXIMUM MOTOR FRAME SIZE: 56

100DHP BCRD/BCRD-E
STATIC PRESSURE (INCHES W.G.)
0.50 0.625 0.75 0.875 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
331
1275
0.04 5.4
436 344
1400
0.06 8.3 0.06 6.3
570 513 441 332
1/4 1600
0.09 9.9 0.09 10.2 0.09 8.2 0.08 7.4
702 657 608 553 484
1820
0.13 11.9 0.13 11.3 0.13 11.6 0.13 11.2 0.13 8.7
949 921 890 854 817 738 639 499
2280
0.24 18.1 0.24 16.2 0.25 14.7 0.25 13.7 0.25 13.7 0.26 14.0 0.25 11.9 0.24 10.8
1016 992 965 933 899 829 748 647 495
2415
0.29 19.5 0.29 18.3 0.29 16.4 0.30 15.3 0.30 14.4 0.30 14.8 0.31 14.8 0.30 11.9 0.28 11.4
1/3
1083 1061 1037 1010 979 914 844 763 662 502
2550
0.33 22 0.34 21 0.34 18.7 0.35 17.4 0.35 16.3 0.36 15.6 0.36 16.4 0.36 15.3 0.35 12.6 0.32 12.5
1169 1149 1128 1105 1079 1020 958 892 815 722 596
2725
0.41 24 0.41 24 0.41 23 0.42 21 0.42 19.4 0.43 17.5 0.44 17.6 0.44 17.9 0.44 16.9 0.43 14.1 0.41 14.1
1/2
1254 1235 1216 1196 1174 1123 1066 1008 944 872 786 681
2900
0.49 27 0.49 27 0.49 26 0.50 24 0.50 23 0.51 20 0.52 19.3 0.53 19.5 0.53 20 0.53 18.9 0.52 16.4 0.51 15.8
MAXIMUM MOTOR FRAME SIZE: 56

120D BCRD/BCRD-E
STATIC PRESSURE (INCHES W.G.)
0 0.125 0.25 0.375 0.50 0.625 0.75 0.875 1.00 1.125 1.25 1.50
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
745 563
575
0.02 3.1 0.02 2.7
1068 940 817 633
825
0.06 6.3 0.06 5.4 0.07 5.6 0.07 4.9
1/4
1360 1255 1163 1067 942
1050
0.12 9.2 0.12 8.7 0.13 7.9 0.13 7.9 0.14 8.2
1684 1598 1517 1444 1371 1284 1181 1068
1300
0.22 12.6 0.23 12.6 0.24 11.5 0.25 10.8 0.25 10.7 0.26 11.3 0.26 11.3 0.26 10.1
1768 1686 1609 1537 1469 1393 1302 1200 1084
1365
0.25 13.6 0.27 13.6 0.28 12.7 0.28 11.7 0.29 11.6 0.30 11.7 0.30 12.3 0.30 11.7 0.30 10.3
1/3
1852 1774 1699 1629 1565 1497 1417 1324 1226 1099
1430
0.29 14.5 0.30 14.5 0.32 13.8 0.32 12.9 0.33 12.4 0.34 12.5 0.34 13.1 0.35 13.3 0.35 12.5 0.34 11.3
1994 1921 1852 1785 1723 1663 1598 1523 1437 1346 1245
1540
0.36 16.4 0.38 16.4 0.39 15.7 0.40 14.7 0.41 13.9 0.42 13.8 0.42 14.0 0.43 14.7 0.43 14.8 0.43 14.0 0.43 12.6
1/2
2137 2068 2003 1940 1880 1824 1767 1705 1634 1555 1470 1265
1650
0.45 17.9 0.46 17.9 0.48 17.9 0.49 16.8 0.50 15.9 0.51 15.5 0.51 15.1 0.52 15.6 0.53 16.0 0.53 16.5 0.53 15.9 0.53 13.5
MAXIMUM MOTOR FRAME SIZE: 56

NOTES:
1. Performance certified is for Installation Type A: Free inlet, free outlet.
2. Power rating (BHP) does not include transmission losses.
3. Performance ratings do not include the effects of appurtenances (accessories).
4. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
5. Values shown are for installation Type A: Free inlet fan hemispherical sone levels.

WWW.TCF.COM 17
PERFORMANCE DATA

140D BCRD/BCRD-E Outlet Area = 2.34 ft2 Fan Efficiency Grade: FEG67
STATIC PRESSURE (INCHES W.G.)
0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1.00 1.25 1.50 1.75
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
850 584
475
0.02 2.2 0.02 2.0
984 762
550
0.03 3.2 0.03 3.0
1/4
1477 1345 1183 1017
825
0.09 6.8 0.10 6.7 0.11 6.2 0.11 6.2
1978 1883 1779 1659 1536 1415 1264
1105
0.22 11.0 0.24 11.0 0.25 10.5 0.25 9.6 0.26 10.2 0.26 10.3 0.26 8.7
2085 1996 1898 1788 1670 1558 1433
1165
0.26 12.0 0.28 12.0 0.29 11.6 0.30 10.7 0.30 10.8 0.30 11.6 0.30 10.6
1/3
2193 2108 2016 1915 1803 1694 1586 1457
1225
0.30 13.0 0.32 13.0 0.33 13.0 0.34 11.7 0.35 11.6 0.35 12.3 0.35 12.4 0.35 11.1
2345 2266 2181 2091 1989 1883 1783 1681 1559
1310
0.37 14.4 0.39 14.4 0.41 14.8 0.42 13.8 0.42 13.3 0.43 13.4 0.43 14.2 0.43 13.9 0.43 12.1
1/2
2506 2432 2354 2272 2181 2083 1985 1892 1796 1544
1400
0.45 16.2 0.47 16.2 0.49 16.2 0.51 16.1 0.51 15.6 0.52 15.2 0.52 15.4 0.52 16.3 0.53 15.9 0.52 12.7
2685 2616 2544 2469 2388 2300 2208 2117 2031 1840
1500
0.55 19.0 0.58 19.0 0.60 19.0 0.61 18.6 0.63 17.9 0.63 16.9 0.64 16.7 0.64 17.3 0.64 17.9 0.65 16.2
3/4
2873 2809 2742 2673 2600 2522 2438 2351 2266 2104 1911
1605
0.68 21 0.70 21 0.73 21 0.75 21 0.76 19.9 0.77 18.8 0.78 18.5 0.78 18.2 0.79 18.9 0.79 19.4 0.79 16.9
3016 2955 2892 2827 2758 2687 2609 2527 2445 2288 2125 1921
1685
0.79 23 0.81 23 0.84 23 0.86 23 0.88 22 0.89 21 0.90 19.7 0.90 19.5 0.91 19.6 0.91 21 0.92 19.9 0.91 16.7
1
3159 3101 3041 2979 2915 2848 2777 2701 2622 2468 2320 2150
1765
0.90 24 0.93 24 0.96 24 0.98 24 1.00 24 1.02 23 1.03 22 1.03 21 1.04 21 1.05 22 1.05 22 1.05 20
MAXIMUM MOTOR FRAME SIZE: 143T

140DHP BCRD/BCRD-E
STATIC PRESSURE (INCHES W.G.)
0.50 0.625 0.75 0.875 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
499
1310
0.07 6.4
870 811 747 677 600
1/4 1750
0.17 11.6 0.17 12.2 0.17 12.4 0.17 10.9 0.16 10.4
1069 1018 966 913 857 731
2015
0.25 14.7 0.26 13.9 0.26 14 0.26 14.9 0.26 15.0 0.25 12.4
1147 1101 1052 1003 952 841 715
2125
0.30 16.4 0.30 15.2 0.30 15 0.30 15.3 0.30 16.1 0.30 14.7 0.29 13.8
1/3
1224 1182 1136 1089 1043 943 830
2235
0.34 17.8 0.35 16.9 0.35 16 0.35 16 0.35 16.5 0.35 16.7 0.34 14.2
1337 1300 1259 1217 1173 1085 989 882
2400
0.42 21 0.42 19.7 0.43 18.8 0.43 17.9 0.43 17.8 0.43 19.1 0.43 18.5 0.43 15.7
1/2
1445 1411 1375 1337 1296 1215 1130 1039 937 825
2560
0.51 23 0.51 23 0.52 22 0.52 21 0.52 19.9 0.53 20 0.53 21 0.52 20 0.52 17.4 0.5 18.3
1597 1567 1536 1503 1468 1394 1319 1242 1159 1070 973
2790
0.65 28 0.66 26 0.66 26 0.67 25 0.67 24 0.68 23 0.68 23 0.68 24 0.68 24 0.67 21 0.66 21
3/4
1682 1654 1625 1594 1562 1493 1422 1349 1274 1194 1107 1014
2920
0.74 29 0.75 29 0.76 28 0.76 27 0.77 26 0.78 25 0.78 24 0.78 25 0.78 26 0.78 25 0.77 22 0.76 22
MAXIMUM MOTOR FRAME SIZE: 56

NOTES:
1. Performance certified is for Installation Type A: Free inlet, free outlet.
2. Power rating (BHP) does not include transmission losses.
3. Performance ratings do not include the effects of appurtenances (accessories).
4. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
5. Values shown are for installation Type A: Free inlet fan hemispherical sone levels.

18 TWIN CITY FAN - CATALOG 4050


PERFORMANCE DATA

160D BCRD/BCRD-E Outlet Area = 2.53 ft2 Fan Efficiency Grade: FEG75
STATIC PRESSURE (INCHES W.G.)
0 0.125 0.25 0.375 0.50 0.625 0.75 0.875 1.00 1.25 1.50 1.75
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
1321 1001
475
0.03 3.2 0.04 2.8
1738 1519 1235
625
0.07 5.5 0.08 4.8 0.08 4.9
1/4
2155 1987 1783 1551 1199
775
0.13 7.9 0.14 7.6 0.15 6.5 0.15 7.0 0.15 5.8
2586 2449 2296 2117 1927 1697
930
0.23 10.6 0.24 10.6 0.25 9.6 0.26 8.7 0.26 9.2 0.26 9.1
2711 2582 2438 2273 2093 1898 1634
975
0.26 11.4 0.27 11.4 0.28 10.4 0.30 9.7 0.30 9.8 0.30 10.0 0.30 8.8
1/3
2837 2713 2578 2425 2255 2078 1865 1547
1020
0.30 12.1 0.31 12.1 0.32 11.5 0.33 10.4 0.34 10.0 0.35 10.6 0.34 10.3 0.33 9.0
3059 2945 2822 2687 2535 2376 2209 2006 1724
1100
0.38 13.3 0.39 13.3 0.40 13.0 0.41 12.0 0.43 11.2 0.43 11.4 0.44 12.0 0.43 11.5 0.42 10.1
1/2
3282 3176 3063 2942 2807 2661 2512 2354 2164
1180
0.46 14.5 0.48 14.5 0.49 14.5 0.50 13.6 0.52 12.7 0.53 12.3 0.54 12.8 0.54 13.2 0.53 12.6
3504 3405 3301 3190 3070 2938 2800 2660 2510 2116
1260
0.57 16.2 0.58 16.2 0.59 16.2 0.61 15.4 0.62 14.5 0.64 13.7 0.65 13.6 0.65 14.1 0.65 14.5 0.64 13.0
3/4
3727 3634 3537 3435 3326 3207 3080 2949 2817 2515 2059
1340
0.68 17.6 0.70 17.6 0.71 17.6 0.73 17.2 0.74 16.2 0.76 15.3 0.77 14.7 0.78 14.7 0.79 15.5 0.78 15.5 0.75 13.8
3907 3819 3727 3631 3529 3420 3303 3179 3054 2791 2453
1405
0.78 18.6 0.8 18.6 0.82 18.6 0.83 18.6 0.85 17.8 0.86 16.7 0.88 16.3 0.89 15.8 0.90 16.2 0.91 17.2 0.89 16.5
1
4102 4018 3931 3840 3745 3645 3537 3422 3304 3063 2786 2410
1475
0.91 20 0.92 20 0.94 20 0.96 19.7 0.97 19.4 0.99 18.4 1.01 17.6 1.02 16.9 1.04 16.8 1.05 17.9 1.05 18.2 1.02 16.0
MAXIMUM MOTOR FRAME SIZE: 143T

160DHP BCRD/BCRD-E Outlet Area = 2.53 ft2 Fan Efficiency Grade: FEG63
STATIC PRESSURE (INCHES W.G.)
0.50 0.625 0.75 0.875 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
1021 872
1100
0.16 8.7 0.15 7.6
1231 1133 1003 826
1/4 1225
0.21 9.8 0.21 10.2 0.21 9.3 0.21 8.4
1352 1263 1162 1029 850
1300
0.25 10.2 0.25 11.1 0.26 11.1 0.26 9.8 0.24 9.0
1464 1377 1291 1186 1051
1370
0.29 11.0 0.29 11.7 0.30 12.4 0.30 11.8 0.30 9.7
1/3
1567 1482 1401 1314 1204
1435
0.34 11.7 0.33 12.0 0.34 12.7 0.34 12.8 0.35 12.2
1737 1658 1580 1505 1425 1208
1545
0.42 13.4 0.42 12.9 0.42 13.4 0.42 14.2 0.43 14.4 0.43 11.9
1/2
1902 1830 1757 1685 1615 1454 1229
1655
0.52 14.6 0.52 14.4 0.51 14.4 0.51 14.9 0.52 15.8 0.53 15.5 0.52 12.5
2071 2006 1938 1869 1802 1669 1503 1280
1770
0.63 16.7 0.64 16.2 0.63 16.1 0.63 16.1 0.63 16.5 0.64 17.4 0.65 16.5 0.63 13.6
3/4
2244 2185 2123 2059 1995 1871 1741 1575 1362
1890
0.77 18.6 0.77 17.9 0.77 17.4 0.77 17.9 0.76 17.3 0.77 18.4 0.79 18.9 0.79 17.6 0.77 14.8
2372 2317 2259 2199 2138 2017 1899 1764 1590 1374
1980
0.88 20 0.89 19.7 0.89 18.9 0.89 18.7 0.88 18.5 0.88 18.8 0.90 20 0.91 20 0.90 17.7 0.88 16.3
1
2506 2454 2401 2345 2287 2169 2057 1941 1801 1626 1410
2075
1.01 21 1.02 21 1.02 21 1.02 19.9 1.02 19.8 1.01 19.8 1.02 21 1.04 22 1.05 21 1.04 18.5 1.00 17.4
MAXIMUM MOTOR FRAME SIZE: 143T

NOTES:
1. Performance certified is for Installation Type A: Free inlet, free outlet.
2. Power rating (BHP) does not include transmission losses.
3. Performance ratings do not include the effects of appurtenances (accessories).
4. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
5. Values shown are for installation Type A: Free inlet fan hemispherical sone levels.

Twin City Fan

WWW.TCF.COM 19
PERFORMANCE DATA

180D BCRD/BCRD-E Outlet Area = 3.37 ft2 Fan Efficiency Grade: FEG60
STATIC PRESSURE (INCHES W.G.)
0 0.125 0.25 0.375 0.5 0.75 1.00 1.25 1.50 1.75 2.00 2.25
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
2320 1826 1376
475
0.08 5.5 0.09 4.2 0.10 4.5
2809 2389 2036 1632
1/4 575
0.15 8.0 0.16 6.5 0.17 6.4 0.17 6.2
3224 2857 2516 2225 1852
660
0.22 9.9 0.24 8.9 0.25 7.7 0.26 8.3 0.26 7.9
3371 3020 2685 2409 2084
690
0.25 10.6 0.27 9.6 0.29 8.2 0.30 8.8 0.30 9.0
1/3
3542 3207 2882 2613 2328
725
0.29 11.4 0.31 10.8 0.33 8.9 0.34 9.3 0.35 10.0
3810 3498 3192 2924 2681 2019
780
0.37 13.0 0.39 12.3 0.41 10.4 0.42 10 0.43 11.1 0.43 9.5
1/2
4055 3761 3472 3203 2977 2440
830
0.44 14.3 0.47 13.9 0.48 11.8 0.50 11.2 0.51 11.8 0.53 12.1
4348 4073 3804 3541 3316 2864 2229
890
0.54 15.8 0.57 15.8 0.59 13.9 0.61 12.6 0.62 12.6 0.64 14.0 0.63 11.3
3/4
4641 4383 4131 3880 3652 3250 2752 1968
950
0.66 17.6 0.69 17.6 0.71 15.9 0.73 14.2 0.75 14.0 0.77 15.0 0.79 15.0 0.71 12.1
4885 4640 4400 4160 3933 3550 3119 2540
1000
0.77 19.0 0.80 19 0.83 17.2 0.85 15.7 0.87 15.0 0.90 15.8 0.92 17.0 0.89 14.2
1
5105 4870 4640 4411 4187 3808 3422 2940 2215
1045
0.88 20 0.91 20 0.94 19.1 0.96 17.2 0.98 16.1 1.01 16.6 1.04 17.9 1.05 17.0 0.95 14.2
5471 5252 5036 4823 4610 4229 3894 3501 3010 2273
1120
1.08 22 1.12 22 1.15 22 1.18 20 1.20 18.8 1.23 17.9 1.26 19.1 1.29 20 1.28 18.0 1.15 15.8
1-1/2
5838 5632 5429 5230 5028 4649 4331 3998 3608 3117 2397
1195
1.32 25 1.35 25 1.39 25 1.42 23 1.44 21 1.48 19.7 1.52 20 1.55 22 1.57 22 1.54 19.5 1.39 17.6
6131 5935 5741 5551 5360 4988 4670 4370 4026 3627 3115
1255
1.53 27 1.56 27 1.60 27 1.63 25 1.66 23 1.71 22 1.75 21 1.78 22 1.81 24 1.82 23 1.75 20
2
6424 6237 6052 5869 5688 5326 5005 4722 4417 4071 3662 3137
1315
1.76 29 1.80 29 1.83 29 1.87 27 1.90 26 1.95 23 1.99 23 2.03 23 2.06 25 2.09 26 2.08 24 1.99 21
MAXIMUM MOTOR FRAME SIZE: 145T

180DHP BCRD/BCRD-E Outlet Area = 3.37 ft2 Fan Efficiency Grade: FEG67
STATIC PRESSURE (INCHES W.G.)
0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00 3.25
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
1089
775
0.14 6.9
1597
1/4 890
0.22 9.9
1755 1260
935
0.26 10.5 0.25 8.6
1900 1488
980
0.30 10.8 0.30 10.8
1/3
2035 1700
1025
0.34 11.6 0.34 12.3
2260 2010 1585
1105
0.42 12.9 0.43 13.7 0.42 12.0
1/2
2476 2280 1969 1502
1185
0.51 14.8 0.53 14.8 0.53 15.3 0.50 12.0
2701 2535 2300 1945 1451
1270
0.63 16.9 0.64 15.9 0.65 16.9 0.65 15.6 0.59 12.8
3/4
2925 2772 2590 2325 1950
1355
0.76 18.7 0.78 17.4 0.79 17.5 0.79 18.4 0.78 15.5
3096 2948 2792 2572 2270 1880
1420
0.87 20 0.89 18.7 0.90 18.4 0.91 19.5 0.91 18.5 0.87 14.6
1
3281 3135 2994 2814 2569 2238 1843
1490
1.00 22 1.02 19.8 1.04 19.2 1.05 20 1.05 20 1.04 18.1 0.98 15.4
3557 3413 3284 3143 2957 2718 2404 2046
1595
1.21 25 1.24 22 1.26 21 1.28 21 1.29 22 1.29 22 1.28 20 1.22 17.0
1-1/2
3844 3702 3579 3457 3315 3132 2905 2615 2289
1705
1.47 29 1.50 26 1.53 24 1.55 23 1.57 24 1.58 25 1.58 25 1.57 22 1.52 19.5
4065 3926 3804 3689 3568 3418 3230 3006 2721 2411 2004
1790
1.70 33 1.73 28 1.76 26 1.78 25 1.81 25 1.82 25 1.83 27 1.82 27 1.81 25 1.76 21 1.63 20
2
4286 4150 4028 3918 3807 3683 3527 3339 3119 2842 2546 2178
1875
1.94 36 1.98 31 2.01 29 2.04 28 2.06 27 2.08 27 2.10 28 2.10 28 2.10 28 2.08 26 2.03 22 1.91 22
MAXIMUM MOTOR FRAME SIZE: 145T

NOTES:
1. Performance certified is for Installation Type A: Free inlet, free outlet.
2. Power rating (BHP) does not include transmission losses.
3. Performance ratings do not include the effects of appurtenances (accessories).
4. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
5. Values shown are for installation Type A: Free inlet fan hemispherical sone levels.

20 TWIN CITY FAN - CATALOG 4050


PERFORMANCE DATA

210D BCRD/BCRD-E Outlet Area = 4.61 ft2 Fan Efficiency Grade: FEG56
STATIC PRESSURE (INCHES W.G.)
0 0.125 0.25 0.375 0.50 0.625 0.75 1.00 1.25 1.50 1.75 2.00
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
3078 2673 2193 1535
480
0.15 7.0 0.17 6.2 0.18 6.1 0.18 5.2
1/4
3431 3080 2646 2203 1471
535
0.21 8.7 0.23 7.9 0.25 6.9 0.26 7.2 0.24 6.3
3527 3188 2766 2346 1709
550
0.23 9.2 0.25 8.5 0.27 7.2 0.28 7.8 0.26 6.5
1/3
3816 3507 3125 2747 2311 1588
595
0.29 10.5 0.31 10.1 0.33 8.3 0.35 8.8 0.35 8.2 0.32 7.4
4168 3890 3558 3199 2845 2407 1705
650
0.37 12.5 0.40 12.5 0.42 10.2 0.44 9.8 0.46 10.5 0.46 9.1 0.42 8.5
1/2
4361 4096 3789 3439 3111 2739 2188
680
0.43 13.4 0.45 13.4 0.48 11.4 0.50 10.5 0.52 11.3 0.53 10.8 0.50 9.3
4617 4369 4089 3758 3446 3120 2732
720
0.51 15.1 0.53 15.1 0.56 13.3 0.59 11.6 0.61 12.2 0.63 12.7 0.63 11.2
3/4
4938 4707 4452 4154 3850 3562 3244 2298
770
0.62 17.0 0.65 17.0 0.68 15.7 0.70 13.7 0.73 13.3 0.76 14.3 0.77 14.3 0.72 11.8
5130 4909 4667 4389 4089 3812 3520 2745
800
0.70 18.2 0.72 18.2 0.75 17.2 0.78 15.0 0.81 14.3 0.84 14.8 0.86 15.4 0.83 12.5
1
5483 5277 5054 4808 4527 4257 3999 3412 2478
855
0.85 20 0.88 20 0.91 19.2 0.94 17.6 0.97 16.1 1.00 16.1 1.03 16.7 1.05 16.3 0.97 14.1
5772 5577 5368 5141 4882 4616 4369 3848 3148
900
0.99 22 1.02 22 1.05 21 1.09 19.8 1.12 18.1 1.15 17.3 1.19 17.7 1.23 18.4 1.20 15.3
1-1/2
6253 6073 5884 5681 5459 5213 4970 4514 4005 3292
975
1.26 25 1.29 25 1.33 25 1.36 23 1.40 22 1.44 20 1.47 19.6 1.54 21 1.56 20 1.50 17.5
6477 6304 6122 5929 5721 5488 5248 4806 4337 3766 2905
1010
1.40 27 1.44 27 1.47 27 1.51 26 1.54 24 1.58 22 1.62 21 1.69 22 1.73 22 1.72 19.1 1.6 18.2
2
6894 6732 6563 6385 6196 5989 5765 5333 4918 4455 3864 3028
1075
1.69 31 1.73 31 1.76 31 1.80 29 1.84 27 1.88 25 1.92 24 2.00 23 2.07 24 2.10 24 2.06 20 1.92 20
MAXIMUM MOTOR FRAME SIZE: 145T

210DHP BCRD/BCRD-E Outlet Area = 4.61 ft2 Fan Efficiency Grade: FEG60
STATIC PRESSURE (INCHES W.G.)
0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00 3.25
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
2532 1925
700
0.37 9.9 0.40 10.1
1/2
3001 2538 1900
775
0.48 11.4 0.52 12.5 0.53 12.0
3215 2788 2238
810
0.53 12.4 0.59 12.8 0.61 12.9
3/4
3605 3214 2779 2217
875
0.65 14.5 0.71 13.7 0.76 15.1 0.77 14.5
3752 3371 2968 2453
900
0.70 15.2 0.76 14.5 0.82 15.4 0.84 15.3
1
4152 3803 3452 3041 2541
970
0.86 18.2 0.92 16.2 0.99 16.8 1.04 17.9 1.05 17.3
4593 4287 3960 3629 3231 2766
1050
1.06 21 1.14 19.1 1.21 18.6 1.28 19.3 1.32 20 1.33 19.4
1-1/2
4916 4640 4329 4024 3692 3291 2836
1110
1.23 24 1.31 21 1.39 20 1.47 20 1.53 21 1.57 21 1.57 21
5129 4870 4574 4278 3974 3617 3204 2695
1150
1.35 25 1.44 23 1.52 21 1.60 21 1.68 23 1.73 23 1.75 22 1.72 22
2
5498 5263 4995 4711 4435 4139 3792 3401 2941
1220
1.58 28 1.69 26 1.78 24 1.86 23 1.95 23 2.02 25 2.07 25 2.09 25 2.07 25
5915 5701 5463 5200 4936 4676 4395 4069 3706 3310 2629
1300
1.88 32 2.00 30 2.10 28 2.19 26 2.28 25 2.37 26 2.45 27 2.51 28 2.53 27 2.53 27 2.39 26
3
6405 6210 6001 5768 5520 5275 5032 4775 4482 4155 3806 3401
1395
2.29 36 2.42 35 2.53 32 2.64 30 2.73 29 2.83 28 2.93 29 3.01 30 3.08 31 3.12 31 3.13 30 3.10 30
MAXIMUM MOTOR FRAME SIZE: 182T

NOTES:
1. Performance certified is for Installation Type A: Free inlet, free outlet.
2. Power rating (BHP) does not include belt drive losses.
3. Performance ratings do not include the effects of appurtenances in the airstream.
4. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
5. Values shown are for installation Type A: Free inlet fan hemispherical sone levels.

WWW.TCF.COM 21
PERFORMANCE DATA

240D BCRD/BCRD-E Outlet Area = 5.60 ft2 Fan Efficiency Grade: FEG60
STATIC PRESSURE (INCHES W.G.)
0 0.125 0.25 0.375 0.50 0.625 0.75 0.875 1.00 1.25 1.50 1.75
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
4128 3525 2834 1981
410
0.16 6.0 0.20 5.4 0.22 5.8 0.21 4.7
1/4
4380 3809 3180 2487
435
0.20 6.6 0.24 6.1 0.26 6.2 0.26 5.4
4631 4089 3525 2886 1850
460
0.23 7.4 0.28 6.9 0.30 6.7 0.31 6.7 0.28 5.8
1/3
4833 4312 3789 3168 2444
480
0.26 7.9 0.31 7.5 0.34 7.1 0.35 7.5 0.35 6.3
5336 4864 4405 3856 3315 2575
530
0.35 9.3 0.41 9.1 0.44 8.5 0.47 8.8 0.47 8.8 0.46 7.7
1/2
5537 5082 4640 4134 3600 3002
550
0.40 9.9 0.45 9.7 0.49 8.9 0.52 9.3 0.53 9.5 0.53 8.2
5839 5407 4987 4538 4010 3516 2806
580
0.46 10.9 0.52 10.8 0.57 10.0 0.60 10.0 0.61 10.6 0.62 10.3 0.60 9.2
3/4
6292 5891 5497 5106 4634 4164 3683 2992
625
0.58 12.5 0.65 12.5 0.70 12.0 0.73 11.6 0.76 12.0 0.77 12.5 0.78 11.5 0.75 10.8
6544 6158 5777 5406 4977 4505 4073 3538
650
0.65 13.3 0.72 13.3 0.78 12.8 0.82 12.5 0.85 12.6 0.87 13.4 0.87 13.1 0.87 11.6
1
6947 6583 6222 5874 5502 5059 4634 4218 3688
690
0.78 14.9 0.86 14.9 0.92 14.4 0.96 14.0 1.00 13.9 1.02 14.7 1.04 14.9 1.05 14.5 1.04 13.0
7551 7216 6883 6558 6236 5875 5460 5070 4695 3654
750
1.01 16.8 1.09 16.8 1.16 16.5 1.21 16.0 1.26 15.8 1.29 15.9 1.32 16.6 1.33 16.8 1.34 16.6 1.31 14.7
1-1/2
7954 7636 7320 7008 6704 6384 6013 5618 5259 4467
790
1.17 18.1 1.26 18.1 1.34 17.6 1.40 17.2 1.45 16.9 1.49 16.8 1.53 17.3 1.55 17.8 1.56 18.3 1.57 16.3
8457 8158 7860 7565 7278 6989 6674 6313 5943 5271 4415
840
1.41 19.8 1.50 19.8 1.59 19.6 1.66 19.1 1.72 18.7 1.77 18.6 1.81 18.6 1.84 18.8 1.86 19.7 1.89 19.7 1.87 17.1
2
8759 8470 8183 7897 7618 7342 7051 6721 6360 5697 4974 3809
870
1.57 21 1.67 21 1.75 21 1.83 19.8 1.89 19.5 1.94 19.2 1.99 19.2 2.03 19.7 2.06 20 2.09 21 2.09 18.9 1.97 18.0
MAXIMUM MOTOR FRAME SIZE: 145T

240DHP BCRD/BCRD-E Outlet Area = 5.60 ft2 Fan Efficiency Grade: FEG67
STATIC PRESSURE (INCHES W.G.)
0.50 0.625 0.75 0.875 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
3080 2656 2117
600
0.41 8.5 0.43 8.7 0.43 8.5
1/2
3471 3120 2692 2149
640
0.47 9.1 0.50 9.8 0.52 9.5 0.52 9.6
3750 3435 3064 2621
670
0.53 9.7 0.57 10.3 0.59 10.5 0.60 10.3
3/4
4238 3970 3671 3325 2922
725
0.64 11.2 0.68 11.2 0.72 11.7 0.75 11.8 0.76 11.5
4451 4201 3924 3611 3248
750
0.70 11.9 0.74 11.6 0.78 12.2 0.82 12.5 0.84 12.6
1
4909 4690 4450 4187 3896 3191
805
0.83 13.4 0.88 12.9 0.93 13.0 0.97 13.8 1.01 14.1 1.04 13.6
5357 5157 4947 4718 4471 3896 3178
860
0.98 15.2 1.04 14.6 1.09 14.4 1.14 14.5 1.19 15.2 1.25 15.6 1.27 14.9
1-1/2
5878 5693 5506 5309 5096 4625 4059 3371
925
1.18 17.1 1.24 16.5 1.30 16.2 1.36 15.9 1.41 15.9 1.51 17.0 1.57 17.0 1.57 16.6
6076 5896 5715 5528 5326 4883 4362 3741
950
1.27 18.0 1.33 17.4 1.39 16.7 1.45 16.7 1.51 16.6 1.61 17.7 1.68 18.1 1.71 17.4
2
6589 6419 6251 6081 5904 5518 5084 4579 3991 3238
1015
1.51 19.9 1.58 19.2 1.64 18.7 1.71 18.1 1.77 18.0 1.89 18.4 1.99 19.5 2.06 19.7 2.09 18.9 2.04 18.9
7250 7093 6936 6781 6625 6295 5931 5530 5072 4551 3940
1100
1.88 23 1.95 22 2.01 21 2.08 21 2.16 21 2.30 20 2.42 21 2.53 22 2.61 22 2.65 21 2.64 21
3
7750 7602 7454 7307 7160 6861 6537 6184 5797 5360 4869 4311
1165
2.21 25 2.27 24 2.34 24 2.41 24 2.49 23 2.64 23 2.78 23 2.91 23 3.02 24 3.10 24 3.15 23 3.15 24
MAXIMUM MOTOR FRAME SIZE: 182T

NOTES:
1. Performance certified is for Installation Type A: Free inlet, free outlet.
2. Power rating (BHP) does not include transmission losses.
3. Performance ratings do not include the effects of appurtenances (accessories).
4. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
5. Values shown are for installation Type A: Free inlet fan hemispherical sone levels.

22 TWIN CITY FAN - CATALOG 4050


PERFORMANCE DATA

300D BCRD Outlet Area = 7.88 ft2 Fan Efficiency Grade: FEG67
STATIC PRESSURE (INCHES W.G.)
0 0.125 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
5000 4086 3166
330
0.14 4.0 0.17 5.4 0.20 5.7
1/4
5454 4579 3880
360
0.18 4.6 0.22 6.1 0.26 6.7
5757 4902 4264
380
0.22 5.3 0.25 6.5 0.29 7.3
1/3
6136 5303 4714
405
0.26 5.9 0.30 7.1 0.34 8
6514 5702 5151 3222
430
0.31 6.5 0.35 7.7 0.40 8.8 0.43 8.6
1/2
6818 6021 5497 3978
450
0.36 7 0.40 8.3 0.45 9.4 0.52 9.6
7120 6339 5834 4571
470
0.41 7.7 0.45 8.8 0.50 10.0 0.59 10.3
3/4
7878 7138 6652 5702 3467
520
0.55 9.1 0.60 10 0.65 11.5 0.77 12.8 0.71 10.8
8030 7298 6814 5892 4107
530
0.59 9.4 0.63 10.1 0.68 11.9 0.80 13.1 0.81 12.5
1
8560 7855 7375 6529 5292
565
0.71 10.5 0.75 10.9 0.81 12.4 0.94 14.1 1.03 14.1
9090 8412 7934 7144 6215 3958
600
0.85 11.6 0.90 12 0.96 13.2 1.09 14.9 1.21 15.2 1.09 13.1
1-1/2
9848 9203 8731 8004 7233 6039
650
1.08 13.4 1.13 13.4 1.19 14.4 1.33 15.9 1.48 17.4 1.56 15.9
10150 9519 9050 8338 7602 6609 4338
670
1.18 14.3 1.23 14.3 1.30 15.1 1.44 16.4 1.59 17.8 1.71 17.4 1.50 14.8
2
10832 10228 9769 9077 8403 7659 6398
715
1.44 16.2 1.49 16.2 1.56 16.1 1.71 17.2 1.86 19.1 2.02 19.5 2.08 17.5
11362 10779 10328 9643 9013 8342 7414 5829
750
1.66 17.2 1.71 17.2 1.78 17.2 1.94 17.8 2.10 19.4 2.27 21 2.39 19.3 2.30 18.4
3
12423 11876 11443 10766 10203 9604 8973 8079 6697
820
2.17 20 2.23 20 2.30 19.7 2.46 19.1 2.64 19.9 2.82 22 3.00 22 3.13 20 3.06 19.5
12878 12345 11919 11244 10697 10129 9540 8823 7693 5744
850
2.41 21 2.47 21 2.55 21 2.72 20 2.90 21 3.09 22 3.28 24 3.44 23 3.49 20 3.13 20
5
14696 14215 13817 13157 12637 12164 11666 11155 10613 9918 8909 7602
970
3.59 26 3.65 26 3.73 26 3.91 25 4.12 25 4.33 25 4.54 27 4.76 29 4.97 29 5.14 28 5.20 25.0 4.99 25.0
MAXIMUM MOTOR FRAME SIZE: 184T

300DHP BCRD Outlet Area = 7.88 ft2 Fan Efficiency Grade: FEG71
STATIC PRESSURE (INCHES W.G.)
0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00 3.25
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
3881
500
0.47 8.9
1/2
4121 2721
515
0.51 9.5 0.52 9.6
4645 3617
550
0.60 10.7 0.66 10.5
3/4
5066 4201
580
0.69 11.4 0.76 10.9
5469 4715 3587
610
0.78 11.9 0.86 11.5 0.88 12.0
1
5860 5190 4279
640
0.88 12.5 0.97 13.1 1.03 12.8
6617 6061 5372 4450
700
1.10 14.2 1.22 15.4 1.31 14.2 1.35 14.5
1-1/2
7048 6537 5931 5168 4054
735
1.25 15.6 1.37 15.8 1.48 16.3 1.56 15.6 1.52 15.9
7230 6737 6160 5445 4469
750
1.31 16.0 1.44 16.4 1.56 16.9 1.64 15.8 1.65 16.5
2
7950 7512 7023 6448 5753 4824
810
1.60 17.6 1.75 17.7 1.88 18.8 2.00 18.3 2.08 17.7 2.07 18.2
9007 8629 8222 7774 7261 6666 5946 4959
900
2.10 21 2.29 20 2.45 20 2.59 22 2.72 21 2.82 20 2.88 21 2.79 21
3
9297 8933 8543 8118 7640 7090 6448 5636 4430
925
2.25 23 2.46 22 2.63 21 2.77 23 2.91 23 3.02 21 3.11 21 3.10 22 2.90 21
10160 9831 9483 9112 8711 8266 7763 7193 6515 5629
1000
2.77 25 3.00 25 3.20 25 3.37 25 3.52 26 3.67 27 3.80 24 3.90 24 3.94 24 3.85 25
5
11297 11005 10699 10379 10041 9680 9289 8858 8381 7850 7234 6474
1100
3.57 29 3.83 30 4.07 29 4.29 29 4.48 29 4.65 31 4.81 31 4.97 30 5.10 27 5.20 28 5.25 28 5.18 29
MAXIMUM MOTOR FRAME SIZE: 184T

NOTES:
1. Performance certified is for Installation Type A: Free inlet, free outlet.
2. Power rating (BHP) does not include transmission losses.
3. Performance ratings do not include the effects of appurtenances (accessories).
4. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
5. Values shown are for installation Type A: Free inlet fan hemispherical sone levels.

WWW.TCF.COM 23
PERFORMANCE DATA

360D BCRD Outlet Area = 10.50 ft2 Fan Efficiency Grade: FEG60
STATIC PRESSURE (INCHES W.G.)
0 0.125 0.25 0.375 0.50 0.625 0.75 0.875 1.00 1.25 1.50 1.75
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
7390 5833 2981
250
0.21 5.4 0.25 4.1 0.22 3.7
1/3
8277 6936 4828
280
0.29 6.9 0.34 5.5 0.35 5.2
8868 7627 5885
300
0.36 7.8 0.42 6.5 0.44 6.2
1/2
9459 8302 6836 4624
320
0.43 9.0 0.50 7.7 0.53 6.9 0.49 6.6
10050 8966 7703 5758
340
0.52 9.9 0.59 9.0 0.63 7.6 0.62 7.6
3/4
10789 9786 8688 7084 5047
365
0.64 11.2 0.72 10.4 0.77 8.9 0.78 8.9 0.72 8.3
11233 10272 9239 7824 5964
380
0.72 12.2 0.81 11.3 0.86 9.6 0.89 9.5 0.85 9.2
1
11824 10915 9949 8733 7041 5076
400
0.84 13.1 0.93 12.9 1.00 10.9 1.03 10.2 1.01 10.6 0.91 10.0
12415 11552 10640 9582 8103 6389
420
0.97 14.7 1.07 14.1 1.14 12.1 1.19 11.2 1.19 11.6 1.13 10.8
1-1/2
13598 12814 11989 11120 10001 8555 6994
460
1.28 17.0 1.39 17.0 1.48 15.0 1.53 13.7 1.57 13.4 1.56 13.8 1.49 13.1
14189 13439 12652 11837 10859 9590 8098 6484
480
1.46 18.1 1.57 18.1 1.66 16.6 1.73 15.3 1.77 14.6 1.79 15.1 1.74 14.3 1.62 14.0
2
14928 14217 13474 12709 11860 10764 9430 8018 6349
505
1.69 19.7 1.82 19.7 1.92 18.6 1.99 17.2 2.05 16.2 2.08 16.4 2.06 16.3 1.99 15.2 1.82 15.1
16258 15608 14933 14236 13518 12686 11646 10426 9124
550
2.19 22 2.32 22 2.44 22 2.53 20 2.60 19.4 2.66 18.9 2.69 19.4 2.67 20 2.60 18.5
3
16997 16376 15733 15070 14395 13657 12756 11692 10454 7837
575
2.50 25 2.64 25 2.77 24 2.87 23 2.95 22 3.01 21 3.06 21 3.08 21 3.03 21 2.79 19.6
19214 18667 18105 17527 16937 16340 15706 14979 14119 12069 9860
650
3.61 31 3.78 31 3.92 31 4.05 29 4.16 29 4.25 28 4.32 28 4.39 27 4.43 28 4.39 28 4.19 24
5
20249 19730 19199 18654 18097 17536 16958 16334 15613 13865 11781 9583
685
4.23 34 4.40 34 4.56 34 4.70 34 4.83 32 4.93 32 5.01 31 5.08 31 5.15 31 5.20 31 5.07 30 4.76 27
MAXIMUM MOTOR FRAME SIZE: 184T

360DHP BCRD Outlet Area = 10.50 ft2 Fan Efficiency Grade: FEG67
STATIC PRESSURE (INCHES W.G.)
0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00 3.25
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
6426 4046
430
0.83 9.3 0.82 7.9
1
7282 5562
460
0.99 10.0 1.05 8.8
8354 7039 4872
500
1.21 11.4 1.34 11.7 1.30 10.4
1-1/2
9001 7821 6151
525
1.35 12.3 1.52 13.1 1.56 11.2
9631 8545 7169 4906
550
1.51 13.8 1.71 13.9 1.79 13.2 1.67 12.0
2
10368 9372 8214 6549
580
1.72 15.6 1.95 14.9 2.08 15.7 2.09 13.4
12024 11202 10283 9234 7842 5754
650
2.27 21 2.55 19.1 2.78 19.1 2.93 19.6 2.96 16.9 2.74 16.5
3
12255 11455 10558 9553 8254 6364
660
2.36 22 2.65 20 2.89 19.1 3.05 20 3.10 17.8 2.98 17.2
14293 13648 12921 12132 11284 10289 9032 7308
750
3.27 28 3.60 26 3.92 24 4.20 23 4.41 25 4.53 24 4.55 21 4.38 21
5
15072 14469 13799 13063 12287 11431 10404 9111 7383
785
3.69 30 4.03 27 4.37 26 4.69 24 4.94 25 5.12 26 5.21 24 5.20 22 4.96 22
16721 16189 15616 14988 14312 13607 12851 11991 10969 9701 8092
860
4.70 33 5.07 31 5.44 29 5.82 28 6.17 27 6.45 27 6.66 29 6.81 28 6.86 27 6.83 26 6.52 25
7-1/2
17592 17090 16557 15978 15351 14693 14007 13265 12420 11427 10217 8705
900
5.31 36 5.71 34 6.09 32 6.49 31 6.87 30 7.21 29 7.47 30 7.68 31 7.82 31 7.86 28 7.83 27 7.55 27
MAXIMUM MOTOR FRAME SIZE: 213T

NOTES:
1. Performance certified is for Installation Type A: Free inlet, free outlet.
2. Power rating (BHP) does not include transmission losses.
3. Performance ratings do not include the effects of appurtenances (accessories).
4. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
5. Type A: Free inlet fan hemispherical sone levels.

24 TWIN CITY FAN - CATALOG 4050


PERFORMANCE DATA

420D BCRD Outlet Area = 11.40 ft2 Fan Efficiency Grade: FEG63
STATIC PRESSURE (INCHES W.G.)
0 0.125 0.25 0.375 0.50 0.625 0.75 1.00 1.25 1.50 1.75 2.00
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
9414 7930 5813
230
0.31 5.3 0.37 4.3 0.40 4.4
1/2
10232 8872 7303
250
0.40 6.3 0.47 5.2 0.51 5.2
11051 9794 8433 5934
270
0.50 7.3 0.58 6.3 0.63 5.9 0.63 5.2
3/4
11665 10476 9220 7415
285
0.59 8.1 0.68 7.2 0.73 6.4 0.77 6.8
12279 11152 9983 8553 5471
300
0.69 8.9 0.78 8.2 0.84 7.1 0.88 7.6 0.79 6.1
1
12893 11822 10721 9463 7218
315
0.80 9.9 0.89 9.4 0.96 7.8 1.01 8.3 1.01 7.4
13507 12486 11440 10291 8641 5396
330
0.92 10.9 1.02 10.2 1.09 8.8 1.15 8.9 1.19 9.0 0.98 7.0
1-1/2
14734 13802 12846 11853 10712 8855
360
1.19 12.7 1.31 12.5 1.39 10.7 1.45 10.0 1.51 10.8 1.54 10.1
15144 14237 13308 12355 11280 9751 7010
370
1.29 13.5 1.41 13.5 1.50 11.5 1.57 10.8 1.63 11.4 1.68 11.3 1.51 8.9
2
16167 15319 14450 13574 12621 11530 9759
395
1.57 15.2 1.70 15.2 1.81 13.4 1.88 12.2 1.95 12.2 2.01 13.0 2.04 12.2
17599 16822 16028 15227 14403 13498 12464 8417
430
2.03 17.3 2.17 17.3 2.29 16.0 2.39 14.5 2.46 14.1 2.53 14.3 2.59 15.0 2.41 11.7
3
18623 17889 17141 16383 15621 14804 13918 11167
455
2.40 18.7 2.55 18.7 2.69 17.8 2.80 16.3 2.88 15.4 2.95 15.4 3.03 16.1 3.11 15.3
20464 19797 19120 18433 17744 17045 16298 14606 11622
500
3.19 22 3.36 22 3.51 21 3.64 20 3.75 18.7 3.83 17.9 3.91 17.9 4.07 19.1 4.07 16.9
5
22102 21485 20860 20227 19588 18950 18297 16865 15089 11869
540
4.01 25 4.20 25 4.37 25 4.52 23 4.65 22 4.75 21 4.84 21 5.02 21 5.17 22 5.03 18.6
23739 23165 22585 21998 21404 20810 20215 18955 17555 15664 12437
580
4.97 28 5.17 28 5.36 28 5.53 27 5.68 26 5.80 24 5.91 24 6.10 24 6.29 25 6.45 25 6.17 20
7-1/2
25171 24630 24084 23532 22975 22413 21854 20709 19455 18048 15960 12702
615
5.93 31 6.14 31 6.34 31 6.52 31 6.69 29 6.84 27 6.96 27 7.17 26 7.37 27 7.57 28 7.71 27 7.23 22
MAXIMUM MOTOR FRAME SIZE: 213T

480D BCRD Outlet Area = 14.11 ft2 Fan Efficiency Grade: FEG63
STATIC PRESSURE (INCHES W.G.)
0 0.125 0.25 0.375 0.50 0.625 0.75 0.875 1.00 1.25 1.50 1.75
HP RPM
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone BHP Sone
10494 8604 4418
190
0.30 4.8 0.37 4.0 0.32 3.0
1/2
11599 9890 7393
210
0.41 5.7 0.48 4.8 0.51 4.5
12427 10824 8907
225
0.50 6.5 0.58 5.5 0.64 6.0
3/4
13256 11745 10130 6645
240
0.61 7.4 0.69 6.4 0.76 6.8 0.70 5.0
13808 12355 10874 8149
250
0.69 8.0 0.78 6.9 0.85 7.2 0.85 5.5
1
14636 13265 11921 9923
265
0.82 8.7 0.91 7.8 1.00 7.7 1.04 7.6
15741 14466 13228 11702 8899
285
1.02 10.1 1.12 9.4 1.21 8.5 1.28 9.1 1.24 7.0
1-1/2
16570 15358 14177 12864 10809 6905
300
1.18 11.2 1.30 10.6 1.39 9.4 1.48 10.1 1.50 9.1 1.24 7.5
17674 16538 15419 14291 12753 10144
320
1.44 12.8 1.56 12.5 1.66 10.5 1.76 10.9 1.83 11.2 1.76 8.9
2
18503 17418 16341 15292 13984 12038 8684
335
1.65 13.7 1.77 13.7 1.89 11.8 1.99 11.4 2.08 12.3 2.09 11.2 1.84 9.5
19331 18293 17257 16261 15120 13570 11035
350
1.88 14.4 2.01 14.4 2.13 12.6 2.24 12.4 2.34 13.3 2.40 13.2 2.30 10.3
3
20988 20031 19076 18147 17208 16057 14548 12193 8837
380
2.41 16.6 2.55 16.6 2.68 15.4 2.81 14.4 2.93 14.7 3.02 15.6 3.07 15.4 2.96 12.5 2.54 11.9
23197 22332 21467 20607 19781 18915 17874 16582 14786
420
3.25 19.0 3.41 19.0 3.56 18.8 3.70 17.0 3.84 16.9 3.96 16.9 4.07 17.9 4.14 18.1 4.11 16.2
5
25131 24331 23533 22735 21957 21194 20377 19407 18246 14685
455
4.13 22 4.31 22 4.47 22 4.63 19.7 4.78 18.7 4.92 18.6 5.05 19.5 5.17 19.9 5.25 19.9 5.10 16.4
27616 26889 26162 25435 24710 24011 23317 22585 21748 19643 16297 11145
500
5.48 24 5.68 24 5.86 24 6.04 24 6.21 22 6.37 22 6.53 21 6.67 22 6.80 23 6.99 23 6.79 18.8 5.67 18.5
7-1/2
28721 28021 27322 26624 25926 25243 24579 23899 23161 21338 18766 14603
520
6.17 26 6.37 26 6.56 26 6.75 25 6.92 24 7.10 23 7.26 22 7.42 23 7.57 23 7.80 25 7.83 23 7.15 20
MAXIMUM MOTOR FRAME SIZE: 213T
NOTES:
1. Performance certified is for Installation Type A: Free inlet, free outlet.
2. Power rating (BHP) does not include transmission losses.
3. Performance ratings do not include the effects of appurtenances (accessories).
4. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
5. Values shown are for installation Type A: Free inlet fan hemispherical sone levels.

WWW.TCF.COM 25
DIMENSIONAL DATA
Model DCRD, Direct Drive

D DIA.

2.00"
C
E SQUARE
A DIA.

CURB
CURB SIZE
DAMPER

ROOF OPENING
(DAMPER SIZE
+ 0.50 INCHES)

Notes:
1. All dimensions are in inches unless otherwise noted.
2. Dimensions are not to be used for construction.
3. Outside dimensions of dampers are nominal.
4. Outside dimensions of roof curb should be 1" to 1.50" less than inside curb cap dimension 'E', depending on thickness of flashing material used.
If curb hinges are used, specify 1.50" difference.
5. Self-flashing roof curbs are 1" larger than canted curbs.

EC MOTOR PSC MOTOR FAN DIMENSIONS CANTED DAMPER AVG. SHIP


SIZES SIZES A B C D E CURB SIZE SIZE WT. (LBS.)
060BE/070BE 060B/070B 18.50 15.63 2.06 15.12 17.00 15.5 x 15.5 10 x 10 30
080BE 080B 18.50 15.63 2.06 15.12 17.00 15.5 x 15.5 10 x 10 32
085BE/090BE/ 085B/090B/
21.00 19.31 2.63 15.12 17.00 15.5 x 15.5 10 x 10 43
095BE 095B
100BE 100B 21.00 17.31 2.63 15.12 17.00 15.5 x 15.5 10 x 10 48
120BE 120B 27.50 22.38 3.63 22.00 20.00 18.5 x 18.5 14 x 14 50
130BE 130B 27.50 23.25 4.44 22.00 24.00 22.5 x 22.5 18 x 18 65
140BE 140B 27.50 23.50 4.69 22.00 24.00 22.5 x 22.5 18 x 18 67
150BE 150B 30.44 26.75 4.63 24.00 24.00 22.5 x 22.5 18 x 18 77
160BE 160B 30.44 27.25 5.19 24.00 24.00 22.5 x 22.5 18 x 18 82
170BE 170B 38.38 29.25 4.06 30.00 30.00 28.5 x 28.5 24 x 24 95
180BE 180B 38.38 30.25 5.06 30.00 30.00 28.5 x 28.5 24 x 24 100
D-4051F

DIMENSIONS NOT TO BE USED FOR CONSTRUCTION. CERTIFIED DRAWINGS AVAILABLE UPON REQUEST.

26 TWIN CITY FAN - CATALOG 4050


DIMENSIONAL DATA
Model BCRD, Belt Driven

2.00"
C

E SQUARE

A DIA.
CURB
CURB SIZE

DAMPER

ROOF OPENING
(DAMPER SIZE
+ 0.50 INCHES)

Notes:
1. All dimensions are in inches unless otherwise noted.
2. Dimensions are not to be used for construction.
3. Outside dimensions of dampers are nominal.
4. Outside dimensions of roof curb should be 1" to 1.50" less than inside curb cap dimension 'E', depending on thickness of flashing material used.
If curb hinges are used, specify 1.50" difference.
5. Self-flashing roof curbs are 1" larger than canted curbs.

FAN DIMENSIONS CANTED DAMPER AVG. SHIP


SIZE
A B C D E CURB SIZE SIZE WT. (LBS.)
070D/075D 25.88 22.13 2.06 22.00 17.00 15.5 x 15.5 10 x 10 58
085D 27.50 23.94 2.38 22.00 17.00 15.5 x 15.5 10 x 10 67
100D/100DHP 27.50 23.94 2.38 22.00 20.00 18.5 x 18.5 14 x 14 74
120D 30.44 28.13 2.56 24.00 20.00 18.5 x 18.5 14 x 14 78
140D 30.44 28.25 2.81 24.00 24.00 22.5 x 22.5 18 x 18 93
140DHP 30.44 28.25 2.81 24.00 24.00 22.5 x 22.5 18 x 18 88
160D/160DHP 32.63 29.00 3.38 24.00 26.00 24.5 x 24.5 20 x 20 107
180D/180DHP 38.38 33.88 3.75 30.00 30.00 28.5 x 28.5 24 x 24 130
210D/210DHP 38.38 34.06 4.00 30.00 30.00 28.5 x 28.5 24 x 24 160
240D/240DHP 43.13 35.88 4.88 30.00 34.00 32.5 x 32.5 28 x 28 220
300D/300DHP 51.38 38.88 4.88 42.00 40.00 38.5 x 38.5 34 x 34 270
360D/360DHP 60.75 44.38 6.88 50.00 46.00 44.5 x 44.5 40 x 40 360
420D 65.81 47.81 7.00 50.00 52.00 50.5 x 50.5 46 x 46 420
480D 74.06 50.25 7.75 58.00 58.00 56.5 x 56.5 50 x 50 475
D-4105G

DIMENSIONS NOT TO BE USED FOR CONSTRUCTION. CERTIFIED DRAWINGS AVAILABLE UPON REQUEST.

WWW.TCF.COM 27
DIMENSIONAL DATA
Model BCRD-E, Belt Driven,
Endurex™ Housing

2.00
C

E SQUARE
A DIA.

CURB
CURB SIZE
DAMPER

ROOF OPENING
(DAMPER SIZE
+ 0.50 INCHES)

Notes:
1. All dimensions are in inches unless otherwise noted.
2. Dimensions are not to be used for construction.
3. Outside dimensions of dampers are nominal.
4. Outside dimensions of roof curb should be 1" to 1.50" less than inside curb cap dimension 'E', depending on thickness of flashing material used.
If curb hinges are used, specify 1.50" difference.
5. Self-flashing roof curbs are 1" larger than canted curbs.

FAN DIMENSIONS CANTED DAMPER AVG. SHIP


SIZE
A B C D E CURB SIZE SIZE WT. (LBS.)
070D/
25.87 21.75 2.03 20.68 17.00 15.5 x 15.5 10 x 10 58
075D
085D 27.88 26.25 2.41 22.44 17.00 15.5 x 15.5 10 x 10 67
100D 27.88 26.25 2.41 22.44 20.00 18.5 x 18.5 14 x 14 74
120D 30.96 29.19 2.56 22.44 20.00 18.5 x 18.5 14 x 14 78
140D 30.96 29.44 2.81 22.44 24.00 22.5 x 22.5 18 x 18 93
160D 33.81 33.25 3.36 24.50 26.00 24.5 x 24.5 20 x 20 107
180D 39.54 36.06 3.75 27.25 30.00 28.5 x 28.5 24 x 24 130
210D 39.54 36.31 4.00 27.25 30.00 28.5 x 28.5 24 x 24 160
240D 43.00 37.44 4.83 27.25 34.00 32.5 x 32.5 28 x 28 220
D-4106B

DIMENSIONS NOT TO BE USED FOR CONSTRUCTION. CERTIFIED DRAWINGS AVAILABLE UPON REQUEST.

28 TWIN CITY FAN - CATALOG 4050


TYPICAL SPECIFICATIONS

Model
DCRD
Roof exhaust fans shall be of the direct drive centrifugal type, Model DCRD, as manufactured by Twin City Fan &
Blower, Minneapolis, Minnesota.

PERFORMANCE — Fans shall be tested in accordance with AMCA 210 and AMCA 300 test codes for air moving
devices and shall be guaranteed by the manufacturer to deliver rated published performance levels. Fans shall be
licensed to bear the AMCA certified ratings seal for both sound and air. Models shall be CULUS 705 listed.

CONSTRUCTION — Fans shall be constructed of aluminum for durability and appearance. Fan spinnings shall have a
rolled bead edge for rigidity. Units shall have a deep venturi inlet to prevent snow and rain entry into the building. The
curb cap shall include prepunched mounting holes for ease of installation. A conduit chase constructed of electrical
metallic tubing shall be provided to the motor compartment. The curb base shall provide protection from weather. Fans
shall bear a permanently attached nameplate displaying model and serial number of the unit for future identification.

MOTOR ASSEMBLY — Motor assembly shall be mounted on vibration isolators to eliminate vibration and noise
transmission into the ductwork. Motors shall be mounted out of the exhaust airstream.

WHEEL — Fan wheels shall be of the centrifugal backward inclined type, containing a matching inlet venturi for
optimum unit performance. Wheels shall be statically and dynamically balanced.

MOTOR — Motors shall be heavy-duty ball bearing type, closely matched to the fan load. All single-phase ODP motors
shall contain thermal overload protection. All motors shall be UL and /or CSA recognized. Motors for use with speed
control shall provide good speed controllability without any objectionable noise.

DISCONNECT SWITCH — A NEMA 1 disconnect switch shall be supplied with wiring leading from the motor to the
junction box (ODP and TEFC motors).

ACCESSORIES — When specified, accessories such as backdraft damper, roof curb, curb hinge, retaining chain,
security hasp, variable speed controller, NEMA 3R, 4 disconnect switch, firestat, aluminum bird screen, aluminum
insect screen and special coatings shall be provided by Twin City Fan & Blower to maintain one source responsibility.

FACTORY RUN TEST — All fans prior to shipment shall be completely assembled and test run as a unit at operating
speed or maximum RPM allowed for the particular construction type. Each wheel shall be statically and dynamically
balanced in accordance with ANSI/AMCA 204-96 "Balance Quality and Vibration Levels for Fans" to Fan Application
Category BV-3, Balance Quality Grade G6.3. Balance readings shall be taken by electronic type equipment in the axial,
vertical, and horizontal directions on each of the bearings. Records shall be maintained and a written copy shall be
available upon request.

GUARANTEE — The manufacturer shall guarantee the workmanship and materials for its roof and wall mounted
centrifugal exhaust fans for at least one (1) year from startup or eighteen (18) months from shipment, whichever occurs
first.

Twin City Fan

WWW.TCF.COM 29
TYPICAL SPECIFICATIONS

Model
BCRD
Roof mounted exhaust fans shall be of the belt driven centrifugal type, Model BCRD (Spun Aluminum Housing) and
as manufactured by Twin City Fan & Blower, Minneapolis, Minnesota.

PERFORMANCE — Fans shall be tested in accordance with AMCA 210 and AMCA 300 test codes for air moving
devices and shall be guaranteed by the manufacturer to deliver rated published performance levels. Fans shall be
licensed to bear the AMCA certified ratings seal for both sound and air. Models shall be CULUS 705 listed.

CONSTRUCTION — BCRD fans housings shall be -constructed of spun aluminum and shall offer finish durability and
aesthetic appearance. Fan spinnings shall have a rolled bead edge for rigidity. All units have a deep venturi inlet to
prevent snow and rain entry into the building. The curb cap shall include prepunched mounting holes for ease of
installation. A conduit chase constructed of electrical metallic tubing shall be provided to the motor compartment. The
curb base shall provide protection from weather. Lifting lugs shall be provided inside the motor compartment for ease
of handling and installation. Fans shall bear a permanently attached nameplate displaying model and serial number of
the unit for future identification.

MOTOR AND DRIVE ASSEMBLY — Motor and drive assembly shall be mounted on vibration isolators to eliminate
vibration and noise transmission into the ductwork. Motors and drives shall be mounted out of the exhaust airstream.

WHEEL — Fan wheels shall be of the centrifugal backward inclined type, containing a matching inlet venturi for
optimum unit performance. Wheels shall be statically and dynamically balanced.

SHAFT — Fan shafts shall be precision-ground and polished. Shafts shall have a first critical speed of at least 125%
of the fan’s maximum operating speed.

BEARINGS — Bearings shall be of the one-piece, pillow block type with relubricable zerk fittings. Bearings shall
be designed for air handling service with a minimum L-10 life in excess of 100,000 hours; L-50 500,000 hours at
the maximum cataloged operating speed. Bearing mounting plate shall have self-aligning tabs for exact locating and
alignment of bearings.

DRIVE — Drive assembly shall be constructed of heavy-gauge galvanized steel. Drives shall be sized for a minimum
of 150% of driven horsepower. Machined, cast iron motor sheaves shall be adjustable for final system balance.

MOTOR — Motors shall be heavy-duty ball bearing type, closely matched to the fan load. All single-phase ODP motors
shall contain thermal overload protection. All motors shall be UL and /or CSA recognized. Motor adjustment shall allow
precise belt tensioning for optimum belt life and one-person adjustment and servicing.

DISCONNECT SWITCH — A NEMA 1 disconnect switch shall be supplied with wiring leading from the motor to the
junction box (ODP and TEFC motors).

ACCESSORIES — When specified, accessories such as backdraft damper, roof curb, curb hinge, retaining chain,
security hasp, NEMA 3R, 4 disconnect switch, 2-speed switch, firestat, aluminum bird screen, aluminum insect screen
and special coatings shall be provided by Twin City Fan & Blower to maintain one source responsibility.

FACTORY RUN TEST — All fans prior to shipment shall be completely assembled and test run as a unit at operating
speed or maximum RPM allowed for the particular construction type. Each wheel shall be statically and dynamically
balanced in accordance with ANSI/AMCA 204-96 "Balance Quality and Vibration Levels for Fans" to Fan Application
Category BV-3, Balance Quality Grade G6.3. Balance readings shall be taken by electronic type equipment in the axial,
vertical, and horizontal directions on each of the bearings. Records shall be maintained and a written copy shall be
available upon request.

GUARANTEE — The manufacturer shall guarantee the workmanship and materials for its roof and wall mounted centrifugal
exhaust fans for at least one (1) year from startup or eighteen (18) months from shipment, whichever occurs first.

30 TWIN CITY FAN - CATALOG 4050


TYPICAL SPECIFICATIONS

Model
BCRD-E
Roof mounted exhaust fans shall be of the belt driven centrifugal type, Model BCRD-E (Endurex™ Polymeric Housing),
as manufactured by Twin City Fan & Blower, Minneapolis, Minnesota.

PERFORMANCE — Fans shall be tested in accordance with AMCA 210 and AMCA 300 test codes for air moving
devices and shall be guaranteed by the manufacturer to deliver rated published performance levels. Fans shall be
licensed to bear the AMCA certified ratings seal for both sound and air. Models shall be CULUS 705 listed.

CONSTRUCTION — BCRD-E housings shall be constructed of Endurex™ for impact, weather, corrosion and UV
resistance. All units have a deep venturi inlet to prevent snow and rain entry into the building. The curb cap shall
include prepunched mounting holes for ease of installation. A conduit chase constructed of electrical metallic tubing
shall be provided to the motor compartment. The curb base shall provide protection from weather. Lifting lugs shall be
provided inside the motor compartment for ease of handling and installation. Fans shall bear a permanently attached
nameplate displaying model and serial number of the unit for future identification.

MOTOR AND DRIVE ASSEMBLY — Motor and drive assembly shall be mounted on vibration isolators to eliminate
vibration and noise transmission into the ductwork. Motors and drives shall be mounted out of the exhaust airstream.

WHEEL — Fan wheels shall be of the centrifugal backward inclined type, containing a matching inlet venturi for
optimum unit performance. Wheels shall be statically and dynamically balanced.

SHAFT — Fan shafts shall be precision-ground and polished. Shafts shall have a first critical speed of at least 125%
of the fan’s maximum operating speed.

BEARINGS — Bearings shall be of the one-piece, pillow block type with relubricable zerk fittings. Bearings shall
be designed for air handling service with a minimum L-10 life in excess of 100,000 hours; L-50 500,000 hours at
the maximum cataloged operating speed. Bearing mounting plate shall have self-aligning tabs for exact locating and
alignment of bearings.

DRIVE — Drive assembly shall be constructed of heavy-gauge galvanized steel. Drives shall be sized for a minimum
of 150% of driven horsepower. Machined, cast iron motor sheaves shall be adjustable for final system balance.

MOTOR — Motors shall be heavy-duty ball bearing type, closely matched to the fan load. All single-phase ODP motors
shall contain thermal overload protection. All motors shall be UL and /or CSA recognized. Motor adjustment shall allow
precise belt tensioning for optimum belt life and one-person adjustment and servicing.

DISCONNECT SWITCH — A NEMA 1 disconnect switch shall be supplied with wiring leading from the motor to the
junction box (ODP and TEFC motors).

ACCESSORIES — When specified, accessories such as backdraft damper, roof curb, curb hinge, retaining chain,
security hasp, NEMA 3R, 4 disconnect switch, 2-speed switch, firestat, aluminum bird screen, aluminum insect screen
and special coatings shall be provided by Twin City Fan & Blower to maintain one source responsibility.

FACTORY RUN TEST — All fans prior to shipment shall be completely assembled and test run as a unit at operating
speed or maximum RPM allowed for the particular construction type. Each wheel shall be statically and dynamically
balanced in accordance with ANSI/AMCA 204-96 "Balance Quality and Vibration Levels for Fans" to Fan Application
Category BV-3, Balance Quality Grade G6.3. Balance readings shall be taken by electronic type equipment in the axial,
vertical, and horizontal directions on each of the bearings. Records shall be maintained and a written copy shall be
available upon request.

GUARANTEE — The manufacturer shall guarantee the workmanship and materials for its roof and wall mounted
centrifugal exhaust fans for at least one (1) year from startup or eighteen (18) months from shipment, whichever occurs
first. All Endurex™ housing components shall have a limited lifetime warranty.

WWW.TCF.COM 31
INDUSTRIAL PROCESS AND
COMMERCIAL VENTILATION SYSTEMS
CENTRIFUGAL FANS | UTILITY SETS | PLENUM & PLUG FANS | INLINE CENTRIFUGAL FANS

MIXED FLOW FANS | TUBEAXIAL & VANEAXIAL FANS | PROPELLER WALL FANS | PROPELLER ROOF VENTILATORS

CENTRIFUGAL ROOF & WALL EXHAUSTERS | CEILING VENTILATORS | GRAVITY VENTILATORS | DUCT BLOWERS

RADIAL BLADED FANS | RADIAL TIP FANS | HIGH EFFICIENCY INDUSTRIAL FANS | PRESSURE BLOWERS

LABORATORY EXHAUST FANS | FILTERED SUPPLY FANS | MANCOOLERS | FIBERGLASS FANS | CUSTOM FANS

Twin City Fan

TWIN CITY FAN & BLOWER


WWW.TCF.COM

Twin City Fan


5959 TRENTON LANE N | MINNEAPOLIS, MN 55442 | PHONE: 763-551-7600 | FAX: 763-551-7601

©2018 Twin City Fan Companies, Ltd., Minneapolis, MN. All rights reserved. Catalog illustrations cover the general appearance of Twin City
Fan & Blower products at the time of publication and we reserve the right to make changes in design and construction at any time without notice.

You might also like